Anda di halaman 1dari 1

ANNEX A 33–29

A.1.1.4 There are many industrial applications that involve authority. For insurance purposes, an insurance inspection de-
routine use of small quantities of flammable or combustible partment, rating bureau, or other insurance company repre-
liquids (e.g., coatings, lubricants, adhesives) on a regular or sentative may be the authority having jurisdiction. In many
periodic basis. An example would be touch-up of manufac- circumstances, the property owner or his or her designated
tured articles using aerosol containers or small, portable spray agent assumes the role of the authority having jurisdiction; at
application equipment. The intent of this provision is to allow government installations, the commanding officer or depart-
such use without having to comply with the requirements of mental official may be the authority having jurisdiction.
NFPA 33.
A.3.2.4 Listed. The means for identifying listed equipment
A.1.1.5 This standard does not cover spray application opera- may vary for each organization concerned with product evalu-
tions that are conducted outdoors on buildings, bridges, ation; some organizations do not recognize equipment as
tanks, or similar structures. These situations occur only occa- listed unless it is also labeled. The authority having jurisdic-
sionally for any given structure and overspray deposits are not tion should utilize the system employed by the listing organi-
likely to present a hazardous condition. Also, the space where zation to identify a listed product.
there might be an ignitible vapor–air or dust–air mixture is
very limited due to atmospheric dilution. A.3.3.1 Ambient. Most lower explosive limit (LEL) (also
known as “lower flammable limit” or “LFL”) values are re-
A.1.1.6 The occasional use of small portable spray equipment ported at 25°C (77°F), although several are given at 100°C
or aerosol spray containers is not likely to result in hazardous (212°F). The LEL value decreases at higher temperatures, so it
accumulations of overspray. Therefore, such operations are is necessary that the LEL value for the particular solvent be
not within the scope of this standard. The following safe- corrected for the operating temperature of the spray booth or
guards, however, should be observed: spray room when operating above 25°C (77°F). See 12.6.8.3 of
(1) Adequate ventilation should be provided at all times, par- NFPA 86, Standard for Ovens and Furnaces, for calculation of the
ticularly where spray application is conducted in relatively correction factor. Note that NFPA 86 uses the term lower flam-
small rooms or enclosures. mable limit (LFL).
(2) Spray application should not be conducted in the vicinity A.3.3.2.3 Spray Area. For the purpose of this standard, the
of open flames or other sources of ignition. Either the authority having jurisdiction can define the limits of the spray
spray operation should be relocated or the source of igni- area in any specific case. The spray area in the vicinity of spray
tion should be removed or turned off. application operations will necessarily vary with the design
(3) Containers of coating materials, thinners, or other haz- and arrangement of the equipment and with the method of
ardous materials should be kept tightly closed when not operation. Where spray application operations are strictly con-
actually being used. fined to predetermined spaces that are provided with ad-
(4) Oily or coating-laden rags or waste should be disposed of equate and reliable ventilation (such as a properly designed
promptly and in a safe manner at the end of each day’s and constructed spray booth), the spray area ordinarily will
operations, due to the potential for spontaneous ignition. not extend beyond this space. When spray application opera-
(5) The same fundamental rules for area cleanliness and tions are not confined to an adequately ventilated space, then
housekeeping that are required for industrial spray appli- the spray area might extend throughout the room or building
cation operations should be observed. area where the spraying is conducted.
A.1.2.2 The requirements of this standard are intended to A.3.3.14 Spray Booth. Spray booths are manufactured in a
minimize the risk of fire and explosion; they are not intended variety of forms, including automotive refinishing, downdraft,
and might not be adequate to protect personnel from the open-face, traveling, tunnel, and updraft booths. This defini-
toxic or negative effects from exposure to the materials used. tion is not intended to limit the term spray booth to any particu-
A.3.2.1 Approved. The National Fire Protection Association lar design. The entire spray booth is part of the spray area. A
does not approve, inspect, or certify any installations, proce- spray booth is not a spray room.
dures, equipment, or materials; nor does it approve or evalu- A.3.3.15 Spray Room. The entire spray room is considered
ate testing laboratories. In determining the acceptability of part of the spray area. A spray booth is not a spray room.
installations, procedures, equipment, or materials, the author-
ity having jurisdiction may base acceptance on compliance A.4.1 Fires involving spray application operations and pro-
with NFPA or other appropriate standards. In the absence of cesses can be expected to develop rapidly and to generate
such standards, said authority may require evidence of proper copious quantities of heat and smoke. In sprinklered build-
installation, procedure, or use. The authority having jurisdic- ings, such fires can also result in the operation of a greater-
tion may also refer to the listings or labeling practices of an than-normal number of sprinklers. The following guidance is
organization that is concerned with product evaluations and is offered:
thus in a position to determine compliance with appropriate
(1) Operations and equipment should be arranged and lo-
standards for the current production of listed items.
cated so that there is adequate egress for personnel and
A.3.2.2 Authority Having Jurisdiction (AHJ). The phrase “au- adequate access for fire-fighting operations. Where spray
thority having jurisdiction,” or its acronym AHJ, is used in application operations are extensive, they should be lo-
NFPA documents in a broad manner, since jurisdictions and cated in a separate building or in an area that is separated
approval agencies vary, as do their responsibilities. Where pub- by fire-rated construction from all other operations or
lic safety is primary, the authority having jurisdiction may be a storage.
federal, state, local, or other regional department or indi- (2) Spray application operations that incorporate assembly lines
vidual such as a fire chief; fire marshal; chief of a fire preven- or conveyor systems present special problems. If conveyor
tion bureau, labor department, or health department; build- systems extend between separate buildings, a noncombus-
ing official; electrical inspector; or others having statutory tible or limited-combustible, sprinkler-protected enclosure

2011 Edition

Anda mungkin juga menyukai