Anda di halaman 1dari 7

Hot Oil

Systems
Double Drop-Leg with Back-Pressure
Control on Bypass
Good system design, smart fluid-
handling procedures and regular
System Relief Valve Expansion Tank (See Options Below)
maintenance can help you maximize
System Vent the performance of your thermal fluid
(At All High Points) heating system.
1/3 Main Pipe Warmup TIC
Diameter Line PIC
BY MARK E. SMITH, MULTITHERM LLC
Heater

Process

esigning, building and operating a ther-

Circulating Pump

PIC
Denotes Uninsulated Equipment
Denotes Pressure Indicator
Sample Line

TIC
Drain Line (At All Low Points)
Denotes Insulated Equipment
Denotes Temperature
Back-
Pressure
Valve

D mal oil heat transfer system can be cost-


effective if planned for properly from the
start. Starting with common design lay-
outs and continuing through operations, cleaning and
troubleshooting, these 10 tips will help you maximize
and Controller Indicator and Controller your investment.
Expansion Tank Options
Relief Valve (30 psi) Manual TIP 1: Plan Thermal Fluid System Layout Carefully
Vent There are an infinite number of layouts, and that is
Back- To
Pressure Inert Gas Catch because each layout must be specifically designed for
Control Supply Tank
(0.5 to
your facility to meet your process needs. Some typical
Valve
Open To 2 psi) layouts are shown in figure 1. At a minimum, every
Cold Seal Pot
Catch system needs a heater, pump and expansion tank.
Tank Blanketed

Dearator with Thermal Buffer Tank and Three-Way Control Valve TIP 2: Select System Components Wisely
Expansion Tank System components comprise piping, threaded installa-
System Relief Valve Warmup System Vent tions, flanges, gaskets, studs, nuts, insulation, valves and
Line (All High
Points) pumps. When specifying components for a hot oil system,
be sure that they are designed for hot oil systems and for
temperatures that exceed your system’s bulk temperature.
TIC
Thermal
Buffer Tank
Piping. Welded installations are recommended. If
Dearator
you use threaded installations, back-weld all connec-
Heater

Process

tions or use thread sealant.


Flanges. Select flanges with the following charac-
teristics: 300 lb forged steel construction; welding
neck; 1/16" raised face, Schedule 40 bore; and
Circulating Pump ASTM A 181 rating. The use of backing rings at pipe-
Sample Line
to-flange welds is recommended.
Drain Lines (All Low Points)
Gaskets. Select spiral-wound, graphite-filled or
Denotes Uninsulated Equipment Denotes Insulated Equipment
expanded/filled PTFE gaskets.

Figure 1. Each thermal fluid heating system should be designed specifically for your facility to meet your process needs.
An inert gas blanketed expansion tank, which can be insulated if necessary, is recommended for systems that operate with a
bulk temperature above 500°F (260°C). A cold seal pot is recommended if the expansion tank operates above 140°F (60°C)
or if you are located in an area that has high humidity.

www.process-heating.com S E P T E M B E R 2 0 0 4 35
Studs. Choose alloy steel, continu- the thermal fluid system. leaks consist of fluid seeping from
ously threaded, ASTM A 193, Grade Flashpoint and Fire Point. The flash- threaded fittings, flange gaskets,
B7 or higher studs. point and fire point of a thermal fluid mechanical seals and valve-stem and
Nuts. Use heavy hex nuts, ASTM A are determined through laboratory pump-shaft-packing glands. Any drop-
194, Grade 2H or higher. testing of unused fluid. The most com- lets formed will cool rapidly on expo-
Insulation. Calcium silicate or fiber- mon test method is the ASTM D92 sure to air. Extremely low volume leaks
glass rated to 850°F (454°C) is accept- Cleveland Open Cup (COC). The may produce a light gray smoke. This is
able where the potential for leaks is lowest temperature at which the vapor an indication that the fluid is oxidizing
H E AT T R A N S F E R

minimal. Closed-cell foamed glass is ignites is called the flashpoint. The immediately on exposure to air.
recommended within several feet of temperature at which sufficient vapor There are several conditions under
flanges, valves, pipe taps or other is generated to support a continuous which “normal” leaks can present a risk
potential leak points. Flanges should be flame is the fire point. of fire:
left uninsulated to ease leak detection. While these test results provide data
Valves. Select cast or forged carbon for comparing different fluids, any • Certain types of insulation such as
steel valves with a socket weld or flanged extrapolation of these results into real- mineral wool, fiberglass or calcium
silicate have an open or porous
structure that allows fluid to wick
PI PI away from the source of a leak. As
the fluid disperses within the insula-
tion, its surface area increases dra-
Block Valves
matically while its temperature
remains at or near the system operat-
Drain Valve Flow Control Valve ing temperature. The danger is that
a substantial percentage of the
leaked fluid will remain unreacted
within the insulation due to the lim-
ited amount of oxygen available. If
the supply of oxygen suddenly
increases, the remaining fluid in the
Figure 2. A side-stream filtration system is recommended for systems with cen-
trifugal pumps. insulation will burst into flames.
Prevent insulation fires by using
(300 lb) design. Graphite or expanded/ life situations must recognize the three nonporous insulation within several
filled PTFE valve-stem packing or bel- basic conditions required for a vapor feet of areas prone to leaks such as
lows seal is recommended. Isolation ignition to occur: valves and flanges.
valves should be ball-type valves; for • If a low volume leak occurs within a
these uses, control valves or globe valves • The fluid must be at or above the tightly enclosed area such as a cabi-
are recommended. Install valve stems flashpoint or fire point while in con- net, the available oxygen may be
pointing down to allow any leaking fluid tact with air for any vapor combus- consumed, allowing unreacted vapor
to drain away from the insulation. tion to occur. This situation may not to accumulate. Prevent this by
Pumps. For positive-displacement exist around leaks because the leak- ensuring that all portions of a ther-
pumps, select those made of alloy steel ing fluid will cool rapidly on expo- mal fluid system are located in areas
with a gear-within-a-gear or sliding-vane sure to air. with adequate ventilation.
design. For centrifugal pumps, be sure • Enough vapor must be present to
the pump selected has ductile or cast support combustion. Any dissipation Catastrophic Equipment Failure. A
iron wetted parts. For the pumps’ of the vapor may reduce the concen- catastrophic equipment failure may
mechanical seals, select bellows type. For tration below the level required for result in the rapid release of large
applications with low particulate load- ignition. quantities of thermal fluid. As the fluid
ing, carbon seal faces are recommended • The source of ignition must be is released, the relatively larger surface
over silicon or tungsten carbide seal located within the vapor cloud. area of the droplets and their velocity
faces. For applications with high particu- Good electrical installation practice will result in rapid cooling. When this
late loading, use tungsten carbide seal dictates that potential ignition occurs, there will be a certain amount
faces rather than silicon carbide. sources are located a distance from of smoke present due to the hot fluid
piping or are enclosed properly. reacting with air (oxidizing). Any
TIP 3: Keep Thermal Fluid resulting fire or catastrophic failure
Safety in Mind If any one of these three conditions hazards can be minimized through
The potential for fire should be con- is not met, vapor ignition cannot occur. proper design, operation and mainte-
sidered in the design and operation of Leaks. Normal thermal fluid system nance of the equipment:

36 S E P T E M B E R 2 0 0 4 Process Heating
• Never operate a thermal fluid above out causing the heater to shutdown. switch should be wired to shutdown
its boiling point. Under this no-flow condition, the the system immediately on loss of flow.
• Maintain good ventilation in the temperature of the fluid inside the still-
area around equipment. energized heater increases rapidly to TIP 4: Practice Safe Fluid Handling
• Minimize the fuel available for a fire. well above its boiling point. Following a few simple recommen-
To do this, the expansion tank should Equipment failures may result in dations for storing the fluid, filling the
be equipped with a low level switch spontaneous ignition of any leaking system and removing air pockets will

H E AT T R A N S F E R
to shut down the entire system. fluid. The most effective protection is ensure safe fluid handling.
to install a high/low pressure switch When storing the fluid, the drums
Loss of Circulation in the Heater. on the pump discharge or a low differ- should be protected from exposure to
Severe potential for fires can exist if the ential pressure switch across an orifice direct sunlight and precipitation.
thermal fluid flow is interrupted with- plate or similar type flow meter. The Before filling or refilling the system,
open all of the vent or bleed valves,
process block valves, control valves and
any valves connecting the system to the
PI PI
expansion tank. To pump the heat
Block Valves
transfer fluid into the system, any
portable or drum pump with sufficient
capacity is acceptable. Do not use the
Drain Valve system-circulating pump to add fluid
Bypass Valve
because seal damage can result from
running the pump dry.
Once the valves are open, add the
fluid to the system. Fluid should be
added at the lowest point of the sys-
tem, preferably at the suction side of
Figure 3. Inline filters only should be used with positive-displacement pumps. the circulating pump. Avoid aerating

1 1
⁄4 ⁄4
www.process-heating.com S E P T E M B E R 2 0 0 4 37
the fluid; do not add fluid directly to TIP 5: Extend Fluid Life Through mal cracking and premature fluid fail-
the expansion tank. Close the vent and Good Operating Practices ure. Excessive thermal cracking can be
bleed valves when the fluid runs out. The fluid service life and the process minimized by following good operat-
Stop filling the system when fluid runs operating efficiency can be increased ing practices:
out of the highest point. by minimizing thermal fluid cracking,
To remove air pockets, use the sys- oxidation and contamination. • Maintain the design fluid velocity at
tem-circulating pump to circulate fluid Thermal Cracking. Under certain all times through the heater.
slowly through system until all of the gas conditions, all heaters are capable of • Bring cold systems up to tempera-
H E AT T R A N S F E R

bubbles have escaped into the expansion exceeding the maximum recommend- ture slowly.
tank or vented through vent/bleed ed film temperature of the heat transfer • Avoid rapid shutdowns.
valves. Add fluid as required to maintain fluid. Exceeding this temperature for a • Maintain system instrumentation.
the expansion tank level at quarter-full. period of time can cause excessive ther- • Check the combustion chamber for
improper flame propagation or
TABLE 1. TROUBESHOOTING TIPSHEET burner alignment.
Potential Problem Potential Causes
Oxidation. When a heat transfer fluid
Carbon Buildup on Heater Rods Thermal Cracking; Contamination
oxidizes, it can cause fouling or corro-
Pump Seals Require Heater; Heat User; sion of the expansion tank. Minimizing
Frequent Replacement Thermal Cracking; Contamination oxidation is relatively simple:
Fluid Turns Dark and Thick Heater; Heat User;
Thermal Cracking; Oxidation • Keep the expansion tank tempera-
Uneven System Temperature Control Heater; Heat User ture below 140°F (60°C).
Frequent Y Strainer Plugging Oxidation; Thermal Cracking;
• Maintain positive net pump suction
Contamination
head (NPSH) at all times.
Pump Cavitation Thermal Cracking; Contamination
Contamination. Contaminants can
Smoking Oxidation promote fluid degradation as well

1 1
⁄4 ⁄4
38 S E P T E M B E R 2 0 0 4 Process Heating
as cause operational problems. Con- increase the temperature of the bulk fluid molecules decompose into solid coke
taminants can enter the system in sev- by 20 to 25°F (11 to 14°C) increments (90 to 95 percent carbon) and small,
eral ways. Guard against their entry by until the fluid reaches a viscosity of 10 cP. lower boiling molecules. The presence
following good operating practices: At this point, there will be turbulent flow of these smaller and larger molecules
through the heater, and the heater can be can be determined by tests that meas-
• In new systems, make sure that all turned up to the process temperature. ure fluid properties affected by molec-
fabrication debris or protective coat- During shutdown, it is recommended ular weight, and the results then can be

H E AT T R A N S F E R
ings are removed before assembly. that the circulating pump be run inde- compared to the properties of clean
Pressure test the system with either pendently of the heater to maintain con- fluid. Other tests measure specific
heat transfer fluid or inert gas. Never tinuous fluid circulation until the bulk byproducts of cracking.
pressure test with water. fluid temperature falls below 250°F Among the tests that can be con-
• In daily operation, always use fresh (121°C). Once the fluid has reached this ducted to determine whether thermal
fluid to top off system. temperature, the residual heat in the cracking has occurred are tests for dis-
• When using organic-based solvents heater has been removed and the entire tillation range, kinematic viscosity, fluid
or flushing fluids, completely drain system is starting to cool down. flashpoint and pentane insoluables.
the system from all system low
points during system cleaning. TIP 7: Perform Regular • The distillation range test establishes
Fluid Analysis the relative amounts of large and
TIP 6: Start and Stop Sensibly Organic heat transfer fluids degrade small molecules in a sample by meas-
Good startup and shutdown proce- over time due to thermal cracking, oxi- uring the temperature at which cer-
dures can help ensure that you are not dation and contamination. Regular tain volume fractions boil.
promoting thermal cracking. During fluid analysis will evaluate the fluid • The kinematic viscosity of chemical-
startup, it is recommended that the sys- condition and help identify when sys- ly similar fluids is proportional to the
tem pump be used to circulate the fluid tem maintenance or fluid replacement average molecular weight. The
through the system prior to turning on is necessary. results for the heat transfer fluid
the heater. Once there is circulation Thermal Cracking. Thermal cracking being analyzed may or may not devi-
through the heater, the operator should is the phenomena by which large oil ate from characteristics of unused

1
⁄2
Horizontal
www.process-heating.com S E P T E M B E R 2 0 0 4 39
fluid due to mix of larger (high vis- used to determine the level of fluid tion. The data must be put into a time
cosity) and smaller (low viscosity) oxidation is the total acid number perspective along with the operating
molecules, so this test alone is not a (TAN) test, which is a measure of the history to obtain a complete system
valid indicator of fluid condition. organic acid concentration in the fluid. analysis. This allows corrective action to
• Flashpoint is the temperature at Contamination. Contaminants can be implemented before the fluid life or
which the fluid vapor will flash when catalyze fluid degradation and result in equipment efficiency is compromised.
a small flame is passed a specified dis- severe operating and equipment prob- When preparing a fluid sample to
tance above the sample. The fluid’s send out for analysis, take the sample
H E AT T R A N S F E R

flashpoint may drop as smaller, more DO NOT USE WATER from a “live” part of the system,
volatile molecules are formed. TO CLEAN OUT AN preferably at the heat user or the circu-
• Pentane insolubles testing measures lating pump. The fluid should be cir-
the amount of coke and other partic- ASSEMBLED SYSTEM OR culating at a temperature of 200°F
ulate matter that is suspended in the TO PRESSURE TEST THE (111°C). Do not sample from the
fluid. To conduct the test, the solids expansion or drain tank. Also, it is
are removed by filtering, washed SYSTEM. INSTEAD, USE A important that the sample be put
with pentane to remove the heat FLUSHING FLUID, THE directly into the sample jar.
transfer fluid, dried and weighed.
HEAT TRANSFER FLUID TIP 8: Install Effective
Oxidation. All organic heat transfer OR INERT GAS. Thermal Fluid Filters
fluids react with air to form organic Filtration will extend the service life
acids. This oxidation rate is low at lems. The most common contaminant of the fluid and reduce system mainte-
ambient temperature but increases rap- in heat transfer fluids is water. The Karl nance costs. These benefits increase as
idly as the fluid temperature rises. Fischer water test determines the the system operating temperature
These acids can undergo free-radical amount of water present in the fluid. increases.
polymerization, which will increase the Evaluation and Recommendations. For general components, a 10 µm
fluid viscosity and ultimately can result The laboratory data from these tests filter is recommended. Block valves
in deposits. The most common test provide a snapshot of the fluid condi- should be a positive-shutoff type to

40 S E P T E M B E R 2 0 0 4 Process Heating
allow for filter cleaning without shut- ings, dirt and water. The abrasive con- vent air. Filling from the top (pouring
ting system down. tamination can damage pump seals, into the expansion tank) hinders air
A side-stream filtration system is rec- bearings and control valves. Mill scale venting and needlessly aerates the
ommended for systems with centrifu- and weld splatter can promote fluid fluid. Often, a convenient place to fill
gal pumps (figure 2). With a side- oxidation and cracking. The oil, coat- the system is through the blowdown
stream configuration, the optimal flow ings and flux are thermally unstable connection on the strainer. Use a small
rate through the filter is 10 percent of and can cause fluid degradation. Using positive-displacement pump to transfer

H E AT T R A N S F E R
full system flow. At a minimum, circu- a flushing fluid to clear these contami- the fluid rather than the system pump.
late at least 3 percent of the full system nants out of the system before adding
flow through the side-stream filter. the clean heat transfer fluid will mini- TIP 10: Use a
Inline filters only should be used mize maintenance concerns and help Troubleshooting Tipsheet
with positive-displacement (gear-type) extend fluid life. Flushing fluid also is Table 1 shows a list of problems
pumps (figure 3). Never install an useful to remove particulate, sludge, that you may have with your system
inline filter on a system that uses a cen- some coked-on material and left and the possible causes. If you can
trifugal pump. A second filter in paral- behind, used heat transfer fluid prior to identify the causes, then you can sys-
lel (duplex) can be installed in place of recharging a system with new heat tematically work through them to get
the manual bypass for critical applica- transfer fluid during a fluid changeout. your system back to running smooth
tions such as high temperature electric Do not use water to clean out an and efficiently. PH
systems. assembled system or to pressure test
the system. Instead, use either a flush-
TIP 9: Clean the System ing fluid, the heat transfer fluid or inert Mark E. Smith is general manager at
with a Flushing Fluid gas. Also, pressurize the fluid with MultiTherm LLC, Devault, Pa. For more
A flushing fluid is intended for use in nitrogen rather than air to minimize information on MultiTherm’s heat transfer
startup or general maintenance of heat fluid oxidation. fluids:
transfer fluid systems. New systems When filling the system with the Call (610) 408-8361.
may contain mill scale, weld splatter, flushing fluid, slowly pump the fluid Email: techinfo@multitherm.com
slag, flux, quench oil, protective coat- into the system from the bottom up to Visit www.multitherm.com.

www.process-heating.com S E P T E M B E R 2 0 0 4 41

Anda mungkin juga menyukai