RECORD OF AMENDMENTS
7
8
10
NAVAL ENGINEERING STANDARD 719
ISSUE 2
Published by:
MOD(PE) Ship Department Section D191
Foxhill, Bath
Ci)
NES 719
Issue 2
CONDITIONS OF ISSUE
General
1. This Standard has been designed for the use of the Ministry of Defence
and its contractors in the execution of Contracts for the Ministry.
The Ministry accepts no liability whatever whether in contract or in
of the
tort (including but without limitation negligence on the part
Ministry,, its servants or agents) for any deficiencies in design
information where the Standard is used for other purposes.
9. This Standard may call for the use of processes, substances and pro-
cedures that may be injurious to health if adequate precautions are not
taken. It refers only to technical suitability and in no way absolves
either the supplier or the user from statutory obligations relating to
health and safety at any stage of manufacture or use.
10. Where attention is drawn to hazards, those quoted may not necessarily
be exhaustive.
(ii)
NES 719
Issue 2
CONTENTS
AUTHORIZATION (i)
CONTENTS (iii)
INTRODUCTION (xi)
SECTION I SCOPE I
SECTION 3 DRAWINGS 6
SECTION 5 ENVIRONMENT 11
(iii)
NES 719
Issue 2
SECTION 9 PUMPS 47
SECTION 10 VALVES 57
1004 to 1009
Location
1014 and 1015
Locking Arrangements
1016 to 1026
Relief Valves and Reducing Valves
1010 to 1013
Remote/Local Control
1001 to 1003
Types and Selection
SECTION 11 PIPEWORK 64
Alarms 1525
Fittings 1501 to 1512
Pressure Gauges 1513 to 1516
Sensors 1517 to 1519
Sight Flow Indicators 1526
Thermometers 1520 to 1524
(v)
NES 719
Issue 2
General 2001
LPSW Systems with Fixed Opening Flow Control 2051 to 2059
Devices in Equipment Branches and Supplied
from the HPSW Main
LPSW Systems with Variable Opening Flow 2060 to 2063
Control Devices in Equipment Branches
and Supplied from the HPSW Main
Multi-pump Systems 2026 to 2044
Single Pump Systems 2002 to 2025
The Influence of Pump Characteristics on the 2045 to 2050
Selection of Pump Types )
INDEX TO FIGURES (vii)
INDEX TO TABLES (x)
(vi)
NES 719
Issue 2
INDEX TO FIGURES
6 15 TONNE/HOUR EDUCTOR 31
7 75 TONNE/HOUR EDUCTOR 31
8 HYDRAULIC GRADIENT 39
(vii)
FES 719
Issue 2
(viii)
NES 719
Issue 2
49 DELETED
(ix)
NES 719
Issue 2
INDEX TO TABLES
(x)
NES 719
Issue 2
INTRODUCTION
4. Any user of this Standard either within MOD or in outside industry may
propose a change to an NES. Proposals for changes which are:
to
a. not directly applicable to a particular contract are to be made
the sponsor of the NES
Cxi) /Cxii)
NES 719
Issue 2
1. SCOPE
0101. This Standard states the requirements for the design, manufacture,
installation, test and setting to work of the sea water system in
surface ships.
a. Fire fighting
c. Prewetting
d. Domestic
The above systems are described to the branch isolation valve only.
0104. The LPSW system includes requirements for the supply of cooling sea
water to main and auxiliary machinery and other components such as
shaft seals etc.
NES 719
Issue 2
Amdt 2
2. R E L A T E D O C U M E N T S
D----------------- Referred to in
0201. Reference is made to: Clause
DEF STAN 66-2 Gauges, Pressure, Dial Indicating 1514
(Bourdon Tube Type)
BS 336 Fire Hose Coupling and Ancillary 1002
Equipment
BS 381C Colours for Specific Purposes 1151
2
NES 719
Issue 2
Referred to in
Clause
NES 710 Fluid Systems. Low Pressure General 0603, 1210,
Requirements 1211
3
NES 719
.Issue 2
Referred to in
Clause
)
Welding, Minimum Standards 1158, 1195
*NES 773
(DG Ships/G/10000)
Protection of Sea Water Systems using 1702
NES 781
Sodium Dimethyl Dithiocarbamate
1522
DG Ships 64 Thermometers, Liquid in Glass Expansion
Type
4
NES 719
Issue 2
Referred to in
Clause
DG Ships TP 214 Symbols and Abbreviations 0305
003 503 965 Design of Gratings for Sea Tubes 1322 and 1329
5
NES 719
Issue 2
3. DRAWINGS
to conform to
0305. Symbols used in the preparation of diagrammatics are
BS 1553 supplemented by DG Ships TP 214.
a. The maximum and minimum water flows, water speeds and pressure
losses through each branch pipe.
6
NES 719
Issue 2
4. DEFINITIONS AND TECHNICAL TERMS
Definitions
0401. Cooling Water System - A system which uses the sea as a heat sink for
cooling auxiliary machinery; supplied -either by low pressure sea water
pump(s) or from the HPSW System.
0402. Domestic Sea Water System - A system for supplying the water
requirements of the toilets, the cooling requirements of certain
auxiliaries OMS and miscellaneous domestic equipment; usually supplied
with sea water from the HPSW System.
0403. Fire Fighting System - A system for supplying water to the fire
hydrants, compartment water sprayers (excluding explosive stores) and
for compartment flooding; supplied from the HPSW System.
0404. High Pressure Sea Water System (HPSW) - A system for supplying the high
pressure sea water requirements of a ship with a maximum working
pressure of 7 bar.
0405. Low Pressure Sea Water System (LPSW) - A system for supplying the low
pressure sea water cooling requirements of a ship with a nominal working
pressure of 14 to 2 bar.
0408. Salvage and De-ballastina System - A system for pumping out water from
ship's bilges under flooding conditions and from ship's ballast tank;
normally pumped out using eductors supplied with motive water from the
HPSW System.
Technical Terms
NOTE: The terms Pressure and Head are interchangeable throughout this
Standard.
7
NES 719
Issue 2
In practice the system designer will inform the pump maker of the
NPSH available at the pump suction flange; the pump suction
flange is taken as the pump inlet. -
t. Pump design - The total pressure rise and flow rate duty
point for which the pump is designed; the point
of maximum pump efficiency and the conditions
from which the pump specific speeds are
calculated.
9
NES 719
Issue 2
bb. Relief valve - A valve design to pass the total flow.of the
full bore system in which it is fitted when under
conditions of pressure in excess of the
designed working pressure.
dd. Surplus valve - Fitted to the HPSW pump to ensure the HPSW
System is not overpressurised when the pump
is working at no delivery.
10
NES 719
Issue 2
5. ENVIRONMENT
Environmental Conditions
Sea
ep -
Atmospheric Air
Dry Bulb with Relative
Climatic Condition Temp Humidity up to 100%
., 0C oC
0
Arctic - 2 - 29
Sub Arctic (Winterisation) 1 - 10
Temperate Winter 4 - 4
Temperate Summer 13 15
Average Tropical 30 32
Extreme Tropical 35 40
0505. Unless otherwise specified,the sea water systems are to be designed to:
II
NES 719
Issue 2
Vibrational Environment
environment
is to operate in a vibrational
RM Ships
0509. All equipment in
It is not
which is defined by the tests detailed in NES 725.
vibration tested,
necessary for all mechanical equipments to be
However, items such as automatic
particularly the more rugged items.
are to be vibration
control units or special linkage equipments
the Ministry will
tested. Where this is considered necessary,
tests to be carried out. This
specify the vibrational environmental
characteristics of
in no way affects the calculation of vibration
equipment required by NES 334.
Submersion
electric generation
0510. It is desirable to maintain propulsive power and
flooded to any waterline which
with the machinery compartments
in a damaged condition. It is, however,
might arise with the ship
machinery units capable of operation
impracticable to make certain
location of any
when submerged beyond a limited extent, and the
in a machinery compartment limit
machinery unit of this category
can be provided for in that
the extent of flooding which
compartment.
for which
0511. The extent of flooding in each machinery compartment
consequent extent of submersion
provision is to be made, and the
for the maintenance of
which each machinery unit, essential
be capable of withstanding, will
propulsion and generation, is to
NES. However, it is to
be specified for each unit in the relevant
uniformity of design, the
be noted that, from considerations of
required
submersibility of SW system equipments may exceed that
for a particular
to satisfy the extent of flooding specified
compartment in which any such equipment is to be situated.
wholly or
0512. All machinery specified to be capable of operation when
doing so for a period of not
partially submerged is to be capable of
less than 8 hours.
12
NES 719
Issue 2
6. OVERALL REQUIREMENTS - ASSESSMENT
General
0602. The systems are to be designed to operate with sea water, the
properties of which are given in Figures 2 and 3.
0603. The general requirements for fluid system design are given in NES 710.
0604. The details of the shock levels to which the system has to be designed
are given in CB 5012.
Location of Equipment
0607. Where flexible expansion pieces are fitted between a pump and adjoining
system pipework, the pump suction and discharge valves are to be
located at the ends of the expansion pieces remote from the pump.
0610. The siting of pumps is covered in Clauses 0923 and 0924. However,
where it is not necessary for sea water pumps to be capable of starting
under the ship specified angle of heel and trim, eg air conditioning
plant and distilling plant where a quick start-up is not essential, a
priming connection is to be specified to be provided from an adjacent
operational sea water system.
13
NES 719
Issue 2
14
NES 719
Issue 2
0618. For fire protection and firefighting the largest requirement arising
from one of the following incidents shall be the criterion to be
adopted:
c. Flight deck and hangar and major fires and portable eductors.
(1) Operating a high or low level sea water spray system, but
not bdth together, and taking the larger of these two
loadings.
15
NES 719
Issue 2
0620. Removal of water poured into the ship by the firefighting operation is
not to be considered as a simultaneous operation with firefighting.
Pumping out is to follow as fires are extinguished and eductor capacity
is made available. The exception to this rule is that portable
eductors for removal of free surface water may be required during
firefighting to remove the threat of a loll condition. This requirement
is to be added to the firefighting requirement on the basis of using all
portable eductors carried, up to a maximum of four at any one time with
a sea water supply of 12 tonne/h to each eductor.
0622. The total supply requirements for the HPSW System are to be provided by
electrical driven sea water pumps selected from SDP 13.
in
0623. Having determined the total capacity of the HPSW System and bearing
mind the minimum pressure in the main (see Clauses 0612 and Q613),
select a suitable size pump using the information given in Section 9
and assess the total number of pumps required. To the pump complement
so obtained, must be added one pump to account for a pump being under
overhaul and therefore not available at the time of the incident. Also
where the prime factor is 1B of Fig 1, ie "a fire in the largest
machinery space", the pump(s) assumed to be in that space must be added
to obtain the total number of pumps required for the HPSW system.
Portable pumps provided in accordance with NES 119 are not to be
included in determining the number of HPSW pumps required by the HPSW
system.
0624. The total supply requirements for a LPSW System, whether a common system
ie pump(s) or water supply source supplying different auxiliaries or an
integral system ie pump or water supply source supplying the require-
ments of a single unit eg diesel generating set, are simple to establish
compared to the HPSW System.
0625. Basically the sea water requirements of all .the sea water cooled
equipments in a system are added together to establish the total supply
requirements; the equipment sea water requirements are to be based on
the system design operating pressure and the specified design sea
temperature. For nominal pressure see Clause 0801.
0626. It is preferred that sea water flow to each sea water cooled equipment
is maintained to each unit whether the unit is in use or not. However,
where the system is supplied from the HPSW System, consideration may be
given to a stand-by unit with a large sea water requirement, such as a
steam drains cooler, being shut-off when not in use in order to reduce
HPSW demand providing detailed instructions are proposed for:
16
NES 719
Issue 2
STEP I
STEP 2
3. THEN ADD FOR PORTABLE EDUCTORS (SEE CLAUSE 0620). THE TOTAL GIVES
THE FIREFIGHTING REQUIREMENT
STEP 3
STEP 4
ASSESS NO. OF PUMPS REQUIRED (SEE CLAUSE 0623)
17
NES 719
Issue 2
Amdt 2
i c St 10-6 m 2/ S
C
--2.0.
z
15
1.0 _
u-h
0
05 10 15. 20 25 30 3S
S TEMPERATURE OC
18
NES 719
Issue 2
Amdt 2
1.0290
1.0270r
2 1.0250
1.0230
w 1.0210
1.01901
0 5 10 15 20 25 30 35
0C
TEMPERATURE
19
NES 719
Issue 2
7. HIGHY ST E M HP S W)
General
a ring main
0701. The HPSW supplies sea water throughout the ship by means of
system; a typical arrangement is shown in Figure 4 with standard
symbols shown in Figure 5.
0702. The ring main is to be supplied with sea water from non-submersible
pumps of at least 100 tonne/hour capacity whilst maintaining a pressure
of 7 bar in the main when working at their designed output.
c. Prewetting.
d. Domestic Services.
20
NES 719
Issue 2
NOTES:
0709. Pumps. The pumps shall be well distributed throughout the main and
auxiliary machinery spaces, avoiding as far as possible two pumps in any
one space. For large vessels, separate pump rooms forward and aft are
to be provided as necessary to ensure a good distribution of pumps
throughout the ship. Where it is necessary to fit two pumps in one
compartment they are to be sited well away from each other. Pumps in
adjacent spaces are not to be sited close to one another against the
separating bulkhead, such that both are vulnerable to a single incidence
of action damage. Remote start facilities for pumps shall be fitted in
the Ship Control Centre in addition to local or any automatic start
arrangements.
0710. The pump suctions are to be taken direct from the sea, either from
separate or common inlets. The suction lead is to be as short as
possible and to terminate at the hull valve, this lead is to be
exclusive to the pump in order to be fully available at all times. See
Clause 0605.
0711. Each pump is to discharge directly into the ring main through risers.
0715. Wherever the "warm water" provision is made, a well insulated leak-off
of 65mm nominal size is to be fitted as remote from the pump riser as
practical and arranged to discharge overboard.
21
NES 719
Issue 2
22
NES 719
Issue 2
0724. A swing check valve and isolating valve is to be fitted in each pump
riser as near to the pump discharge as possible, with the swing check
valve located between the isolating valve and the pump.
0726. Control of spray valves for manually operated spray systems are to be
as specified in BR 862 and NES 119.
0727. The valves in the machinery space section of the HPSW System are to be
arranged for remote operation so as to best marry the twin requirements
of machinery arrangement aspects and ease of operation. The valves in
the HPSW System outside machinery spaces are to be operated locally.
0729. Where the extreme fore and after ends of the HPSW Main are in exposed
positions, leak-offs are to be-fitted to ensure a continuous circulation
of water. The leak-offs are to be 15mm nominal bore, well insulated
and so arranged to discharge either directly overboard or into a
scupper with a warmed storm valve.
0731. Stand Pipes and Overboard Discharges. For the provision of internal
stand pipes and overboard discharges for use by the portable pumps, see
NES 119.
0734. Design. Fittings are listed in NES 119 and BR 2170. The size of
hydrant valves are to be 65= bore for flight decks. All other
hydrants are to be 50mm.
0736. Having collated all demands and subsequently sized the fire fighting
system it will be necessary to theoretically check sea water
the
availability from the system whatever the combination of demands on
system. Consequently it may be necessary to adjust the sea water
etc
system pipe size, position of the link up of pumps into the system
system to supply the
to ensure that the resultant water speeds in the
required quantities are not above the basic design requirements of the
HPSW System. C
0737. It should be noted that water speeds in the pipework of the spray
system can be accepted of up to 8m/s in order to keep the weight of the
system to a minimum. When in use some erosion/corrosion will occur but
in view of the short period of operation for checking out the system
from time to time this can be accepted.
Magazine Spraying
0739. The HPSW System is required to supply sufficient sea water to any
other occurrences are making demands on the
Q
magazine spray system whenNES 119.
HPSW Main as detailed in
spray system,
0740. Design. The quantity of water required from the magazine
of
the types of spray nozzles and the positions for a particular type
drawing by the
weapon stowage will be indicated on the magazine layout
of the spray
Magazine Safety Policy Section of MOD(PE). The line-out
water
system is given in BR 862. The pressure and quantity of sea
spray system is to be calculated using the
required to operate the
A hereof and assuming a minimum pressure at
procedures given in Annex
the furthermost nozzle necessary to supply the required area density of
pressure in the main as defined in
water and a minimum permissible
the
Clause 0612. The demand of this system is to be checked against
Main, then to ensure that the sea water
supply available in the HPSW
on the
supply is adequate. Due regard is to be made to other demands
system as laid down in Clause 0618 et seq.
24
NES 719
Issue 2
Amdt 1
0741. Materials. Pipework materials up to and including the branch isolating
valve are given in this Standard. Details of the materials of the.
magazine system are given in NES 161.
Prewetting
.0743. Design. Details of spray coverage is given in NES 118; the spray
nozzles are to be positioned throughout the ship to ensure that all
exposed surfaces are adequately covered. From the pressure losses etc
in the connecting system, can be calculated the overall quantity and
pressure of sea water required from the HPSW Main. The pressure loss
calculations are to be carried out in accordance with Annex A. The
initial calculation is to be based on providing at least 3 bar pressure
at each nozzle as this should not require more than 5 bar at the HPSW
Main when the pre-wetting system is operating. The minimum permissible
pressure in the main is defined in Clause 0612.
0744. For the integration of this system with theHPSW System see NES 11'.
0745. Materials. Connections to the HPSW Main and including the isolating
valves are given in this Standard.
25
NES 719
Issue 2
Amdt 2
0750. Ballasting and De-ballasting. Ballast tanks may be water ballast only,
or fuel tanks which are to be filled with sea water after being
emptied of fuel. The latter arrangement is different from the fuel
water compensated system which is detailed in NES 320.
0751. Ships with water ballast tanks are to be provided with a fixed pipe
system for ballasting from the HPSW Main. Deballasting is to be
carried out by fitting 75 tonne/hour eductors or utilising conveniently
sited salvage eductors. See Figure*7 for illustration of the eductor..
0752. Where sea water ballast is required to be carried after fuel usage, the
to the
tanks are to be filled by hoses connected to the HPSW System and
tank by a hose fed into a filling funnel connection on the tank. The
size of the hose is not to be of a larger bore than the tank air vent
pipe. To facilitate the filling of the tank and to avoid over
pressurising the tank, the hose connection from the HPSW System is to
be positioned adjacent to the filling position.
0754. The ballast tanks are to be structural tanks integrated into the
ship's structure. The tank design is to take account of stresses
induced by ship's movement as well as the hydrostatic pressures due to
the tank contents. The method for determining the structural
scantlings is given in NES 155.
0755. For the prevervation of tanks, fittings for tanks and the calibration
of tanks see:
a. orifice plates
b. reducing valves
valves
0757. In both cases it will be necessary to fit suitably sized relief
the equipment is not subject
to ensure that under no flow conditions
to overpressurisation; see Clauses 1016 to 1026.
26
3-.- 2
- - -
- - -
- - -
- - -
-
-
- EPO S--- -----
- - - - - ---- HYDRANT HYDRANT WE HYDRANTS
HYDRANT - - - STED RTOR STBD
STIBO
--- WEAPONS
SPRAY 02 DECK
02 DECK 02~0 DECEN
sTO ;GE
o's WE __JO K
W
INCINERATOLRM SCULLERY SRS
SITEH 6.
POTATO
H gAL
CEOWGES WEIG
T
BSLG TSTPRTOR--E s TANTAK FLAMMABLE
H EDEUEOUCTOREHOSELEHROCKE STORE
HSPRAY
SONAR
SONAR HGENERATOR
-I
DIEHLSEWAGE
xC I--
TOUCIOR
HPI L AIR IPLANT ERYROOM
MACH
C
H DEK
IOP ENINER M COMPARTMENT
- --
MO.EOPT.ST
- -COMPARTMENT
STBD TOREFRIGY
. ..
OIGPORT
OF HIGH PRESSURE
ARRANGEMENT
FIG.'. GENERAL
SYSTEM
SEA WATER
NES 719
-'- PRESSURE CONTROL VALVE (INCREASE PRESSURE OPENS VALVE) EMERGENCY CONNECTIONS THROUGH BULKHEAD
jFOAM INDUCTORS
]i RE RESERVOIR
FIGURE S- LIST OF STANDARD
SYMBOLS
29/30
NES 719
Issue 2
Amdt 1
NOZZLE
ICKPRESSUR Boo,
SEA WATR''
"': ;SUCTION
PLUG
SEE CLAUSEW0751
7 T-RAT
HIGHPRESURE O
SEE CLAUSE 0751
31
NES 719
Issue 2
8. L O W P R E S S U RE S E A W A T E R SY S T E M iSW
0801. LPSW Systems are used primarily for cooling auxiliary equipment
throughout the ship; the pressure in each system is nominally 14 to
2 bar.
the sea
0802. The supply requirements are established by adding together
sea water temperature of
water requirements at the specified design
in operation or to which
each sea water cooled equipment in the system
the unit is in use. It
a water supply is maintained whether or not
should be noted that:
cooling
a. the SYMES HP air compressors automatically shut-off the
water supply when the unit is not running.
be given to a
0803. In addition to the above examples, consideration may
water requirement, such as a steam
stand-by unit with a large sea
drains cooler, being shut-off when not in use providing detailed
instructions are proposed for:
0805. Flow Rates. The equipment flow rates are to be obtained from the
Where a SYMES
equipment supplier or the SIXES dossier as appropriate. to
dossier
equipment is used, the designer is to check the SYNES is for
provided
establish whether or not the cooling water information for the
specified
the same water temperature as the water temperature
project/installation. Where the water temperatures differ, the
flow to suit
equipment maker should be approached for a revised water
the conditions.
sea water
0806. Equipment Pressure Drops. In selecting/specifying
of a common LPSW System supplied by an
equipments, which form a part
pressure drop" across
electric motor driven sea water pump, a "limiting
on the basis
the sea water cooled units is to be considered/specified
the lower the pump power
that the lower the "limiting pressure drop"
The choice and performance of the LPSW pumps available
requirements. sea water
in selecting the
in the SY11ES range is to be considered
cooled unit limiting pressure drop.
32
NES 719
Issue 2
0807. Any maximum pressure drop across an equipment in an LPSW System will be
specified. The pressure drop across an equipment at the design flow
rate may be obtained from the equipment manufacturer or the SYMES
dossier as appropriate after considering the requirement in
Clause 0805. Where a margin in system flow, to cover for pump wear,
fouling-and-frequency variation, is included in accordance with
Clause 0812 then the equipment pressure drop is to be calculated for
the increased flow using the square law basis as follows:
rl 2
P2 2 x P1
where
0809. System pressure drops. The pressure loss across a system is to be kept
to a minimum consistent with such practical limitations as:
33
I4S 719
Issue 2
0811. The system pressure losses are to be calculated using SDP 25 taking
into account any margin specified in Clause 0812.
0815. In both the syphonic and non-syphonic systems, the pump when starting
is to be capable of overcoming the 'head above waterline' measured from
the waterline to the highest point in the system. It should be noted
that start-up in adverse heeled condition will require a higher pump
discharge head than when on an even keel. Once a syphonic system is
primed this head is cancelled by the action of the syphon ie the pump
duty point total head rise is based on the system fluid friction and
dynamic losses only. For a non-syphonic system the pump duty is based
on the 'head above waterline' and the head loss due to friction up to
the syphon breaker plus the dynamic head loss at the syphon breaker.
35
NES 719
issue 2
Main irculating
circulating
are not required for the main
082i. Scoop systems, in general, or propulsion diesel engines.
systems f6r propulsion gas turbines
is to be
sea water supply to the system
0822. The provision of a standby or from the HPSW System with remote
either by a motor-driven SW pump compartments.
with unmanned machinery
control of the supply in ships
with sea
main propulsion engine is supplied
6823. Where a variable speed overboard discharge is
driven pump, each
water by an associated engine all conditions of
load waterline under
to be located below the light and associated
sea water cooled equipment
heel and roll. The ancillary
the light load waterline wherever
piping is to be located below the
and/or piping is located above
practical. Where the equipment the HPSW System;
is to be provided from
waterline a priming connection either a low flow or low
a surveillance system incorporating
to be provided to identify loss of
is
differential pressure device arrangements of main circulating12.
system flow. Typical diagramnatic 11 and
SW pump are shown in Figures
systems with an engine driven
1
Self-contained AuxiliarM Circulating
with
are preferably to be provided
0824. The following auxiliaries systems:
self-contained auxiliary circulating
e. Desalination plants.
share any service with
generating sets are-_nOt to
NOTE: The systems for the be interconnected to another
system the
another cooling system or to to generating
in the loss of sea water
failure of which would result
sets.
36
NES 719
Issue 2
0825. A typical system for a diesel generating set is shown in Figure 13.
0826. Emergency bilge suctions are not to be provided in association with the
pumps for any of the above auxiliaries.
0827. A stand-by supply of sea water is to be provided from the HPSW System
to each gas turbo-generating set and to each diesel genertfig set.
Where the generating sets are provided in pairs, one stand-by supply
may be provided for each pair; this supply is to be sized for the sea
water requirements for one of the units only.
pump,
0833. Where the system is supplied with sea water by one motor-driven
an emergency supply is to be provided from the HPSW System.
machinery
0834. Where an auxiliary circulating system supplies more than one
,! compartment, a stand-by supply connection from the HPSW System is to be
which does not include an
provided in each machinery compartment
auxiliary circulating pump capable of supplying the system.
Water Supply to Shaft Bearings, Stern Seals and Stern Tube Bearings
or from
0835. The supply is to be provided either from a circulating system
the HPSW System.
a sea water
0836. White metal lined plummer bearings are to be provided with
supply for emergency cooling purposes.
water supply
0837. Stern seal/stern tube bearings are to be provided with a
of minimum pressure 0.35 bar above sea pressure in way of shaft
seal cooling and bearing lubrication.
penetration at maximum draft, for
bearing at this low
To ensure there is positive flow through the
to be fitted in the supply
pressure differential, a flow indicator is
propulsion with
line. Where the ship is to be capable of maintaining
arrangements are not to be
loss of electrical power and the electrical
power within at least
assumed to be capable of restoring electrical
supply is to
half an hour of a total electrical failure, the sea water
supplied with water
be taken from the main circulating water system
from an engine driven sea water pump.
37
NiES 719
Issue 2
in the HPSW
a. the system is to be designed for the maximum pressure
System.
associated
b. the system is to include a pressure reducing valve and
relief valve.
relief valve.
c. the system is to include an orifice and associated
to match the
0839. Because of the difficulty in obtaining a relief valve
valve
varying system requirements and the uncertainty of the
at the time of the emergency, every effort should
functioning correctly
maximm
be made to design all components to withstand full HPSW
Where constant flow valves are fitted in the LPSW System and
pressure.
valves is not
the supply branch and/or component downstream of the
designed for the maximum pressure in the HPSW System, a full bore
in each branch and sized to pas's the
relief valve is to be provided
the associated constant flow control
maximum design flow rate through
valve.
Valve Policy )
in Section 10.
0841. The types of valves to be used are given
the
0842. Reliability can be designed into the system by considering
following:
where they will be
a. Providing isolating valves at those junctions
failure.
most effective in limiting flooding from pipe
pairs of SW cooled
Arranging the inlet and outlet branches to
b.
be independent of
equipment which are vital eg lub oil pumps to
each other.
in the supply and one in the
0843. Each equipment will be fitted with a valve
isolated for
discharge line so that the equipment can be
repair/replacement. Generally the valve in the discharge line is to be
a glandless diaphragm valve. See Clauses 1216-1220.
38
INES 719
Issue 2
HRL LSHYDRAULIE
ISE INE
W.L.
~DISCHARGE SYSTEM
~PUMP
"-;y:.,"HYDRAULIC LOSSES IN
PUMP SUCTION
NOTE.
POINT b:MUST BE LOWER THAN POINTa
y = ABSOLUTE PRESSURE
39
NES 719
Issue 2
A TO C
NON -SYPHONIC
ATO B ONLY
A TOC ONLY
HEAD ABOVE
WATER LINE
=3m
FLOW RATE
AQ
;HIE C
40
NES 719
Issue 2
STARTING HEAD
ABOVE WATER LINE
41
IES 719
Issue 2
PROP
OIL
- Ri
E-j
TO OTHER
S.W.PUMPS
L.O. PUMP
HYDROSTATIC
DRIVE OIL COOLER FAIl
GEAR DRIVEN
SWPUMP OIL
I-T
IBLOCK L- P• LO,
HYDROSTASTIC V'"
• DRIVE OIL COOLER L
OTHER
-.---- T--O FriO P-1
S.W PUMPS 1IL
0"-
42
NOTE:- COMPONENTS SHOWN ARE TYPICAL ONLY y/CAN BE INCLUDED IN THE FW CIRCUIT.
SEE FIG.S FOR STANDARD SYMBOLS
tnSTANDBY SUPPLY e-
4 STERN GLANDS FROM HPS.W SYST
~(FIRE MAIN)
0
' MAIN DIESEL O
CSE
t LOCOOLER TUB
GEAR BOX
LUB OIL FWCOOLER
,. ,COOLE
NES 719
Issue 2
SEETUBE
LOCKED
OPENOVERBOARD
SET
FW j
DIESELDI
SEE FIO.5 FOR STANDARD SYMBOLS
44
NES 719
Issue 2
AUX
CIRE.
.P. . ] PUMP
AIR I IR I ABLI
RELIEF
VALVE
STAND-BY SUPPLY
FROM H.PS.W SYSTEM M
OR OTHER CIRC.PUMP MAIN
IO RELIEF VALVE LO
REQUIRED IF STAND-BY PUMP
ISFROM ANOTHER 'MOIRS,
CIRC. PUMP.
'lCOOL4 ,ISER,
Lj. L.
45
NOTES:- u DISTILLING PLANT 1NOT SHOWN c) COMPRESSORS HPSW SUPPLY-
A/C PLANT F-BUT HAVE INDIVIDUAL ORIFICES £
REFRIG. PLANT I INTEGRAL SUPPLY RELIEF VALVES FITTED
WHERE UNITS CANNOT
b)VENT COOLERS - HPSW SUPPLY WITH-STAND FULL" PRESSURE
"- I
SEE FIG.5. FOR STANDARD SYMBOLS ISTAB IL-ISR d) COMPONENTS SHOWN ARE TYPICAL ONLY
ISER
FUEL EM
SSPECIAL
DRAIN ERVIE TRANSFER CPMS
COOLER AIR. PUMP OL
COoLER MOTOR COOLER
co
0
4cnrn
S..S
PUMP
En
, LUB LUB
t )ANOIL OIL
PUMP
OMPR COOLER PUMP oMP
TANK
-A--
--
--TAN K MOTOR MOTOR
Ar
Q . . . Q
Y S
NES 719
Issue 2
9. PUMPS
General
0901. All SW pumps are to conform to the requirements given in the NES 327.
Selection
0902. Pumps for the HPSW and LPSW Systems are to be selected on the basis of
Type Number (Specific Speed) against pump efficiency curve as indicated
in NES 327. The use of the Type Number: pump efficiency curve will
indicate that normally the centrifugal pump is the best selection for a
HPSW pump duty because the Type Number of the mixed flow or axial flow
pumps will usually be outside the Type Number at which such pumps are
efficient and economic. Similarly, the use of the Type Number: pump
effiency curve will indicate that normally the centrifugal pump is the
best selection for a LPSW pump duty but that on occasions the duty may
merit the consideration of mixed flow type, axial flow type or turbine
type (covering vortex, regenerative side channel etc) pumps. A turbine
type pump is to be considered where a self-priming feature at a small
flow rate is required. Turbine type pumps are usually limited to flows
up to 70m 3 /h and at low, medium or high total pressure rise.
0903. Axial flow pumps and mixed flow pumps with an axial flow bias when
fitted in parallel are to be provided with automatic by-pass to sea
arrangements; see Clause 2046.
0907. The High Pressure System and the circulating water pumps are to be
selected where possible from the SYMES Index range which covers a wide
range of pump duties. Each SYMES dossier for pumps includes a "Range
Chart" for all the pumps showing head against flow rate envelopes for
various indicated synchronous speeds, pump impellers and pump impeller
diameters. The head against flow rate curves for each pump is
superimposed on this Range Chart.
47
NES 719
Issue 2
0908. Some pump dossiers contain lists of optional impeller sizes some of 0-
which are recognised as "SYHES range'?, and others which take the pump
out of that classification. In certain examples these impellers may be
found as part of another SYNES unit. Exceptionally it may be necessary
to use one of the listed impellers, which is not part of the SYMES
range, to meet the required duty, but the system duty is to be amended
to suit an available pump if this proves to be more convenient and cost
effective. Each index number has one motor as standard and this covers
quite a broad band of impeller sizes and duties. A larger motor may be
available or can be made available comercially for each range of pump
and design but the selection of such a motor results in a different
equipment existing in so far as SYMES indexing is concerned.
0909. The information required before making reference to a SYMES dossier
is:
d. NPSH available.
Performance
0914. Axial flow and some mixed flow pumps have a pronounced increase in
total pressure rise hence rise in power, as the discharge valve is shut
together with an unstable zone between about 50 to 70% of the best
efficiency flow rate and because of this their use is usually limited
to flow rates above the unstable zone.
48
NES
Issue7192
2
where 2 = H1 x [1]
3
kW = x kW
Q = flow rate
H = head rise
kW = power
0917. The NPSH available to a pump is significant to its design and to its
operating characteristics as installed in a ship. The NPSH available
-J is therefore an important aspect in the design of suction piping,
location of pump and selection of pump. Figure 16 shows the type of
NPSH available characteristic to be constructed.
0919. Where a number of pumps are connected to a common suction main the
pipework friction losses in the main are to be calculated with the
maximum number of pumps in use as dictated by the systems' flow rate
requirements.
0920. The NPSH required by a pump is the total head of water above the vapour
pressure necessary to induce the water into the pump impeller vanes
without significant drop of pump differential head below that provided
when adequate NPSH is available. If the NPSH available at the pump
suction is less than the NPSH required a significant loss will be
incurred in pump total pressure rise relative to the normal
49
NES 719
Issue 2
0921. The useful normal operating range of a pump is limited to those flow
rates whereby the NPSH available exceeds the NPSH required. The
operating range, for an existing pump, can only be extended by
increasing the NPSH available. This is to be achieved by lowering the
pump to increase the height of water above the impeller and/or
reducing the suction pipe friction head losses. Methods for reducing
friction head losses are as follows:
b. Selecting a pump from the SYMES range, see Clauses 0907 to 0911
inclusive.
Siting
0923. Non-self -priming sea water pumps are to be located so that the pump
impeller is below the waterline under all conditions of heel and trim,
unless otherwise specified (for example see Clause 0610). The effects
of heel and trim on water level above the pump impeller can be
minimised by locating the pumps at or near the ship's centreline and
avoiding extreme forward or aft locations.
0924. Care is to be taken to arrange the floorplates and the pipework around
sea water pumps so that the gland seal, which must be inspected for
leaks, can be seen without difficulty and so that the necessary access
is provided for pump end maintenance.
50
NES 719
Issue 2
0925. Seats. The term seating covers the actual connection and structural
members between the ships structure and the baseplate or holding down
points of the equipment concerned. Alternative terminology may
sometimes be found in equipment specifications, such as,. stools or
spacers.
a. Be of adequate strength.
to be avoided.
51
NES 719
Issue 2
0932. Access holes for maintenance or services are to be arranged such that
strength and rigidity is unimpared.
0937. The top plate and bearers are to take the holding down bolts and are to
be of the required thickness after machining as necessary.
0938. The seatings sited close to other equipment seatings may be built as a
single unit.
0939. The seatings are to be abrasive blasted and zinc sprayed and painted
on completion of welding and before the installation of any services or
machinery. Zinc spraying is to be in accordance with BS 2569 Pt 1.
0940. The seats are to be erected, faired and welded in position as shown on
the approved drawings within a tolerance of + 5vu.
0941. Bedplates where indicated are to be planed true before installation and
are to be checked and/or trued after installation. Alternatively the
bedplates are to be hand finished locally in way of mounts in ship as
follows:
After completion of welding the mounting areas are to be machined
so that on completion they are all parallel to the Master Datum
and within + 5-, of the designed position.
52
NES 719
Issue 2
Control
NOTE: Where the motor driving the pump is cooled by water, taken from the
pump discharge and return to the pump suction, the motor heat losses
are to be added to the pump heat losses; for estimation purposes the
heat loss at the specified (normal operating) duty may be used as this
is a reasonable approximation and is the work done on the fluid at low
flow which can be read from the pump performance curve in the SYES
dossier.
Air Venting
53
NES 719
Issue 2
54
NES 719
Issue 2
HEAD EQUIVALENT TO
I - VAPOUR-PRESSURE-
I FRICTION (H'v)
PS H AVAILABLE U(T
SN
sc N P SH AVAILABLE I
a- AT DUTY FLOW
0AVAILABLE A
CD 9-3m (S W)
-4
PIPE HEA D EQUIVALENT TO
~~SUCTION TPIPEO VAPOURHPRESSURE
-5
NPSH= (HA+HSP-.-2 - HF)+-L -HV...(1)
HA+HSp - HF -Hv
NOTE:- ABSOLUTE STATIC HEAD AT PUMP SUCTION
IS HS = HAI HSp -2gnHF
16
S2
NPSH AVAILABLE.
PUMP
DUTY
10- CPI NT.
I I LIMIT
• ON PUMP
OUTPUT
(I) IF NPSH (REQUIRED) IS PROVIDED. O
I
(2) WITH NPSH (AVAILABLE) AS SHOWN. I
a
<6
I 2)
NPSH REQUIRED\I
2
SI I
56
NES 719
Issue 2
10. VALVES
1001. Valves are to be selected from NES 360 with the further guidelines on
valve usage outlined in this Section.
Location
or box system
1004. An isolating valve is to be fitted at each sea inlet tube
opening. See Clause 1027.
if fitted or
1005. An isolating valve is to be fitted at each discharge tube
on the hull. See Clause 1027.
systems is
1006. In all positions where the reduction of noise in piping
important such as adjacent to the sonar, adjacent to quiet compartments,
cavitation
and below the waterline, valves are to be chosen for minimum
and flow disturbance as follows:
57
NES 7.19
Issue 2
1008. In accordance with the requirements of Clauses 0721 and 0722,valves are
to be provided at bulkheads when the sea water system extends through
more than one watertight compartment. The valves are to be operable
from the same side of bulkhead as the part of the system remaining in
operation. This means that:
1010. All hull valves are to be fitted to enable operation to be carried out
both locally and remotely by rod gearing from the communications deck
over the compartment in which the valves are sited. Where excessive
lengths of rod gearing are involved, power assistance is to be
considered and proposals forwarded to MOD(PE). The valves are not to
have the facility for being locked.
1011. The motive water supply valves for the salvage eductors are to be
fitted to enable operation to be carried out both locally and remotely
by rod gearing from the communications deck and the compartment in
which the valves are fitted. Where the salvage eductors are used for
deballasting, the salvage suction and cross-connection valves to the
ballast system are to be similarly arranged. The valves are not to
have the facility for being locked.
58
NES 719
Issue 2
Locking Arrangements
1015. The HPSW pump discharge valves are to have the facility for being
locked open.
1017. System Design to avoid Excess Pressure. Where practical, a sea water
system is to be designed to avoid the provision of a relief valve by:
1018. Relief Valves. Full bore and partial bore flow relief valves are
defined in Clause 0409 bb and cc respectively. A full bore valve
safeguards the system including all components against excess sea water
pressure in conditions where pressure exceeds the design working
pressure. A special type of relief valve is the Surplus Valve which is
required to reduce the delivery pressure of the HPSW pumps into the
main to the design working pressure when the pump is on low demand.
The design of this special valve is such that consultation with MOD(PE)
and the valve manufacturer is essential to ensure that the final design
results in an effective valve that meets the design requirements. See
Clause 0703.
1019. Where the system design, extent and arrangement makes it unlikely that
the system will be operated with all or the majority of the branch
discharges shut-off only a partial flow relief valve is to be provided
to prevent excess pressure. Where the above conditions are not
obtainable, a full bore relief valve is to be provided.
59
NES 719
Issue 2
'.
1020. The requirements for relief valves are as follows:
d. The relief valve system (ie the discharge pipework from the
valve) pressure loss, at the flow rate appropriate to the valve
full open pressure, is to be considered when specifying relief
valves. In general a system loss of less than 10% of the valve
pressure loss at this flow rate is considered to be acceptable.
Where the relief valve is set in the ship the downstream system
pressure loss is to be represented when the valve is tested in a
test rig.
1027. Valves up to 50mm bore may be mounted directly on to the hull in all
positions (see Clause 1318). Valves over 50mm bore may also be
mounted directly on to the hull when fitted above the RED waterline.
For positions below the RED waterline, valves over 50mm bore are to
be mounted on short sea tubes which can be incorporated into the hull
framing by additional stiffening. Sea chestsare to-be specified
as the hull when applying these rules.
-02 )
ORIFICE P: QCURVE (APc
0ORIFICE P.D.
FULh RV DESIGN FLOW u taCAT., A
S(A)
FLOW
QRV as
61
xEs 719
issue 2
WORKIN
" ~PRESNSURE" !
Ln
FLOW (Q)
62
NES 719
Issue 2
SYSTEM RESISTANCE
MAXIMUM PERMISSIBLE NUMBER
MARGIN OF LEGS SHUT
(PRESSURAT V TRS LF
DELIVERY OPRESSURE
SIDE OF SYSTEM RESISTACEPRSUE
ORIFICE) SOE P UT I
,C
FLOW (Q) QS
63
NES 719
Issue 2
11. P I P E W 0 R K
Design
1101. Pipes should be formed by bending to at least 3D, taken to the centre
line of the pipe whenever practicable. The requirements for the
bending of metallic pipes is given in NES 743 Part 1. In cases of
extreme limitations, pre-formed elbows of 2D or cast gunmetal bends as
specified in BR 3013(2) may be used.
1103. Bends are to be of the largest practicable radius. The minimum radius
for bends is given in Clause 1101. Short stiff bends are to be avoided
particularly in positions likely to be subjected to vibration.
1105. At least one bend is to be introduced into the suction line between the
pump and the sea inlet to reduce transmission of pump noise to the sea.
1107. Inlet piping to relief valves is to be short and direct. Stop valves
are not to be fitted between the equipments or piping being protected
and the relief valve.
1108. Where pipes are taken through the bulkheads they are to be generally
curved or other arrangements made to ensure that such pipes will not
form a rigid connection between the bulkhead and internal structure.
Where straight lengths are unavoidable flexible rubber expansion pieces
to
are to be fitted. Rigid pipe supports from the ship's structure are
be fitted to the pipework about 100mm clear of the connecting flange
each side of the rubber expansion piece to ensure correct alignment
at
axially yet allow the longitudinal movement induced by ship movement
sea. For assembly and testing'precautions see DG Ships 6969 & 6970.
shop
1109. Where practicable, piping layouts are to be designed to permit
prefabrication as far as possible. In such designs, an adequate number
Closing lengths are to be
of closing lengths is to be incorporated.
made to template.
as far
1110. In all sea water systems the straight portions are to be worked
as possible in standard lengths, convenient for dismantling.
64
NES 719
Issue 2
NOTES:
1113. The system resistance of the suction pipework is not to exceed the pump
nett positive suction head under any pump operating condition, see
Clauses 0917 to 0922.
b. A NPSH available curve for comparison with the pump NPSH required
curve to ensure than an adequate margin exists, see Clause 0812.
65
NES 719
Issue 2
Water Speeds
from flow rates for maximum duty
1122. Water speeds are to be calculated for each system.
conditions at the temperatures specified
on
copper-nickel-iron pipework based
1123. The water speed through 90/10 given in Table 2:
to exceed the values
minim- pipe bore sizes, is not
oom
below10 41 54 72 84 &
Avrage 14 18 22 27 35
pipe 10 10 abov
bore
m
66
NES 719
Issue 2
1126. Where extrusions and right angled tee pieces are used in a system the
following water speed limitations apply:
1127. The maximum and minimum permissible water speeds through cooler tubes
are specified in NES 329. The minimum water speed should be as high as
practicable to prevent/minimise fouling build-up; the designer should
aim at a design target minimum water speed of 1 m/s. The conditions at
which the water speed is assessed is normally to be that of maximum
specified duty. In the case of coolers involving temperature control
by restriction of water flow, this will be the maximum water speed
experienced. Maximum water speeds are specified to prevent premature
system failure due to erosion/corrosion. Minimum water speeds are
specified to prevent fouling. Fouling could interfere with the
designed heat transfer of the system and may cause premature failing of
the tubes due to localised erosion/corrosion.
1128. Experience indicates that for fluids with poor partial heat transfer
coefficients, such as lub oil, fuel oil and air, the use of water
speeds of I m/s and above through cooler tubes will probably increase
the quantity of sea water flow and increase the size of the pipe bore
of the fluid pipework without achieving any worthwhile reduction in
cooler size.
1129. The minimum tube water speeds refer to operation at full output.
Examples of system installations whereby even lower tube water speeds
would occur at lower powers and/or seas colder than the design sea
temperature are as follows:
1130. The water speed through tubes/pipes may be calculated using the
following equation:-
V =Q x 353.6
2
d
where
67
NES 719
Issue 2
1131. Table 4 provides a ready means for establishing pipe bores for )
variations in supply pressures ranging from 0 to 80%. The figure also
includes an example of how to use the Table.
1132. The consistent use of water speeds approaching the maximum permissible
is to be avoided where it would lead to a substantial pressure loss
imbalance across the equipment branches and an unnecessarily high
overall system pressure loss. Annex B gives an example illustrating
the above aspect.
1133. For the pressure testing of systems and components, see Section 19.
Arrangement
a. foot of bulkheads
b. bulkhead stiffeners 9
c. deck beams
68
NES 719
Issue 2
1141. All ferrous and non-ferrous pipes are to be kept clear of aluminium
alloy structure. At least 13mm is to be provided between the pipes or
the pipe insulation and the structure.
1143. For the reasons given in Clause 1142, tail pipes, strum boxes, filling
pipes, inside steel tanks are to be of steel which is to be hot dipped
galvanised in accordance with Clause 1326 upon completion of all
welding and any other constructional work.
1144. Unnecessary high and low points are to be avoided; where these are
unavoidable, vents and drains as appropriate are to be provided. For
the provision of air vents and drains, see Clauses 1178 to 1182
inclusive.
1145. Open ends of relief valve discharges are to be readily seen and are to
be arranged to preclude injury to personnel and damage to machinery by
the discharged fluid.
1146. Pump relief valve discharges and temperature control valve by-pass
discharges into pump suction pipes are to be sited so that the valves
are as far from the pump inlet as possible to avoid cavitation.
1147. The penetration .of bulkheads or other ship structure below the RED
waterline that affects the ship's watertight integrity is to be
referred to the Ministry for approval.
, -tIdentification/Colour Marking
1150. Piping, rod gearing and spindles are to be marked for system
identification purposes by painting with a specified colour or by the
use of adhesive plastic tapes with the service printed on the specified
background colour in accordance with the details given in Form S1188.
1151. Branch pipes from the HPSW Main for fire fighting services are to be
painted SIGNAL RED to BS 381c shade number 537 throughout their length.
Fittings
a. flanges to BR 3013(2).
69
NES 719
Issue 2
1154. Galvanised and ungalvanised steel pipes up to and including 42mm pipe
size are to be connected by screwed sleeves. Long screws, bends and
springs and return bends are to be in accordance with BS 1387 to allow
for parallel screwing. Pipes and fittings are to be selected from
BR 3013(2) and BS 1387.
1155. Steel pipes above 42mm pipe size are to be connected by butt welded
joints, sleeve welded joints, or by flanges welded to the pipes. Except
for the final weld on the sleeve welded joint all welding and machining
is to be completed prior to any galvanising being carried out. Pipes
are to be selected from BR 3013(2).
1159. Wherever welded joints are proposed to save weight and space, care is
to be taken to ensure that the joints are located in positions where
welding and testing is possible.
1160. The greatest care is to be taken to ensure that mating flanges are
parallel and truly aligned before bolting up. Care is also to be taken
to ensure that accurate aligiment of capillary brazed joints and joints
made with screwed union fittings. Accordingly closing lengths of
piping, or single lengths of pipe, are to be made to template.
1162. Where screwed hose connections are fitted they are to be provided with
screwed caps or plugs secured by chain to a suitable fixture. The
chain and its end-connections are to be of a secure (non-openable link)
design.
70
NES 719
Issue 2
1163. Compression fittings are not to be used with any steel piping nor with
copper nickel alloy pipes in sea water systems, except in instances
where connections may be required directly onto toilet flushing valves.
Capillary type fittings may only be used on copper nickel alloy pipes
but not in positions where operation of a blow lamp on piping may
result in damage to adjacent fittig& or when-pipe-joints cannot be made
satisfactorily in place. In such cases either a flanged joint is to be
used or the system redesigned to permit satisfactory access.
1164. Branch pipes are to be connected to the main leads by gunmetal tee
pieces (angle or swept) or extruded tees (see Clause 0716). Fittings
are to be selected from BR 3013(2). Reducing branches are to be
tapered. The use of the "Scotch" (cup socket) and brazed "saddle
branch" is not permitted in any circumstances. Attention is drawn to
the limitation on water speed for extrusions and right angled tee
pieces, see Clause 1126.
1165. The joints of pipes, valves and fittings are not to be made at
bulkheads or decks but are to be so arranged that any joint can be
remade from one side of the bulkhead or deck only or it is to be
arranged at least 150mm clear of the deck/bulkhead: any flange con-
nection necessary to the bulkhead or deck is to be made entirely
independent of the pipe joint, (see Clause 1176).
1166. Generally "dry pipes" of steel such as sounding tubes, air escapes,
overflows or weather deck drains where they penetrate boundaries are to
be welded to a sleeved deck piece which in turn is to be welded to the
steel structure. In way of aluminium structure only galvanised steel
sleeve bulkhead/deck pieces as Clause 1175 are to be used. Fastening
to the aluminium is to be by zinc plated steel bolts dipped in Jeffery's
Sealing Compound, barium chromate inhibited, and the interfaces treated
and sealed using calico or similar insulant with Jeffery's Sealing
Compound in accordance with the requirements of NES 110.
1168. All joint rings are to be ordered from the manufacturer as pre-cut
joints. Jointing material and dimensions are to be in accordance with
BR 3013(2) Section 3. Rubberised cork gaskets are not to be coated
with jointing paste.
1169. Pipe Supports - Sea water systems are to be supported and located by
pipe clips designed and fitted in accordance with BER 3021. Pipe clips
are to be lined with rubber where the system is subject to vibration.
1170. The number of pipe supports shall prevent excessive vibration but
should not restrain the pipes so as to cause excessive transfer of load
from structure to pipes and pipe joints.
1171. The positioning of the pipes and supports is to take into account the
designed deflections of system components under shock; due account is
to be taken of the deflection of the supporting structure and
surrounding equipment under the shock load.
71
NES 719
Issue 2
1175. Bulkhead and Deck Fittings. Where system flanged pipes are used the
watertight bulkhead and deck connections are to be in accordance with
BR 3013(2). Adequate compensation of the structure by insert pieces is
to be worked in way of the penetration to ensure that the stress
concentration factor is commensurate with the working stress in the
area concerned. Riveted or welded doublers are not to be used.
Galvanised mild steel sleeves with flanges may be used as bulkhead or
deck pieces. Where the through pipe of the system is not less than .)
2.5-m it is to be sealed to the sleeve by welding. Where the thickness
is less than 2.sm the connection is to be by brazing.
1177. Strainers. For the requirements of strainers see NES 321 and NES 748.
Strainers are to be provided:
(6) Such other systems where an emergency supply from the HPSW
System would be inadequate.
72
NES 711
issue
Materials
73
NES 719
Issue 2
74
NES 719
Issue 2
1189. To avoid cavitation in areas of low pressure (ie pump suctions), pump
as
relief/by pass valve returns to the suction line are to be located
far as possible and at least 10 pipe diameters from the pump suction
flange.
1190. Erosion damage is caused by too high a water speed either general
overspeed or local overspeed. General fluid overspeed can be avoided
by following the rules specified in Clauses 1122 to 1133.
Corrosion
the effects of
1192. For the design of sea water systems to avoid/minimise
corrosion, see BR 1254.
Manufacture
and the degree
1193. General. The working speeds, combined with the pressure
of flexibility of operation called for, necessitate meticulous
attention to materials and detail of design and call for the highest
throughout
standards of workmanship, finish, cleanliness and inspection
construction.
NES's 706, 729, 745, 769, 771, 772 and 773, and DG Ships/PS/9020.
75
NES 719
Issue 2
76
NES 719
Issue 2
60
EQUIPMENT DESIGN FLOW RATE PLUS MARGIN
50 D
HxO.c .
40 COMPONENT HEAD LOSS
4' I
* .30 C
C3
20 B
10
0 25 50 75 100
FLOW RATE%
125
UTY
100 OVERALL SYSTEM HEAD LOSS POINT
50 H-K Q2< ca
J. .
25
0 25 50 75 100
FLOW RATE %
SUCTION PUMP ,_DISCHARGEI I DISCHARGE I
TYPICAL SYSTEM
77
NES 71'9
Issue 2
10
10 8
8--6
uiH
FRICTION
Q2 LOSSES
tti
tA
LA
C3
ol
-rz
'-I
CD 4-
L 20 4O 60 80 100
SFLOW RATE (m3/1h)
PUMP
78
NES 719
Issue 2
DTO E OTOF
BRANCHES
SYSTEM
CHARACTERISTIC.
DUTY
POINT
a:-
O*FQ
... A TO B
FLOWTION
TOTAL DESIG
NOTE :-
(1) Oc=EQUIPMENT MAKERS FLOW RATE
2
PLUS MARGIN.
LAW H"
01) ALL CURVES FOLLOW
A MULTI BRANCH
FIGURE 23 - HEAD:FLOW CHARACTERISTICS FOR
SYSTEM WITH NO HEAD ABOVE WATERLINE
SEE CLAUSE 1118
79
NES 719
issue 2
ST 0
LDUTY POINT.
O. DG
< a F
+
mfl
ER 9
C
I'
< = D' D"QG
2 *?POIT OF INLETTIO
3 A C TOTAL DESIGN FLOW= .
FLOW RATE -- - - -C
NOTE PE
FQ EQUIPMENT MAKERS FLOW RATE HEAD ABOVEKANC
PLUS MARGIN. WATER LINE WL
-.I+=POINT OF INFLECTION -'- -
3 ALL CURVES FOLLOW LAW Hw (12
80
NES 719
Issue 2
Given information
From Table:
81/82
NES 719
issue 2
14.0 1.25 0.69 0.66 0.63 0.61 0.59 0.56 7' 0.52
NOTE:- (i) 7 At this point the water speed falls below minimum allowable given in Clause 1123 specific approval is
required to exceed this pressure range for this size of pipe.
83/84
NES 719
Issue 2
12. ZLS,_.W__Q.,_._,_,_,L
c. In some cases the water speeds do not fall below the minimum
permissible water speeds at extreme operating conditions, see
Clauses 1127 to 1129 inclusive.
1202. Factors to be taken into account in assessing the flow rates in a sea
water system are:
1205. The flow control devices, excluding temperature control devices, used
in Naval cooling systems are in general suitable for a working pressure
gauge up to 10 bar. They are as follows:
85
NES 719
Issue 2
1206. Typical examples of the use of these main types of flow devices
together with their advantages and disadvantages and suggestions as to
when and where to use the various flow control devices are outlined in
Clauses 1207-1240. Combinations of the various devices can be used in
system design.
b. Any leakage would be from the cooled fluid to the sea water when
the equipment is operating.
the
1208. These devices are to be fitted at least ten pipe diameters from
heat exchanger header inlet flange to reduce risk of poor water
distribution across the heat exchanger stack face and/or tube plate
erosion. See Clause 1191.
1209. Where the equipment is above the waterline and arrangement aspects
in
prevent the outlet rising above the equipment, flow control devices,
of
particular constant flow control valves, are to be fitted downstream
sea water cooled equipment. Constant flow control valves ensure:
Orifices
86
NES 719
Issue 2
1211. Orifices may be of the single plate, multiple plate or opposed type;
see NES 710. Size of orifice is to be arranged so that impingement
corrosion and/or erosion corrosion does not take place, see Annex D.
1212. Advantages of an Orifice are that they are a cheap and simple means of:
b. The flow is dependent upon the pressure at the orifice inlet and
at outlet, ie fluctuation in either of these pressures will vary
the flow rate; for example the firemain pressure can vary by 50%
resulting in a change in flow rate of 221% through a HPSW main
supplied orifice.
c. They are noisy if the pressure loss across the orifice is too
high; for the design of orifices to minimise noise see Annex D.
87
NES 719
Issue 2
88
NES 719
Issue 2
1230. Where a system is supplied from a system at a higher pressure, then the
total flow of water is to be set by means of a fixed opening flow
control device such as an orifice or diaphragm glandless valve located
at the offtake from the higher pressure system(eg HPSW System).
1232. With this type of system the pipework is to be sized to ensure that: C)
1236. This type of system is usually restricted to simple one pump arrange-
ments such as air conditioning plant and refrigeration plant for
example.
1237. With this type of system the pump and system characteristics are to be
matched and tuned to ensure the design flow to the equipments. When
this type of system is used as an auxiliary cooling water system
attention is to be given to the following:
90
NES 719
Issue 2
1238. Automatic temperature control devices of the water throttling type may
be included in this type of system. The provision of such temperature
control affects the maximum working pressure of system, depending on
the particular system arrangement in which it is fitted, as follows:
91
iES 719
Issue 2
13. INLETS AN D I S C HA R G E S
1330.
1310. Gratings are to be fitted as Clauses 1322 to
92
NES 719
Issue 2
Construction
1312. The required shape of the hole is ideally elliptical. The practically
acceptable alternative is either a circular shaped hole or one with
semi-circular ends. On no account shall openings with square corners
be fitted. The width of the hole is to be limited to ensure the
following conditions are met:
a. It is not greater than 2/3 the panel width. The width being
taken as the minimum dimension of the hull plating panel,
irrespective of direction.
1313. The hull plating thickness is to be increased locally by 50% when the
hole is greater than, ie extends beyond, the middle third of the panel
width. The local thickening is to be taken beyond the passing
continuous member wherever possible. For a more accurate assessment of
the insert plate thickness, see NES 110. The minimum distance from the
edge of the hole to the edge of the local thick plating is to be equal
to the width of the hole.
1314. All sea tubes of 65mm nominal size and below are to be manufactured in
matching material of the same strength as the hull plating it is
penetrating, with a maximum wall thickness of 10mm. The tube bore is
to match the bore of the hull valve attached to its head. Large holes
such as main inlets and discharges, are to be worked structurally with
the hull and reinforced by thicker plating and additional stiffening as
necessary.
1315. Sea tubes over 65mm nominal size including, the short lengths of large
diameter tube required on conical shaped sea tubes are to be fabricated
with one. welded seam.
1317. Sea tubes and pipes to inlets and discharges are to be of lOmm minimum
thickness arranged so that they do not act as struts when fitted
between fixed structures such as inner and outer bottoms. The pipes
are to be cranked and the sea tubes are to be provided with shearing
joints, the strength of which is to be less than the connections to the
fixed structure to prevent the displacement of the fixed structure due
to shock or grounding. The shearing joints are to be double fillet
welded with a leg length of t/3 but never less than 3mm, where 't' is
the thickness of the sea tube.
93
NES 719
Issue 2
1319. Where ship side valves are to be mounted direct to the hull they are to
be fitted on hull inserts. The hull inserts are to be sufficiently
thickened to compensate for the opening in the hull and to take the
securing studs for the valve fastenings. Where the shape of the hull
and the diameter of the insert requires that a very thick insert has to
be fitted, a sea tube is to be provided in lieu.
1320. All valve boxes are to have flanges parallel or at right angles to the
axis of the sea tube unless otherwise approved; different angles are to
be provided for in the sea tube.
Gratings
1322. Anti-sabotage portable gratings are to be fitted to all sea inlets and
to all underwater sea outlets greater than 65mm nominal size. The
grating bars are to be angled as shown in Figure 25 (see SDN 003 503 965).
1323. The width of each dividing bar for sea inlets is to be:
2
a. Sea inlet up to 300mm dia or 0.07m -10mm
2
c. Sea inlet over 600mm dia or 0.28m - 20mm
1325. Where suction strainers are not fitted the clear openings of inlet
grating are not to exceed 20mm. Where one tube or box serves more than
one valve, the clear width between the bars is to be suitable for the
smallest valve using that tube. The bars are to be angled as shown in
Figure 25 (See Service Drawing No 003 503 965).
94
NES 719
Issue 2
FLOW
FORWARD
1326. The clear area through each sea inlet grating is to be based on the
equivalent diameter of the total area of the valves associated with the
sea tube or box, and is to be calculated as follows:
1327. For discharges,. gratings are to be arranged with maximum clear openings
between bars of 65mm. The width of each dividing bar is to be as for
inlet gratings. The clear area through each outlet grating is to be
not less than twice the total valve area.
1328. Where the size of the hull opening is large, the grating is to be
arranged so that it can be removed in portions, each portion being of
manageable weight, by one diver.
Air Venting
a 5Onn nominal size vent
1332. A sea inlet box is to be provided with
sea inlet may be prone to air
connection when it is considered that the
pumps could be expected
ingestion in excess of what the SW circulating
or remotely started
to handle which would cause damage to automatic
pumps such as the HPSW pumps. Details of suitable arrangements are
is mandatory. Both
shown in Figure 26 ; the shut-off valve shown
pipe opening for air to
arrangements allow a space above the sea inlet
connection. The vent
collect prior to finding its way to the vent
aft with the sea inlet pipe
connection should be "in-line" forward and
any effect of roll and heel.
opening as far as practical, to minimise
to be led above the
Similarly, air vent pipes, if provided, are
of the ship centreline to
waterline and preferably in the vicinity flow indicator is to
A sight
eliminate the effects of heel and roll.
indicate the presence of air.
be provided, in First of Class ships, to
that certain vents are not
Should it prove in subsequent sea trials
off.
required, these vents are to be blanked
proves a problem in service, an air
1333. Where air entrainment in sea inlets
air chamber with an automatic
eliminator is to be fitted comprising an
forms the cover of a specially
shut-off valve venting connection, which
the entrained air to be
designed sea inlet strainer which causes
discharged by vortex action.
Preservation
inlet and discharge boxes are to
1334. Inlet and discharge tubes and grouped
free epoxy (SFE)
be abrasive blasted and coated with solvent
to 250 microns. Any fairing
composition to a thickness of between 175
with Epoxide Putty to
of plate laps, welds etc is to be made
SFE is dry. Upon completion of
DG Ships 8900 before the first coat of tie coat composition
the SFE application, one coat of the appropriate as applied to the
coatings
(ALBIT or ADMAR) followed by antifouling
Inlets and discharges whose size and
outer bottom. (See NES 760).
are to be galvanised and coated
geometry does not permit this treatment
anti-fouling coatings as applied
with four coats of ALBIT, followed by are to be painted as for
to outer bottoms. All galvanised gratings
96
NES 719
Issue 2
galvanised sea tubes. Sea tubes sited within diesel oil tanks are not
to be galvanised on the tank side.
1335. When coating the outer bottom and sea boxes/sea tubes, all valves are
to be closed. On completion the valves are to be operated at frequent
intervals to ensure that they will operate properly when the paint has
hardened.
97
NES 719
Issue 2
2m S0mm BORE
ABOVE AIR VENT RED
RED, W.L.
WATER V~ - _ -
LINE
100m
SEA INLET
ARRANGEMENT 1
DJW.L
BALL
VA LVES
PUPlOOmm~l
SUCTION
SEA INLET
ARRANGEMENT 2
"98
NES 7192
Issue
General
1401. The tanks are to form an integral part of the ship's structure and are
to be arranged so that air pockets will not form during fil-ling-and
such that the water will level itself as fast as it is delivered;
escape and limber holes being cut in beams, frames etc as necessary to
facilitate filling and draining. Where air pockets are unavoidable, an
additional air escape may be fitted. To ensure that the tank is not
overpressurised during filling, the supply to the tank is to be via a
filling funnel. The size of the pipe supplying the filling funnel is
to be one size smaller than the pipe from the filling funnel into the
tank. This will ensure that at all times there is adequate drainage
from the filling funnel. A valve is to be fitted above the filling
funnel to control the supply and a second valve is to be fitted below
the funnel to seal the tank after filling.
1402. The internal structure is to allow ready access to all parts of the
tank for preservation (by abrasive blasting and painting) and for
inspection and cleaning.
Manholes
Air Escapes
1404. Two air escapes are. to be fitted at the highest position in each tank,
the two positions being as remote from one another as can be arranged.
For tanks of capacity of 75 tonne or more the pipes are to be 60mm
nominal size; for tanks of less than 75 tonne the pipes are to be 40mm
nominal size. The air escape pipes are to be galvanised steel to
BS 3602, Part 1; HFS or CFS 360 and BR 3013(2),*generally 2.%n
thick. From inner bottom to just above the floor plates in machinery
compartments, these pipes are to be not less than 10mm in thickness.
of the
1405. The air escape pipes may be grouped into single pipeswhen clear
same compartment are
red zone by not less than 2m but pipes from the
number of separate air
not to be led to the same common pipes. Where a
pipes are joined into a common lead the sectional area of the final
lead should not be less than 75 per cent of the sum of the areas of the
are not
smaller pipes. Care is to be taken to ensure that these pipes
combined with the air escapes from tanks containing oil.
the position
1406. The air pipes may be terminated inside the ship, provided
clear
is at least 2m above the red zone and in a well ventilated area
of living spaces.
-99
NES 719
Issue 2
Sounding Tubes
tank and is to be of nominal
1409. A sounding tube is to be fitted to each
to pass the MOD standard sounding
size 60mm which is of a suitable bore
thickness to air escapes
tapes. The pipe is to be of similar
be combined with one of the
(Clause 1404). The sounding tube may
642 and 003 503 703.
tank's air escapes. See SDN's 003 503
and are to extend from within
1410. The sounding tubes are to be vertical least 300mm above the top of the
at
100mm of the bottom of the tank to
structure has special coatings for preservation
tank. Where the tank striking
the is
be damaged bytube
which can the to be
eg zinc spray, and coal tar epoxy,
the bottom of sounding
recording device
of the depth
as those fitted in FW tanks, see
sealed and worked in the same manner coating is used for
NES 728. In instances where no special
tube is to be worked as for fuel
preservation then the bottom of the the ending to be fitted on
tanks, see NES 320. Figure 27 illustrates
sounding weight/transducer being
the bottom of the tube to prevent the
structure.
trapped between the tube and adjacent
tube is to be fitted with a locked
1411. The upper end of the sounding
vicinity of the filling funnel
screwed cap and is to be fitted in the
to be arranged where practical
where fitted. Sounding tubes are
their upper ends may be extended
alongside bulkheads etc, in order that
deck. Elsewhere they are to be
permanently about 300mm above the
fitted with locked watertight deckplates.
dipped galvanised internally and externally
1412. Sounding tubes are to be hot
been completed.
after all welding and working has
Calibration
in tonne by either filling with
1413. Ballast tanks are to be calibrated preference being given to
known:quantities of.water or by calculation; cannot be readily checked.
the filling method where the tank dimensions curves showing capacity in
capacity
The results are to be tabulated and
prepared and forwarded to MOD for approval.
tonne against depth,
for sounding marked in metres and
1414. Steel tapes of a standard type for use through the sounding
millimetres are supplied by the MOD(N)
be provided in the vicinity of the
tube; stowage for these tapes is to
sounding tubes.
Preservation
epoxy
is to be treated with a coal tar
1415. Water ballast tank structure
system in accordance with NES 756.
100
NES 719
Issue 2
Amdt 2
MINIM UM
300 mm
TANK TOP
-TTOM
PIPE BEVELLED INTERNALLY AT
450 TO 12 THICKNESS.
_____
HULL OR TANK PLATING
101
NiS 719
Issue 2
Fittings
1501. The system designer is to ensure that for all instruments called for,
the necessary isolating valves, thermometer-pockets and other facings
and tapped bossen-are provided.. These are to be provided by the;
Shipbuilder/Main Machinery Contractor in.the case of systems and by the
equipment maker in the case of individual items of machinery, except in
the case of isolating valves fitted to instruments located on a console,
eg in the machinery control room, which are to be provided by the
console supplier.
1503. The service of gauges is not to be marked on the dial faces but on
separate tally plates conforming to NES 723.
1505. All pressure, flow and level sensing devices are to be fitted with
isolating valves at source, conforming to the working pressure of the
system.
1506. Vacuum gauges, gauges subject to pulsating pressures and gauges which
are fitted in another compartment or in cases where the isolating valve
at source is not readily accessible from the gauge position are to be
fitted with an isolating valve at the gauge itself.
1507. All isolating valves fitted local to gauges are to conform to the
requirements of NES 360.
1508. Source stub connections associated with isolating valves are to be not
less than 20mm nominal size.
102
NES 719
Issue 2
1511. The material of the pocket is to be compatible with the pipe material
and its contents.
Pressure Gauges
a. Local:
b. Remote:
(1) LPSW System - gauges either side of the pumps and gauges in
the main to be relayed to the SCC.
(2) HPSW System - gauges at the risers to be relayed to the
NBCD HQ.
1514. All local pressure gauges are to be of the dial indicating Bourdon type
to DEF STAN 66-2.
1516. The static pressure at any datum ie tapping point, where transducers
are not used, as indicated by a pressure gauge is obtained by
adding/subtracting the height of the pressure gauge relative to the
tapping point.
103
NES 719
Issue 2
Sensors
1517. Sensing points are to be located at the precise point the information/
control is required. The sensing points for control purposes are to be
independent of those used for instrumentation purposes.
1519. They are to indicate loss of pressure in the main and to indicate flow
through any automatic spray system. Indication is to be relayed to
NBCD HQ and SCC and elsewhere as specified.
Thermometers
Alarms U
1525. The following alarms are to be provided in the SCC:
104
NES 7i9
Issue 2
Flooding Bonnets
Shore Connections
1607. In cases where the forward and after ranges overlap near amidships it
is acceptable to provide two connection points, one port and one
starboard within the overlapping area. On small ships it is acceptable,
provided they are sited near the centre line, one forward and one aft
within the above ranges. Service positions are to be sited as near to
the ship's side as practicable to minimise hose runs across the deck,
obstruction to passageways or damage to paintwork of structure: the
connections are to be readily accessible.
1608. A deck elbow, 6 inch female, NSN 4730-99-458-9483 to mate with the deck
fitting is to be supplied and stowed onboard, together with flange
adaptor NSN 4730-99-458-9506.
105
NES 719
Issue 2
SEALING
OASKET
o FF) .
(12
0 BOLT
FOOK
SEALINGR
SWASHE
' WASHER
S BONNET
CAP1
COUPLING
DECKPLATE k/,AAPTOR
BOSS BODY
~CASKET ~SEALIN.G
'"
FIGURE 29 - SHORE CONNECTION
SEE CLAUSE 1602
106
NES 719
Issue 2
17. PRESERVATION
107
NES 719
Issue 2
18. I=N=SULATION
1801. All HPSW and prewetting piping (up to isolating valves on pressure
side) is to be insulated in accordance with the requirements of NES 703
using approved pre-formed half round sections efficiently bedded on to
the pipe.
1802. Lagging is not required to spray pipes which are normally dry or
contain static water.
10
108
NES 719
Issue 2
19. F L U S H IN.G__TESTI N G A N D T U N IN G
Flushing
1901. Prior to basin trials, sea water systems are to be flushed through with
the valves worked so as to isolate each section of the systems in turn
to ensure that the flow through the piping is unimpeded. Each branch
is to be flushed through in this way for at least five minutes.
Equipments which could become choked during flushing such as orifice
plates and constant flow control valve inserts are to be removed during
flushing. A sample of flushing water is then to be drained off and
allowed to settle. If the sample is dirty, the flushing procedure is
to be repeated until clean samples indicate that the systems are clean.
Working Pressure
1903. The working pressure of the systems is defined in Clauses 0404 and 0702
for the HPSW Systems and Clauses 0405 and 0801 for the LP systems.
Because of the shape of the pump characteristic curve, the pressure at
zero flow may be so great as to equal or nearly equal the installation
test pressure if this is defined as 1.5 x WP. To ensure that the.
system is capable of withstanding the flow pressures, for test purposes
the greater of the following pressures must be used in the relative
tests:
Pressure Testing
1904. The pressures to which the systems are to be designed will be the
maximum working pressure as defined in Clause 1903.
109
NES 719
Issue 2
1908. Clean fresh water is to be used for all tests during manufacture.
Pressure testing after installation on board may be carried but using
sea water provided that the system has first been treated with SDD-
solution (see Clause 1702). Otherwise clean fresh water is to be used.
1910. The shop pressure tests are to be carried out after all welding/brazing
and machinery has been completed including all holes for securing,
being drilled and before paint, insulation or covering of any kind has
been applied. The tests after installation may be carried out with
insulation in place but the joints of pipe flange connections and
valves are to be uncovered.
1911. Any equipment that may be opened up after the Makers Shop Test must be
retested to shop or installation test pressure as appropriate and show
that it functions correctly after reassembly.
Details of Tests
1913. Valves. All valve bodies are to be tested to 2X working pressure (see
Clause 1916). After assembly, all valves are to be tested to the
working pressure with the valve half open to test the gland. All
except ball valves are then to be tested closed with 14XWP on the inlet
side of the valve. Valves which may admit pressure from either side in
service except ball valves, are to have the test pressure applied
independently on each side. Ball valve seats are to be tested to
working pressure only for freedom from seat leakage as the design of
these valves is such that an increase in pressure ensures a tighter seal
and therefore the lower pressure is more critical.
1915. For ball and butterfly valves, directly on completion of the tests above,
at least one in five of a production batch is to be air bubble tested
from 0.35 to 0.7 bar on each seat independently; no leakage is to
occur.
1916. All valves are to be suitable for a working pressure of 10 bar, and the
test pressure is to be based on this figure irrespective of the working
pressure of the systems.
1917. Test pressures for Shop Tests on sea water systems and for Tests after
Installation are given in Table 5.
.110
NES 719
Issue 2
NOTES:
1. WP - Working Pressure.
III
NES 719
issue 2
b. The ability of the system to supply the design sea water capacity
at the design pressure with the appropriate number of pumps or
HPSW supplies in use, including the use, where applicable, of the
emergency supply.
in
1919. Firefighting tests and trials are to be carried out as detailed
NES 119 and BR 2170.
as
1921. Prewetting initial test and subsequent trials are to be carried out
detailed in IES 118.
Tuning
112
NES 719
Issue 2
1928. If, during the tuning procedure, the system pressure is measured by
using a special or local pressure gauge, this gauge must be fitted to
the same tapping point as the gauge used for control purposes and must
be calibrated and corrected, if necessary, in accordance with
Clause 1925b.
c. Open the branch valve(s) and the overboard discharge valve in the
branch which is being tuned. Adjust the diaphragm glandless valve
to achieve the required pressure drop while maintaining the system
pressure constant by adjusting diaphragm valves of other system.
equipments.
113
NES 719
Issue 2
1930. Tuning a System Fitted with Orifices. The method is the same as that
outlined in Clause 1927 except that there is no external means of
adjusting the orifice size and the initial orifice size is determined
by calculation; (for the calculation of orifice sizes see Clause 1210).
Should a check prove that a branch flow rate is inadequate then the
orifice is to be reamed out if the flow is too low and replaced with a
smaller orifice if the flow is too high.
1931. Tuning a System Fitted with Constant Flow Control Valves. When tuning
a system fitted with constant flow control valves the pressure drop
across each equipment can be checked against the pressure drop: flow
rate curve of the equipment; this will ensure that the flow rates are
correct within the flow tolerance of the valve. If the flbw is
inadequate the valve is to be changed and the flow rechecked. Where
the system is supplied from a HPSW System through an orifice, the
system pressure established in Clause 1925b is to be checked with all
equipment normally in use being supplied with cooling water and with
the HPSW System pressure at the minimum level specified in Clause 0612
and corrected in accordance with Clause 1925b. If there is a large
discrepancy between system pressure obtained and that specified,
consideration is to be given to the reasons for the discrepancy and the
pressure is to be adjusted by changing the orifice size and/or the
initial calculations/assumptions rechecked.
1933. Pressure Warning Devices. All pressure warning devices are to be set
during system tuning; attention is drawn to Clause 1925b.
Records
114
NES 719
Issue 2
h. Pressure tests.
j. Trials.
115.
NES 719
Issue 2
General
b. multi-pump systems.
2003. Where a SYMES range pump is specified whose duty is in excess of the
system duty, after making allowance for the margin required by
Clause 0812, the excess pump head is to be dissipated by means of flow
control devices included in the system.
c. Weight.
116
NES 719
Issue 2
2006. When a pump is selected from the SYMES range for a particular system it
is to be ascertained whether or not pump suction aspects relative to
NPSH required and NPSH available impose any limit on the performance of
the pump. This aspect is covered in Clauses 0917 to 0922 inclusive.
Any performance limitation at the system duty point is not acceptable
and Ministry approval is to be obtained for any performance limitations
at alternative or emergency duties.
2007. "Matched flow" systems are basically single pump systems where the
pump characteristic is selected and/or the overall system
characteristic tuned by means of fixed flow devices so that the pump
and system duty points are 'matched'. The systems are tuned by means
of orifices and/or diaphragm glandless valves.
2008. "Matched flow" systems fall into the following two categories:
117
NES 719
Issue 2
2016. The flow rate through constant flow control valves will vary dnly
slightly with the pressure differential across the valve and the flow
rate tolerance can vary from maker to maker.
2017. Where constant flow control valves are specified for sea water systems
the pressure range differential is to be specified so that the valve
maker can:
a. Provide a valve which will ensure the design flow rate at the
highest pressure differential normally to be expected to occur in
the system.
2018. The system designer is to calculate the size of the system pipework,
the equipment tube water speeds and the size of pump on the basis of
the maximum flow rate through the constant flow valves to avoid
unnecessary risk of erosion problems and also to ensure each equipment
receives not less than its design flow rate in all normal conditions of
operation.
2019. In this type of system the margin, to provide for pump wear fouling and
electrical frequency variation, is included on the pressure side; see
Clause 0812.
2020. Constant flow control valves are for use primarily in sea water systems
supplied from the HPSW System. However, where they are used in "pumped"
systems the pump characteristic is to be selected bearing in mind that
the lower variation in pressure differential across these valves the
smaller the flow rate variation through them; a lower range of flow
rates in the branches could lead to smaller pipe bores being acceptable.
118
NES 719
Issue 2
2021. Systems with Equipment and/or Overboards Located above the Waterline.
Syphonic and non-syphonic system H:Q characteristics include a component
of head defined as "head above waterline" this takes account of the
parts of such systems or their equipments which are located above the
waterline. The requirements for these systems are given in
Clauses 0813 to 0819 inclusive. The three main system categories are
as follows:
a. Syphonic system, where the "head above waterline" is of influence
only uten priming during start-up. Once the system is primed the
syphonic action cancels the head loss due to height above the
waterline. The type of characteristic to be constructed for this
type of system is shown in Figure 35.
d. The motor is sized to meet the highest pump power required; most
probably the power associated with point B.
119
NES 719
Issue 2
2024. Pumps directly driven from a main engine are to have a margin on flow
in accordance with Clause 0812 to allow for pump wear and system
fouling. Where a pump supplies a number of auxiliaries whose water
requirements are expressed at varying engine speeds, the pump duty flow
is obtained using the undernoted shaft speed correction factor:-
Multi-pump Systems
2026. General. The requirements, given in the earlier parts of this Section
are, in general, applicable to multi-pump systems. This part of the
section gives the additional requirement and performance aspects
particular to the operation of multi-pump systems.
2027. The Operation of Pumps in Parallel. Axial flow, mixed flow and
centrifugal pumps can be operated in parallel.
2029. The intersection of characteristic B with the pump curve shows the
increase in flow rate when two pumps are used over that when one pump
only is required. Conversely, if curve B is the normal system
characteristic then the intersection with the pump curve shows the
futility of operating pumps in parallel to increase the flow rate
through a given system. Where an increase in system flow rate is
required in a system, the system resistance is to be reduced by
removing/adjusting flow restrictors, increasing the pipe bore or
re-routing the pipework.
19
120
NES 719
Issue 2
2031. Systems with Fixed Opening Flow Control Devices. Figure 40 is the type
of characteristic the system designer is to construct for a system
fitted with multi-pumps and fixed opening flow control valves in order
to prepare instructions on starting and stopping pumps for the
operators of the machinery/equipment. The operating instructions are
to take the following form:
b. Stop one pump when "static pressure in the main" rises to maximum
acceptable pressure except when only one pump is running (1.8 bar
in example).
2032. It will be noted, however, that there are flows when the number of
pumps in use could be reduced by stopping at a lower pressure but this
would complicate matters for the ship staff and is not to be advocated.
2033. Operation of the pumps at static pressures (gauge) below that defined
as the "minimum" pressure in the main may result in an inadequate flow
rate to the equipment and/or increased noise, vibration and wear of the
pump due to cavitation and is not permitted. Operation of the pumps at
a static pressure (gauge) higher than that defined as the "maximum"
would result in a waste of power and a reduction in pump reliability as
a result of the increase in the total number of hours the pumps are in
operation and is not desirable.
2034. The detailed procedure for establishing the system pressure: flow rate
characteristics is given in Annex B.
2035. Annex C Paragraph 2n indicates that where a SYMES range pump is used
with a somewhat excessive total head rise the choice may increase the
number of pumps required over that which may be practical with a pump
specified for the precise duty.
121
NES 719
Issue 2
Amdt 1
2036. Systems with Automatic Variable Opening Flow Control Devices. Figure 41 3
is the type of characteristic the system designer is to construct for a
system fitted with multi-pumps and with system constant flow control
valves in order to prepare instructions on starting and stopping pumps
for the operators of the machinery/equipment 2 The operating
instructions are to take the form given in Clause 2031.
c. The margin for pump wear etc is on head instead of flow, see k
Clause 0812.
2039. In both these situations the pump will "run out" on its H:Q
characteristic and operate beyond its specified duty point ie operate
at a higher flow rate and a lower total head rise than the pump's
specified duty. The effect of "run out" on a pump is an increase or
decrease in power depending on whether the power flow rate
characteristic is a rising power of a non-overloading power
characteristic.
122
NES 719
Issue 2
NOTES:
123
NES 719
Issue 2
2050. In general, the shape of the H:Q characteristic for centrifugal type
A "steep" H:Q
pumps is chosen to suit the system design requirements. opening
for a system with variable flow
characteristic is preferred
it could lead to a smaller motor than would be
control devices because
required for a corresponding "flat" H:Q characteristic; however,
is
attention is drawn to Clause 2020. A "flat" H:Q characteristic
preferred:
124
NES 719
Issue 2
2051. The performance of LPSW Systems of this type supplied from an HPSW Main
is affected by changes of pressure in:
b. The LPSW System when equipments in the system are shut-off, see
Clauses 2056 to 2059 inclusive.
2052. The maximum pressure in the main is the pump total pressure rise at
zero flow plus or minus the difference in height between the main and
the waterline. The minimum value is set by the static pressure (gauge)
required at the firefighting equipment.
2053. Effect of Change of UPSW System Pressure. The HPSW System which
supplies the LPSW Main varies between:
PH2
PL 2 = PL x (1)
in the
and the effect on flow in the LPSW Main with change in pressure
HPSW System is to be taken as:
125
NES 719
Issue 2
Q = flow rate
p = pressure
H = high
L = low
1 = initial condition
2 = final condition
2056. Effect of Isolation of Some Branches in the LPSW Systems. The change
in LPSW Main pressure and the resulting change in sea water flow in
individual branches due to changes in the number of branches open to
the main is to be taken as: )
PH x PL I
PL 2 -
PL + x2 (PH 1 - PL1 )
2058. Where the resulting LPSW Main pressure exceeds that which is recognised
by the use of equation (2) in Clause 2055 as giving excessive water
speeds in the LPSW Main or in one or more of its branches, then either
an alternative fixed orifice flow control device between HPSW and LPSW
Systems or an additional adjustable control (eg a diaphragm valve) in
series with the fixed orifice control is to be provided.
126
NES 719
Issue 2
2060. The (gauge) pressure in a LPSW Main, with variable opening flow control
devices, changes:
b. When branches in the LPSW System are shut-off; see Clause 2062.
NOTE: The flow in the system may vary slightly with increase in
pressure because of the pressure and flow characteristic of
constant flow control valves.
PL 2 = PH - (PH - PL 1 ) (x) 2
127
NES 719
Issue 2
12 SYPHONIC SYSTEM
II
B NT.
A ~OVERALL SYSTEM
m CHARACTERISTIC
w4
0 00 200
FLOW RATE -Q (m3/it)
14
NON-SYPHONIC SYSTEM
13
IaI
t
_
OVERALL SYSTEM
CHARACTERISTIC. 0
I I SYSTEM
( I FRICTION
<6 HEAD
'.) LOSS.
O 100 200
FLOW PATE -
128
NES 719
Issue 2
16
ACTUAL -SYSTEM
CTE ST CHARACTERISTIC
TO SUIT PUMP
12
TO BE
DISSIPATED
BY TUNING.
I !
(3 I SYSTEM
<=w IFRICTION
HEAD LOSS
BASED ON
DESIGN
4 FLOW
N~o TUNING
IN BRANCH
INTA SSE WHICH
INITIALSYSTEMDICTATES,
CHARACTERISTIC I HEAD LOSS)
H e Q2
... ,.:
0 - DESIGN FLOW.
100j200
FLOW RATE- (ITn3/
NOTES:-
I. 1 REPRESENTS PUMP ACTUAL DUTY POINT
129
NES 719
Issue 2
Amdt I
OPERATING SYSTEM
POINT CHARACTERISTIC
WITH BRANCH DUTY POINT
HHC3 0 HC0
3 1h )
FLOW RATE -Q(m
130
NES 719
Issue 2
Amdt 1
PERENTAGE OF EQUIPMENT
DESIGN FLOW SHUT-OFF
120I
860
0 90 100 120
FLOW RATE-Q(%)- -
EXAMPLES
A DUTY POINT
AQ INCREASE INFLOW THROUGH BRANCHES
WHEN SHUTTING-OFF EQUIPMENT (S)
131
NES 719
Issue 2
Amdt 1
BRANCH ES I
OE OF 06. PUMP
CHARACTER191 C
24
DUTTY POINT
- - - -
22 - - -- - -
BRANCH VALVEI
CHARACTERISTICS (A)
MARGIN 4m
D(B) ")
MINIMUM HEAD LOSS
T DESIGN FLOW- Q.=Q DE.
TOTAL
0 DF + IDGPROVIDE VALVES
-S-iACROSS 'TO
REaUIRED
AND TOTAL DESIGN HEAD-H= A+B'4 POVID REQUIR
r II
(C)
FOR DERIVATION OF SYSTEM MAXIMUM BRANCH
CHARACTERISTIC SEE FIG 21 7 HEAD LOSS;
SEA INLEr TO
OVERBOARD
DISCHARGE BASED
ON O
0 100. 200
FLOW RATE- 0 (m3/h)
NOTES:-
BRANCH VALVE CHARACTERISTICS ARE IN FACT CONSTANT
FLOW CONTROL VALVE CHARACTERISTICS AND ARE SHOWN
INCLINED FOR CLARITY
G
[A-+* k
,*3,,
NES 719
Issue 2
Amdt 1
0 TO E
NON - SYSTEM CHARACTERISTIC
SYPHONIC WITH A TO E SYPHONIC
ATO E +ATO F + A TO G
START UP WITH
T TO E NON-SYPHONIC
F Q = DF'+&O
.BRNHU~
P TOAANBTPIEDWE F A OIE/
NORAECH-
TTT ISW
3 AL AR RW N H AI ToVE
TOTA DEIGDFOW
FLO SRATE+MRGIN BRG
I 33
NES 719
Issue 2
Amdt I
PUMP CHARACTERISTIC
OPERATING POINTS
HEAD AVAILABLE TO
PRIME EQUIPMENT
.... \EHLEDED
TO PORT
c - --
STARBOARO
STARTING
HEAD
(HEELED)
OPERATING HE$D
-(HEE T LED)'
OPERATING HEAD
(EVEN KEEL)
QD
op
FLOW RATE
D = - EQUIPMENT MAKERS FLOW PLUS MARGIN IF APPROPRIATE
OP = FLOW RATE FOR SIZING PIPE BORES AND CALCULATING EQUIPMENT
TUBE WATER SPEEDS
S DUT( POINT
HEAD ABOVE
WLfSTARTINQ) I-HEAD ABOVE
°
W L (OPERATING)
SYPHONIC LEG
PORT STARBOARD
134
NES 719
Issue 2
Amdt I
• DuT[Y POINT
C3
NOTE'- WL 30
CHARACTERISTICS ARE APPLICABLE- Y.
TO A SINGLE PUMP SYSTEM WITH A
HEAT EXCHANGER TO ONE SIDE OF
THE SHIP
135
NES 719
Issue 2
Amdt 1
PS PUMP SPEED
20 MSS = MAIN SEHAFT SPEED
PUP±FICEC 40010
CURVES HO.CQ 2
I S 200 R
f M40fof
/0 1
S YST'IF CHARACTERISTIC
Si-PS 32,RPM
MSS -50 RPM
AO 60 So. 00 120 140 S
0 20
:3
?LOWRATE Q (m /h)
RATCHARACTERISTIC
8I A
V= DUTY PoINT
137
NES 719
Issue 2
Amdt 1
Q: o ., -- ------
-- ALLOWALE
MAXIMUM ,-
PRESSURE --
- (GAUGE) -
STATIC
STATIC
FIGURE 40 - MULTI-PUMP, MULTI-EQUIPMENT SYSTEM;
PRESSURE IN MAIN; FLOW RATE; FIXED OPENING
FLOW CONTROL DEVICES. SEE CLAUSE 2031
138.
NES 719
Issue 2
Amdt I
Ln
DESIGN FLOW
RATE THROUGH VALVES
139
NES 719
Issue 2
Amdt I
ChARh
PUMP CHARACrEpIS17C/
DUYPOINTf
FLOW RATE 0
(TO H.P SW MAIN)
L P SW MAIN N
IDENTICAL PUMPS.
140
NES 719
Issue 2
Amdt 1
FLAT CHARACTERISTIC
FLOW RATE- 0 -
NOTE- PUMP 'B" CAN BE 'SHUT OFF' BY PUMP ' WHEN
EQUIPMENTS ARE ISOLATED IT IS THEN
INEFFECTIVE AND LIABLE TO OVERHEAT
MPAB
_TEESYSTEM LOSS AE
CD
.
FLOW RATE-Q-
PUMP'S' CANNOT BE 'SHUT OFF'. BY PUMP 'A'
WHEN EQUIPMENTS ARE ISOLATED
141
NES 719
Issue 2
Amdt 1
N--T
SOPERATING
RA NGE.
QC UNS TABLE
N-1
FLOW RATE - Q
142
NES 719
Issue 2
Amdt 1
PUMP DESIGN
PUMP POINTr
- ! EFICIENCY S/
OEA.L DUTY /
.o 1/D / /
- 1-/
Ponnp / I "
Ir / I I /
FLOW RATE-
143
NES 719
Issue 2
Amdt 1
HP SW MAIN
DOG VALVE SUPPLY DEVICE FIXED OPENING
7 P SW MAIN FLOWCONTROL
E QUIPMENT
/ VALVE
/ /
/
7
/ /
/ /
DGVALVE
6 SHIP SIDE /
/
CURVE BASED ON /
PH 7BAR / /
PLi 1-5 BAR (FULL) / I
0"7 BAR (DOTTED) / /
2.5 BAR (DOTTEC)
/, / .
//
/ / / i/i
/
/
2'
/HR -
/ AT FLi
OESL.
2 ' / P2:PRESSUREINLPSWMAIN
0.
1
144
NES 719
Issue 2
Amdt 1
IHP SW MAIN
0- VALVE VARIABLE OPENING
SUPPLY DEVICE /FLOW CONTROL
LP SW MAIN / VALVE
C C C C= CONSTANT
EQUIP FLOW VALVE
6-
tSIPSIDE
PL =/H (HPL)()
- /PH = PRESSURE IN HP SW MAIN
PLI1 PRESSURE IN LP SW MAIN AT DESIGN FLOW 01
.... :- L2 =PRESSURE IN LP SW MAIN WITH SOME EQUIPMENTS
/SHUT-OFF
:-.-- ::.2. (FLOW 02)
I 0 DESIGN FLOW RATE
02 =DESIGN FLOW RATE TO THOSE SYSTEM LEGS LEFT OPEN
/~ Q3
1.SEE 2056, &205
//ALL SYSTEM PRESSURES ARE REFFERED TO WATER LINE
145
NES 719
Issue 2
ANNEX A
SPRAY SYSTEM CALCULATIONS
Pre-requisites
b. Pipe lengths.
C. Pipe bends.
d. Pipe material
Procedure
case of
2. For the spray nozzle farthest from the supply point, N3A in the
distribution from the
Figure 48, assume a pressure that will ensure a good
rate through the spray
nozzle. This pressure will -determine what the flow
will be, using l(f). This flow rate passing through the pipe of a given
loss of
length and of-a given diameter will result in a pressure drop or
head. C
This can be calculated from the formula:
ANNEX A 146
NES 719
Issue 2
3. For the next spray assume the same initial pressure head as the first
and add to the actual pipe length the effect of the diverting tee.
Calculate as before the total head required and compare it with the head
required for the first nozzle. Should there be a difference adjust using
the formula Q =[ HI] 0.54 when balanced add Ql to Q2 to obtain the
Q2 tH2J
flow rate through the next pipe ie from A 1 to A. Again using the procedure
in paragraph 2 the head loss can be calculated.
4. Twice the flow rate through A-A 1 ie 2XQ 3 = Q4 gives the flow rate
through A-B so the head loss up to point B can be calculated. This value
at point B is the pressure supplying water to nozzles NlB and N2B. To
obtain this flow, start at NIB with an assumed pressure, say the same as
for nozzle N3A, and as in paragraph 2 calculate the head loss to B0 and on
to B. Should there be a difference, adjust the flow/head until the total
head equates to the head in the main using the formula in paragraph 3 of
.... Ql - [ii] 0.54
Q1 = HI]
Q2
5. Summing the quantities and proceeding as before the head loss from B to
C can be found and this added to give the total head at C. In a similar
manner to that used to balance B to the main line pressure, the branch C can
be calculated and balanced.
6. This procedure is continued until the complete system has been calculated
and the resultant quantity Q can be compared with the design requirement for
the compartment of area x density, of spray. If the quantity has to be
adjusted the pressure will also change by the ratio given in paragraph 3 viz:
= r1
H 0.54
= H1 Should the revised pressure be greater than that
Q2 [12
available in the mains, the pipe sizes should be increased and if necessary
A larger nozzles or more nozzles with lower initial pressure assumed and the
whole system recalculated.
147 ANNEX A
NES 719
Issue 2
Table 6
Valves
15
Ball/Plug
3-Way Ball/Plug 60
Butterfly 30
Diaphragm 150
Gate 12
3-Way Temperature Control 160
Swing Check 60
Strainers 40
Bends
900 R/D < 8 12
4500 8
Branch 1-' 3
250
Vb/V 0.5
70
Vb/V 1.0
60
Vb/V 1.25
Vb/V 1.50 50
Main 1 2 Negligible
Vb = Branch Velocity
ANNEX A 148
NES 719
Issue 2
Calculation Sheet
Assumed CHW for Cu Ni pipework to be 130
Branch B
N B-B0 0.027 2.3 1 x 60 1 x 12 0 4.14m
1 49
ANNEX A
NES 719
Issue 2
0.2 1 x 70 0 0 3.11m
BO-B 0.0415
- 3 m 3/s Head = 32.83
Q6= 2 x Q5 = 4.5 x 10
33.81
Head at B = 32.83 + 0.98 -0.20
Change in Height
33.61m
of 1% of head
The assumed Q gives a balance at B outside
54 -3 3
in line A-B viz 34.14. 4.54 x 10 i Is
Increase Q6 to 4.5 x (34.14)
(33.61)
Main Line
0 0 0 2.0
B-C 0.072 2.0
-3 Head = 34.14m
Q 7 = Q4 + Q6 = 13.58 x 10 m3 Is
34.47m
Head at C = 34.14 + 0.33
No change in height
Branch C
1 x 60 1 x 12 0 4.14m
*IC-C 0.027 2.3
3 /s
- 3 mi Head =30.Om
Q 8 =2.25 x 10
32.93
Head at C0 = 30.0 + 2.93 Change in Height -0.10
32.83m
1 x 7 0 0 3.941m
0.0415 0.2
CO- C
(34.01)
Main Line
0 0 0 1.0
C-D 0.072 1.0
-3 Head = 34.47m
Q10 = Q7 + Q9 = 18.11 x 10 m3 /s
3.48 bar
Head at D = 34.47 + 0.28 = 34.75m or
required to supply 18.11 litres/second
A50
ANNEX A
NES 719
Issue 2
BORE SHOWN BY ® m
....
X 0..1 0 1
9
01 N2C
09 RISER 15
N16 6
o5 xs
IB/.2 RI E
0.1 07 N021
N3A 2
• ;Q2 A S X
N4A
151
ANNEX A
NES 719
Issue 2
ANNEX B
First
Max. Estimate
Permissible Pipe Actual
Flow Water Speed Bore Water Speed
(m /h) (mls) (mm) (mls)
Strainer 0 0 0 0 1 0.11
Inlet 0 0 0 0 1 0.11
152
ANNEX B
NES 719
Issue 2
The total system head loss (H) is dictated by the plummer bearing
Increasing the plummer bearing branch to 22mm bore reduces the head
from 14 to 22 mm bore the head loss through this branch is reduced below
that through the main LO cooler branch. The system head loss is thus now
dictated by the main LO cooler branch and results in a saving on head loss
of some 50%. By adopting a lower water speed than the maximum permitted
a saving in power and probably pump weight and space is therefore obtained
with minimal penalty in piping weight and space. The increase in plummer
153
ANNEX B
WEB 719
Issue 2
00
153mm
153mm
PLUMMER BEARING
PUMP
ANNEX B 154
NES 719
Issue 2
ANNEX C
PROCEDURE FOR ESTABLISHING PRESSURE:
FLOW RATE CHARACTERISTICS
IN MULTI-PUMP, MULTI-EQUIPMENT SYSTEMS
2. Figure 52 shows the pump and system head flow rate characteristics to
be constructed for the specification of the pumps and the design of the
system pipework. The procedure for establishing the characteristics is as
follows:
c. Select a pump from the SYMES range which will provide the
head required such that.the number of pumps in each machinery
space and in total are reasonable.
d. The actual overall system head loss is obtained from the pump
H:Q curve at the design flow rate, see Figure 53. Any excess
head in the LP system is dissipated in the tuning valve and
for the HP system by the use of a surplus valve.
e. Estimate the head in the main at duty flow excluding the zero
flow static head by adding any excess head loss in d. above
to the head loss from the main to overboard obtained in b.
above.
f. Obtain the pump shut valve total head rise which is also
the head in the main in this condition of operation, (assume
the system is required to operate with one pump and a small
cooling water flow requirement,ie one auxiliary in use only).
155
ANNEX C
NES 719
Issue 2
k. Calculate the maximum head loss from sea inlet to the main
for one pump at the design flow rate, the loss in each pump
should be roughly the same.
q. The static head in the main, excluding the zero flow static
head, is equal to the overall system head loss less the head
loss from the sea inlet to the main and less the dynamic
head in the main at the gauge tapping point.
156
ANNEX C
NES 719
Issue 2
157 AN C
NES 719
Issue 2
OG)
06G
0 GG
DG c 5
DGG
@~ --
SEEPARGRPH. .
DG
N~ OG
ANNEX C 158
NES 719
Issue 2
12
LE
10,10AVAILAI
E8
HF FRICTION HEAD LOSS FROM INLET TO MAIN
HD DYNAMIC HEAD
6 A POINTS AT WHICH A PUMP WOULD BE STARTED
0 POINTS AT WHICH A PUMP WOULD BE STOPPED
20
C
:r
/ SYSTEM CHARACTERISTIC
< CURVES DRAWN
i HEA LOSS FROM It')&
ORIG IN THROUGH
z INLET TO MAIN PLUSI
0 S1500
L DESIGN FLOW RATE m3 /h
159 ANNEX C
NES 719
Issue 2
P CHA CTERIS 0
OVERALL SYSTEM
CHARACTERISTIC
Ho' Q 2 OVRL
(TUNED) SSE
E P CHARACTERISTIC
(NO TUNING I BRANCH
WHICH DICTATES
HEAD LOSS)
FLOW RATE
ANNEX C 160
NES 719
Issue 2
PUMP
C RRCTE R
TI
FROMAI-FROMS
.. :. ,IX ' /T
" C6M
DISIPAED AOS
EA SEL NOHEA
R
S
4 -
-44-a F R OM A E
SHAD LOSS
w FRO -,FROAMIh-
T
OiO PA LOSDSLFL 01T.O /
AS DICTATED
BY NPSH
REQUIREMENTS
INITIAL ESTIMATE I
-l
161
ANNEX c
NES 719
Issue 2
2k
-00
;%@
N C162
NES 719
Issue 2
ANNEX D
where:
3 - 5 diameters upstreaT) of
Pu absolute static pressure measured orifice Wk/m
k Loss coefficient
a Cavitation number
ANNEX D
163
NES 719
Issue 2
'((
C Contraction coefficient
c ( 0)
orifice
Q Quantity of water required to flow through
Pi PTP
Vu J Vd. = Vu"
=
AV Ad Au
is given by:
The loss coefficient k for such an orifice
pressure
4. For an orifice required to pass 37m3/hr with 5.8 bar
in a 72.2 bore pipe.
upstream and 1.0 bar downstream of the orifice
Velocity through the pipe 2.51 m/s.
5
(5.8- 1.0)10
= 148
Loss coefficient k = I x 1027.4 x 2.512
2.0 - 0.02 1.98 = 0.41
4.8 4 ,
Cavitation numberO= 6.8 - 2.0
164
ANNEX D
NES 719
Issue 2
form is
4
= I + 4
a critical
3- -- ___
0 CA NO SIGNIFICANT EROSION
OOIERATE TO0
SEVERE EROSIOq
1 104 1,001000
LOSS COEFFICIENT - K
6. With the cavitation number being lower than the critical number, it
is necessary to assess the degree of cavitation which if unacceptable
requires the arrangement to be modified by introducing additional orifices
in the form of a cascade to progressively reduce the pressure, whilst at
the same time ensuring the cavitation number never falls below the critical
cavitation number. Such an exercise may appear tedius but in the long
term the cost effectiveness of such a system will be appreciable. The
use of orifice plates made in a cascade in a special section of pipe
allowing approximately five diameter spacings is advocated.
165 ANNEX D
NES 719
Issue 2
2 2 P2 3 P3 04 0
Vu Pu d P
Assume that pressure loss between upstream point and throat will
be low. 0
Then if Vu = m = AT from Bernoulli:
VT Au
for
Pu + jPVu 2 = PT + jpVT and substituting from (1)and (2) values
2
Pu and PT.
m = /2-
. .. ........ (6)
ANNEX D 166
NES 719
Issue 2
d = diameter of orifice
D = diameter of pipe bore
diameter can be calculated.
Hence knowing D, the value d, orifice
Plate I Pu (abs)
= 8.8 bar. Vu = 0.873 m/s
I pVu 2 = x 1027.4 x 0.8732
p= 1027.4 kg/m
3 Dynamic pressure =
D = 27mm. 2
= 391.5 N/a
M =/24- = 0.0298
k = (I-m.)2 = 1060
in
d 0.216 . di = 5.832mm
From Fig 59 (with slight extrapolation), D
with d =.0.222
Hence drill size determinesd = 6.0mm,
Plate 2
with d = 0.259
Hence drill size becomes d = 7.00mm,
Plate 3
f0.0527
3
721.3
k = 323.7
300 x 391.5:
= 1.67 bar abs
P3 = 2.84
105
Plate 4
to give the final pressure of
This is the plate that is required
Pd
1.30 bar =
0.37 bar
So head loss = 1.67 - 1.30
=
2
- Pd - k (I pV )
Using equation (8) P 3
5 94.5
k = 0.37 x 10 =
391 .5
168
ANNEX D
NES 719
Issue 2
Plate I
m = 0.0995
Sk = 85.7
unchanged
Thus d becomes 28.5mm and k remains
Plate 2
m = 0.127
k = 47.6
Plate 3
bar abs, hence using equation (8)
The final pressure required is 2.0
we can obtain
15.76
k = P2 - P3 = (2.51 - 2.0)105 =
777 3236.4
0.558 .. d3 = 40.3mm
From Fig 59, we get d =
169
ANNEX D
NES 719
Issue 2
105
acritical = I + 4 = 1.99
2.51- 1.98
that if the last orifice plate
10. In both the above cases it can be seen
valve there would be a capability for
was replaced by a diaphragm glandless
to the valve from erosion. An
adjustment, without any damage being incurred
para 4 and recalculated in para 9 can
extension of the arrangement given in
shown in Fig 13 and that only a
be applied by assuming it is the arrangement
the connection to the HPSW main. From
two plate orifice cascade is fitted to of
1 .51 bar gauge on the discharge side
para 9 the resultant pressure will be through system loss
say 1.29 bar gauge
the second orifice. This will drop to,
upstream side of the disphragm valve which
which will be the pressure on the
fresh water cooler. Assuming 5m of
is sited on the discharge side of the head at the discharge opening in
pipework (loss of 0.04 bar) and no pressure overcome at the downstream side
to be
the hull, the total discharge pressure
of the valve would be 1 .04 bar abs then,
= 1.64
critical = I + 4
and
that the valve will be about 15% open
In these conditions it is estimated it should be near
of 0.4 to 0.2 whilst
will cavitate with T in the region
1.0. It has been assumed that the static head remains constant although it is
appreciated that at the low pressures, considered
it is unlikely to remain so. Q
main and the relief valve not
11. Should the pressure increase in the HPSW
gauge (3.0 bar abs), considerable
lift until the pressure rises to 2.0 bar the level of corrosion/erosion
increase in flow will develop and inevitablyIt is therefore essential to con-
attack at the valve will be quite severe.
the system where the risk of corrosion/
sider the pressure field throughout
erosion can occur.
ANNEX D 170
I -fli
.-. 'ITj
I inq 'I
d'tV !
'fTjFl 7
HH %! R IM
.*
,~~l
-.
a , -
j
i
:!::I-N
IiI'
i! i t
IO
is
iO
:i-iINi1it I
IIM
liit
tI
I i
M.1I
I
Ii
kil
III;'
I-I-.t:
NES 719
Issue 2
ANNEX E
2. The actual pages of the Check List contained in this Appendix are to
be regarded as MASTER COPIES. Xerox working copies are to be reproduced from
them as required.
17'3 ANNEX E
NES 719
Issue 2
Notes:
/ - included
NA = not applicable
NES 719 No
Clause or NA
Check Chk
No
Scope
NES 719 to be invoked in the Procurement Scope
Specification
Related Documents
2 List any necessary documents or drawings Section 2
not clearly included in NES 719
Drawings
3 State types and quantities required Section 3
Environment
5 Refer to NES 725 0501
174
ANNEX E
NES 719
Issue 2
175 ANNEX E
WES 719
Issue 2
NES 719 No or NA
Check Clause
Check
No
HPSW Systems
Has the extent of the HPSW Main been 0701 to 0705
32
specified
0707
33 Has the extent of the services supplied
from the HPSW Main been laid down
Have the HPSW pumps been dispersed 0709
34
0710
35 Has the provision of separate and short
suctions been laid down for the HPSW
pumps
Has provision been made for a warm 0713 to 0715
36
water supply
0716
37 Have "take offs" been provided as laid
down
0717
38 Two supply branches or one supply branch
laid down for each magazined spray
system as specified
0718
39 Local and remote control specified for
hull valves
0721 to 0727
40 Sufficient valves provided to enable
each system to fulfil its functions
under all conditions of operation
0726
41 Has remote control been provided for
manually operated spray system
0728 to 0730
42 Has provision been made for
insulating piping in exposed positions
0735
43 Has the fire fighting demands been
calculated in accordance with NES 119
0735
44 Has attention been drawn to Annex A -
Procedure for Establishing Flows
and Pressure Drops
0737
45 Has attention been drawn to the
relaxation in water speeds
0738 to 0741
46 Has provision been made for spraying
magazines
176
ANNEX E
NES 719
issue 2
NES 719 No or NA
Check Clause
Check
No
.0740
47 Has attention been drawn for the system
line-out to be in accordance with BR862
48 Attention drawn to the control details 0740
in BR 862
0743
49 Prewetting in accordance with NES 118
0747
50 Has attention been drawn to NES 712,
717 and 720 for domestic services
0748
51 Have arrangements been provided for
isolating domestic services
0749
52 Has attention been drawn to NES 119
for salvage and counter flooding
systems
0750 to 0755
53 Have the ballast and de-ballast
arrangements been detailed
0753
54 Has the method of filling the tanks
been selected
0754
55 Has reference been made to the
Structural Design Guide for tank design
0755
56 Tank preservation; ref made to NES 320
and Section 14 of this Standard
0756 and 0757
57 Are equipments supplied from the HPSW
System capable of withstanding maximum
pressure or alternatively pressure
reducing devices and relief valve
provided
ILW Systems
0802 and 0803
58 Has it been stated whether or not the
water
equipments are to be supplied with
at all times -
the 0804
59 If the LPSW System is supplied from
HPSW System, has the "minimum pressure
in the HPSW Main" been specified
0805
60 Equipment cooling flow rate requested/
obtained at the specified design sea
temp
drop 0806 to 0808
61 Has an equipment limiting pressure
been stated
0809 and 0810
62 The system pressure drop kept to a
minimum
system 0811
63 Has the requirement to calculate
pressure drops using SDP 25 been
stated
177 ANNEX E
NES 719
Issue 2
ANNEX E 178
NES 719
Issue .2
179 ANNEX E
NES 719
Issue 2
___0
Valves
102 Valves selected from NES 360 1001
Pipework
118 Bends meet the specified limits - with 1101 and 1103
ref to BR3013(2) for exceptions
119 BR3013(2) is called up for fittings 1102
ANNEX E 180
NES 719
Issue 2
181 ANNEX E
NES 719
Issue 2
ANNEX E 182
NES 719
Issue 2
Flow Control
181 Flow control devices have been specified 1201, 1203 &
as required to ensure the correct flow 1204
distribution
182 In assessing flow rates, factors such as 1202
variation in supply pressure and the
isolation of equipments have been taken
into account
183 The flow control devices are provided 1207 to 1209
in the correct positions
184 The orifices have been specified 'to 1210 and 1211
conform to NES 710 and to BS 1042
185 Orifices have been provided for the 1212 to 1215
proper situations
183
ANNEX E
NES 719
Issue 2
ANNEX E
184
NES 719
Issue 2
185 ANNEX E
NES 719
Issue 2
NES 719 No
Clause or NA
heck
No-
Check
221 Air pipes are run and joined as required 1404 to 1407
Instrumentation
1501
228 Ensure that pockets and other facings
and tappings are provided for all
instruments called-up
1502
229 Gauge boards are called-up and mounted
as required
Tally plates are specified for indicating 1503
230
the services of the various gauges
1504
231 Ensure that makers' provide the necessary
equipment tappings for remote
instrumentation
1505
232 Isolating valves are provided for all
pressure flow and level sensing devices
1506
233 Isolating valves are provided for vacuum
gauges, gauges subject to pulsating K)
pressure and remote gauges
1507
234 All isolating valves conform to NES 360
1508
235 Isolating valve stub pipes are of
appropriate size
236 Ensure that where thermometer pockets 1509
are not fitted in equipments, provision
is made for fitting them in adjacent
pipes
1510
237 Thermometer pockets are in accordance
with requirements and are installed in
accordance with laid down procedures
Ensure the pocket material is compatible 1511
238
with pipe material and contents
1512
239 Has the procedure for fitting thermo-
...
meters in the pockets been laid-down
186
ANNEX E
NES 719
Issue 2
Shore Supplies
252 Provision is made for flooding bonnets 1601
253 Provision is made for shore connections 1602 to 1608
254 The connection is to SDN 000875955 1604
255 The piping is the same size as the Ring 1605 to 1607
Main
256 A "deck elbow" is supplied and stowed 1608
onboard
Preservation
257 Cleaning and preservation is in 1701
accordance with NES 341 and 766
258 Is Protection by Sodium Dimethyl 1702
Dithiocarbamate required? If so it is
to be in accordance with NES 781
259 Provision is made for Cathodic protection; 1703
to be carried out in accordance with
NES 704
187 ANNEX E
NES 719
Issue 2
Insulation
260 Provision is made for insulating HPSW 1801
System and prewetting piping
267 The instruments for tuning are called-up 1923 and 1924
268 Advise the Shipbuilder of the 1925
information required before commencing
to tune
269 Call-up the precautions to be taken 1926
before tuning, calibration of instruments
270 Advise that all pressure warning devices 1933
are to be set during tuning
271 Specify the records which are to be 1934
kept during tuning
272 Single.pump system performance is 2002 to 2004
carried out in accordance with
requirements
273 Multi pump system performance is 2001 to 2061
carried out in accordance with
requirements
274 Where a SYMES pump is used excess 2003
head is dissipated by flow control devices
275 The single pump characteristic is 2004
provided as indicated in Fig 31
276 Is a SYMES pump acceptable for the 2005
H:Q duty?
277 Is a SYMES pump acceptable from NPSH 2006
aspects
A
ANNEX E 188
NES 719
Issue 2
189 ANNEX E
NES 719
Issue 2
190
ANNEX E
NES 719
Issue 2
ALPHABETICAL INDEX
Clauses
Alarms 1525
Aluminium structure 1141
Arrangement - pipework 1134 to 1149
Atmospheric pressure 0506
Axial flow pump selection 0902 0903
2046 2047
B
Brazing 1196
- valves 1008
C
Calculations - system pressure drops * 0811
Calibration - tanks 1413
Capilliary - fittings 1163
Castings 1194
191
iES 719
Issue 2
Clauses
0501 to 0503
Climatic conditions
Clips 1169 to 1174
1 6
1160
Closing pipe lengths
Colour marking 1150 1151
0830 to 0834
Common auxiliary SW systems
1163
Compression fittings
1221 to 1225
Constant flow control valves
1238 to 1240
Controlled flow systems
1225
Controlled pressure systems - general
- manual control 1226 to 1231
1232 to 1234
- automatic control 1193
1193
Corrosion
steel 1185
Corrosion pieces -
0720
Cross-connections
0748
Counter flooding
D0749 to 754
De-ballast arrangements
1166
Deck pieces for steel pipes
1176
Deckhead - fittings
1147
- penetrations
1216 to 1220
Diaphragm glandless valves - general
- limit stops 1220
0813 o823
82
Discharges083 1301 to 1304
1306 1307
1309
0746 to 0748
Domestic services
Draining 1181
E615 0620
Eductors - salvage capacity 1140
1140
Electrical areas
1112
Electrical connections/earths to piping
0826
Emergency bilge suctions
0823
Engine - driven pump system design
192
NES 719
Issue 2
Clauses
0805
Equipments - flow rates
0504
- performance
0627
- pressure drops
0806 to 0808
1190
Erosion
1126
Extrusions - maximum water speed
F
capacity 0618 0619
Fire - protection and firefighting
0732 0733
Firefighting - requirements
0734 to 0737
- design
1163
Fittings - capilliary
1163
- compression
1102
- pipes
1160
Flanged joints - alignment
1148 1165
- clearance
1176
Flexible connections - general
0607
- location
1601
Flooding bonnets
1205 to 1209
Flow control - devices
1201 to 1204
- requirements
0805
Flow rates - cooling equipment
1120
- general
1131 Table 4
- pipe size: water speed (table)
1104 1191
Flow straighteners
i~ Flushing1901
Flushing 1902
12 o12
C 1142
1141
Galvanic - action - piping
1167
- insulation
0603
General requirements for systems
1322 to 1330
Gratings - general
1329 1330
- materials
1334
- preservation
1329 1330
- securing
1323 to 1328
- size
193
NES 719
Issue 2
-
Clauses
H
0702 07o6
HPSW Main & Ring Main
0612
HPSW Main - maximum pressure
0612
- minimum pressure
0623
HPSW pump - assessment
0709
- location
0622
- selection
0710
- suctions
0611 to 0623
HPSW system - assessment
0615 to 0621
- capacity
0611 to 0614
- pressures
0707 0838
HPSW system supplies ,
- to LJPSW system - effect of change
in HPSW pressure
(orifices and/or
DG valves) 2053 to 2055
- effect of
isolating LPSW
(orifices and/or
DG valves) 2056 2059
effect of change
in HPSW pressure
(constant flow
control) 2061
effect of isolating
LPSW System
branches (constant
flow control) 2062
0756 t20
UPSW supplies to cooling equipment
2011 to 2020
Head: quantity characteristics - equipments
plating 1301 to 1307
Holes - in inner and outer bottom
1303
- noise .6
Hose connections - screwed
0718
Hull valves - control
1319 to 1321
- interfaces
0816
Hydraulic gradients
1 1150 to 1151
Identification - painting
1501 to 1526
Instrumentation - general
1501 to 1512
- fittings
194
NES 719
Issue 2
Clauses
Insulation - HPSW Systems 0728 to 0730
- piping 1801 to 1802
1136
Isolating valves - provision of in HPSW Systems 0723
0721 to 0726
- sensing devices 1505 to 1507
J
195
NES 719
Issue 2
Clauses
Manholes 1403
- welding 1195
1235 1236
Matched flow systems
Materials 1183 to 1187
1329 1330
- gratings
- magazine spraying 0741
- PVC 1125
- steel 1124
0612
Minimum pressure in HPSW Main
Minimum water speeds 1127 to 1129
0902 0903
Mixed flow pumps - selection
2046 2047
N
0917 to 0922
NPSH available
1113
1186
Naval brass
Noise - low, valves 1006 0
1303
- holes in outer bottom
0814 0815
Non-syphonic systems
0
196
NES 719
Issue 2
pClauses
.
197
NES 719
Issue 2
Clauses kjm
S
1902
SDD treatment
0749
Salvage arrangements
0615 0751
Salvage eductors - capacity
1011
- valve control
198
NES 719
Issue 2
Clauses
Scoops 0821
- finish 1318
- preservation 1415
199
HES 719
Issue 2
Clauses .)
- reliability 111
T
1401 .1402
Tanks
0754
- design
0608
- discharges
0751 0752
- filling
0753 1415
- preservation
1106
Tapered pieces
1917
Tests after installation
1918 to 1921
Tests and trials
1520 to 1524
Thermometers
- fittings 1512
0718
Valves - control, local and remote
1010 to 1013
200
NES 719
Issue 2
Clauses
Water testing - air escapes 1408
Weed box 1321
Welded joints 1153 to 1159
Welding 1195
Winterisation 0728 to 0730
Working pressure 1903
201/202
© Crown Copyright 2000
Copying Only as Agreed with DStan
DStan Helpdesk
File Reference
Contract Requirements
When Defence Standards are incorporated into contracts users are responsible for their correct
application and for complying with contractual and statutory requirements. Compliance with
a Defence Standard does not in itself confer immunity from legal obligations.