1.) Purpose: To check the effect of proposed roof louver on parapet roof.
2.) Procedure: The louver with below configuration & applied wind loads as per ASCE-07/10
with following parameters:
where
Kd = wind directionality factor defined in Section 26.6
= 0.85 (open signs) 1.30m
Kz = velocity pressure exposure coefficient defined in Section 30.3.1
=1.09
Kzt = topographic factor defined in Section 26.8
=1.0 as per (26.8.2)
V = basic wind speed from Section 26.5
Wind load acting on parapet due to wind load as extracted from approved calculations:
INPUT CELL
fc' = 27.6 N/mm2
fy = 420 N/mm2
b= 1000 mm
cvr.
d= 110 mm = 40
h
Mu = 9.06 KN-m = 150
Vu = 7.25 KN
FLEXURE DESIGN
Element Type :
Mu = 9.06 kN-m
As = ρbd = 220
ρ = 1/m {1-√(1 - Ru / F )} = 0.002
ρ(max)
= 0.64 (0.85*fc'/fy) (600/(600+fy))≤0.025 = 0.0210
m= fy / 0.85 fc' = 17.90
0.3825
F= fc' = 10.557
Ru = Mu / bd2 = 0.75
UNDER R/F
Dia of bar =
Area of
bar = 78.5 mm2
As
(reqd.) = 270 mm2
mm
Spacing (for slab) = 291 c/c
As provided = 270.0 mm2
5.) Conclusion: Parapet wall section is found adequate and hence safe.