Anda di halaman 1dari 7

Available online at www.sciencedirect.

com

ScienceDirect
Solar Energy 96 (2013) 187–193
www.elsevier.com/locate/solener

Power conditioning system for grid-connected photovoltaic system


Xin Tang a,⇑, K.M. Tsang b, W.L. Chan b
a
Department of Electrical Engineering, Changsha University of Science and Technology, Changsha, Hunan 410076, PR China
b
Department of Electrical Engineering, Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong, China

Received 30 August 2012; received in revised form 10 July 2013; accepted 20 July 2013
Available online 12 August 2013

Communicated by: Associate Editor Elias K. Stefanakos

Abstract

This study develops a new control strategy for an expandable grid-connected photovoltaic (PV) system. The proposed system per-
forms dual functions of a PV generation and an active power filter, or either one. To this end, the grid current, instead of output current
of the converter, is shaped to be a sinusoidal current in phase (or opposite phase) with the grid voltage. Furthermore, its reference current
is generated in multiplying the voltage loop controller output by the grid voltage waveform, and therefore non-active components anal-
ysis for harmonics elimination and reactive power compensation in the conventional design is not necessary. As a result, the algorithm is
simple and easy to implement, and only one sensor for current detection plus two voltage sensors are required. Experimental results ver-
ified the effectiveness of the proposed method.
Ó 2013 Elsevier Ltd. All rights reserved.

Keywords: Photovoltaic system; Active power filter; Non-active components analysis

1. Introduction 2009), however, the harmonics and the reactive current


produced by the local nonlinear load will inject to the grid.
Interest in renewable energy is increasing due to concerns Consequently, the total harmonic distortion (THD) of the
about global warming, air quality and sustainability. Photo- grid current iS(t) is high and the power factor is low.
voltaic technology is an important technology for the large- In order to solve the problem of power quality produced
scale adoption of a renewable energy source. The power flow by the nonlinear load using the PCS, two independent con-
between the PV array and the grid is often controlled by a trollers have been designed for PCS wherein the PV system
power conditioning system (PCS), which should be reliable can act as a solar generation on sunny days and an active
and inexpensive. power filter on rainy days (Kuo et al., 2003). In contrast,
An example of single-stage grid-connected PV systems, a single controller was designed for the PCS to provide
which consists of solar array, input capacitor C, single- non-active power of nonlinear load in addition to active
phase inverter, filter inductor L, is shown in Fig. 1 (Kim power supply (Calleja and Jimenez, 2004; Koen et al.,
et al., 2006). To obtain the high-quality power flow, the 2004; Yu et al., 2005; Tsengenes et al., 2011). In addition,
output currentiU(t) of PCS is often controlled to be a sinu- an alternative harmonic analysis using adaptive neural fil-
soidal current in opposite phase with the grid voltage vS(t) tering was developed for a single-phase distributed genera-
(Choi and Lai, 2010; Libo et al., 2007; Kwon et al., 2006; tion system to compensate the utility current harmonics
Gonzalez et al., 2007; Kwon et al., 2008; Kim et al., (Cirrincione et al., 2008).
The above distribution generations with integrated
active filter are generally required to measure and analyze
⇑ Corresponding author. Address: Chiling Road 45, Changsha, Hunan
the load current to acquire the information of non-active
410076, PR China. Tel.: +86 731 82318966.
E-mail address: tangxin_csu@163.com (X. Tang). power components.

0038-092X/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.solener.2013.07.021
188 X. Tang et al. / Solar Energy 96 (2013) 187–193

Fig. 3. Current, power, and power derivative of the PV array versus


Fig. 1. A single-stage grid-connected PV system. voltage.

Unlike the conventional methods, the proposed method The inner loop is the current control loop. Its function is
does not need harmonics analysis. In this paper, a double- to shape the grid current into a sinusoidal in phase (or
loop with a voltage loop outside an inner current loop is opposite phase) with the grid voltage. To this end, a cur-
designed. The grid current, not the output current of PCS rent sensor is placed at the grid terminals and this current
in the aforementioned methods, is controlled to be a sinu- is used as the feedback signal in the current control loop. It
soidal current in phase (or opposite phase) with the grid is worth mentioning that current sensor is not required at
voltage using the repetitive control algorithm. Further- the load terminal or at the filter inductor. In this case,
more, the voltage controller is developed. In the voltage the load current is seen as a disturbance signal for the grid
loop, the reference current is generated in multiplying the current control loop, so, if the current control loop is prop-
voltage loop controller output by the supply voltage wave- erly designed to attenuate its disturbance in a sufficiently
form. As a result, the algorithm is simple and easy to imple- large frequency band then the performance specification
ment, and only one sensor for current detection plus two will be achieved in spite of the disturbance phase
voltage sensors are required. The experimental results will characteristic.
be presented to verify the excellent performance of the pro- The outer control loop is the voltage control loop. Its
posed method. main function is to maintain the DC bus voltage close to
the reference value tracking the maximum power point
2. Controller structure (MPP). In this manner, controlling the DC voltage level
is equivalent to perform an active power balance for the
The proposed controller, which is composed of two con- whole system. When the solar array injects active power
trol loops, is shown in Fig. 2 where a is a constant, iS(t) is to the DC capacitor C, it will accumulate the DC voltage
the grid current and ir(t) is its reference signal, vPV(t) is the level while the PCS will maintain the voltage level by trans-
DC bus voltage and vr(t) is its reference signal, Vdc is the mitting the active power to the grid. On the contrary, when
initial voltage and DVdc is the expected change quantity there is no irradiance, the PCS will maintain the voltage le-
of the DC voltage computed by the maximum power point vel by absorbing power from the grid for acting as an active
tracking (MPPT) algorithm. power filter (APF). Since the inner current loop controls
the grid current and its reference is the output of the voltage
controller multiplied by a sinusoidal carrier signal avS(t) in
phase with the grid voltage, it is not necessary to calculate
the harmonics component and the reactive power compo-
nent of the load current and a phase-locked-loop circuit
is not required.

3. MPPT algorithm

The aim of any MPPT algorithm is to extract the


maximum power from the PV array. Usually, the condition
op/ov = 0 is adopted to locate this operating point, i.e., (op/
ov) > 0 means that the operating point is on the left side of
MPP of the P–V characteristic curve shown in Fig. 3 and
(op/ov) < 0 means that the operating point is on the right side
of the P–V characteristic curve.
Based on (Casadei et al., 2006) the MPPT algorithm is
Fig. 2. Controller structure. shown in Fig. 4. When (op/ov) > 0, the integrator increases
X. Tang et al. / Solar Energy 96 (2013) 187–193 189

Fig. 4. MPPT algorithm.

its output DVdc, and the reference vr(t) moves toward MPP. The transfer function of the current controller is written
On the contrary, when (op/ov) < 0, the integrator decreases as
DVdc, and the reference vr(t) moves toward MPP. The rate U r ðsÞ 1
of change of vr(t) is set by the gain K determined by the ¼ ð1Þ
Ec ðsÞ 1  K q ðsÞesTd
slope of op/ov at MPP.
where Td is the period of the input and Kq(s) is a low-pass
4. Current control loop filter. The low-pass filter Kq(s) is used to improve the stabil-
ity of the close-loop system and has free parameters to be
4.1. Repetitive control designed.

If the reference signal is a periodic signal, conventional 4.2. Parameters design of current controller
PI is difficult to track the waveform of the input reference
and to eliminate the effects of the disturbance. Repetitive The characteristic equation of the current closed-loop
control (Tsai and Yao, 2002) originated from the internal system is given by
model principle provides a solution to eliminate periodic
1 þ GO ðsÞ  K q ðsÞesTd ¼ 0 ð2Þ
error occurred in dynamic systems. A repetitive controller
can be viewed as a periodic waveform generator, aug- where GO(s) = Gi(s)/Ls.
mented within the control loop of a control system. That Define the regeneration spectrum as
is a closed-loop regulated by a feedback controller, so that
RðwÞ ¼ jK q ðjwÞS O ðjwÞj ð3Þ
the periodic error can be eliminated.
In order to remove the error due to the period input and where SO(jw) = 1/(1 + GO(jw)) is the sensitivity function of
disturbance of the fundamental and harmonics, a plug-in the original unity feedback system.
repetitive controller (Tang et al., 2011) is adopted as the It is easy to ensure that 1 + GO(s) = 0 has no zeros on
current controller. The block diagram representation of the right half of the s-plane by adjusting the constant
the current loop control is shown in Fig. 5 where ec(t) is KPWM. Based on the above condition, if R(w) < 1 for all
the error between the reference current and the grid cur- w, the closed-loop system of Fig. 5 is stable for all values
rent, ur(t) is the output of the current controller, vU(t) is of Td. The effect of the free design parameter of Kq(s) on
the output voltage of the converter, Gi(s) is the transfer the stability of the repetitive control system is clearly
function of the converter, vS(t) and iL(t), which are the illustrated by (3).
disturbance in the current loop, are the grid voltage and Let Kq(s) be a first-order filter with the form
the load current respectively. In this paper, the power K q ðsÞ ¼ 1=ð1 þ sq sÞ ð4Þ
converter controlled by voltage-mode control acts as a
voltage amplifier with the transfer function represented and its magnitude–frequency characteristics, which satisfy
by Gi(s) = Kpwm/(1 + sps), where Kpwm is the ratio of kK q ðsÞk1 6 1, are shown in Fig. 6 . The magnitude–fre-
the DC bus voltage to the amplitude of the carrier signal quency characteristics of S O ðsÞ, which satisfy kS O ðsÞk1 ¼
of the pulse width module and sp is the time constant deter- M s and jS O ðjws Þj ¼ 1 , are also shown in Fig. 6
mined by the switching time of the power electronics in the From (3), the Kq(s) is designed as
converter. jK q ðjws Þj ¼ j1=ð1 þ jws sq Þj < 1=M s ð5Þ

Fig. 5. Block diagram of current control loop.


190 X. Tang et al. / Solar Energy 96 (2013) 187–193

where fnm is the maximum frequency of characteristic har-


monics of the load current which must be eliminated.

5. Voltage control loop

It is known that the whole system is always keeping


active power balance, i.e.
P S ðtÞ ¼ P L ðtÞ þ P U ðtÞ ð13Þ
where PS(t), PL(t) and PU(t) are the average power sup-
plied/absorbed by the grid, consumed by the load and sup-
plied/consumed by the PCS within a fundamental period.
Assuming that the grid current iS(t) can track the refer-
ence signal ir(t) then
iS ðtÞ ¼ ir ðtÞ ¼ avS ðtÞwðtÞ ð14Þ
Fig. 6. Magnitude–frequency characteristics of the sensitivity function where x(t) is the output of the voltage controller. There-
and the low-pass filter. fore, the average power supplied/absorbed by the grid
within a period is written as
Z Z
1 T 1 T
P S ðtÞ ¼ vS ðtÞiS ðtÞ ¼ awðtÞv2S ðtÞ ð15Þ
T 0 T 0
where T is the fundamental period. As the DC voltage
change slowly, x(t) can be considered as a constant within
Fig. 7. Block diagram of voltage control loop.
a period. Therefore, PS(t) can be approximated as
P S ðtÞ  awðtÞV 2S
This characterizes the basic criterion on the stability for where VS is the root-mean-square (RMS) of the grid
design of Kq(s). voltage.
In addition to the stability, it is interest of the tracking Neglecting the power loss of the PCS, the change quan-
performance of the current loop. From Fig. 5, the follow- tity DvPV of the capacitor C is determined by
ing transfer functions are obtained. Z t
1 2
I S ðsÞ Gi ðsÞ ðP U ðtÞ þ P PV ðtÞÞdt ¼ CðV PV þ DvPV ðtÞÞ
Glr ðsÞ ¼ ¼ ð6Þ 0 2
I r ðsÞ sLð1  K q ðsÞesTd Þ þ Gi ðsÞ
1
 CV 2pv ð16Þ
I S ðsÞ 1  K q ðsÞesTd 2
Gls ðsÞ ¼ ¼ ð7Þ
V S ðsÞ sLð1  K q ðsÞesTd Þ þ Gi ðsÞ where PPV(t) is the power generated PV array andVPV is a
I S ðsÞ sLð1  K q ðsÞe Þ sTd constant.Using Laplace transform and neglecting the term
Gll ðsÞ ¼ ¼ ð8Þ Dv2PV ðtÞ, (16) is rewritten as
I L ðsÞ sLð1  K q ðsÞesTd Þ þ Gi ðsÞ
DvPV ðsÞ ¼ ðP U ðsÞ þ P V ðsÞÞ=sCV PV ð17Þ
where Glr(s), Gls(s) and Gll(s) are the transfer function of
the reference current ir(t), the disturbance vs(t) and the dis- The block diagram of the voltage loop is shown in
turbance iL(t), respectively. Fig. 7, where GCV(s) is the transfer function of the voltage
It is known that Kq(s)  1 at 0 6 x < xc where xc is the controller and Gv ðsÞ ¼ 1=sCV PV .
cut-off frequency of the low-pass filter. Using the Euler A classical PI controller is adopted to regulate the DC
Equation of ejx ¼ cos x þ j sin x , we obtains the relation voltage to its reference. Consider a PI controller of the
equations: form
Glr ðsÞ  1 at x ¼ 2pn=T d < xc ; n ¼ 1; 2; 3    ð9Þ KI
GcV ðsÞ ¼ K P þ ð18Þ
s
Gls ðsÞ  0 at x ¼ 2pn=T d < xc ; n ¼ 1; 2; 3    ð10Þ
The voltage loop characteristic equation is given by
Gll ðsÞ  0 at x ¼ 2pn=T d < xc ; n ¼ 1; 2; 3    ð11Þ
DðsÞ ¼ CV PV s2 þ aV 2S K P s þ aV 2S K I ¼ 0 ð19Þ
Thus, to obtain small track error to the reference current
and eliminate the effect of the disturbance, an upon bound with the undamped natural frequency
of sq can be found as rffiffiffiffiffiffiffiffiffiffiffi
aK I
xn ¼ V S ð20Þ
sq ¼ 1=xc < 1=2pfnm ð12Þ CV PV
X. Tang et al. / Solar Energy 96 (2013) 187–193 191

Table 1 or
Parameters of the PV array.
Parameters
aV 2S K P
n¼ ð21Þ
Rated power 0.5 KW
2xn CV PV
Rated voltage 200 V If the bandwidth of the voltage loop is set to 1/n times
Rated current 2.5 A
Open-circuit voltage 250 V
the supply frequency fv, the integral gain KI becomes
Open-circuit current 3A
ð2pfv Þ2 CV PV
KI ¼ ð22Þ
n2 aV 2S
Table 2 If the damping ratio of the voltage loop is set to one, the
Parameters of the PCS.
proportional gain KP becomes
Parameters
4pfv CV PV
Grid voltage 110 V, 50 Hz KP ¼ ð23Þ
Filter inductor 1 mH naV 2S
IPM module PM15CSJ060
Switching frequency 15 KHz
DC capacitor 470 lF 6. Experimental results
Current control parameters sq ¼ 0:0003
Voltage control parameters n = 10, Kp = 0.6, KI = 10
DSP chip TMS320F2808
To verify the effectiveness of the proposed method, an
experimental setup was built and was tested under different
conditions. The following parameters of the PV array were
and the damping ratio is governed by listed in Table 1.
As the voltage of the PV array at MPP always varied
around 200 V, the initial voltage reference Vdc was selected
aV 2S K P as 200 V. To obtain good dynamic performance, the gain K
2nxn ¼
CV PV in MPPT algorithm was set as 1. The Td is selected as 20 ms

Fig. 8. Performance of the proposed system acting as a PV generation alone at low irradiance (a) waveforms (channel 1: the grid voltage, channel 2: the
grid current, channel 4: the DC voltage); and (b) spectrum of the grid current.

Fig. 9. Local nonlinear load (a) waveforms (channel 1: the grid voltage, channel 2: the grid current, channel 4: the DC voltage); and (b) spectrum of the
grid current.
192 X. Tang et al. / Solar Energy 96 (2013) 187–193

Fig. 10. Performance of the proposed system acting as an APF alone (a) waveforms (channel 1: the grid voltage, channel 2: the grid current, channel 4: the
DC voltage); and (b) spectrum of the grid current.

Fig. 11. Performance of the proposed system performing dual functions simultaneously (a) waveforms (channel 1: the grid voltage, channel 2: the grid
current, channel 4: the DC voltage); and (b) spectrum of the grid current.

Then, the proposed system, acting as an APF alone, was


tested. Fig. 9 shows the waveform and spectrum of a local
nonlinear load current. The RMS load current was 1.61 A.
There were clearly a lot of high-order harmonics and the
current THD was 61.8%. The power factor was 0.76. After
the proposed system was added, the experimental plot was
shown in Fig. 10. It can be seen that the high-order har-
monics had clearly been reduced and the current THD
was 5.6%. The power factor of overall system was 0.99.
The RMS grid current was 1.92 A (it was greater than
Fig. 12. Dynamic performance of the proposed system (channel 1: the the RMS load current by an amount used to support the
grid voltage, channel 2: the grid current, channel 4: the DC voltage). DC voltage of PCS).
Furthermore, the proposed system, which performed
for the foundational frequency is 50 Hz. Let a be 0.01 such dual functions simultaneously, was tested. Fig. 11 shows
that the peak value of aVs(t) was about 1.56 V. The setting performance of the proposed system with a local nonlinear
ofa was set to make sure that the multiplier output would load at low irradiance. It can be seen that the proposed sys-
not be easily saturated. Since the DC voltage VPV(t) varied tem effectively performed dual functions. The power factor
around 200 V, the constant VPV was selected as 200 V. The of overall system was 0.97. The grid current THD was 6.7%
other parameters of the PCS were listed in Table 2. and its RMS reduced to 0.90 A.
The proposed system, acting as a PV generation alone, In addition, the dynamic performance of the proposed
was firstly tested. Fig. 8 shows performance of the PV gen- system was tested. Fig. 12 shows performance of the pro-
eration at low irradiance. The spectrum was obtained from posed system with a sudden change of the irradiance. A
Fluke 41B. It can be seen that the grid current was sinusoi- voltage spike was caused by the sudden change of the irra-
dal and in the opposite phase with the grid voltage. The diance. As the value of DC voltage going down and the
RMS grid current was 0.77 A. The power factor of system RMS of the grid current increasing, the proposed system
was 0.99, and the current THD was 3.71%. arrived at another balance point after around 7 cycles.
X. Tang et al. / Solar Energy 96 (2013) 187–193 193

7. Conclusion Casadei, Domenico, Grandi, Gabriele, Rossi, Claudio, 2006. Single-phase


single-stage photovoltaic generation system based on a ripple corre-
lation control maximum power point tracking. IEEE Trans. Energy
A novel unified control method for PV system is pro- Convers. 53, 562–567.
posed in this paper. The proposed system can perform dual Choi, Woo-Young, Lai, Jih-Sheng, 2010. High-efficiency grid-connected
functions, acting as a PV generation and as an APF, or photovoltaic module integrated converter system with high-speed
either one. The grid current, which can replace output cur- communication interfaces for small-scale distribution power genera-
rent of the PCS, is controlled in the PV system and can be tion. Sol. Energy 84 (4), 636–649.
Cirrincione, Maurizio, Pucci, Marcello, Vitale, Gianpaolo, 2008. A single-
shaped to be a sinusoidal current in phase (or opposite phase DG generation unit with shunt active power filter capability by
phase) with the grid voltage using a repetitive controller. adaptive neural filtering. IEEE Trans. Ind. Electron. 55, 2093–2110.
The experimental results show that the proposed system Gonzalez, R., Lopez, J., Sanchis, P., Marroyo, L., 2007. Transformerless
can not only compensate the harmonic current and the inverter for single-phase photovoltaic systems. IEEE Trans. Power
reactive current produced by the local non-linear load, Electron. 22, 693–697.
Kim, Il-Song, Youn, Yung-Joong, 2006. New maximum power point
but also reduce the grid current. Controlling the DC volt- tracker using sliding-mode observer for estimation of solar array
age level can be equivalent to perform an active power bal- current in the grid-connected photovoltaic system. IEEE Trans. Ind.
ance for the whole system, and then, the reference current Electron. 53, 1027–1035.
can be generated in multiplying the voltage loop controller Kim, Seul-Ki, Kim, Eung-Sang, Jeon, Jin-Hong, 2009. Modeling and
output by the grid voltage waveform, and then harmonics simulation of a grid-connected PV generation system for electromag-
netic transient analysis. Sol. Energy 83 (5), 664–678.
analysis in the conventional design is not necessary. Macken, Koen J.P., Vanthournout, Koen, Van deneybus, Jeroen, 2004.
The apparent power of the proposed system is set to the Distributed control of renewable generation units with integrated
square root of sum of square of the maximum active power active filter. IEEE Trans. Power Electron. 19, 1353–1360.
of the PV array and reactive power of local nonlinear load. Kuo, Yeong-Chau, Liang, Tsorng-Juu, Chen, Jiann-Fuh, 2003. A high-
The reactive power of local nonlinear load can be estimated efficiency single-phase three-wire photovoltaic energy conversion
system. IEEE Trans. Ind. Electron. 50, 116–122.
since the local load is normally planned and its power fac- Kwon, J.M., Nam, K.H., Kwon, B.H., 2006. Photovoltaic power
tor can be estimated. So, the power converter is not easy to conditioning system with line connection. IEEE Trans. Ind. Electron.
overload. It needs to be point out that the redundant 53, 1048–1054.
capacity caused by low irradiation may not be efficiently Kwon, Jung-Min, Kwon, Bong-Hwan, Nam, Kwang-Hee, 2008. Three-
utilized, however, the capacity of the proposed system is phase photovoltaic system with three-level boosting MPPT control.
IEEE Trans. Power Electron. 23, 2319–2327.
smaller than the sum of capacities of two independent Libo, W., Zhengming, Z., Jianzheng, L., 2007. A single-stage three-phase
equipments – a PV generator and an APF to achieve the grid-connected photovoltaic system with modified MPPT method and
same purpose. reactive power compensation. IEEE Trans. Energy Convers. 22, 881–
886.
Acknowledgment Tang, X., Tsang, K.M., Chan, W.L., 2011. Active power filter using
nonlinear repetitive controller. Int. J. Control Autom. Syst. 9 (1), 132–
138.
The authors gratefully acknowledge the support of the Tsai, M.-C., Yao, W.-S., 2002. Design of a plug-in type repetitive
National Natural Science Foundation of China (No. controller for periodic inputs. IEEE Trans. Control Syst. Technol. 10,
51277013). 547–555.
Tsengenes, Georgios, Adamidis, Georgios, 2011. A multi-function grid
connected PV system with three level NPC inverter and voltage
References oriented control. Sol. Energy 85 (11), 2595–2610.
Yu, Huajun, Pan, Junmin, Xiang, An, 2005. A multi-function grid-
Calleja, Hugo, Jimenez, Humberto, 2004. Performance of a grid connected connected PV system with reactive power compensation for the grid.
PV system used as active filter. Energy Convers. Manage. 45, 2417– Sol. Energy 79 (1), 101–106.
2428.

Anda mungkin juga menyukai