Anda di halaman 1dari 3

Transformer Differential Relay (87T) Test Report

Model : SIPROTEC 7UT612 Make: Siemens

Serial No:

Location:

CT Data:

Location Primary Current in A Secondary Current in A


Transformer HV Bushing 300 5
Transformer LV Bushing 900 2.89

Power Transformer Data:

Power Transformer Rating 10/13.33 MVA


Rated Primary Current in 13.33 MVA
233.2 A
Base
Rated Secondary Current in 13.33 MVA
699.6 A
Base
Rated HV Voltage 33 kV
Rated LV Voltage 11 kV
Vector Group Dyn11
% Impedance 11.33%

Physical Inspection:

Visual Check for External Damage Found OK


Condition of Front HMI Found OK
Condition of Key Pad Found OK
Condition of LED Found OK

Measurement and Status Checks:

Analog Input (CT Current) Checks Found OK


Binary Input/Opto-Coupler Status Found OK
Binary Output/Contact/Command Relay Found OK
Front HMI LED Found OK
LED Labels:

LED Serial No Signal


1 Differential Trip HV Side
2 Differential Trip LV Side
3 External Trip
4 External Trip
5 General Over Current Trip
6 Phase Over Current Trip
7 3I0 Trip (Residual O/C Trip)

Functions Configured in the Relay (Base on Function Availability):

Serial No Function Name


1 Differential Function (87T)
2 HV Phase O/C Function (51)
3 HV Phase Residual O/C (51N)

Test of HV Differential Function:

Phase Set I/In Operated at I Delay Remark


R 0.30 1.13 A 28 ms OK
Y 0.30 1.13 A 28 ms OK
B 0.30 1.14 A 29 ms OK

Test of LV Differential Function:

Phase Set I/In Operated at I Delay Remark


R 0.30 0.63 A 29 ms OK
Y 0.30 0.64 A 29 ms OK
B 0.30 0.63 A 29 ms OK

Test of Phase O/C Function (DMT):

Phase Set I Set t Operated at I Delay Remark


R 4.0 A 500 ms 3.97 A 504 ms OK
Y 4.0 A 500 ms 3.97 A 503 ms OK
B 4.0 A 500 ms 3.98 A 504 ms OK
Test of Residual O/C Function (DMT):

Phase Set I Set t Operated at I Delay Remark


R 1.5 A 400 ms 1.52 A 402 ms OK
Y 1.5 A 400 ms 1.49 A 403 ms OK
B 1.5 A 400 ms 1.51 A 403 ms OK

Differential Stability Check: Found stable at load condition and external faults.