Anda di halaman 1dari 1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

NOTE: FOR UNITS WITH OR WITHOUT OPTIONAL PUMP PACKAGE


L POWER ENTRY L
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING SNOW, FOR WINTER 196.8 MM [7.75"] WIDE X 120.6 MM [4.75"] HIGH
OPERATION) OR AIR-CIRCULATION ENSURES RATE PERFORMANCE, RELIABLE OPERATION
AND EASE OF MAINTENANCE. SITE RESTRICTIONS MAY COMPROMISED MINIMUM CLEARANCES
INDICATED BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. JOHNSON CONTROLS UNIT CONTROLS WILL OPTIMIZE OPERATION
WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT. HOWEVER, THE SYSTEM DESIGNER
MUST CONSIDER POTENTIAL PERFORMANCE DEGRADATION. 39.4 [1.55]
1.1. RECOMMENDED MINIMUM CLEARANCES:
K 1.1.1. COIL SIDE TO WALL - 1828.8 MM [72.00"] K
1.1.2. COMPRESSOR SIDE TO WALL - 1219.2 MM [48.00"]
1.1.3. CONTROL PANEL TO WALL - 1828.8 MM [72.00"]
1.1.4. TOP - NO OBSTRUCTIONS ALLOWED. 15.9 MM [5/8"]
1.1.5. DISTANCE BETWEEN ADJACENT UNITS - 3048 MM [120.00"] MOUNTING HOLES (TYP.)
1.1.6. NO MORE THAT ONE ADJACENT WALL MAY BE HIGHER THAN UNIT.
2. WEIGHT AND CENTER OF GRAVITY- REF TO PERFORMANCE SPECIFICATION 21.3 [0.84]
3. FOR MONTERREY, MEXICO AND SAN ANTONIO, TEXAS BUILDS ONLY

CONTROL PANEL
J BOTTOM VIEW
J

I I
1069.9
[42.12]

H H

27.9
[1.10]
G G
125.3 2218.0
[4.93] [87.32]
2" NOMINAL PIPE
2-3/8" O.D. VICTAULIC
WATER CONNECTION - IN

F F

E E

1148.9
[45.23]

D D

323.5
[12.74] 213.2
[8.39]

C C

1125.7 307.4 575.8 762.0 731.0 156.4 280.4


[44.32] [12.10] [22.67] [30.00] [28.78] [6.16] [11.04]

2773.7 2" NOMINAL PIPE 476.5


[109.20] 2-3/8" O.D. VICTAULIC [18.76]
WATER CONNECTION - OUT
2807.7
B [110.54] B
JOHNSON CONTROLS - BUILDING EFFICIENCY
THIRD ANGLE 507 EAST MICHIGAN STREET, MILWAUKEE, WI, 53202 USA
THIS DRAWING PERTAINS TO THE FOLLOWING UNITS REV. DATE EC. NO. DR. CHK. ENG. "ALL PROPRIETARY RIGHTS IN DO NOT SCALE MATERIAL
A 17-NOV-2014 DX14-0394 ETE DLO THE SUBJECT MATTER HEREOF ENG. STD.
YCAL 0019 YCAL PRODUCT DRAWING
CONITNUED

ARE RESERVED AND NO


REVISION

ADDED NOTE ABOUT OPTIONAL PUMP PACKAGE PERMISSION IS GRANTED TO PART NO.
YCAL 0022 REPRODUCE THIS PRINT IN DRAWN D.B.NEWSWANGER 15-APR-2014 CUT SIZE
WHOLE OR IN ANY PART, OR
DISCLOSE ANY OF THE MODELER C.F. JUDGE 22-MAR-2006 CAGE NUMBER DRAWING NUMBER REVISION
A A
INFORMATION UPON IT TO
OTHERS WITHOUT WRITTEN
RELEASE BY JOHNSON
CHKD
ENG
D.B.NEWSWANGER 15-APR-2014
A1 66935 035-23980-001
A
VERSION
0
CONTROLS INCORPORATED" SCALE: 1.000 MASS (kg): 2930.812 ORIG. NO.: 035-23980-001 SHEET 1 OF 1 Eng Chg

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1