Anda di halaman 1dari 56

Marine Cables

Contents HELKAMA - a true specialist in marine cables


Helkama - a true specialist Helkama is specializing in development and production of
in marine cables ......................2
Approvals..................................3 marine cables. Our experience in this field goes back more
0,6/1kV cables than thirty years. Our high technical quality has been achieved
LKM-HF.....................................4 by continuous development work support by our clients. In
LKM-HF FLEX NEW ...................6
LKSM-HF...................................8 this catalogue we proudly present our most comprehensive
LKSM-HF FLEX NEW...............10 range of marine cables.
LKSM-EMC NEW.....................12
LKSM-VFD NEW......................14
LKAM-HF.................................16 We have chosen to produce only halogen-free cables. They
LKEM-HF.................................18
remarkably improve the fire safety of the ships by not emitting
0,6/1kV FR cables
LKM-FRHF...............................20
toxic burning fumes or thick smoke. In addition no corrosive
LKSM-FRHF ............................22 gases damaging the ship and its equipment are emitted in
LKAM-FRHF NEW....................24 case of a fire. Using the latest technology we have been able
250V cables
LKSM-HF.................................26 to reduce cable weight and size to a minimum and still
RFE-HF ....................................28 maintain quality as well as enabling easy and fast installation.
RFE-HF (i) ...............................30
RFA-HF ....................................32
The halogen free range of cables includes both flame-retardant
RFA-HF (i) ...............................34 (IEC 60332-3) and fire resistant (IEC 60331-21) cables.
250V FR cables Helkama marine cables are approved by all major classification
RFE-FRHF................................36
RFE-FRHF (i) ...........................38 societies.
RFA-FRHF................................40
RFA-FRHF (i) ...........................42
60V cables
As a specialized and independent
PBS .........................................44 company, focusing on service, we have
Optical fibre cables been able to grow steadily by quickly
FXMSU ....................................46
FXMMS ...................................47 responding to our customers’ needs.
LifeCord-FRHF.........................48 Our short delivery times, backed up by
Cabled optical fibres
characteristics.........................49
extensive stocks, enable us to deliver
Technical information punctually and keep our clients satisfied.
General information.................50 This remains our goal for the future, too.
Bending radius ........................51
Diameter tolerance ..................51
Core identification ...................51
Current rating..........................52
Short circuit current ................52
Short time duty .......................53
Short circuit factors.................54
Voltage drop............................55

Marine cable factory in Kaarina, Finland.


3

TYPE APPROVALS
Type Approval Certificates for factories in Finland and China
ABS BV CCS DNV GL KRS LRS RMRS NK RINA TC
0,6/1kV FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN
LKM-HF ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ● ● ❍ ●
LKM-HF FLEX ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ● ● ❍ ●
LKSM-HF ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ● ● ❍ ●
LKSM-HF FLEX ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ● ● ❍ ●
LKSM-EMC ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍
LKSM-VFD ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍
LKAM-HF ● ● ● ● ● ● ❍ ● ● ● ●
LKEM-HF ● ● ● ● ● ● ❍ ● ❍ ● ● ● ● ● ● ❍

www.helkamabica.fi
LKM-FRHF ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ❍ ● ❍ ●
LKSM-FRHF ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ❍ ● ❍ ●
LKAM-FRHF ● ❍ ❍ ●
250V FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN FI CN
LKSM-HF ● ● ● ● ● ● ❍ ● ❍ ● ● ● ❍
RFE-HF ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ● ● ❍ ●
RFE-HF(i) ● ● ● ● ❍ ● ● ● ● ❍ ● ● ● ● ● ● ❍ ●
RFA-HF ● ● ● ● ❍ ● ● ● ❍ ❍ ❍ ● ● ● ● ● ● ❍
RFA-HF(i) ● ● ● ● ❍ ● ● ● ❍ ❍ ❍ ● ● ● ● ● ● ❍
RFE-FRHF ● ● ● ● ❍ ● ● ● ❍ ● ❍ ● ● ● ● ● ● ❍ ●
RFE-FRHF(i) ● ● ● ● ❍ ● ● ● ❍ ● ❍ ● ● ● ● ● ● ❍ ●
RFA-FRHF ● ● ● ● ● ● ❍ ● ❍ ● ● ● ❍ ● ● ❍
RFA-FRHF(i) ● ● ● ● ● ● ❍ ● ❍ ● ● ● ❍ ● ● ❍

● Combined TAC for Finland and China Please check updated approval situation on www.helkamabica.fi
● ● Separate TAC for Finland and China
❍ Type Approval pending
No Type Approval

Marine cable factory in Shanghai, China.


4
0,6/1kV CABLES

LKM-HF Unarmoured power and control cable


0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation Flame-
retardant
- XLPE plastic IEC 60092-351
Fire-
3. Bedding resistant
- separator tape
Halogen-
4. Sheath free
- polyolefine plastic, SHF1 IEC 60092-359
3/2008

Low
- standard colour black, other colours on request smoke
emission

Application: For fixed installation in most areas and on open deck in ships.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


5

0,6/1kV CABLES
LKM-HF 0,6/1kV Number of Nominal Min. bending
conductors & outer Approximate Current radius fixed
Part number cross-section diameter weight kg/km rating A installation
Normal G-type n x mm2 mm mm
25 642 – 1x6 6,5 95 52 30
25 644 – 1x10 7,5 140 72 30
25 646 – 1x16 8,5 205 96 35
25 648 – 1x25 11,5 320 127 50
25 650 – 1x35 12,0 420 157 50
25 652 – 1x50 14,0 555 196 60
25 654 – 1x70 17,0 790 242 70
25 656 – 1x95 18,0 1040 293 75
25 658 – 1x120 20,0 1300 339 80
25 660 – 1x150 23,5 1610 389 95
25 662 – 1x185 26,0 2005 444 160
25 664 – 1x240 29,0 2615 522 175
25 666 – 1x300 32,0 3235 601 195
25 670 – 2x1,5 8,0 80 20 35
25 686 – 2x2,5 10,0 115 26 40
25 702 – 2x4 11,0 155 34 45
25 701 – 2x6 11,5 205 44 50
25 717 – 2x10 14,5 315 61 60
25 711 – 2x16 16,5 465 82 70
25 713 – 2x25 20,5 700 108 85
25 715 – 2x35 23,5 990 133 95
25 671 25 672 3x1,5 8,5 100 16 35
25 688 25 689 3x2,5 10,5 145 21 45
25 703 25 704 3x4 11,0 200 28 45

3/2008
25 705 25 706 3x6 12,5 280 36 50
25 707 25 708 3x10 15,5 425 50 65
25 709 25 710 3x16 18,0 630 67 75
25 712 25 851 3x25 21,5 960 89 90
25 714 25 852 3x35 25,0 1335 110 150
25 716 25 853 3x50 28,5 1785 137 175
25 718 25 854 3x70 33,5 2570 169 205
25 720 25 855 3x95 37,5 3380 205 225
25 722 25 856 3x120 42,0 4255 237 255
25 724 25 857 3x150 48,0 5235 272 290
25 673 25 674 4x1,5 9,5 135 16 40
25 690 25 691 4x2,5 11,5 180 21 50
25 725 25 726 4x4 13,0 260 28 55
25 727 25 728 4x6 14,5 355 36 60
25 729 25 730 4x10 17,0 545 50 70
25 731 25 699 4x16 20,0 820 67 80
25 732 25 700 4x25 24,0 1265 89 100
25 733 25 719 4x35 27,0 1725 110 165
25 734 25 721 4x50 32,0 2325 137 195
25 735 25 723 4x70 38,0 3325 169 230
25 984 25 985 4x95 43,0 4425 205 260
25 879 – 4x120 47,5 5515 237 285
25 676 25 677 5x1,5 10,5 160 14 45
25 692 25 693 5x2,5 12,5 220 18 50
25 864 25 865 5x4 14,0 315 25 60
25 866 25 867 5x6 15,0 445 30 60
25 868 25 869 5x10 18,0 675 44 75
25 870 25 871 5x16 21,0 1015 56 85
25 678 – 7x1,5 12,0 200 12 50
25 694 – 7x2,5 13,0 285 16 55
25 667 – 10x1,5 14,5 290 11 60
25 993 – 10x2,5 16,5 415 14 70
25 680 – 12x1,5 16,0 335 10 65
25 696 – 12x2,5 17,0 470 13 70
25 991 – 14x1,5 16,0 375 10 65
25 995 – 14x2,5 19,0 545 13 80
25 989 – 16x1,5 17,5 425 9 70
25 997 – 16x2,5 20,0 615 12 80
25 682 – 19x1,5 18,0 490 9 75
25 873 – 19x2,5 21,0 700 11 85
25 875 – 24x1,5 21,5 635 8 90
25 877 – 24x2,5 25,0 925 10 150
25 684 – 27x1,5 22,5 690 8 90
25 675 – 37x1,5 24,5 910 7 100
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
6
0,6/1kV CABLES

LKM-HF FLEX Unarmoured power cable


with flexible conductor
0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 5
2. Insulation Flame-
retardant
- XLPE plastic IEC 60092-351
Fire-
3. Bedding resistant
- separator tape
Halogen-
4. Sheath free
- polyolefine plastic, SHF1 IEC 60092-359
3/2008

Low
- standard colour black, other colours on request smoke
emission

Application: For fixed installation in most areas and on open deck in ships.

Note! This cable is not designed for movable or portable applications.


Flexible conductor cables ease the installation in areas involving
tight bending radius or high vibration.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
For details see general information section

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


7

0,6/1kV CABLES
LKM-HF FLEX 0,6/1kV Number of Nominal Min. bending
conductors & outer Approximate Current radius fixed
Part number cross-section diameter weight kg/km rating A installation
Normal G-type n x mm2 mm mm
25 647 – 1x16 9,0 185 94 40
25 649 – 1x25 12,0 290 123 50
25 651 – 1x35 13,0 385 153 55
25 653 – 1x50 16,0 535 196 65
25 655 – 1x70 17,5 745 240 70
25 657 – 1x95 20,0 965 284 80
25 659 – 1x120 22,5 1215 331 90
25 661 – 1x150 25,5 1530 381 155
25 663 – 1x185 29,0 1865 429 175
25 665 – 1x240 33,0 2475 507 200
26 047 – 1x300 35,5 3030 582 215
26 054 – 2x16 17,0 405 80 70
26 055 – 2x25 22,5 615 105 90
26 056 – 2x35 24,5 840 130 100
26 071 26 072 3x16 19,0 555 66 80
26 073 26 074 3x25 24,0 855 86 100
26 075 26 076 3x35 26,0 1170 107 160

3/2008
26 077 26 078 3x50 31,0 1650 137 190
26 079 26 080 3x70 36,0 2300 168 220
26 081 26 082 3x95 43,0 3010 199 260
26 083 26 085 3x120 47,5 3815 232 285
26 084 26 086 3x150 54,0 4760 267 325
26 101 26 102 4x16 20,0 725 66 80
26 103 26 104 4x25 26,5 1125 86 160
26 105 26 106 4x35 29,5 1530 107 180
26 107 26 108 4x50 35,0 2170 137 210
26 109 26 110 4x70 40,5 3010 168 245
26 111 26 112 4x95 47,0 3990 199 285
26 113 26 114 4x120 52,5 4995 232 315
26 131 26 132 5x16 22,5 900 55 90
26 133 26 134 5x25 28,5 1425 71 175

G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
8
0,6/1kV CABLES

LKSM-HF Armoured power and control cable


0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- XLPE plastic IEC 60092-351 Flame-
retardant
3. Bedding Fire-
- filler tape resistant
4. Armour Halogen-
- copper wire braid, coverage > 90% IEC 60092-350 free
5. Sheath
3/2008

Low
- polyolefine plastic, SHF1 IEC 60092-359 smoke
- standard colour black, other colours on request emission

Application: For fixed installation in most areas and on open deck in ships.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


9

0,6/1kV CABLES
LKSM-HF 0,6/1kV Number of Cross- Nominal Min. bending
conductors & section of outer Approximate Current radius fixed
Part number cross-section screen diameter weight kg/km rating A installation
Normal G-type n x mm2 mm2 mm mm
25 742 – 1x6 3,1 7,5 130 52 30
25 744 – 1x10 3,5 9,0 185 72 40
25 746 – 1x16 4,1 10,0 255 96 40
25 748 – 1x25 4,9 13,0 380 127 55
25 750 – 1x35 5,5 14,0 495 157 60
25 752 – 1x50 8,7 16,0 665 196 65
25 754 – 1x70 9,9 18,5 915 242 75
25 756 – 1x95 11,8 20,5 1180 293 85
25 758 – 1x120 12,3 22,5 1455 339 90
25 760 – 1x150 13,7 25,0 1775 389 150
25 762 – 1x185 15,1 27,5 2180 444 165
25 764 – 1x240 17,0 31,0 2815 522 190
25 766 – 1x300 18,7 33,5 3465 601 205
25 770 – 2x1,5 3,8 10,0 130 20 40
25 785 – 2x2,5 4,3 11,0 160 26 45
25 801 – 2x4 4,9 12,0 205 34 50
25 803 – 2x6 5,4 13,5 260 44 55
25 805 – 2x10 8,7 16,0 400 61 65
25 807 – 2x16 10,0 18,0 555 82 75
25 809 – 2x25 12,3 22,5 835 108 90
25 811 – 2x35 14,0 25,5 1075 133 155
25 772 25 773 3x1,5 4,1 10,5 155 16 45
25 786 25 787 3x2,5 4,6 11,5 195 21 50
25 802 25 880 3x4 5,2 13,0 260 28 55

3/2008
25 804 25 882 3x6 5,8 13,5 335 36 55
25 806 25 884 3x10 9,3 17,0 515 50 70
25 808 25 886 3x16 10,7 19,5 735 67 80
25 810 25 888 3x25 13,2 24,0 1110 89 100
25 812 25 890 3x35 15,1 26,5 1450 110 160
25 814 25 892 3x50 17,5 31,0 1915 137 190
25 816 25 894 3x70 20,1 36,0 2670 169 220
25 818 25 896 3x95 22,7 40,0 3475 205 240
25 820 25 897 3x120 35,0 44,5 4425 237 270
25 822 25 898 3x150 39,1 50,0 5410 272 300
25 774 25 775 4x1,5 4,5 11,5 185 16 50
25 788 25 789 4x2,5 5,0 12,0 245 21 50
25 830 25 831 4x4 5,8 14,0 315 28 60
25 832 25 833 4x6 8,8 16,0 445 36 65
25 834 25 835 4x10 10,3 18,5 650 50 75
25 836 25 837 4x16 11,9 21,0 945 67 85
25 838 25 839 4x25 14,7 26,5 1415 89 160
25 840 25 841 4x35 16,7 29,5 1860 110 180
25 842 25 843 4x50 19,4 34,0 2460 137 205
25 844 25 845 4x70 22,4 39,5 3455 169 240
26 005 26 006 4x95 35,0 44,5 4645 205 270
26 007 26 008 4x120 39,1 49,5 5750 237 300
25 776 25 777 5x1,5 5,0 12,0 220 14 50
25 790 25 791 5x2,5 5,6 13,0 285 18 55
26 011 26 012 5x4 8,6 15,0 410 25 60
26 013 26 014 5x6 9,7 16,5 535 30 70
26 015 26 016 5x10 11,8 19,5 795 44 80
26 017 26 018 5x16 13,2 23,5 1150 56 95
25 778 – 7x1,5 5,4 12,5 265 12 50
25 792 – 7x2,5 11,4 14,5 405 16 60
26 025 – 10x1,5 9,6 16,0 395 11 65
26 033 – 10x2,5 11,7 18,0 540 14 75
25 780 – 12x1,5 9,9 17,0 440 10 70
25 794 – 12x2,5 11,8 19,5 595 13 80
26 027 – 14x1,5 10,5 17,5 495 10 70
26 035 – 14x2,5 11,9 20,0 680 13 80
26 030 – 16x1,5 11,8 18,5 550 9 75
26 037 – 16x2,5 12,5 21,0 760 12 85
25 782 – 19x1,5 11,8 20,0 610 9 80
25 796 – 19x2,5 13,2 22,0 855 11 90
25 828 – 24x1,5 13,9 23,5 790 8 95
25 798 – 24x2,5 15,7 26,0 1100 10 160
25 783 – 27x1,5 14,1 23,5 845 8 95
25 784 – 37x1,5 16,0 26,5 1085 7 160
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
10
0,6/1kV CABLES

LKSM-HF FLEX Armoured power cable


with flexible conductor
0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 5
2. Insulation
- XLPE plastic IEC 60092-351 Flame-
retardant
3. Bedding Fire-
- filler tape resistant
4. Armour Halogen-
- copper wire braid, coverage > 90% IEC 60092-350 free
5. Sheath Low
3/2008

- polyolefine plastic, SHF1 IEC 60092-359 smoke


- standard colour black, other colours on request emission

Application: For fixed installation in most areas and on open deck in ships.

Note! This cable is not designed for movable or portable applications.


Flexible conductor cables ease the installation in areas involving
tight bending radius or high vibration.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
For details see general information section

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


11

0,6/1kV CABLES
LKSM-HF FLEX 0,6/1kV Number of Cross- Nominal Min. bending
conductors & section of outer Approximate Current radius fixed
Part number cross-section screen diameter weight kg/km rating A installation
Normal G-type n x mm2 mm2 mm mm
26 237 – 1x16 4,1 10,0 240 94 40
26 238 – 1x25 4,9 13,5 360 123 55
26 239 – 1x35 5,5 14,5 460 153 60
26 240 – 1x50 8,7 16,5 650 196 70
26 241 – 1x70 9,9 18,5 870 240 75
26 242 – 1x95 11,8 21,0 1115 284 85
26 243 - 1x120 12,3 24,0 1385 331 100
26 244 – 1x150 13,7 27,0 1715 381 165
26 245 – 1x185 15,1 29,5 2065 429 180
26 246 – 1x240 17,0 33,0 2705 507 200
26 247 – 1x300 18,7 35,0 3300 582 210
26 254 – 2x16 10,0 17,5 520 80 70
26 255 – 2x25 12,3 22,5 780 105 90
26 256 – 2x35 14,0 25,0 1010 130 150
26 271 26 272 3x16 10,7 19,5 680 66 80
26 273 26 274 3x25 13,2 24,0 1030 86 100
26 275 26 276 3x35 15,1 26,5 1350 107 160

3/2008
26 277 26 278 3x50 17,5 32,5 1875 135 195
26 279 26 280 3x70 20,1 36,0 2545 168 220
26 281 26 282 3x95 22,7 41,5 3295 199 250
26 283 26 284 3x120 35,0 47,5 4225 232 285
26 285 26 286 3x150 39,1 53,5 5250 267 325
26 301 26 302 4x16 11,9 21,5 875 66 90
26 303 26 304 4x25 14,7 26,5 1315 86 160
26 305 26 306 4x35 16,7 30,0 1730 107 180
26 307 26 308 4x50 19,4 35,0 2410 137 210
26 309 26 310 4x70 22,4 40,5 3290 168 245
26 311 26 312 4x95 35,0 47,5 4405 199 285
26 313 26 314 4x120 39,1 52,5 5490 232 315
26 331 26 332 5x16 13,2 23,5 1065 55 95
26 333 26 334 5x25 16,3 29,0 1635 71 175
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
12

LKSM-EMC
0,6/1kV CABLES

Armoured power and control cable with improved EMC screening 0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor 2
-stranded copper conductor 1,5-10mm 2 IEC 60228, class 2
-stranded copper conductor 16-240mm IEC 60228, class 5
2. Insulation Flame-
- XLPE plastic IEC 60092-351 retardant
Fire-
3. Bedding resistant
- filler tape - copper tape, coverage 100%
Halogen-
4. Armour free
- copper wire braid, coverage > 90% IEC 60092-350
3/2008

Low
5. Sheath smoke
- polyolefine plastic, SHF1 IEC 60092-359 emission
- standard colour black, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
Design to meet requirements for improved EMC screening properties.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)

Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
Transfer impedance IEC 61196-1 (typical value 26dB over 1mΩ/m
at 100MHz [20mΩ/m])
For details see general information section

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: See technical information section.


Cable with yellow/green protective earth (PE)
conductor on request

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


13

0,6/1kV CABLES
LKSM-EMC 0,6/1kV Number of Cross- Nominal Approx- Min. bending
conductors & section of outer imate Current radius fixed
cross-section screen diameter weight rating A installation
Part number n x mm2 mm2 mm kg/km mm
26 861 3x1,5 3,8 10,5 155 16 65
26 863 3x2,5 4,3 11,5 195 21 70
26 865 3x4 5,0 12,5 260 28 75
26 867 3x6 5,6 14,0 335 36 85
26 869 3x10 8,9 23,5 680 50 145
26 871 3x16 10,4 26,0 695 66 160
26 873 3x25 12,9 29,0 1000 86 175
26 875 3x35 14,7 31,5 1310 107 190
26 877 3x50 17,1 35,5 1825 137 215
26 879 3x70 27,3 39,0 2565 168 235
26 881 3x95 22,4 44,0 3185 199 265
26 883 3x120 34,7 48,0 4090 232 290
26 885 3x150 38,8 51,5 5055 267 310
26 942 4x1,5 3,8 10,5 155 16 265
26 944 4x2,5 4,3 11,5 195 21 290
26 946 4x4 5,0 13,0 265 28 310
26 948 4x6 5,6 14,0 340 36 340

3/2008
26 950 4x10 8,9 16,5 510 50 375
26 952 4x16 10,4 19,0 695 66 115
26 954 4x25 12,9 24,0 1000 86 145
26 956 4x35 14,7 26,5 1310 107 160
26 958 4x50 17,1 31,5 1825 137 190
26 960 4x70 27,3 36,0 2565 168 215
26 962 4x95 22,4 41,5 3185 199 250
26 964 4x120 34,7 46,5 4090 232 280
14

LKSM-VFD
1,8/3kV CABLES

Armoured power and control cable with improved EMC screening 1,8/3kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 5
2. Insulation
- XLPE plastic IEC 60092-351 Flame-
retardant
3. Bedding Fire-
- filler tape - copper tape, coverage 100% resistant
4. Armour Halogen-
- copper wire braid, coverage > 90% IEC 60092-350 free
5. Sheath
3/2008

Low
- polyolefine plastic, SHF1 IEC 60092-359 smoke
- standard colour black, other colours on request emission

Application: For fixed installation in most areas and on open deck in ships.
Design to meet requirements for Variable Frequency Drivers (VFD).
Suitable for voltage peaks to 3kV (for cables ≥ 10mm2).

Main characteristics
Rated voltage 1,8/3kV (3,6kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
Transfer impedance IEC 61196-1 (typical value 26dB over 1mΩ/m
at 100MHz [20mΩ/m])
For details see general information section

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: See technical information section.


Cable with yellow/green protective earth (PE)
conductor on request

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


15

1,8/3kV CABLES
LKSM-VFD 1,8/3kV Number of Cross- Nominal Approx- Min. bending
conductors & section of outer imate Current radius fixed Note
cross-section screen diameter weight rating A installation
Part number n x mm2 mm2 mm kg/km mm
26 920 1x16 5,2 13,5 340 96 85 1)
26 922 1x25 5,8 15,0 455 127 90 1)
26 924 1x35 11,5 16,5 625 157 100 1)
26 926 1x50 9,8 18,0 740 196 110 1)
26 928 1x70 10,9 20,0 990 242 120 1)
26 930 1x95 12,1 22,0 1275 293 135 1)
26 932 1x120 13,2 23,5 1535 339 145 1)
26 934 1x150 14,3 25,5 1830 389 155 1)
26 936 1x185 15,4 27,5 2210 444 165 1)
26 938 1x240 17,1 30,0 2830 522 180 1)
26 940 1x300 18,6 33,0 3470 601 200 1)
26 869 3x10 13,3 23,5 680 50 145 1)
26 871 3x16 16,1 26,0 915 67 160 1)
26 873 3x25 16,5 29,0 1215 89 175
26 875 3x35 18,2 31,5 1570 110 190
26 877 3x50 25,1 35,5 2040 137 215
26 879 3x70 35,0 39,0 2820 169 235

3/2008
26 881 3x95 35,0 44,0 3645 205 265 1)
26 883 3x120 38,1 48,0 4465 237 290 1)
26 885 3x150 41,2 51,5 5335 272 310 1)
26 887 3x185 44,7 56,0 6545 311 340 1)
26 889 3x240 49,8 62,0 8445 365 375 1)
26 893 3x95+3x16 35,0 44,0 4565 205 265 2)
26 895 3x120+3x25 38,1 48,0 5190 237 290 2)
26 897 3x150+3x25 41,2 51,5 6055 272 310 2)

NOTE!
1) = Protective earth (PE) rules are not fulfilled.
(PE rules, for cables over 16mm2 the PE-conductor have to be half of main conductor
and min. 16mm2. This according to IEC 60092-352, Electrical installations
in ships –Choice and installation of electrical cables)

2 = Three additional protective earth (PE) conductors.


Protective earth (PE) rules are fulfilled.
16
0,6/1kV CABLES

LKAM-HF Screened power and control cable


0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 2

2. Insulation Flame-
- XLPE plastic IEC 60092-351 retardant
Fire-
3. Screen resistant
- drain wire of tinned copper 1,5mm2 (in all sizes) Halogen-
- aluminium polyester tape, IEC 60092-350 free
coverage 100%
Low
3/2008

4. Sheath smoke
- polyolefine plastic, SHF1 IEC 60092-359 emission
- standard colour black, other colours on request

Application: For fixed installation in most areas and on open deck in ships,
especially when lightweight cables are needed.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


17

0,6/1kV CABLES
LKAM-HF 0,6/1kV Number of Nominal Min. bending
conductors & outer Approximate Current radius fixed
Part number cross-section diameter weight kg/km rating A installation
Normal G-type n x mm2 mm mm
27 102 – 2x1,5 8,0 100 20 35
27 104 – 2x2,5 10,0 130 26 40
27 106 27 107 3x1,5 8,5 120 16 35
27 108 27 109 3x2,5 10,0 165 21 40
27 110 27 111 4x1,5 10,5 150 16 45
27 112 27 113 4x2,5 11,5 200 21 50
27 114 27 115 5x1,5 10,5 180 14 45
27 116 27 117 5x2,5 12,0 245 18 50
27 118 – 7x1,5 11,5 220 12 50
27 120 – 7x2,5 13,0 305 16 55
27 140 – 10x1,5 15,0 310 11 60
27 142 – 10x2,5 17,5 430 14 70
27 122 – 12x1,5 15,5 355 10 65
27 124 – 12x2,5 18,0 490 13 75
27 126 – 19x1,5 18,0 515 9 75
27 128 – 19x2,5 21,0 725 11 85
27 134 – 27x1,5 22,0 715 8 90

3/2008
27 138 – 27x2,5 25,0 1030 10 150
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
18
0,6/1kV CABLES

LKEM-HF Switchboard wire


0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design

1. Conductor
- stranded flexible IEC 60228, Flame-
copper conductor class 5 retardant
Fire-
resistant
2. Insulation
Halogen-
- HF90 plastic IEC 60092-351 free
3/2008

- standard colour black, other colours on request


Low
smoke
emission

Application: For fixed wiring in switchboards, control panels and other enclosures.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Identification: Cable type, cable size, voltage and manufacturer's name

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


19

0,6/1kV CABLES
LKEM-HF 0,6/1kV Number of Nominal Min. bending
conductors & outer Approximate Current radius fixed
Part number cross-section diameter weight kg/km rating A installation
n x mm2 mm mm
25 120 1x0,75 2,7 14 14 15
25 121 1x1,0 2,8 17 17 15
25 122 1x1,5 3,1 21 22 15
25 124 1x2,5 3,6 32 29 15
25 125 1x4 4,1 45 37 20
25 126 1x6 4,7 63 49 20
25 128 1x10 5,7 103 69 25
25 130 1x16 6,7 154 91 30
25 132 1x25 8,6 244 118 35
25 134 1x35 9,7 334 148 40
25 136 1x50 11,9 476 196 50
25 138 1x70 13,7 671 238 55
25 165 1x95 16,2 887 275 65
25 166 1x120 18,2 1125 322 75

3/2008
20
0,6/1kV CABLES

LKM-FRHF Fire-resistant unarmoured power


and control cable 0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 2

2. Insulation
Flame-
- Mica tape retardant
- XLPE plastic IEC 60092-351
Fire-
3. Bedding resistant
- separator tape Halogen-
free
4. Sheath Low
3/2008

- polyolefine plastic, SHF1 IEC 60092-359 smoke


- standard colour orange, other colours on request emission

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Fire-resistant IEC 60331-21 series
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


21

0,6/1kV CABLES
LKM-FRHF 0,6/1kV Number of Nominal Min. bending
conductors & outer Approximate Current radius fixed
Part number cross-section diameter weight kg/km rating A installation
Normal G-type n x mm2 mm mm
28 132 – 2x1,5 9,5 85 20 40
28 134 – 2x2,5 10,0 110 26 40
28 136 – 2x4 12,0 165 34 50
28 138 – 2x6 13,0 225 44 55
28 140 – 2x10 15,0 330 61 60
28 142 – 2x16 17,5 480 82 70
28 162 28 163 3x1,5 10,0 105 16 40
28 164 28 165 3x2,5 11,0 140 21 45
28 166 28 167 3x4 11,5 205 28 50
28 168 28 169 3x6 13,0 275 36 55
28 170 28 171 3x10 16,0 415 50 65
28 172 28 173 3x16 18,5 605 67 75
28 174 28 175 3x25 21,5 1000 89 90
28 176 28 177 3x35 24,5 1360 110 100
28 178 28 179 3x50 29,0 1785 137 175
28 180 28 181 3x70 33,0 2545 169 200
28 202 28 203 3x95 37,5 3340 205 225

3/2008
28 182 28 183 4x1,5 11,0 130 16 45
28 184 28 185 4x2,5 11,5 185 21 50
28 186 28 187 4x4 13,5 260 28 55
28 188 28 189 4x6 15,0 350 36 60
28 190 28 191 4x10 17,0 535 50 70
28 192 28 193 4x16 20,5 790 67 85
28 194 28 195 4x25 24,0 1300 89 100
28 196 28 197 4x35 27,5 1765 110 165
28 198 28 199 4x50 31,5 2320 137 190
28 212 28 213 5x1,5 11,5 165 14 50
28 214 28 215 5x2,5 13,0 225 18 55
28 216 – 7x1,5 13,0 210 12 55
28 218 – 7x2,5 14,5 285 16 60
28 220 – 12x1,5 16,5 345 10 70
28 222 – 12x2,5 18,5 485 13 75
28 224 – 19x1,5 19,5 510 9 80
28 226 – 19x2,5 22,0 730 11 90
28 232 – 27x1,5 24,0 725 8 100
28 234 – 37x1,5 27,0 965 7 165
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
22
0,6/1kV CABLES

LKSM-FRHF Fire-resistant armoured power


and control cable 0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- Mica tape
- XLPE plastic EC 60092-351 Flame-
retardant
3. Bedding
Fire-
- separator tape resistant
4. Armour Halogen-
- copper wire braid, coverage > 90% IEC 60092-350 free
Low
3/2008

5. Sheath
- polyolefine plastic, SHF1 IEC 60092-359 smoke
emission
- standard colour orange, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Fire-resistant IEC 60331-21 series
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


23

0,6/1kV CABLES
LKSM-FRHF 0,6/1kV Number of Cross- Nominal Min. bending
conductors & section of outer Approximate Current radius fixed
Part number cross-section screen diameter weight kg/km rating A installation
Normal G-type n x mm2 mm2 mm mm
28 576 – 1x10 3,4 10,0 195 72 60
28 578 – 1x16 3,9 11,0 270 96 70
28 580 – 1x25 4,7 13,0 390 127 80
28 582 – 1x35 5,4 14,0 495 157 85
28 584 – 1x50 8,6 16,5 670 196 100
28 586 – 1x70 9,8 18,5 915 242 115
28 588 – 1x95 11,0 20,5 1180 293 125
28 590 – 1x120 12,2 22,5 1465 339 135
28 592 – 1x150 13,5 25,0 1770 389 150
28 594 – 1x185 14,9 28,0 2190 444 170
28 596 – 1x240 16,8 30,5 2820 522 185
28 598 – 1x300 18,5 34,0 3475 601 205
28 602 – 2x1,5 4,0 11,0 145 20 70
28 604 – 2x2,5 4,4 11,5 175 26 70
28 606 – 2x4 5,0 13,0 225 34 80
28 608 – 2x6 5,6 14,0 280 44 85
28 610 – 2x10 8,8 16,5 415 61 100

3/2008
28 612 – 2x16 10,2 19,0 580 82 115
28 622 28 623 3x1,5 4,3 11,0 175 16 70
28 624 28 625 3x2,5 4,8 12,5 215 21 75
28 626 28 627 3x4 5,3 13,5 275 28 85
28 628 28 629 3x6 8,6 15,0 385 36 90
28 630 28 631 3x10 9,5 17,5 530 50 105
28 632 28 633 3x16 11,0 20,0 765 67 120
28 634 28 635 3x25 13,9 25,0 1155 89 150
28 636 28 637 3x35 15,7 28,0 1495 110 170
28 638 28 639 3x50 18,1 32,0 1955 137 195
28 640 28 641 3x70 20,9 37,0 2705 169 225
28 691 28 692 3x95 32,2 42,0 3630 205 255
28 693 – 3x120 35,9 46,0 4460 237 280
28 642 28 643 4x1,5 4,7 12,5 205 16 75
28 644 28 645 4x2,5 5,3 13,5 260 21 85
28 646 28 647 4x4 8,6 15,5 370 28 95
28 648 28 649 4x6 9,1 16,5 470 36 100
28 650 28 651 4x10 10,6 19,5 675 50 120
28 652 28 653 4x16 12,2 22,5 980 67 135
28 654 28 655 4x25 15,5 27,5 1455 89 165
28 656 28 657 4x35 17,5 30,5 1895 110 185
28 658 28 659 4x50 20,2 35,5 2505 137 215
28 662 28 663 5x1,5 5,2 13,5 245 14 85
28 664 28 665 5x2,5 5,8 14,5 315 18 90
28 666 – 7x1,5 5,8 14,5 295 12 90
28 668 – 7x2,5 8,8 16,5 415 16 100
28 670 – 12x1,5 10,7 19,0 495 10 115
28 672 – 12x2,5 12,0 21,5 665 13 130
28 674 – 19x1,5 12,8 22,5 665 9 135
28 676 – 19x2,5 14,4 25,0 895 11 150
28 682 – 27x1,5 15,6 27,0 900 8 165
28 686 – 27x2,5 17,5 30,0 1335 10 180
28 684 – 37x1,5 17,7 30,0 1160 7 180
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
24
0,6/1kV CABLES

LKAM-FRHF Fire-resistant screened power


and control cable 0,6/1kV

DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- Mica tape IEC 60092-351 Flame-
- XLPE plastic retardant
Fire-
3. Screen resistant
- drain wire of tinned copper 1,5mm2 (in all sizes)
- aluminium polyester tape, IEC 60092-350 Halogen-
coverage 100% free
Low
3/2008

4. Sheath smoke
- polyolefine plastic, SHF1 IEC 60092-359 emission
- standard colour orange, other colours on request

Application: For fixed installation in most areas and on open deck in ships,
especially when lightweight cables are needed.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 0,6/1kV (1,2kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Fire-resistant IEC 60331-21 series
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: see technical information section

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


25

0,6/1kV CABLES
LKAM-FRHF 0,6/1kV Number of Nominal Min. bending
conductors & outer Approximate Current radius fixed
Part number cross-section diameter weight kg/km rating A installation
Normal G-type n x mm2 mm mm
28 741 – 2x1,5 10 120 20 60
28 742 – 2x2,5 11 145 26 70
28 743 28 744 3x1,5 10 140 16 60
28 745 28 746 3x2,5 11 180 21 70
28 747 28 748 4x1,5 11,5 170 16 70
28 749 28 750 4x2,5 12 225 21 75
28 751 28 752 5x1,5 12 210 14 75
28 753 28 754 5x2,5 14 270 18 85
28 755 – 7x1,5 13 255 12 80
28 757 – 7x2,5 15 340 16 90
28 759 – 10x1,5 17,5 355 11 105
28 761 – 10x2,5 19,5 485 14 120
28 763 – 12x1,5 18 405 10 110
28 765 – 12x2,5 20 555 13 120
28 775 – 19x1,5 28,5 1085 9 175
28 777 – 19x2,5 29 1015 11 175
28 783 – 27x1,5 30,5 805 8 185

3/2008
28 785 – 27x2,5 31 735 10 190

G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
26
250V CABLES

LKSM-HF Armoured control and


instrumentation cable
250 V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation Flame-
- XLPE plastic IEC 60092-351 retardant
3. Bedding Fire-
- separator tape resistant
4. Armour Halogen-
- copper wire braid, coverage > 90% IEC 60092-350 free
Low
3/2008

5. Sheath smoke
- polyolefine plastic, SHF1 IEC 60092-359 emission
- standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Core identification: black numbers on white base

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


27

250V CABLES
LKSM-HF 250V Number of Cross- Nominal Min. bending
conductors & section of outer Approximate Current radius fixed
cross-section screen diameter weight kg/km rating A installation
Part number n x mm2 mm2 mm mm
26 402 2x0,75 3,6 7,5 90 11,3 45
26 403 3x0,75 3,6 8,0 105 9,8 50
26 404 4x0,75 3,6 9,0 125 8,9 55
26 405 5x0,75 4,1 9,5 145 8,3 60
26 407 7x0,75 4,1 10,0 165 7,4 60
26 410 10x0,75 5,1 12,5 220 6,6 75
26 412 12x0,75 5,3 12,5 245 6,2 75
26 414 14x0,75 5,6 13,0 270 5,9 80
26 416 16x0,75 11,4 14,5 355 5,6 90
26 419 19x0,75 8,7 15,0 360 5,3 90
26 424 24x0,75 11,7 17,0 460 4,9 105
26 427 27x0,75 11,7 17,5 490 4,7 105
26 432 32x0,75 11,8 18,0 545 4,5 110
26 437 37x0,75 11,9 20,0 620 4,3 120

3/2008
28
250V CABLES

RFE-HF Armoured instrumentation and


communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation Flame-
- XLPE plastic IEC 60092-351 retardant
3. Bedding Fire-
- filler tape resistant
4. Armour Halogen-
- drain wire copper (in all sizes) free
- copper wire braid, coverage > 94% IEC 60092-350 Low
3/2008

5. Sheath smoke
- polyolefine plastic, SHF1 IEC 60092-359 emission
- standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Electrical data: 0,5mm2 0,75mm2 1,5mm2 Unit


Loop resistance of pair, max. / +20°C 80 52 24,4 ohm/km
Pair capacitance, nom. / 800Hz 55 50 60 nF/km
Loop inductance, nom. 0,6 0,6 0,7 mH/km
Insulation resistance / +20°C ≥1500 ≥1500 ≥1500 Mohm*km.

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


29

250V CABLES
RFE-HF 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
20 362 1x2x0,5 7,5 80 45
20 364 2x2x0,5 (Quad) 8,0 100 45
20 366 4x2x0,5 12,0 170 75
20 368 7x2x0,5 13,5 245 85
20 369 8x2x0,5 15,0 265 90
20 370 10x2x0,5 16,5 350 100
20 371 12x2x0,5 17,0 390 105
20 372 14x2x0,5 19,0 440 115
20 374 19x2x0,5 21,5 545 130
20 376 24x2x0,5 24,0 665 145
20 378 37x2x0,5 28,5 930 175
20 382 1x2x0,75 8,0 95 50
20 384 2x2x0,75 (Quad) 8,5 125 55
20 386 4x2x0,75 13,0 215 80
20 388 7x2x0,75 15,0 330 90
20 389 8x2x0,75 16,5 375 100
20 390 10x2x0,75 18,0 440 110

3/2008
20 391 12x2x0,75 19,5 490 120
20 392 14x2x0,75 21,0 565 130
20 394 19x2x0,75 23,0 715 140
20 396 24x2x0,75 25,5 860 155
20 490 1x2x1,5 10,0 135 60
20 491 2x2x1,5 (Quad) 11,5 190 70
20 493 4x2x1,5 16,5 375 100
20 494 7x2x1,5 19,5 545 120
20 495 8x2x1,5 22,0 625 135
20 496 10x2x1,5 24,5 760 150
20 497 12x2x1,5 26,0 855 160
20 498 14x2x1,5 27,5 960 165
20 499 19x2x1,5 31,5 1230 190

Twisted two pair cable on request.


20 363 2x2x0,5
20 383 2x2x0,75
20 492 2x2x1,5

Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....


(Quad)cable is built up as a star quad
with the following identification
1 core white
2 core blue
3 core white
4 core blue
30
250V CABLES

Armoured and pair screened


RFE-HF (i) instrumentation and
communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- XLPE plastic IEC 60092-351
3. Pair screen Flame-
- plastic coated aluminium tape retardant
and a tinned copper drain wire
Fire-
4. Bedding resistant
- filler tape
Halogen-
5. Armour free
- drain wire copper (in all sizes)
3/2008

- copper wire braid, coverage > 94% IEC 60092-350 Low


smoke
6. Sheath emission
- polyolefine plastic, SHF1 IEC 60092-359
- standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

0,75mm2 1,5mm2 Unit


Electrical data:
Loop resistance of pair, max. / +20°C 52 24,4 ohm/km
Pair capacitance, nom. / 800Hz 70 90 nF/km
Loop inductance, nom. 0,6 0,7 mH/km
Insulation resistance / +20°C ≥1500 ≥1500 Mohm*km.
Minimum recommended installation temperature -15 °C
Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


31

250V CABLES
RFE-HF(i) 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
22 010 2x2x0,75 11,0 170 70
22 012 4x2x0,75 12,5 240 75
22 014 7x2x0,75 16,0 375 100
22 016 8x2x0,75 17,0 420 105
22 018 10x2x0,75 19,0 520 115
22 020 12x2x0,75 19,5 585 120
22 022 14x2x0,75 21,0 650 130
22 024 19x2x0,75 23,5 835 145
22 026 24x2x0,75 26,5 1035 160
22 054 2x2x1,5 14,0 255 85
22 056 4x2x1,5 17,0 415 105
22 058 7x2x1,5 20,5 610 125
22 060 8x2x1,5 21,5 700 130
22 062 10x2x1,5 24,5 855 150
22 064 12x2x1,5 25,5 965 155
22 066 14x2x1,5 27,5 1105 165
22 068 19x2x1,5 31,5 1440 190

Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....

3/2008
The pairs are also covered by a numbered tape (1, 2, 3, 4, 5....)
32
250V CABLES

RFA-HF Screened instrumentation


and communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- XLPE plastic IEC 60092-351 Flame-
3. Separator retardant
- separator tape Fire-
resistant
4. Screen
- drain wire tinned copper Halogen-
- aluminium polyestercopper tape IEC 60092-350 free
coverage 100% Low
3/2008

5. Sheath smoke
- polyolefine plastic, SHF1 IEC 60092-359 emission
- standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships, especially
when lightweight cables are needed. If the cable is exposed to direct
sun light protective covering or cable with black outer sheath is
recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Electrical data 0,5mm2 0,75mm2 Unit


Loop resistance of pair, max. / +20°C 80 52 ohm/km
Pair capacitance, nom. / 800Hz 55 50 nF/km
Loop inductance, nom. 0,6 0,6 mH/km
Insulation resistance / +20°C ≥1500 ≥1500 Mohm*km.
Minimum recommended installation temperature -15 °C
Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


33

250V CABLES
RFA-HF 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
20 910 1x2x0,5 6,5 45 40
20 912 2x2x0,5 (Quad) 7,0 65 45
20 916 4x2x0,5 11,0 120 70
20 918 7x2x0,5 13,0 175 80
20 920 8x2x0,5 14,0 200 85
20 922 10x2x0,5 16,0 245 100
20 924 12x2x0,5 16,5 280 100
20 926 14x2x0,5 17,0 315 105
20 930 19x2x0,5 19,5 410 120
20 932 24x2x0,5 22,5 515 135
20 936 37x2x0,5 26,5 745 160
20 970 1x2x0,75 7,0 55 45
20 972 2x2x0,75 (Quad) 8,5 80 55
20 976 4x2x0,75 12,0 150 75
20 978 7x2x0,75 13,5 225 85
20 980 8x2x0,75 14,5 260 90
20 982 10x2x0,75 17,5 320 105

3/2008
20 984 12x2x0,75 17,5 365 105
20 986 14x2x0,75 19,0 415 115
20 990 19x2x0,75 21,5 555 130
20 992 24x2x0,75 24,0 680 145

Twisted two pair cable on request.


20 914 2x2x0,5
20 974 2x2x0,75

Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....


(Quad)cable is built up as a star quad
with the following identification
1 core white
2 core blue
3 core white
4 core blue
34
250V CABLES

Collectively and pair screened


RFA-HF (i) instrumentation and
communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- XLPE plastic IEC 60092-351
3. Pair screen
- plastic coated aluminium tape Flame-
and a tinned copper drain wire retardant
4. Bedding Fire-
- separator tape resistant
5. Collective screen Halogen-
- drain wire tinned copper IEC 60092-350 free
- aluminium polyester tape, Low
3/2008

coverage 100% smoke


6. Sheath emission
- polyolefine plastic, SHF1 IEC 60092-359
- standard colour grey, other colours on request

Application: For fixed installation in most areas and on open deck in ships, especially
when lightweight cables are needed. If the cable is exposed to direct
sun light protective covering or cable with black outer sheath is
recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Electrical data 0,5mm2 0,75mm2 Unit


Loop resistance of pair, max. / +20°C 80 52 ohm/km
Pair capacitance, nom. 55 70 nF/km
Loop inductance, nom. 0,6 0,6 mH/km
Insulation resistance / +20°C ≥1500 ≥1500 Mohm*km

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


35

250V CABLES
RFA-HF(i) 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
20 940 2x2x0,5 9,0 95 55
20 942 4x2x0,5 10,5 145 65
20 944 7x2x0,5 13,5 220 85
20 946 8x2x0,5 13,5 245 85
20 948 10x2x0,5 15,5 305 95
20 950 12x2x0,5 17,0 350 105
20 952 14x2x0,5 18,0 395 110
20 956 19x2x0,5 20,5 520 125
20 958 24x2x0,5 23,0 655 140
21 059 2x2x0,75 10,5 115 65
21 061 4x2x0,75 11,5 180 70
21 063 7x2x0,75 14,0 275 85
21 065 8x2x0,75 15,5 310 95
21 067 10x2x0,75 17,0 380 105
21 069 12x2x0,75 18,5 440 115
21 071 14x2x0,75 20,0 520 120
21 075 19x2x0,75 23,0 680 140

3/2008
21 077 24x2x0,75 25,5 840 155

Other sizes on request.

Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....


The pairs are covered by a numbered tape (1, 2, 3, 4, 5....)
36
250V CABLES

Fire-resistant armoured
RFE-FRHF instrumentation and
communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- Mica tape Flame-
- XLPE plastic IEC 60092-351 retardant
3. Bedding Fire-
- filler tape resistant
4. Armour Halogen-
- drain wire (in all sizes) free
- copper wire braid, coverage > 94% IEC 60092-350 Low
3/2008

5. Sheath smoke
emission
- polyolefine plastic, SHF1 IEC 60092-359
- standard colour orange, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Fire-resistant IEC 60331-21
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Electrical data 0,75mm2 1,5mm2 Unit


Loop resistance of pair, max. / +20°C 52 24,4 ohm/km
Pair capacitance, nom. / 800Hz 45 55 nF/km
Loop inductance, nom. 0,6 0,7 mH/km
Insulation resistance / +20°C ≥1500 ≥1500 Mohm*km.

Minimum recommended installation temperature -15 °C


Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


37

250V CABLES
RFE-FRHF 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
20 520 1x2x0,75 9,5 120 60
20 522 2x2x0,75 (Quad) 11,0 160 70
20 526 4x2x0,75 17,0 325 105
20 528 7x2x0,75 19,5 460 120
20 530 8x2x0,75 21,5 505 130
20 532 10x2x0,75 24,0 630 145
20 534 12x2x0,75 25,5 705 155
20 536 14x2x0,75 27,5 800 165
20 538 19x2x0,75 31,5 1015 190
20 540 24x2x0,75 35,5 1245 215
20 575 1x2x1,5 11,0 155 70
20 577 2x2x1,5 (Quad) 12,5 220 75
20 581 4x2x1,5 18,5 430 115
20 583 7x2x1,5 23,0 650 140
20 585 8x2x1,5 24,5 715 150
20 587 10x2x1,5 27,0 875 165
20 589 12x2x1,5 29,5 1000 180

3/2008
20 591 14x2x1,5 31,0 1125 190
20 595 19x2x1,5 35,5 1465 215

Twisted two pair cable on request.


20 524 2x2x0,75
20 579 2x2x1,5

Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....


(Quad)cable is built up as a star quad
with the following identification
1 core white
2 core blue
3 core white
4 core blue
38
250V CABLES

Fire-resistant armoured and


RFE-FRHF (i) pair screened instrumentation
and communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- Mica tape
- XLPE plastic IEC 60092-351 Flame-
3. Pair screen retardant
- plastic coated aluminium tape and a tinned copper drain wire
Fire-
4. Bedding resistant
- filler tape
Halogen-
5. Armour free
- drain wire copper
Low
3/2008

- copper wire braid, coverage > 94% IEC 60092-350


smoke
6. Sheath emission
- polyolefine plastic, SHF1 IEC 60092-359
- standard colour orange, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Fire-resistant IEC 60331-21
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Electrical data 0,75mm2 1,5mm2 Unit


Loop resistance of pair, max. / +20°C 52 24,4 ohm/km
Pair capacitance, nom. / 800Hz 55 75 nF/km
Loop inductance, nom. 0,6 0,7 mH/km
Insulation resistance / +20°C ≥1500 ≥1500 Mohm*km.
Minimum recommended installation temperature -15 °C
Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


39

250V CABLES
RFE-FRHF(i) 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
20 550 2x2x0,75 14,0 225 85
20 552 4x2x0,75 17,0 355 105
20 554 7x2x0,75 20,0 515 130
20 556 8x2x0,75 22,0 585 135
20 558 10x2x0,75 24,5 710 150
20 560 12x2x0,75 26,0 800 160
20 562 14x2x0,75 27,5 910 175
20 564 19x2x0,75 31,5 1175 195
20 566 24x2x0,75 35,0 1425 220
20 605 2x2x1,5 16,5 320 105
20 607 4x2x1,5 19,0 475 115
20 609 7x2x1,5 23,0 720 140
20 611 8x2x1,5 24,5 810 150
20 613 10x2x1,5 28,0 985 185
20 615 12x2x1,5 29,5 1145 195
20 617 14x2x1,5 31,5 1295 205
20 621 19x2x1,5 35,5 1665 235

3/2008
Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....


The pairs are also covered by a numbered tape (1, 2, 3, 4, 5....)
40
250V CABLES

Fire-resistant screened
RFA-FRHF instrumentation and
communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- Mica tape
- XLPE plastic IEC 60092-351 Flame-
3. Bedding retardant
- separator tape
Fire-
4. Screen resistant
- drain wire tinned copper
- aluminium polyester tape Halogen-
free
coverage 100% IEC 60092-350
Low
3/2008

5. Sheath
- polyolefine plastic, SHF1 IEC 60092-359 smoke
emission
- standard colour orange, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Fire-resistant IEC 60331-21
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
For details see general information section

Electrical data 0,75mm2 Unit


Loop resistance of pair, max. / +20°C 52 ohm/km
Pair capacitance, nom. / 800Hz 45 nF/km
Loop inductance, nom. 0,6 mH/km
Insulation resistance / +20°C ≥1500 Mohm*km.
Minimum recommended installation temperature -15 °C
Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


41

250V CABLES
RFA-FRHF 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
20 635 1x2x0,75 8,0 75 50
20 637 2x2x0,75 (Quad) 9,5 120 60
20 641 4x2x0,75 15,0 215 90
20 643 7x2x0,75 18,0 330 110
20 645 8x2x0,75 19,5 380 120
20 647 10x2x0,75 22,5 480 135
20 649 12x2x0,75 24,5 545 150
20 651 14x2x0,75 26,0 620 160
20 655 19x2x0,75 30,0 805 180
20 657 24x2x0,75 33,0 1030 200

Twisted two pair cable on request.


20 639 2x2x0,75

Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....

3/2008
(Quad)cable is built up as a star quad
with the following identification
1 core white
2 core blue
3 core white
4 core blue
42
250V CABLES

Fire-resistant collectively and


RFA-FRHF (i) pair screened instrumentation
and communication cable 250V

DESIGN: STANDARDS:
IEC 60092-376, design
1. Conductor
- stranded copper conductor IEC 60228, class 2
2. Insulation
- Mica tape
- XLPE plastic IEC 60092-351 Flame-
3. Pair screen retardant
- plastic coated aluminium tape and a tinned copper drain wire
Fire-
4. Bedding resistant
- separator tape
Halogen-
5. Collective screen free
- drain wire tinned copper
Low
3/2008

- aluminium polyester tape coverage 100 % IEC 60092-350


smoke
6. Sheath emission
- polyolefine plastic, SHF1 IEC 60092-359
- standard colour orange, other colours on request

Application: For fixed installation in most areas and on open deck in ships.
If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 150/250V (300V)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Fire-resistant IEC 60331-21
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
For details see general information section

Electrical data 0,75mm2 Unit


Loop resistance of pair, max. / +20°C 52 ohm/km
Pair capacitance, nom. / 800Hz 55 nF/km
Loop inductance, nom. 0,6 mH/km
Insulation resistance / +20°C ≥1500 Mohm*km.
Minimum recommended installation temperature -15 °C
Lowest operation temperature -40 °C

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


43

250V CABLES
RFA-FRHF(i) 250V Number of Nominal Min. bending
conductors & outer Approximate radius fixed
cross-section diameter weight kg/km installation
Part number n x mm2 mm mm
20 667 2x2x0,75 13,0 155 80
20 669 4x2x0,75 15,5 245 95
20 671 7x2x0,75 19,0 380 115
20 673 8x2x0,75 20,5 430 125
20 675 10x2x0,75 23,0 545 140
20 677 12x2x0,75 24,0 625 145
20 679 14x2x0,75 26,5 725 160
20 683 19x2x0,75 30,5 945 185
20 685 24x2x0,75 34,0 1205 205

Core identification

Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....


The pairs are also covered by a numbered tape (1, 2, 3, 4, 5....)

3/2008
44
60V CABLES

PBS Field bus cable


60V

DESIGN: STANDARDS:
Twisted pair cable EN 50170
1. Conductor
- stranded copper conductor
2. Insulation
- Polyethylene / foamed polyethylene plastic
3. Pair twisting Flame-
4. Bedding retardant
- separator tape Fire-
5. Screen resistant
- plastic coated aluminium tape and
Halogen-
tinned copper braid, coverage 100% free
6. Sheath
Low
3/2008

- purple, polyolefine plastic


smoke
7. Outer sheath emission
- grey polyolefine plastic, SHF1

Application: For fixed installation in most areas.


If the cable is exposed to direct sun light protective covering or
cable with black outer sheath is recommended.

Main characteristics
Rated voltage 60V
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

Identification: Lot number, cable type, cable size, voltage, temperature,


standards, production month, manufacturer's name and
meter marking printed on the sheath

Core identification
Each pair green - red.

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


45

60V CABLES
PBS
Part number Number of conductors & Nominal outer Approximate Min.bending radius
cross-section n x mm2 diameter mm weight kg/km fixed installation mm
20 506 1 x 2 x 0,34 10,5 145 65

Cable for PROFIBUS DP.


The cable has been tested according to the IEC 61158 specification
and testing guidelines set by PROFIBUS Center Nederland.
Cable is approved as type A cable.

Compatible with the connector of Siemens (6ES7-972-0BA12 0XA0 or similar)


after stripping the outer sheath.

3/2008
Type A bus cable. Maximum length of each bus segment.
Data transfer rate in kbit/s 9.6 – 93.75 187.5 500 1500 3000 – 12000
Max. segment length in m 1200 1000 400 200 100
46
OPTICAL FIBRE CABLE

FXMSU Optical fibre


indoor/outdoor cable

Cable construction: (for example FXMSU 2x6 SML + 3x4 GKL)


Flame-
1. Central element glass fibre, 1,5 mm retardant
2. PP-slotted core, 6,0 mm Fire-
resistant
3. Optical fibres, 250 μm Halogen-
4. Swellable tape free
Low
5. Rip cord smoke
6. UV-protected and halogen free sheath emission
3/2008

- non-metallic
- networks in marine applications
- Fibres: 250 μm SM or MM fibres
- 4 - 48 fibres

Cable characteristics: (for example FXMSU 2x6 SML + 3x4 GKL)


Maximum pulling force 500 N EN 187000 method 501 ✳. Slotted core
cables have
Crush strength / 100 mm (plate) 4000 N EN 187000 method 504 blue and red
Crush strength / 25 mm (mandrel) 650 N EN 187000 method 504 marker threads
for the first and
Impact strength 30 J EN 187000 method 505 last slot
Sheath marking Cable type, manufacturer, man. no., respectively.
man. time, length marking in m.
Minimum bending radius 140 mm during installation,
100 mm in final bending
Nominal cable diameter 9.4 mm
Cable weight 75 kg/km
Minimum installation temperature -15 °C
Operating temperature range -45...+70 °C
Longitudinal water tightness EN 187000 method 605B
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series

For details see general information section

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


47

OPTICAL FIBRE CABLE


FXMMS Optical fibre
installation cable

Cable construction: (for example FXMMS 8 GKT) Flame-


1. FRP central element 2 mm retardant
Fire-
2. PP-slotted core 9,7 mm resistant
3. Installation cable unit FMS 1 (2 mm) Halogen-
free
4. Fire barrier tape
Low
5. Rip cord smoke
emission
6. Halogen free sheath 1,5 mm

3/2008
- For tray installation
- Fibres: 2–8 SM or MM fibres, 900 μm
- Connectors can be mounted directly to the fibres
Cable characteristics: (for example FXMMS 8 SMT)
Maximum pulling force 1500 N EN 187000 method 501
Crush strength / 100 mm (plate) 4000 N EN 187000 method 504
Crush strength / 25 mm (mandrel) 750 N EN 187000 method 504
Impact strength, R = 300 mm 30 J EN 187000 method 505
Sheath marking Cable type, manufacturer, man. no.,
man. time, length marking in m.
Minimum bending radius 195 mm during installation, 130 mm in final bending
Nominal cable diameter 13.1 mm
Cable weight 142 kg/km
Minimum installation temperature -15 °C
Operating temperature range -45...+70 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-24 -test for bunched wires and cables,
category C
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
For details see general information section

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


48
OPTICAL FIBRE CABLE

LifeCord-FRHF Optical fibre


installation cable

DESIGN:
1. Central element - glass fibre, 3,3 mm Flame-
retardant
2. PP-slotted core - 8,0 mm
Fire-
3. Optical fibres - 250 μm resistant
4. Swellable and flame-retardant tape Halogen-
free
5. Corrugated steel tape - 0,15 mm
Low
6. Sheath - polyolefine plastic, halogen-free, UV-protected smoke
- standard colour red emission
- other colours on request
3/2008

Application: Indoor cable for building cabling in places where


the cable has to maintain its functionality during fire.
Main characteristics
Maximum pulling force 2500 N EN 187000 method 501
Crush strength / 100 mm (plate) 7000 N EN 187000 method 504
Crush strength / 25 mm (mandrel) 1500 N EN 187000 method 504
Impact strength 50 J EN 187000 method 505
Minimum bending radius 270 mm during installation,
200 mm in fixed installation
Nominal cable diameter 13.5 mm
Cable weight 196 kg/km
Minimum installation temperature -15 °C
Operating temperature range -30...+70 °C
Fire properties
Fire-resistant IEC 60331-21 -min. 90 min/750 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
Identification: Lot number, cable type, cable size, standards, production month,
manufacturer's name and meter marking printed on the sheath

Standard cable types:


LifeCord FRHF 1x6 SML (OS1) LifeCord FRHF 1x4 SML (OS1) + 2x4 GKL (OM1)
LifeCord FRHF 2x6 SML (OS1) LifeCord FRHF 1x6 SML (OS1) + 3x4 GKL (OM1)
LifeCord FRHF 4x6 SML (OS1) LifeCord FRHF 2x6 SML (OS1) + 3x4 GKL (OM1)
LifeCord FRHF 1x4 GKL (OM1) LifeCord FRHF 1x4 SML (OS1) + 2x4 OM3
LifeCord FRHF 2x4 GKL (OM1) LifeCord FRHF 1x6 SML (OS1) + 3x4 OM3
LifeCord FRHF 3x4 GKL (OM1) LifeCord FRHF 2x6 SML (OS1) + 3x4 OM3
LifeCord FRHF 6x4 GKL (OM1)
LifeCord FRHF 1x4 OM3
LifeCord FRHF 2x4 OM3
LifeCord FRHF 3x4 OM3
LifeCord FRHF 6x4 OM3 Other cables on request

Tel. +358 2 410 8700, fax +358 2 410 8750, www.helkamabica.fi


49

OPTICAL FIBRE CABLE


Cabled optical fibres characteristics
Fibre coating: L = 250 μm ± 10 μm
T = 900 μm ± 50 μm

Single mode fibre 10/125 μm SM / OS1 (ITU-T G.652.D)


Mode field diameter (MFD) 1310 nm 9,3 +/- 0,5 μm
Mode field eccentricity ≤ 1,0 μm
-Installation cables ≤ 0,5 μm
Cladding diameter 125 +/- 2 μm
- Installation cables 125 +/- 1 μm
Cladding ellipticity ≤2%
Fibre attenuation 1310 nm ≤ 0,40 dB/km
1550 nm ≤ 0,25 dB/km
Zero dispersion range 1300...1324 nm
Dispersion coefficient ≤ 0,093 ps/nm2/km
- Dispersion at 1550 nm ≤ 18 ps/nm/km
Cut-off wavelength ≤ 1260 nm
- Installation cables 1180...1250 nm

3/2008
Polarization mode dispersion ≤ 0,5 ps/√km
Proof test 1 % / 1 sec
Fibre identification 6 colour system
according to SFS 5648

Multi mode fibre 50/125 μm OM3


Core diameter 50 +/- 3 μm
Core ellipticity ≤6%
Core eccentricity ≤ 3 μm
Cladding diameter 125 +/- 2 μm
Cladding ellipticity ≤2%
Fibre attenuation 850 nm ≤ 2,7 dB/km
1300 nm ≤ 0,8 dB/km
Bandwidth 850 nm ≥ 1500 MHz x km (LED)
1300 nm ≥ 500 MHz x km (LED)
850 nm ≥ 2000 MHz x km (Laser)
Numerical aperture, NA 0,200 +/- 0,015
Fibre identification 6 colour system
according to SFS 5648

Multi mode fibre 62,5/125 μm GK / OM1


Core diameter 62,5 +/- 3 μm
Core ellipticity ≤6%
Core eccentricity ≤ 3 μm
Cladding diameter 125 +/- 2 μm
Cladding ellipticity ≤2%
Fibre attenuation 850 nm ≤ 3,5 dB/km
1300 nm ≤ 1,0 dB/km
Bandwidth 850 nm ≥ 200 MHz x km
1300 nm ≥ 500 MHz x km
Numerical aperture, NA 0,275 +/- 0,015
Fibre identification 6 colour system
according to SFS 5648
50
GENERAL INFORMATION
TECHNICAL INFORMATION

Insulation material: All Helkama cables comply with the most Halogen-free
severe requirements of Halogen-free refers to the absence
The following designations are used for category A. of halogens, such as chlorine and
insulation materials in this catalog. fluorine, and is determined on
All materials are halogen-free. the basis of halogen content and
Test on the acidity of gases of a cable.
XLPE stands for cross-linked poly- bunched
ethylene compound. It has excellent cables IEC 60754-1 determines the
IEC 60332-3

3.5 m
mechanical and electrical characteristics. halogen content of the material.
Burning is To meet the requirements as
allowed up 4m
halogen-free the halogen content

2.5 m
to max. 2.5
of the material may not exceed
Sheathing material: meters from
0,5 % or 5 mg/g.
the burner
The designation SHF1 stands for within
specified time. IEC 60754-2 determines the
thermoplastic compound. This material 1m
2m degree of acidity of gases evolved
is halogen-free, highly flame-retardant
during combustion. The limit
and has low smoke emission.
values are 4,3 for pH and
10 mikroS for conductivity.
IEC 60332-1 is the test for single insu-
Definition of terms: lated wire and cable. Test procedure and Smoke emission
requirements according to the picture, Smoke emission refers to visibility
Flame-retardant below. in a fire. The greater the light trans-
To be flame-retardant, the cables mittance, the better the visibility.
3/2008

must withstand the test specified in When tested in accordance with


IEC standard 60332-3 or IEC 60332-1. IEC 61034-1 (test method) and
Flame-retardant cables do not propagate IEC 61034-2 (test requirements)
50 mm
fire, and are self-extinguishing. the smoke emission of a cable during
fire must not exceed the following values.
IEC 60332-3 is the test for bunched wires
and cables and has three cate-gories A, 475 550 600
mm mm mm
B and C, defined by different limits for
flammable material and burning times.
Burning time describes how long the
burner is directed towards the bunch of 27m3 cube
cables. The requirement for passing the smoke chamber
test is that after the burner has been
removed the cables must extinguish Requirements:
themselves. Burning may not occur more 60 % light
than 2.5 m from the burner as shown in Min. 50 mm of the cable, measured from transmittance
the figure. the upper support, must remain unburned
after the specified time.

Amount of Fire-resistant
To be classified as fire-resistant the cables must withstand the test specified in standard
Category burning Burning time
IEC 60331-21. The cables must operate for a minimum of 90 minutes while the burner
material
is directed towards the cable as shown below. Helkama fire-resistant cables are also flame-
A 7 litres/m 40 min retardant.
B 3,5 litres/m 40 min
C 1,5 litres/m 20 min 3A 750 °C / 90 min
75 mm

Un

gas burner
610 mm
51
BENDING RADIUS

TECHNICAL INFORMATION
LKM-HF During installation R = 6x D < 25mm
Recommended minimum bending LKM-FRHF During installation R = 9x D > 25mm
radius, ( R ) : LKEM-HF Fixed instalation R = 4x D < 25mm
Fixed instalation R = 6x D > 25mm
(Unarmoured or unscreened cables)

LKSM-HF During installation R = 9x D


LKAM-HF Fixed instalation R = 6x D
LKSM-FRHF
RFE-HF
RFE-HF(i)
Radius (R) RFA-HF
Outer RFA-HF(i)
diameter (D) RFE-FRHF
RFE-FRHF(i)
RFA-FRHF
RFA-FRHF(i)
PBS
(Armoured or screened cables)

3/2008
DIAMETER TOLERANCE Cable outer diameter, mm. Tolerance Cable outer diameter, mm. Tolerance
1 – 10 ±0,5mm 30,1 – 40 ±2,0mm
10,1 – 20 ±1,0mm 40,1 – 50 ±2,5mm
20,1 – 30 ±1,5mm 50,1 – 60 ±3,0mm

CORE IDENTIFICATION

0,6/1kV Normal type G-type 250V


with earth a b
conductor)
Pair
number
1-core BK 1 1 2
2 3 4
3 5 6
2-cores BN BU
4 7 8
5 9 10
BN BK Y/G BU
3-cores 6 11 12
GY BN
etc.
BU BN Y/G BN
4-cores
GY BK GY BK
60V
(PBS)
1 Y/G
2 BU
5-cores 5 GY
4 3 BK BN

2 2
7 3 Y/G 3
7-cores 1 1
6 4 6 4
5 5

Black numbers Black numbers


on white base on white base
Last core
yellow/green.
BU = Blue, BN = Brown, BK = Black, GY = Grey, Y/G = Yellow/Green
52
CURRENT RATING
TECHNICAL INFORMATION

"Current rating (A) at an ambient temperature of 45°C For continuous service. Continuous service for a cable is
according to the standard IEC 60092-352 to be considered as a current-carrying service (with
0,6/1 kV +90°C marine cables." constant load) having a duration longer than three times
the thermal time constant of the cable, i.e. longer than
Current carrying capacities in continous service at the critical duration(see short time duty).
maximum rated conductor temperature of +90°C.
For class 2 conductor cables
Size N 1 2 3 4 5 7 10 12 14 16 19 24 27 37

Factor, n 1 0,85 0,7 0,7 0,58 0,52 0,46 0,44 0,41 0,40 0,37 0,35 0,33 0,30
1,5 mm2 23 20 16 16 13 12 11 10 9 9 9 8 8 7
2,5 mm2 30 26 21 21 17 16 14 13 12 12 11 11 10 9
4 mm2 40 34 28 28 23 – – – – – – – – –
6 mm2 52 44 36 36 30 – – – – – – – – –
10 mm2 72 61 50 50 42 – – – – – – – – –
16 mm2 96 82 67 67 56 – – – – – – – – –
25 mm2 127 108 89 89 – – – – – – – – – –
35 mm2 157 133 110 110 – – – – – – – – – –
50 mm2 196 167 137 137 – – – – – – – – – –
70 mm2 242 206 169 169 – – – – – – – – – –
95 mm2 293 249 205 205 – – – – – – – – – –
120 mm2 339 288 237 237 – – – – – – – – – –
150 mm2 389 331 272 272 – – – – – – – – – –
3/2008

185 mm2 444 377 311 311 – – – – – – – – – –


240 mm2 522 444 365 365 – – – – – – – – – –
300 mm2 601 511 421 421 – – – – – – – – – –
For class 5 conductor cables For class 5 conductor cables
Size N 1 2 3 4 5 Size N 1 2 3 4 5

Factor, n 1 0,85 0,7 0,7 0,58 Factor, n 1 0,85 0,7 0,7 0,58
16mm2 94 80 66 66 55 120mm2 331 281 232 232 –
25mm2 123 105 86 86 – 150mm2 381 324 267 267 –
35mm2 153 130 107 107 – 185mm2 429 365 300 300 –
50mm2 196 167 137 137 – 240mm2 507 431 355 355 –
70mm2 240 204 168 168 – 300mm2 582 495 407 407 –
95mm2 284 241 199 199 –

SHORT CIRCUIT CURRENT


Maximum permissible short circuit current. Cross-section of Duration of the short circuit in s.
0,6/1 kV +90°C marine cables. the conductor
Based on formula: in mm2 0,2 0,5 1 2 3 10
1,5 0,5 0,3 0,2 0,2 0,1 0,1
S 234 + Tk
Ik = 226 X X In 2,5 0,8 0,5 0,4 0,3 0,2 0,1
t 234 + Tb 4 1,3 0,8 0,6 0,4 0,3 0,2
Formula 1: 6 2,0 1,2 0,9 0,6 0,5 0,3
10 3,3 2,1 1,5 1,0 0,8 0,5
S 16 5,2 3,3 2,3 1,7 1,3 0,7
Ik = 146 X 25 8,2 5,2 3,7 2,6 2,1 1,2
t
35 11,4 7,2 5,1 3,6 3,0 1,6
Ik =
Maximum permissible short circuit current. 50 16,3 10,3 7,3 5,2 4,2 2,3
S Cross-section of the conductor in mm2.
= 70 22,9 14,5 10,2 7,2 5,9 3,2
t =
Duration of the short circuit in s. 95 31,0 19,6 13,9 9,8 8,0 4,4
Tk =
Maximum rated conductor temperature, 120 39,2 24,8 17,5 12,4 10,1 5,5
short circuit, °C 150 49,0 31,0 21,9 15,5 12,6 6,9
Tb = Maximum rated conductor temperature,
185 60,4 38,2 27,0 19,1 15,6 8,5
normal, °C
Formula 1: For 0,6/1kV cable with XLPE or HF90 with 240 78,4 49,6 35,0 24,8 20,2 11,1
maximum operating temperature of +90°C (Tb) and 300 97,9 61,9 43,8 31,0 25,3 13,9
short circuit temperature of +250°C (Tk). Short circuit current in kA
53
SHORT TIME DUTY

TECHNICAL INFORMATION
Short time duty according to the standard Overall Service Time Critical
IEC 60092-352 0,6/1 kV +90°C diameter of time, min. constant, duration,
marine cables. the cable, min. min.
mm.
If a cable is intended to supply motor
or equipment operating for periods of half an hour or 30 60 T 3x T
one hour, its current rating given in table “current 1 1,058 1,058 0,245 0,735
rating”, may be increased using the relevant 2 1,058 1,058 0,625 1,87
correction factors given by formula: 3 1,058 1,058 1,08 3,24
4 1,058 1,058 1,59 4,78
5 1,058 1,058 2,15 6,46
correction = 1,12 6 1,058 1,058 2,75 8,26
factor 7 1,058 1,058 3,39 10,2
1-exp(-ts/T) 8 1,059 1,058 4,06 12,2
9 1,059 1,058 4,76 14,3
( ts = service time, min. T = Time constant, min.) 10 1,061 1,058 5,48 16,5
20 1,126 1,066 14,0 41,9
30 1,255 1,105 24,2 72,5
T = 0,245 x d 1,35 40 1,403 1,173 35,6 107
(d = Overall diameter of the cable, mm.) 50 1,554 1,254 48,2 145
60 1,705 1,341 61,6 185

3/2008
Correction factor.

Intermittent service Overall diameter of Correction


the cable, mm. factor.
Correction factor for intermittent service
according to the standard IEC 60092-352 1 1,000
2 1,001
3 1,012
The correction factor given hereby has been
4 1,042
roughly calculated for periods of 10 min, 5 1,083
of which 4 min are with a constant load and 6 1,127
6 min without load. 7 1,170
8 1,208
Intermittence period = 10min. 9 1,242
Intermittence ratio = 40%. 10 1,273
20 1,433
30 1,490
Fi= 1-exp(-10/T) 40 1,518
50 1,534
1-exp(-4/T)
60 1,544
54
SHORT CIRCUIT FACTORS
TECHNICAL INFORMATION

Short circuit factors for single (1) core cables Short circuit factors for two (2) core cables

Cross-section of Duration of the short circuit in s. Cross-section of Duration of the short circuit in s.
the conductor the conductor
in mm2 0,2 0,5 1 2 3 in mm2 0,2 0,5 1 2 3
1,5 23,3 14,7 10,4 7,4 6,0 1,5 27,2 17,2 12,2 8,6 7,0
2,5 27,2 17,2 12,2 8,6 7,0 2,5 32,6 20,6 14,6 10,3 8,4
4 32,6 20,6 14,6 10,3 8,4 4 38,4 24,3 17,2 12,1 9,9
6 38,4 24,3 17,2 12,1 9,9 6 45,6 28,8 20,4 14,4 11,8
10 46,0 29,1 20,6 14,5 11,9 10 54,4 34,4 24,3 17,2 14,0
16 55,0 34,8 24,6 17,4 14,2 16 64,5 40,8 28,8 20,4 16,7
25 65,3 41,3 29,2 20,6 16,9 25 77,7 49,2 34,8 24,6 20,1
35 73,7 46,6 33,0 23,3 19,0 35 84,6 53,5 37,9 26,8 21,9
50 85,9 54,3 38,4 27,2 22,2 50 98,9 62,6 44,2 31,3 25,5
70 95,2 60,2 42,6 30,1 24,6 70 114,3 72,3 51,1 36,1 29,5
95 106,9 67,6 47,8 33,8 27,6 95 – – – – –
120 115,2 72,9 51,5 36,4 29,8 120 – – – – –
150 127,2 80,4 56,9 40,2 32,8 150 – – – – –
185 137,3 86,8 61,4 43,4 35,4 185 – – – – –
240 150,7 95,3 67,4 47,6 38,9 240 – – – – –
3/2008

300 166,0 105,0 74,2 52,5 42,9 300 – – – – –

Short circuit factors for three (3) and Short circuit factors for cables with a core no. from
four (4) core cables five (5) to thirtyseven (37)

The conductor Duration of the short circuit in s. The conductor Duration of the short circuit in s.
in mm2 in mm2
0,2 0,5 1 2 3 0,2 0,5 1 2 3
1,5 32,6 20,6 14,6 10,3 8,4 5x1,5 35,0 22,1 15,6 11,1 9,0
2,5 38,9 24,6 17,4 12,3 10,0 5x2,5 45,3 28,7 20,3 14,3 11,7
4 45,0 28,5 20,1 14,2 11,6 5x4 52,2 33,0 23,4 16,5 13,5
6 54,4 34,4 24,3 17,2 14,0 5x6 65,3 41,3 29,2 20,6 16,9
10 65,3 41,3 29,2 20,6 16,9 5x10 74,2 46,9 33,2 23,5 19,2
16 78,0 49,3 34,9 24,7 20,1 5x16 93,3 59,0 41,7 29,5 24,1
25 91,7 58,0 41,0 29,0 23,7 7x1,5 40,8 25,8 18,3 12,9 10,5
35 108,8 68,8 48,7 34,4 28,1 7x2,5 51,0 32,3 22,8 16,1 13,2
50 120,9 76,5 54,1 38,2 31,2 10x1,5 44,5 28,2 19,9 14,1 11,5
70 134,4 85,0 60,1 42,5 34,7 10x2,5 58,3 36,9 26,1 18,4 15,1
95 151,3 95,7 67,7 47,8 39,1 12x1,5 49,0 31,0 21,9 15,5 12,6
120 163,2 103,2 73,0 51,6 42,1 12x2,5 62,8 39,7 28,1 19,9 16,2
150 181,4 114,7 81,1 57,4 46,8 14x1,5 49,0 31,0 21,9 15,5 12,6
185 198,0 125,2 88,6 62,6 51,1 14x2,5 62,8 39,7 28,1 19,9 16,2
240 214,7 135,8 96,0 67,9 55,4 16x1,5 54,4 34,4 24,3 17,2 14,0
300 236,0 149,3 105,5 74,6 60,9 16x2,5 68,0 43,0 30,4 21,5 17,6
19x1,5 54,4 34,4 24,3 17,2 14,0
19x2,5 74,2 46,9 33,2 23,5 19,2
24x1,5 61,2 38,7 27,4 19,4 15,8
24x2,5 81,6 51,6 36,5 25,8 21,1
27x1,5 61,2 38,7 27,4 19,4 15,8
27x2,5 81,6 51,6 36,5 25,8 21,1
37x1,5 70,0 44,2 31,3 22,1 18,1
37x2,5 90,7 57,4 40,6 28,7 23,4
55
VOLTAGE DROP

TECHNICAL INFORMATION
Cable types: LKM-HF, LKSM-HF, LKAM-HF, LKM-FRHF, LKSM-FRHF (Cables with class 2 conductor)

Size Resistance Resistance Voltage Resistance Current Voltage


at +20°C at +90°C reduction at +45°C rating reduction
ohm/km ohm/km mV/Am *) ohm/km A **) mV/m ***)
1,5 mm2 12,1 15,4 30,9 13,3 23 0,56
2,5 mm2 7,41 9,45 18,9 8,14 30 0,49
4 mm2 4,61 5,88 11,8 5,06 40 0,41
6 mm2 3,08 3,93 7,85 3,38 52 0,35
10 mm2 1,83 2,33 4,67 2,01 72 0,29
16 mm2 1,15 1,47 2,93 1,26 96 0,24
25 mm2 0,727 0,927 1,85 0,798 127 0,20
35 mm2 0,524 0,668 1,34 0,575 157 0,18
50 mm2 0,387 0,493 0,99 0,425 196 0,16
70 mm2 0,268 0,342 0,68 0,294 242 0,14
95 mm2 0,193 0,246 0,49 0,212 293 0,12
120 mm2 0,153 0,195 0,39 0,168 339 0,11
150 mm2 0,124 0,158 0,32 0,136 389 0,10
185 mm2 0,0991 0,1264 0,25 0,1088 444 0,096
240 mm2 0,0754 0,0961 0,19 0,0828 522 0,086
300 mm2 0,0601 0,0766 0,15 0,0660 601 0,078

3/2008
Cable types: LKM-HF FLEX, LKSM-HF FLEX, LKEM-HF (Cables with class 5 conductor)

Size Resistance Resistance Voltage Resistance Current Voltage


at +20°C at +90°C reduction at +45°C rating reduction
ohm/km ohm/km mV/Am *) ohm/km A **) mV/m ***)
0,75 mm2 24,7 31,5 63,0 27,1 14 0,76
1,0 mm2 18,5 23,6 47,2 20,3 17 0,69
1,5 mm2 12,6 16,1 32,1 13,8 22 0,58
2,5 mm2 7,58 9,67 19,3 8,32 30 0,50
4 mm2 4,7 5,99 12,0 5,16 39 0,41
6 mm2 3,14 4,00 8,01 3,45 50 0,35
10 mm2 1,81 2,31 4,62 1,99 71 0,28
16 mm2 1,15 1,47 2,93 1,26 94 0,24
25 mm2 0,740 0,944 1,89 0,813 123 0,20
35 mm2 0,530 0,676 1,35 0,582 153 0,18
50 mm2 0,367 0,468 0,94 0,403 196 0,15
70 mm2 0,258 0,329 0,66 0,283 240 0,14
95 mm2 0,206 0,263 0,53 0,226 284 0,13
120 mm2 0,161 0,205 0,41 0,177 331 0,12

Cable types: LKSM-HF 250V, RFE-HF, RFE-HF(i), RFA-HF, RFA-HF(i), RFE-FRHF, RFE-FRHF(i), RFA-FRHF, RFA-FRHF(i)

Size Resistance Maximum Resistance Voltage Resistance Voltage


at +20°C conductor at +45°C reduction at +90°C reduction
ohm/km temperature, °C ohm/km mV/Am at +45°C ohm/km mV/Am at +90°C
0,5 mm2 40,4 90 44,4 88,7 51,5 103,0
0,75 mm2 26,0 90 28,6 57,1 33,2 66,3
1,5 mm2 12,8 90 14,1 28,1 16,3 32,6

*) at +90°C
**) For continuous service (single core, ambient temperature +45°C)
***) at maximum current rating for continuous service at +45°C
HELKAMA BICA OY
Lakimiehenkatu 4
FI-20780 KAARINA
Finland
Tel. +358 2 410 8700
Fax +358 2 410 8750