0 DESIGN INFORMATION
1.3 Foundation
2.0 REFERENCES
BS 8007 (1987)
Design of concrete structures for retaining aqueous liquids
BS 4466 (1981)
Specification for Bending Dimensions and Scheduling of Reinforcement for Concrete.
Material Properties
Density of Concrete 24 kN/m3
Density of Water 10 kN/m3
Density of water during flooding 14.5 kN/m3
Concrete Grade 30 N/mm2
Strength of high yield Steel 460 N/mm2
Durability Requirement
Exposure Condition - Severe
Clear cover to r/f 75 mm
Foundation
Bearing capacity (assumed) 75 kN/m2
Soil parameters c= 5 kN/m2
j= 30 deg
g sat= 18 kN/m3
(Where c is cohesion, j is friction angle and g is the density)
Reference Calculations Output
Wt of water+Pipe = 16.42 kN
y y
Reference Calculations Output
21.4 kN 21.4 kN
0.6 kN
20.88 kN 7.5 kN
3.0
2.0
Equivalent
21.42 kN 21.42 kN
0.6 kN
7.5 kN
3.00 m
41.8 kN.m
31 kN 31 kN
1.0 kN
33.41 kN 12.03 kN
Reference Calculations Output
3.0
2.0
Equivalent
30.99 kN 30.99 kN
1.0 kN
12.03 kN
3.00 m
67 kN.m
h
X X
h'
b'
Y
b = 300 mm
h = 400 mm
Lex/h = 16.50
> 10 for unbraced
Ley/b =
22.00
> 10 for unbraced
Hence the column should be designed as slender about both axis
Cover = 75 mm
Vertical r/f bar diameter = 25 mm
Stirrups = 8 mm
h' = 204.5 mm
b' = 304.5 mm
K = Nuz - N ≤1
Nuz - Nbal
= 1.32
Take, K = 1.00
ax = (1/2000) (lex/b)2 hK
= 54.5 mm
ay = (1/2000) (ley/h)2 bK
= 40.8 mm
Madd x = NaxK
= 1.69 kN.m
Madd y = NayK
= 1.27 kN.m
N/ (bhfcu) = 0.009
Appendix D,
Manual for the N/ (bhfcu) < 0.1, Hence design as a beam.
design of Consider major axis,
reinforced
concrete building d = 304.5 mm
structures, 1985 d' = 95.5 mm
d/h = 0.76
4T20+4T16
My
Mx
3300
1750
N= 30.1 kN
Mx = 43.6 kN.m
3.300
ex = 1449.2 mm
L/6 = 550.00 mm
e > L/6
Length of pressure diagram, y = 3 (L/2-e)
= 602.43 mm
Using simple elastic analysis,
Pmax = 2N/ (3B(D/2-e))
B = 1.8 m
Pmax = 57.0 kN/m2
Pmax < qall
N= 30.1 kN
My = 22.6 kN.m
1.750
ey = 750.2 mm
B/6 = 291.67 mm
e > L/6
Length of pressure diagram, y = 3 (L/2-e)
= 374.26 mm
Using simple elastic analysis,
Pmax = 2N/ (3B(D/2-e))
B = 3.3 m
Pmax = 48.7 kN/m2
Pmax < qall
3250 1000
Reference Calculations Output
% of moment redistribution = 0
K' = 0.156
K = M/ fcu bd2
= 0.023 kN.m
K < K'
Compression reinforcement not needed,
d = 319.0 mm
z = d {0.5+sqrt(0.25-K'/0.9)}
= 247.83 mm
x = (d-z)/0.45
= 158.2 mm
As = M/0.87f y
z
As,req = 715 mm2
No of bars = 6.33
Spacing = 158
Provide T 12 @ 150 As, pro = 867 mm2
Reference Calculations Output
Reference Calculations Output