Project Code Project Title Sheet No.

01
xx xx Designed abc
Proj. Element: wall footings Checked xyz

Description: Structural Design Date 15/3/18

Design Code: ACI-318


DATA INPUT
A. Dimensions

Width of slab Wslab 19 ft


Length of slab Lslab 22.5 ft
Thickness of slab Tslab 6 in
Thickness of wall Twall 9 in
Height of wall from slab soffit to footing top Hwall 15 ft
Thickness of mud Tmud 3 in
Thickness of tile Ttiles 1.5 in
Depth of soil over footing Z 2.0 ft

B. Material Properties
Concrete 28 Days Crushing Strength fc' 3 ksi
Yield Strength of Steel fy 40 ksi
Unit weight of concrete g concrete 150 lb/ft3
Unit weight of soil g soil 120 lb/ft3
Unit weight of mud g mud 120 lb/ft3
Unit weight of tiles g tile 130 lb/ft3
Unit weight of brick g brick 130 lb/ft3
Bearing capacity of soil B.C 1 ton/ft2
Angle of Internal Friction of Soil f Soil 30 degree
Modulus of rupture of concrete (1:2:4) fr 1:2:4 411 psi
Angle of internal friction for base material f base 30 degree

DESIGN CALCULATIONS
C. Loads

Live load on slab L.L Slab 20 lb/ft2


Slab Case Case 1
Shorter to longer side ratio (m) m 0.84
Load Coefficient for Transfer to Longer Direction Wall Ca 0.71
Load Coefficient for Transfer to Shorter Direction Wall Cb 0.29
Live load on wall/footing L.L Footing 134.9 lb/ft
Load of Slab Load Slab 1425 lb/ft
Load of mud Load Mud 570 lb/ft
Load of tiles Load Tile 308.75 lb/ft
Load of wall Load Wall 1463 lb/ft
Total load Load Total 2304 lb/ft
Total load on Longer walls 1636 lb/ft

1 of 2
Total Dead load on longer wall + Wall load D.L 2280 lb/ft
Utimate Factored Load Wu 2.95 kip/ft
Assume Depth of footing h 8.00 in
clear cover c.c 3.00 in
Effective depth d 4.4 in
Total Weight=Wconc + Wsoil W 0.26 ksf
Effective Presurre= qa - W qe 1.94 ksf
Area =service load/qe A 1.24 ft2/ft
Width of Footing Required B 1.24 ft
Take width of footing B 2.5 ft
Ultimate load=Factored load/B*Area qu 1.18 ksf
D. Shear Capacity
Beam shear capacity=qu((B-S)/2-d) Vud 0.60 kips
Shear capacity of concrete, φVc=φ2√fc' bd φVc 4.37 kips
Check OK
Ultimate Moment=(qu(B-S)^2)/8 Mu 0.45 k-ft
5.42 k-in
Steel Area
Let a=0.2d a 0.89 in
1st Trial
As=Mu/φfy(d-a/2) As 0.05 in2/ft
a=Asfy/0.85fc'b a 0.06 in
2nd Trial
As=Mu/φfy(d-a/2) As 0.04 in2/ft
a=Asfy/0.85fc'b a 0.06 in
3rd Trial
As=Mu/φfy(d-a/2) As 0.04 in2/ft
Area of steel taken As 0.04 in2/ft

Maximum Area=ρmax*bd Asmax 1.08 in2/ft

Minimum Area=0.002*bh Asmin 0.19 in2/ft


Area of steel provided Asp 0.22 in2/ft

E. Final Design
Main Steel Try # 3 bar
Spacing=A1/At*12 S 6.0 in
Distributing Steel Try # 3 bar
Spacing=A1/At*12 S 6.0 in
Main Bars = Use # 3 bars @ 6 in c/c
Distribution Bars = Use # 3 bars @ 6 in c/c
Depth of compression block a 0.3 in
Resisting moment Mn 2.9 kip-ft
Check OK

2 of 2