400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION

TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS
I 400KV GIS SWITCHGEAR; MANUFACTURER : HYUNDAI

Dielectric test on main circuit - lightning


1 impulse Voltage tests, power frequency KERI 11/3/2015 2015TC00961
Voltage withstand tests, partial discharge

Dielectric test on auxiliary and control


2 KERI 6/30/2016 2016TC00521
circuit
3 Temperature rise test KERI 11/3/2015 2015TC00961
Measurement of the resistance of the main
4 KERI 11/3/2015 2015TC00961
circuit

KERI 10/27/2014 2014TC00684


5 Short-time and peak withstand Current tests

Along With Bid Clarification Q1.1


KERI 10/27/2014 2014TC00685

Short-circuit making and


CESI 9/28/2015 B5019213
breaking

Annexure-13
Short-circuit making and breaking, out-of-
phase making and breaking, critical Current
6 Out-of-phase making
and capacitive and inductive (reactor) KEMA 7/1/2015 2127-15
Current switching tests and breaking
Line and cable charging
KERI 4/25/2016 2016TC00325
current
Inductive current (Shunt
KERI 4/25/2016 2016TC00326
reactor)
7 Internal arcing test KERI 8/9/2016 2016TC00638
Mechanical endurance, environmental
8 KERI 11/3/2015 2015TC00961
operation tests
To be submitted at
9 Thermal stability test - - -
design stage
To be submitted at
10 Electromagnetic compatibility (EMC) tests - - -
design stage

11 Verification of the degree of protection KERI 6/30/2016 2016TC00521

12 Tightness tests KERI 11/3/2015 2015TC00961

1 of 16
Alo
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

13 Pressure relief device tests KERI 6/30/2016 2016TC00521

II 400KV GIS SWITCHGEAR CIRCUIT BREAKER; MANUFACTURER : HYUNDAI

Dielectric test on main circuit - lightning


1 impulse Voltage tests, power frequency KERI 11/3/2015 2015TC00961
Voltage withstand tests, partial discharge

2 Temperature rise test KERI 11/3/2015 2015TC00961

Measurement of the resistance of the main


3 KERI 11/3/2015 2015TC00961
circuit

4 Short-time and peak withstand Current tests CESI 9/28/2015 B5019213

Along With Bid Clarification Q1.1


Short-circuit making and breaking, terminal
fault, short-line fault, out-of-phase making
5 and breaking, critical Current and capacitive CESI 9/28/2015 B5019213
and inductive (reactor) Current switching
tests

Annexure-13
6 Internal arcing test KERI 8/9/2016 2016TC00638

7 Insulation co-ordination tests KERI 11/3/2015 2015TC00961

Single-phase and
CESI 9/28/2015 B5019213 double-earth fault tests
8 Synthetic testing Short-line fault tests
Out-of-phase making
KEMA 7/1/2015 2127-15
and breaking
Mechanical endurance, environmental
9 KERI 11/3/2015 2015TC00961
operation tests

10 Thermal stability test Not Applicable - -

To be submitted at
11 Electromagnetic compatibility (EMC) tests - - -
design stage
12 Verification of the degree of protection KERI 6/30/2016 2016TC00521
13 Tightness tests KERI 11/3/2015 2015TC00961
14 Pressure relief device tests KERI 6/30/2016 2016TC00521

III DISCONNECTORS AND EARTHING SWITCHES (400KV GIS); MANUFACTURER : HYUNDAI

Dielectric test on main circuit - lightning


1 impulse Voltage tests, power frequency KERI 11/3/2015 2015TC00961
Voltage withstand tests, partial discharge
Dielectric test on auxiliary and control
2 KERI 6/30/2016 2016TC00521
circuit
3 Temperature rise test KERI 11/3/2015 2015TC00961
rification Q1.1

2 of 16
-13
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

Along With Bid Clarification Q1.1


Measurement of the resistance of the main
4 KERI 11/3/2015 2015TC00961
circuit
KERI 10/27/2014 2014TC00684 Earthing switch
5 Short-time and peak withstand Current tests
KERI 10/27/2014 2014TC00685 Disconnector

Annexure-13
Short-circuit making capability of High
6 KERI 4/25/2016 2016TC00327
speed earthing switches
Bus transfer Current switching capability
7 KERI 10/27/2014 2014TC00685
tests
Bus charging current switching capability of
8 MELCO 11/20/2014 C10-I4F35
disconnectors
9 Internal arcing test KERI 8/9/2016 2016TC00638
10 Insulation co-ordination tests KERI 11/3/2015 2015TC00961
Induced current switching capability of
11 KERI 10/27/2014 2014TC00684
Earth switches
Mechanical and electrical endurance,
12 environmental operation tests. KERI 11/3/2015 2015TC00961

Proper functioning of position indicating To be carried out during


13 - - -
device FAT
IV CURRENT TRANSFORMERS (400KV GIS); MANUFACTURER : HYUNDAI
1 Short Time Current Tests KERI 2/24/2017 2017TS00561
2 Temperature Rise Test KERI 2/24/2017 2017TS00561

Clarification Q1.1
Along With Bid
3 Determination of errors KERI 2/24/2017 2017TS00561

Annexure-13
To be carried out during
4 Proof of low reactance (Class PX CTs) - - - routine test
5 Lightning Impulse Voltage Withstand Test KERI 2/24/2017 2017TS00561
6 High Voltage , Wet Test KERI 2/24/2017 2017TS00561
7 Radio Influence Voltage Type tests Not Applicable
To be carried out during
8 Mechanical strength on HV Terminals routine test
V VOLTAGE TRANSFORMERS (400KV GIS); MANUFACTURER : HYUNDAI
Temperature Rise Test NISSIN (SGS Japan) 6/16/2017 KRL17-2

Clarification Q1.1
Short circuit Test NISSIN (SGS Japan) 6/16/2017 KRL17-2

Along With Bid

Annexure-13
Lightning Impulse NISSIN (SGS Japan) 6/16/2017 KRL17-2
Determination of errors NISSIN (SGS Japan) 6/16/2017 KRL17-2
Radio Influence Voltage Type tests Not Applicable
Verification of Accuracy Over Temperature
range NISSIN (SGS Japan) 6/16/2017 KRL17-2
Measuurement of insertion loss Not Applicable
Short Circuit withand capability NISSIN (SGS Japan) 6/16/2017 KRL17-2

3 of 16
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS
VI BUSHING INSULATOR (400KV GIS); MANUFACTURER : HYUNDAI
To be submitted at
Short Time Current Test Along With Bid design stage
Clarification Q1.1
To be carried out during
Annexure-13 FAT
Internal Discharge and Power Factor Tests
VII 132kV CIRCUIT BREAKER (OUTDOOR); MANUFACTURER: GE

Dielectric test on main circuit - lightning


AREVA Energietechnik GmbH, High Voltage 14-03-2007, 08-03-
1 impulse Voltage tests, power frequency 6351
Institute Kassel, Germany 2007 & 22-03-2007
Voltage withstand tests, RIV test

Along With Bid Clarification Q1.1


AREVA Energietechnik GmbH, High Voltage
2 Temperature rise test 1/21/2008 246 (6565)
Institute Kassel, Germany
Measurement of the resistance of the main AREVA Energietechnik GmbH, High Voltage
3 1/21/2008 246 (6565)
circuit Institute Kassel, Germany

Annexure-20
Short-time and peak withstand Current
tests, Verification test for making and
breaking, Basic Short Circuit Tests, Short
4 CESI 1/25/2008 246 (A80110688)
line fault tests, Out of phase making and
breaking test, single phase and double earth
fault tests

5 Capacitive current switching test CESI 1/24/2008 246 (A8012436)


Mechanical endurance, environmental AREVA Energietechnik GmbH, High Voltage 22-01-2008, 31-01-
6 246 (6563, 6566 & 6567)
operation tests Institute Kassel, Germany 2008, 20-03-2008

7 Shunt reactor current switching KEMA 10/24/2007 469-07

8 Seismic qualification GE Grid GmbH 11/22/2017 3670


VIII 132kV CIRCUIT BREAKER (OUTDOOR); MANUFACTURER: SIEMENS

Dielectric test on main circuit - lightning


impulse Voltage tests, power frequency
1 PEHLA 5/2/2002 0231-1 BS
Voltage withstand tests, Test on auxiliary &
control circuits, RIV

0234 BS

Along With Bid Clarification Q1.1


0247 BS
2 Temperature rise test PEHLA 9/1/2002
0250 BS
0255 BS

0234 BS
Measurement of the resistance of the main 01-09-2002 / 30-07-

Annexure-21
3 PEHLA 0247 BS
circuit 2002
0255 BS

4 Short-time and peak withstand Current tests PEHLA 6/27/2002 0228 BS

4 of 16
Along With Bid Clarification Q1.1
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION

Annexure-21
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS
Short-circuit making and breaking, terminal 0226 BS
23-05-2002/ 27-06-
fault, short-line fault, out-of-phase making 0224 BS
2002/ 27-06-2002 /
6 and breaking, critical Current and capacitive PEHLA 0253 BS
27-06-2002/ 27-06-
and inductive (reactor) Current switching 0254 BS
2002
tests 0225 BS

Mechanical endurance, environmental


7 PEHLA 7/12/2002 PEHLA 0232 BS
operation tests
0145 BS
8 Electromagnetic compatibility (EMC) tests 9/28/2004
Conf. E 0195 A/E
03028 BS
9 Verification of the degree of protection PEHLA 7/2/2003
03036 BS
IX 145kV (2000A) DISCONNECTORS AND EARTHING SWITCHES (OUTDOOR); MANUFACTURER COELME

Dielectric test on main circuit - lightning


1 impulse Voltage tests, power frequency FGH 2012 H 12020
Voltage withstand tests

Along With Bid Clarification Q1.1


2 Temperature risre test CESI 2009 A9035231

Measurement of the resistance of the main


3 CESI 2009 A9035231
circuit

Annexure-22
CESI 2012 B2012572 DS
4 Short-time and peak withstand Current tests
CESI 2012 B2012571 ES

5 Current switching capability tests CESI 2012 B2032261

Induced current switching capability of


6 CESI 2012 A8002774
Earth switches
Mechanical and electrical endurance,
7 environmental operation tests. CESI 2010 B0028091

8 Radio Interfrence Voltage (RIV) test FGH 2012 H 12020

X 145kV (3150A) DISCONNECTORS AND EARTHING SWITCHES (OUTDOOR); MANUFACTURER : COELME

Dielectric test on main circuit - lightning


1 impulse Voltage tests, power frequency FGH 2012 H 12020
Voltage withstand tests

long With Bid Clarification Q1.1


2 Temperature risre test CESI 2009 A9035237

Measurement of the resistance of the main


3 CESI 2009 A9035237
circuit

Annexure-22
CESI 2012 B2012574 DS
4 Short-time and peak withstand Current tests
CESI 2012 B2012573 ES

5 Current switching capability tests CESI 2012 B2032261

5 of 16
Along With Bid Clarification Q1.1
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION

Annexure-22
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS
Induced current switching capability of
6 CESI 2012 A8002774
Earth switches
Mechanical and electrical endurance,
7 environmental operation tests. CESI 2010 B0028091

8 Radio Interfrence Voltage (RIV) test FGH 2012 H 12020

XI 420kV EARTHING SWITCHES (OUTDOOR); MANUFACTURER : COELME

Dielectric test on main circuit - lightning

Along With Bid Clarification Q1.1


impulse Voltage tests, power frequency
1 CESI 2008 8002955
Voltage withstand tests, Switching Impulse
withstand test

2 Temperature rise test Not Applicable

Annexure-18
Measurement of the resistance of the main
3 Not Applicable
circuit

4 Short-time and peak withstand Current tests FGH 2014 L14024

5 Current switching capability tests SVEPPI 2011 RP LS 11/143

Mechanical and electrical endurance,


6 environmental operation tests. CESI 2011 B1021657

7 Radio Interfrence Voltage (RIV) test CESI 2008 8002955

XII 132kV CURRENT TRANSFORMERS (OUTDOOR); MANUFACTURER: GE

1 Short-time Current tests ERDA, Vadodara 1/28/2014 LSCS/504

2 Temperature rise test CPRI, Bangalore 6/12/2015 DCCD-14627

Along With Bid Clarification Q1.1


3 Test of accuracy CPRI, Bangalore 5/24/2010 SC10312A

4 Impulse voltage withstand test CPRI, Hyderabad 4/1/2010 UHV/T/592

Annexure-24
5 Wet Test CPRI, Hyderabad 4/1/2010 UHV/T/592

6 Radio Influence Voltage Type Tests CPRI, Bangalore 4/1/2010 UHV/T/592

6 of 16
Along With Bid Clarification Q1.1
Annexure-24
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

7 Mechanical strength on HV terminals CPRI, Bangalore 6/17/2015 VB.2745.T071.1516

8 Partial Discharge CPRI, Bangalore 5/24/2010 DCCD-11459

9 Ingress Protection CPRI, Bangalore 2/2/2009 028EATDIP0950020

XIII 132kV CAPACITIVE VOLTAGE TRANSFORMER (OUTDOOR); MANUFACTURER : GE

1 Temperature rise test CPRI, Bangalore 8/20/2015 UHV1481516

Short-circuit withstand test, Ferro resonance


2 CPRI, Hyderabad 8/20/2015 UHV1481516
test, Transient response test

Along With Bid Clarification Q1.1


Lightning Impulse, Chopped impulse, wet
3 CPRI, Hyderabad 11/17/2015 UHV2271516
test, EMC test

4 Test of accuracy Alstom T&D India Ltd, Witnessed by CPRI 6/1/2015 1330/06

Annexure-23
5 Radio Influence Voltage Tests CPRI, Hyderabad 11/17/2015 UHV2271516

6 Verfication of the degree of protection CPRI, Bangalore 10/1/2014 314EATDIP13S0267

Enclosure Tightness test at ambient


7 Alstom T&D India Ltd, Witnessed by CPRI 1/3/2014 2314/12
temperature

Capacitance and Tan Delta measurement at


8 CPRI, Hyderabad 8/20/2015 UHV1481516
power frequency

9 Measurement of insertion loss Not applicable

XIV 400kV CAPACITIVE VOLTAGE TRANSFORMER (OUTDOOR) ; MANUFACTURER : GE

1 Temperature rise test CPRI, Hyderabad 9/16/2015 UHV1841516

Short-circuit withstand test, Ferro resonance


2 CPRI, Hyderabad 9/16/2015 UHV1841516
test, Transient response test

Lightning Impulse, Chopped impulse, wet


3 CPRI, Hyderabad 9/16/2015 UHV1841516
test, EMC test

4 Test of accuracy Alstom T&D India Ltd, Witnessed by CPRI 2/5/2016 0124/01A

7 of 16
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

5 Radio Influence Voltage Tests CPRI, Hyderabad 11/17/2015 UHV2271516

6 Verfication of the degree of protection CPRI, Bangalore 10/1/2014 314EATDIP13S0267

Enclosure Tightness test at ambient


7 Alstom T&D India Ltd, Witnessed by CPRI 2/4/2016 0124/01C
temperature

Capacitance and Tan Delta measurement at


8 CPRI, Hyderabad 8/20/2015 UHV1481516
power frequency

9 Measurement of insertion loss Not applicable

8 of 16
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

XV 132KV SYSTEM SURGE ARRESTER (OUTDOOR) ; MANUFACTURER : SIEMENS

Dielectric test on main circuit- lightning


1 impulse volatge test, power frequency Siemens AG, Arrester Test Laboratory 12/6/2012 HBA11095P
voltage withstand test

Test to verify the dielectric withstand of


2 Siemens AG, Arrester Test Laboratory 2/23/2015 HBA11779P
internal components

3 Residual voltage test Siemens AG, Arrester Test Laboratory 2/23/2015 HBA11779P

Along With Bid Clarification Q1.1


Test to verify long term stability under
4 Siemens AG, Arrester Test Laboratory 2/23/2015 HBA11779P
continuous operating voltage

5 Operating duty test Siemens AG, Arrester Test Laboratory 9/25/2015 HBA11959P

Annexure-25
TR-15-005-HS
6 Short circuit tests Pruffeld der Schaltwerke 2/17/2015
10-051-SHS/E

7 Current Distribution test Not applicable as per IEC

8 Test on Surge Monitor Siemens AG, Arrester Test Laboratory 1/19/2012 HBA10891P

9 RIV Test Siemens AG, Arrester Test Laboratory 3/19/2013 HBA09149P

10 Environmental Test Siemens AG, Arrester Test Laboratory 9/16/2013 HBA11358P

11 Bending Moment Test Siemens AG, Arrester Test Laboratory 8/13/2012 HBA10882P

12 Seal Leak rate Test Siemens AG, Arrester Test Laboratory 6/25/2013 HBA11282P

XV 400KV SYSTEM SURGE ARRESTER (OUTDOOR) ; MANUFACTURER : SIEMENS

Dielectric test on main circuit- lightning


1 impulse volatge test, power frequency Pruffeld der Schaltwerke 11/11/2011 11-093-HH

long With Bid Clarification Q1.1


voltage withstand test

Test to verify the dielectric withstand of


2 Siemens AG, Arrester Test Laboratory 2/23/2015 HBA11780P
internal components

Annexure-14
3 Residual voltage test Siemens AG, Arrester Test Laboratory 2/23/2015 HBA11780P

Test to verify long term stability under


4 Siemens AG, Arrester Test Laboratory 2/23/2015 HBA11780P
continuous operating voltage

9 of 16
Along With Bid Clarification Q1.1
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017

Annexure-14
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

5 Operating duty test Siemens AG, Arrester Test Laboratory 2/23/2015 HBA11780P

6 Short circuit tests PEHLA 11/18/2011 11203Bs

7 Current Distribution test Not applicable as per IEC

8 Test on Surge Monitor Siemens AG, Arrester Test Laboratory 1/19/2012 HBA10891P

9 RIV Test Siemens AG, Arrester Test Laboratory 6/12/2012 HBA10986P

10 Environmental Test Siemens AG, Arrester Test Laboratory 9/21/2012 HBA11054P

11 Bending Moment Test Siemens AG, Arrester Test Laboratory 1/10/2013 HBA1113P

12 Seal Leak rate Test Siemens AG, Arrester Test Laboratory 11/23/2013 HBA10863P

XVI POST INSULATORS ; MANUFACTURER : MANUFACTURER :TCi DALIAN TUCHENG INTERNTIONAL CO. LTD

Along With Bid Clarification Q1.1


Electric Power Industry Qulaity Inspection & Test
1 RIV Type test Centre of Electric Power Equipment & 4/20/2008 G2008134
Instrument, China
Electric Power Industry Qulaity Inspection & Test
2 Dielectric tests - dry & wet Centre of Electric Power Equipment & 4/20/2008 G2008134

Annexure-30
Instrument, China
Electric Power Industry Qulaity Inspection & Test
3 Artifical pollution test Centre of Electric Power Equipment & 4/20/2008 G2008134
Instrument, China
Electric Power Industry Qulaity Inspection & Test
4 Mechanical failing load test Centre of Electric Power Equipment & 4/20/2008 G2008134
Instrument, China
Electric Power Industry Qulaity Inspection & Test
5 Porosity Test Centre of Electric Power Equipment & 4/20/2008 G2008134
Instrument, China

XVII INSULATOR STRING; ; MANUFACTURER :TCi DALIAN TUCHENG INTERNTIONAL CO. LTD

Quality Inspection & Testing Centre of Electric


1 Dielectric test 7/4/2003 P.I.No.069
Equipment, Ministry of Electric Power, China
Along With Bid
Quality Inspection & Testing Centre of Electric Clarification Q1.1
2 RIV Type test 7/4/2003 P.I.No.069 Annexure-31
Equipment, Ministry of Electric Power, China

10 of 16
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX Along With Bid
Clarification Q1.1
LIST OF REQUIRED TESTS AS PER Annexure-31
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

3 Tracking & Errosion Test CESI 7/28/2010 B0022813

XVIII 33kVMETAL CLAD SWITCHGEARS ; MANUFACTURER : SIEMENS

Dielectric test on main circuit - Lightning


1 impulse, Power frequency voltage ERDA 3/6/2013 HIMP/04/1884
withstand tests

Along With Bid Clarification Q1.1


2 Temperature rise test (2500A) ERDA 3/25/2013 LSWG/938
Temperature rise test (1250A) ERDA 12/28/2012 LSWG/706
Measurement of the resistance on the main
4 ERDA 3/25/2013 LSWG/938
circuit (2500A)

Annexure-26
Measurement of the resistance on the main
ERDA 12/28/2012 LSWG/706
circuit (1250A)
5 Short Circuit perforamce tests KEMA 9/14/2012 TIC 2148-12
7 Internal arcing test KEMA 9/18/2013 TIC 2565-13
Mechanical endurance, environmental and
8 ERDA 4/3/2013 LSWG/12
operation tests
Verification of the degree of protection and
10 ERDA 6/28/2011 LIPS/125
tightness tests
Earthswitch shorttime withstand current &
11 ERDA 7/7/2014 LSCS/078
peak withstand current test
12 Capacitance current switching test KEMA 9/13/2012 TIC 2146-12

XVIII 33kV XLPE CABLE; MANUFACTURER : KEC INTERNATIONAL LTD

1 Bending Test KEMA 11/22/2013 TIC 1075-13

2 Tan Delta Measurement KEMA 11/22/2013 TIC 1075-13

3 Heating Cycle Test KEMA 11/22/2013 TIC 1075-13

4 Impulse test followed by a volatge test KEMA 11/22/2013 TIC 1075-13

5 Check for cable construction KEMA 11/22/2013 TIC 1075-13

6 Measurement of thickness insualtion KEMA 11/22/2013 TIC 1075-13

Measument of thickness of non metal


7 KEMA 11/22/2013 TIC 1075-13
sheaths

8 Hot set test for XLPE insulation KEMA 11/22/2013 TIC 1075-13

9 Shrinkage test for XLPE insulation KEMA 11/22/2013 TIC 1075-13

10 Resistivity of semi conductor screens KEMA 11/22/2013 TIC 1075-13

11 of 16
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS
Tests for determining the mechanical
11 properties of insulation before and after KEMA 11/22/2013 TIC 1075-13
aging
Tests for determining the mechanical
12 properties of non-metallic shaeths before KEMA 11/22/2013 TIC 1075-13
and after aging
Additional aging test on pieces of
13 KEMA 11/22/2013 TIC 1075-13
completed cable
Pressure test at high temperature on non
14 KEMA 11/22/2013 TIC 1075-13
metallic sheaths

15 Water absorption teston insulation KEMA 11/22/2013 TIC 1075-13

16 Voltage test for 4 hours KEMA 11/22/2013 TIC 1075-13

Loss of mass test on PVC sheaths of type


17 KEMA 11/22/2013 TIC 1075-13
ST2

18 Test on PVC shaeths at low temperature KEMA 11/22/2013 TIC 1075-13

Test on PVC sheaths to cracking ( heat


19 KEMA 11/22/2013 TIC 1075-13
shock test)

20 Flame spead on single cables KEMA 11/22/2013 TIC 1075-13

21 Strippability test for insulation screen KEMA 11/22/2013 TIC 1075-13

XIX LOW VOLTAGE SWITCHBOARD ; MANUFACTURER : CHENNAI HI TECH ENGINEERING (Main Proposal)
Temperature rise test on busbars at
1 CPRI 04.11.2008 DCCD-10640
3200Amps

2 Ingress Protection CPRI 11/4/2008 388EATDSC08S1450

Dielectric Test - Power Frequency


3 CPRI 3/26/2015 723EATDIP15S0083 Along With Bid
Withstand voltage test
Clarification Q1.1
4 Insulation resistance measurement CPRI 3/26/2015 723EATDIP15S0083 Annexure-33

Verification of short circuit strength on


5 CPRI 4/30/2015 SC15222A
busbars of main circuit
Protection against electrick shock &
6 CPRI 4/30/2015 SC15222A
integrity of protective circuit

XX LOW VOLTAGE SWITCHBOARD ; MANUFACTURER : SAS POWER INDUSTRIES (Alternate)


Along With Bid
1 Design Verification KEMA 12/16/2013 2163707.102 Clarification Q1.1
Annexure-33
XXI CONTROL & RELAY PANEL ; MANUFACTURER : ABB

12 of 16
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS
A1 ABB, SWITZERLAND 10/14/1996 1MRK0003112-2
A2 ABB, SWITZERLAND 10/31/2017 1MYN200200-020
A3 ASEA 3/29/1985 RKY85-005E
A4 Auxulliary & Trip Relays ABB, SWITZERLAND 6/20/1994 TRHD94-006E
A5 ABB, SWITZERLAND 9/4/1997 1MRK001503-17
A6 ABB, SWITZERLAND 6/20/1994 TRHD94-007
A7 10/23/2017

Along With Bid Clarification Q1.1


ABB, SWITZERLAND 1MYN200200-019

B RESP07 iABG 11/28/2012 TA34-PB-214-12_01

C Fault Recorder Phoenix Test Lab 6/25/2007 Sherlog-TypeTest-Report

Annexure-36
D1 KEMA 7/27/2009 30920420
REx615
D2 ABB, SWITZERLAND 6/3/2013 1MRS757185

E SEL KEMA 8/2/2011 74100372

F1 ABB, SWITZERLAND 10/4/2013 1KHM007074


REB500
F2 ABB, SWITZERLAND 10/4/2013 1KHA005040-WEN

G REx650 ABB, SWITZERLAND 5/1/2017 1MRK505391

H1 ABB, SWITZERLAND 12/1/2012 1MRK511231


H2 ABB, SWITZERLAND 12/1/2012 1MRK505226
REx670
H3 ABB, SWITZERLAND 12/1/2012 1MRK504117
H4 KEMA 2/17/2010 30920566

XXII 33kV CAPACITOR BANK; MANUFACTURER : SUVIRE ELECTRIC

Short-time and peak withstand current tests TECNALIA 7/26/2016 B25-16-BQ-01E


1
2 Temperature rise test TECNALIA 7/26/2016 B25-16-BQ-02E Along With Bid
Clarification Q1.1
3 Dielectric test TECNALIA 7/28/2016 B25-16-BQ-03E Annexure-35
4 Degree of protection TECNALIA 7/27/2016 B25-16-BQ-04E

13 of 16
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS

XXIII FIRE PROTECTION


FIRE FIGHTING & HYDRANT
1 Air-release Valves for Fire Pumps VAL-MATIC VALVE & MFG CORP 5/7/2017 QWBS.EX5148

2 Check Valves SHIELD FIRE SAFETY & SECURITY LTD 3/6/2014 HMER7.EX6721
3 Carbon Dioxide Extinguishers NATIONAL FIRE FIGHTING MFG FZ CO 20110801 FXHV.EX15223

4 Special System Water Control Valves, Deluge SHIELD FIRE SAFETY & SECURITY LTD 3/10/2014 VLFT.EX6718
5 Fire Hose, Lined, Uncoupled, for Municipal and NATIONAL
Industrial Use
FIRE FIGHTING MFG FZ CO 20150106 MZQE.EX15059
6 Hydrants NATIONAL FIRE FIGHTING MFG FZ CO 20160217 HBOR.EX15350

7 Gate Valves SHIELD FIRE SAFETY & SECURITY LTD 3/25/2014 HMRZ7.EX6704
8 Fire Blankets LPCB 7/11/2017 463c
9 MOBILE FIRE EXTINGUISHER KITEMARK 1/11/2012 KM 560088
10 MOBILE FIRE EXTINGUISHER LPCB 7/22/2011 463M

11 Nozzles, Spray Hose, Portable SHIELD FIRE SAFETY & SECURITY LTD 7/23/2007 VUFZ.EX6709

12 Gate Valves SHIELD FIRE SAFETY & SECURITY LTD 8/26/2014 HMRZ.EX6704
13 PORTABLE FIRE EXTINGUISHER KITEMARK 1/31/2017 KM66677

14 Sprinklers, Automatic and Open SHIELD FIRE SAFETY & SECURITY LTD 2/19/2014 VNIV.EX6699

15 Nozzles, Spray Type, Fixed SHIELD FIRE SAFETY & SECURITY LTD 11/6/2013 VGYZ.EX6715

16 Strainers, Pipeline SHIELD FIRE SAFETY & SECURITY LTD 2/19/2014 HLCV7.EX16175

HFC 227 EA SYSTEM


17 ALARM SOUNDER FIKE CORP 20150723 UOXX.S3217
18 Heatautomatic Fire Detectors for Use in Hazardous Locations
THERMOTECH INC 19930526 UIRV.E35018
19 Clean Agent Fire Extinguishing Systems FM APPROVALS 2/1/2011 HFC227ea FM
20 Smokeautomatic Fire Detectors FIKE CORP 20130910 UROX.S4021

Audible-signal Appliances SYSTEM SENSOR UNINCORPORATED, DIV


21 OF HONEYWELL INTERNATIONAL INC 4/22/2014 ULSZ.S4011

FIRE ALARM SYSTEM


22 Control Units, Releasing Device FIKE CORP 3/15/2016 SYZV.S2203
23 Heatautomatic Fire Detectors FIKE CORP 4/26/2016 UQGS.S4067
24 Control Unit Accessories, System FIKE CORP 4/25/2016 UOXX.S3217

th Bid Clarification Q1.1


25 Control and Communication Equipment FIKE CORP 3/15/2016 PGWM.S2203
Heatautomatic
Fire Detectors for Use in Hazardous
26 Locations THERMOTECH INC 3/26/2017 UIRV.E35018

Annexure-28
27 Smokeautomatic Fire Detectors FIKE CORP 4/26/2016 UROX.S4021

14 of 16
Along With Bid Clarification Q1.1
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS

Annexure-28
TENDER DOCUMENTS

15 of 16
Along With Bid Clarification Q1.1
400 KV QAIA GIS AND EXTENSION OF EXISTING 132/33KV SUSBSTION
TENDER NO 24/2017
TYPE TEST REPORT COMPILATION INDEX

Annexure-28
LIST OF REQUIRED TESTS AS PER
S.No LAB AT WHICH TEST PERFORMED DATE OF TEST REPORT NO SUBMITTED REMARKS
TENDER DOCUMENTS
FIRE PUMP
28 FIRE PUMP NF-S-200-125

CHECK VALUE-FM FM APPROVALS SD-NRV200FF-D, SD-


29 NRV300FF-D, SD-NRV-PN16

30 Check Valves-UL SHIELD FIRE SAFETY & SECURITY LTD 6/13/2014 HMER.EX6721
31 FLOW METER FM APPROVALS

32 Gate Valves SHIELD FIRE SAFETY & SECURITY LTD 8/26/2014 HMRZ.EX6704
33 Outside Screw and Yoke Gate Valves FM APPROVALS SD-OSY250GV-D
34 Pressure Gauges FM APPROVALS SD-P1

35 Gauges, Pressure SHIELD FIRE SAFETY & SECURITY LTD 5/21/2013 VEVX.EX6714

36 Fire Pump Relief Valves GRISWOLD INDUSTRIES, DBA CLA -VA L CO 12/6/2014 QXZQ.EX2855
SD-SVS OSY-1, SD-SVS OSY-
37 TAMPER SWITCH-FM FM APPROVALS 2, SD-SVS OSY-3
EXTINGUISGHIG SYSTEM
38 ATTACHMENTS SHIELD FIRE SAFETY & SECURITY LTD 9/20/2017 USQT-S9078
39 Centrifugal Fire Pumps, Split Case NATIONAL FIRE FIGHTING MFG FZ CO 12/4/2017 QXJY.EX15024

40 Strainers, Pipeline SHIELD FIRE SAFETY & SECURITY LTD 11/3/2014 HLCV.EX16175

FOAM SYSTEM
COPPER
41 cooper-medc cert-ul-cert-compliance_0 2015-MARCH-03 E203310-20141216
cooper-medc-cert-xb11-xb12-s8128- 2014-
42 certificate-compliance NOVEMBER-05 S8128-20020416
cooper-medc-cert-xb11-xb12-ul-certificate-
43 compliance_4 2000 JANUARY 28 E187894
SHIELD FIRE, SAFETY AND SECURITY
44 ALARM SOUNDER - LPCB LTD 7-Jan-14 548e-(cl-4)
45 Proportioners, Foam Concentrate NATIONAL FIRE FIGHTING MFG FZ CO 9/14/2015 GHXV.EX15916
Heatautomatic
Fire Detectors for Use in Hazardous
46 Locations THERMOTECH INC 3/26/2017 UIRV.E35018

SYSTEM SENSOR UNINCORPORA TED, DIV


47 Audible-signal Appliances OF HONEYWELL INTERNA TIONA L INC 12/6/2014 ULSZ.S4011
VESDA SYSTEM
48 Vds Approval for VPS Bauteilen und System en 05.10.2013
49 VESDA Approve for VLP xtralis pvt limited 3/4/2010 0832-CPD-0768

50 Smoke Det ectors for Special Applications XTRAUS INC 10/9/2006 URXG.S5198

16 of 16