3VT5 Molded Case Circuit Breakers up to 1600 A


Catalog - Accessories and Components
Circuit breakers · Switch disconnectors

■ Selection and ordering data for accessories


Rated current Set current of the S function short- Operating cur- DT Article No. PS*/ Weight
In inverse-time circuit protection rent of the instan- P. unit per PU
delayed overload (short-time taneous short- approx.
trip units "L" Ir delayed) "S" Isd circuit releases "I"
Ii
A A A kg
Electronic trip units (ETU)
Distribution protection, ETU DP, LI function
• For protecting lines and trans-
formers
630 250 ... 630 800 ... 10000 3VT9563-6AC00 1 unit 0.670
1000 400 ... 1000 1250 ... 15000 3VT9510-6AC00 1 unit 0.590
1250 500 ... 1250 1500 ... 18000 3VT9512-6AC00 1 unit 0.529
1600 630 ... 1600 2000 ... 20000 3VT9516-6AC00 1 unit 0.533
Motor/generator protection, ETU MP, LI function
• Provides protection for motors and generators
• Suitable also for protecting lines and transformers
630 250 ... 630 800 ... 10000 3VT9563-6AP00 1 unit 0.500
1000 400 ... 1000 1250 ... 15000 3VT9510-6AP00 1 unit 0.500
1250 500 ... 1250 1500 ... 18000 3VT9512-6AP00 1 unit 0.530
1600 630 ... 1600 2000 ... 20000 3VT9516-6AP00 1 unit 0.590
Universal protection, ETU UP LSI function
• Provides protection for complicated loads or loads
not specified in advance
630 250 ... 630 2 ... 10 x IR 800 ... 10000 3VT9563-6AD00 1 unit 0.500
1000 400 ... 1000 2 ... 10 x IR 1250 ... 15000 3VT9510-6AD00 1 unit 0.593
1250 500 ... 1250 2 ... 10 x IR 1500 ... 18000 3VT9512-6AD00 1 unit 0.500
1600 630 ... 1600 2 ... 10 x IR 2000 ... 20000 3VT9516-6AD00 1 unit 0.500
Switch disconnector unit
1600 Switch discon- 3VT9516-6DT00 1 unit 0.400
nector unit

5 Signalling unit
Signalling unit for 3VT9500-6AE00 1 unit 0.670
trip units ETU DP,
MP and UP

Rated control supply voltage Us DT Article No. PS*/ Weight


P. unit per PU
approx.
kg
Auxiliary switches
AC 60 ... 500 V/DC60 ... 240 V 3VT9500-2AF10 1 unit 0.041
AC/DC 5 ... 60 V 3VT9500-2AF20 1 unit 0.041

Shunt trip units


AC/DC 24 V 3VT9500-1SF00 1 unit 0.199
AC/DC 48 V 3VT9500-1SG00 1 unit 0.220
AC/DC 110 V 3VT9500-1SH00 1 unit 0.220
AC 230 V/DC 220 V 3VT9500-1SJ00 1 unit 0.237
AC 400 V 3VT9500-1SK00 1 unit 0.220
AC 500 V 3VT9500-1SL00 1 unit 0.220

Undervoltage trip units


AC/DC 24 V 3VT9500-1UF00 1 unit 0.220
AC/DC 48 V 3VT9500-1UG00 1 unit 0.220
AC/DC 110 V 3VT9500-1UH00 1 unit 0.220
AC 230 V/DC 220 V 3VT9500-1UJ00 1 unit 0.220
AC 400 V 3VT9500-1UK00 1 unit 0.220
AC 500 V 3VT9500-1UL00 1 unit 0.220

* You can order this quantity or a multiple thereof.


5/4 Siemens LV 36 · 2014
© Siemens AG 2014

3VT5 Molded Case Circuit Breakers up to 1600 A


Technical Information - Accessories and Components
Trip units
Trip units ETU DP - Distribution protection Adjustable specifications
• Provides protection for lines and transformers Article No. Rated current Overload Restart Instantaneous
The 3VT95..-6AC00 trip unit is intended only for In protection Ir short circuit
protection Ii
3VT5716-3AA3.-0AA0 switching units. Operation of the trip unit
is controlled by a microprocessor. The trip unit is fitted with a A A kA
thermal memory that can be disabled by turning the switch on 250, 260 0.8
the front panel from position T(t) to position T(0). After having di-
sabled the thermal memory, the thermal tripping function re- 275, 290 1.5
mains active. 305, 315 2
A practical advantage of the trip unit is a specially designed 3VT9563-6AC00 630 345, 360 T(0) 2.5
tripping characteristic that provides for optimal exploitation of
400, 435 T(t) 4.5
transformers up to 1.5 In.
455, 480 6
Another advantage of this trip unit is the simple adjustment of the
tripping characteristic. Set-up includes only rated current and 500, 550 7.5
the tripping level of the short-circuit trip unit. Reaching 80% and 575, 630 10
110% of Ir is indicated by LED diodes on the front panel denoted
400, 435 1.25
as I > 80% of Ir and I > 110% of Ir. Located on the lower part of
the trip unit cover are four photocells for communicating with the 455, 480 2
3VT9500-6AE00 signalling unit. 500, 550 3
Tripping characteristics 3VT9510-6AC00 1000 575, 630 T(0) 5
NSO0_00458
10000 630, 685 T(t) 7
Ir
5000 min. max.
720, 760 9
t [s] Ir Ii
2000 800, 870 12
1000 910, 1000 15
500
500, 550 1.5
200
577, 610 3
100
L 630, 685 5
50
3VT9512-6AC00 1250 722, 760 T(0) 7
20
800, 866 T(t) 9
10
In = 630 A
In=630A
5 909, 1000 12
In=1000A
In = 1000 A 3 3
In = 1250 A
In=1250A

5
2 1100, 1155, 15
In = 1600 A
In=1600A
1 1200, 1250 18
0.5 630, 685 2
I
0.2 720, 800 4
0.1
870, 910 6
0.05 0.8 1.5 2.0 2.5 4.5 6.0 7.5 10
3VT9516-6AC00 1600 1000, 1100 T(0) 8
0.02 In = 630 A I i [kA]
1155, 1200 T(t) 11
0.01
0.1 1250, 1300 14
0.05 1.25 2.0 3.0 5.0 7.0 9.0 12 15
1375, 1445 17
0.02 In = 1000 A I i [kA] 1500, 1600 20
0.01
0.1
0.05 1.5 3.0 5.0 7.0 9.0 12 15 18

0.02 In = 1250 A I i [kA]


0.01
0.1
0.05 2.0 4.0 6.0 8.0 11 14 17
20
0.02 In = 1600 A I i [kA]
0.01
0.1 0.2 0.5 1 2 5 10 20 50
x In

NSO0_00577

* You can order this quantity or a multiple thereof.


5/18 Siemens LV 36 · 2014
© Siemens AG 2014

3VT5 Molded Case Circuit Breakers up to 1600 A


Technical Information - Accessories and Components
Trip units
Trip units ETU MP - Motor protection
• Provides protection of motors and generators Adjustable specifications
• Can protect lines and transformers Article No. Rated Overload tt (7.2 x Ir) Restart Instantane-
The 3VT95..-6AP00 trip unit is intended only for current protection Ir ous short
In circuit pro-
3VT5716-3AA3.-0AA0 switching unit. The operation of the trip tection Ii
unit is controlled by a microprocessor. The trip unit is equipped
with a thermal memory that can be disabled by turning a switch A A S kA
on the front panel from position T(t) to position T(0). After having 250, 260 1 (TV 1) 0.8
disabled the thermal memory, the thermal trip unit remains ac-
tive. 275, 290 3 (TV 3) 1.5
305, 315 10 (TV 10) 2
A practical advantage of the trip unit is a specially designed
tripping characteristic that provides for optimal exploitation of 3VT9563-6AP00 630 345, 360 30 (TV 30) T(0) 2.5
transformers up to 1.5 In. 400, 435 3 (M 3) T(t) 4.5
It is possible to set a total of 8 characteristics on the trip unit. 455, 480 8 (M 8) 6
From these, in mode "M", there are 4 characteristics for motor
500, 550 15 (M 15) 7.5
protection and another 4 characteristics in mode "TV" for protec-
ting transformers and lines. The shape of each characteristic 575, 630 25 (M 25) 10
can be changed using a selector switch. 400, 435 1 (TV 1) 1.25
When one or two phases fail, in the M-characteristic mode, the 455, 480 3 (TV 3) 2
switch will open with a 4 s delay (so-called undercurrent trip-
ping). 500, 550 10 (TV 10) 3
3VT9510-6AP00 1000 575, 630 30 (TV 30) T(0) 5
Another parameter for adjusting the trip unit is the rated current,
which is adjusted in a range of 0.4 to 1.0 of In and the short-cir- 630, 685 3 (M 3) T(t) 7
cuit tripping level. Reaching 80% and 110% of Ir is indicated by 720, 760 8 (M 8) 9
LED diodes on the front panel denoted as I > 80% of Ir and I >
110% of Ir. Located on the lower of the trip unit cover are four 800, 870 15 (M 15) 12
photocells for communicating with the 3VT9500-6AE00 910, 1000 25 (M 25) 15
signalling unit.
500, 550 1 (TV 1) 1.5
577, 610 3 (TV 3) 3
630, 685 10 (TV 10) 5
3VT9512-6AP00 1250 722, 760 30 (TV 30) T(0) 7
800, 866 3 (M 3) T(t) 9
909, 1000 8 (M 8)
1100, 1155, 15 (M 15)
12
15
5
1200, 1250 25 (M 25) 18
630, 685 1 (TV 1) 2
720, 800 3 (TV 3) 4
870, 910 10 (TV 10) 6
3VT9516-6AP00 1600 1000, 1100 30 (TV 30) T(0) 8
1155, 1200 3 (M 3) T(t) 11
1250, 1300 8 (M 8) 14
1375, 1445 15 (M 15) 17
1500, 1600 25 (M 25) 20

NSO0_00578

Siemens LV 36 · 2014 5/19


© Siemens AG 2014

3VT5 Molded Case Circuit Breakers up to 1600 A


Technical Information - Accessories and Components
Trip units
Tripping characteristic ETU MP
NSO0_00459 NSO0_00460
10000 Ir 10000 Ir
min. max.
TV min. max.
M
5000 5000
t [s] Ir tr Ii t [s] Ir tr Ii
2000 2000
1000 1000
500 500 25

200 200
L tr L tr
100 100
30
50 50
30
25
20 20 15 15
10 10 10 10
In = 630 A In = 630 A 8 8
5 In = 1000 A 5 In = 1000 A
3 3 3 3
In = 1250 A In = 1250 A
2 2
In = 1600 A In = 1600 A
1 1 1 1
0.5 0.5
I I
0.2 0.2
0.1 0.1
0.05 0.05
In = 630 A 0.8 1.5 2.0 2.5 4.5 6.0 7.5 10 I i [kA] In = 630 A 0.8 1.5 2.0 2.5 4.5 6.0 7.5 10 I i [kA]
0.02 0.02
0.01 0.01
0.05 0.05
In = 1000 A 1.25 2.0 3.0 5.0 7.0 9.0 12 15 I i [kA] In = 1000 A 1.25 2.0 3.0 5.0 7.0 9.0 12 15 I i [kA]
0.02 0.02
0.01 0.01
0.05 18
0.05 18
In = 1250 A 1.5 3.0 5.0 7.0 9.0 12 15 I i [kA] In = 1250 A 1.5 3.0 5.0 7.0 9.0 12 15 I i [kA]
0.02 0.02
0.01 0.01
0.05 17 0.05 17
In = 1600 A 2.0 4.0 6.0 8.0 11 14 20 I i [kA] In = 1600 A 2.0 4.0 6.0 8.0 11 14 20 I i [kA]
0.02 0.02
0.01 0.01
0.1 0.2 0.5 1 2 5 10 20 50 0.1 0.2 0.5 1 2 5 10 20 50
x In x In

5/20 Siemens LV 36 · 2014