Magnum DS family 1
Magnum DS low voltage In addition, Magnum DS Magnum DS low voltage circuit breakers
power circuit breakers are UL is suitable for use in: UL 1
listed, designed, tested and 1558 “Certified Magnum
certified to all applicable ANSI, DS low voltage metal- 1
NEMA, UL, CSA, IEC, EC and enclosed switchgear”,
IEEE standards. Specifically,
the circuit breakers meet or
UL 891 “Standard for LV
switchboards”, UL CSA TIL
1
exceed the following: No. D-34. Refer to Figure 1 for
a visual reference and Table 1 1
• UL 1066
for a quick ratings reference.
• ANSI C37.13
Product family
1
• ANSI C37.16
• ANSI C37.17 characteristics: 1
• ANSI C37.50 • Up to 635 Vac operating
• IEC 60947-2 (ed.4) voltage 1
• GB14048.2-2008 • Up to 200 kA interruption
• CSA TIL No. D-34 ratings 1
”Interim certification • Up to 130 kA short time
requirements for low voltage withstand ratings 1
power circuit breakers”. • 200–5000A continuous
current 1
• Three- and four-pole
configurations 1
• Fixed and drawout
1
1
Table 1. Magnum DS ANSI breaker family ratings (Class UL 1066)
Interruption
1
rating (kA) 800 Amp 1200 Amp 1600 Amp 2000 Amp 2500 Amp 3200 Amp 4000 Amp 5000 Amp 3
@ 508 Vac Frame Frame Frame Frame Frame Frame Frame Frame 1
200
1
130
1
1
100 1
1
85
1
1
65
1
1
50
1
42 1
1
1 Interruption rating shown based on breaker equipped with integral Digitrip RMS trip unit. = Magnum DS standard frame 1
2 Refer to Section 2 for a detailed ratings table. = Magnum DS narrow frame
3 6000A is available in fan cooled switchgear. See www.eaton.com/lva = Magnum DS double narrow frame
= Magnum DS double standard frame
1
1 Magnum SB family
Magnum SB low voltage Product family Magnum SB insulated case circuit breakers
1 insulated case power circuit characteristics:
breakers are certified by UL
1 1066. The SB Family was • Switchboard class
designed for the performance • Up to 635 Vac
1 and economic requirements
of UL891 switchboard class
• Three- and four-pole
configurations
applications overall. Refer to
1 Figure 2 for a visual reference
• Drawout and fixed mounted
and Table 2 for a quick ratings • 200A to 5000A continuous
1 reference. current
• 50 kA to 150 kA interrupting
1 ratings
• Short-time withstand up to
1 100 kA
1
1
1
1
1
1 Table 2. Magnum SB insulated case breaker family ratings (Class UL 891)
1 Interruption
rating (kA)
@ 440 Vac 800 Amp 1200 Amp 1600 Amp 2000 Amp 2500 Amp 3000 Amp 4000 Amp 5000 Amp 3
1 Icu =Ics Frame Frame Frame Frame Frame Frame Frame Frame
150
1
1 130
1
1 100
1
1 85
1
65
1
1 50
1
1 1 Interruption rating shown based on breaker equipped with integral Digitrip RMS trip unit. = Magnum SB standard frame
Refer to Section 2 for a detailed ratings table.
1 = Magnum SB narrow frame
2
3 6000A is available in fan cooled switchgear. See www.eaton.com/lva = Magnum SB double narrow frame
= Magnum SB double standard frame
1
1
40
1
1
1
1 Interruption rating shown based on breaker equipped with integral Digitrip RMS trip unit. = Magnum IEC standard frame
Refer to Section 2 for a detailed ratings table. = Magnum IEC narrow frame
1
3
= Magnum IEC double narrow frame
= Magnum IEC double standard frame
1
1
1
1
1
1
1
1
1
1 Magnum DC switch ratings
1 100
65kA
1 80
(kA Interruption)
1 60
50kA 50kA
1 40
25kA
1 20
1 0
@300 Vdc @600 Vdc @1000 Vdc
1 (up to 3200A continuous) (up to 3200A continuous) (up to 5000A continuous)
= UL 1066 interrupting/withstand
1 = UL 489 interrupting/withstand
= IEC 60947-2 withstand
1 = IEC 60947-2 interrupting
1
1
1
1
1
1
1
Universal family features • Narrow frame (800 – 2000 Amps): Promoting the most
compact modular enclosures.
As mentioned, Magnum low voltage power circuit breakers
consist of four product families. Although each family has 2
its own unique performance and features, each Magnum
breaker boasts a wide array of common design elements. 1
These common design elements deliver proven performance
with expanded capabilities, no matter which product family is
applied. To fulfill the latest market needs with proven reliability
1
and performance, Magnum is the clear choice for low voltage
applications. 1
1
High performance interruption &
withstand levels • Standard frame (800 – 3200 Amps): Ideally suited for vertically
1
stacked modular construction.
Magnum provides Magnum provides large range withstand 1
and interrupting ratings to maximize selectivity and system
coordination. 1
• A range from 42kA up to 200 kA interrupting - application on
power distribution systems with higher available fault currents. 1
• Up to 130 kA withstand (short-time) - total selectivity/selective
coordination/discrimination between main, feeder, and branch 1
circuit breakers.
• Current limiting performance - lower let-through currents for 1
superior equipment protection.
• Optional Arc Flash Reduction Maintenance System 1
(ARMS™) - reduces arc flash hazards and improves operator
and maintenance safety. • Double narrow frame (4000 Amps): Decreased footprint when 1
• Circuit breakers performance tested - meet or exceed all space is at a premium.
applicable ANSI, NEMA, UL, CSA, IEC, EC and IEEE standards.
Specifically, the circuit breakers meet or exceed the following:
1
UL 1066, ANSI C37.13, ANSI C37.16, ANSI C37.17, ANSI C37.50,
IEC 60947-2, GB14048.2-2008, and CSA TIL No. D-34. 1
1
Continuous current ratings
1
• 800 to 5000A (UL1066), 800 to 6300A (IEC) - ensuring
Double standard frame (3200 – 5000A): Ideal for main and
maximum uptime over expansive frame rating range. •
tie applications.
1
• 100% rated – designed for continuous operation at 100% of
•
current rating.
Reverse feed capable - top or bottom feed for multiple source
1
applications.
1
Sizes, dimensions, weights and 1
configurations Increased ratings in less space provide the flexibility to design 1
more robust electrical distribution systems, capable of handling
Magnum circuit breakers are available in four physical frame larger available fault currents while providing better coordination
sizes, all centered around a modular design approach. The with downstream devices. 1
versatile Magnum design concept maximizes enclosure density
with the same basic height and depth, differing only in width. 1
NNote: For detailed Magnum breaker outline drawings, please refer to
Section 11: Magnum drawings and outlines 1
1
1
1
1
2 Drawout
version -
Vol (dm3/ft 3) 83.5/2.94 107.3/3.79 165.7/5.86 225.8/7.98
(D/O in cass Width (mm/in) 336/13.2 432/17.0 667/26.3 909/35.8
w/terminals)
1 (mm/in) Height (mm/in) 524/20.6 524/20.6 524/20.6 524/20.6
Depth - w/o adapters (mm/in) 474/18.7 474/18.7 474/18.7 474/18.7
1 Adapters are part of Cassette
Bkr + Cass=Total Wgt (lbs) 108 + 61 = 169 138 + 117 = 255 214 + 106 = 320 303 + 199 = 502
1 Pole spacing Distance (mm/ in) 95/3.75 127/5.0 95/3.75 127/5.0
Fixed Vol (dm3/ft 3) 50.4/1.77 65.1/2.3 109.5/3.86 139.6/4.93
1 dimensions
mm/in Width (mm/in) 318/12.5 411.5/16.2 633/24.9 823/31.1
Height (mm/in) 426/16.8 426/16.8 426/16.8 426/16.8
1 Depth (mm/in) 371/14.6 371/14.6 415/16.3 415/16.3
1 Bkr + Cass=Total Wgt (lbs) 136 + 70 = 206 194 + 123 = 317 214 + 106 = 320 366 + 250 = 616
Pole spacing Distance (mm/ in) 95/3.75 127/5.0 95/3.75 127/5.0
1 Fixed
dimensions
Vol (dm3/ft 3) 50.4/1.77 65.1/2.3 109.5/3.86 139.6/4.93
mm/in Width (mm/in) 413/16.3 538/21.2 824/32.4 1120/44.1
1 Height (mm/in) 426/16.8 426/16.8 426/16.8 426/16.8
Depth (mm/in) 371/14.6 371/14.6 415/16.3 415/16.3
1 Weight - Fixed bkr (lbs) 120 160 177 319
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 • Some field installable accessories easily identified by name
and rating through viewing windows. They are the shunt trip, NNote: Non-automatic breakers (AC OR DC type disconnect switches) do
spring release and undervoltage release. not contain a trip unit or current sensors. They are covered in more depth
1 later in this section. Refer to Section 7 for specific Digitrip trip unit and
communication information.
1
1
Optional padlockable cover limits access to “ON” and “OFF”
1 •
pushbuttons.
1
1
1
1
1
1
1
1
1
Drawout mounting Standard frame Cassettes (for standard frame and double
standard frame breakers)
A drawout circuit breaker is used in combination with a cassette.
The cassette provides for all the required drawout features for
For standard and double frame circuit breakers, there are three 2
cassette styles, all with vertical stabs available:
both primary and secondary connections. Mounting locations
for cassette mounted cell switches, primary safety shutters and • Basic Cassette with copper stabs - This cassette comes with 1
various key interlocks are part of the cassette design, to allow factory installed copper stab/terminals on the cassette.
for customized customer options. Refer to Section 11 for specific
drawout circuit breaker and cassette dimensions.
1
1
1
1
1
1
1
1
Cassettes – Available styles
Narrow frame Cassettes (for narrow frame and double
1
narrow frame breakers) 1
For narrow frame circuit breakers, there is one type of cassette
design, which uses horizontal stabs. Horizontal customer 1
busbar terminals are available (sold separately). Optional bolt-on
90-degree adapters can be used to rotate the cassette’s primary
terminals to a vertical orientation as required.
• Basic Cassette without copper stabs - The basic cassette 1
can also be ordered without factory supplied copper stab/
terminals. Ordering without stabs allows the switchgear
builder to integrate the cassette by using their vertical busbars.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
A W C H N E H K L A X
H = Yes No
reset
Yes with
1
240V
reset 1
I = Yes Yes Yes with
24V reset 1
J = Yes Yes Yes with
120V
reset
1
K = Yes Yes Yes with
240V 1
reset
M E 32 3 C A DN N NNN W C
1 Poles
3 = Three-pole
1 4 = Four-pole
1 1 The arc hood option 'D' is recommended for use of ATS applications as
well as on Magnum ANSI DC breakers, 'DAS' and 'DBS' configurations
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Table 6. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI
rms Symmetrical current ratings kA 50/60 Hz 1 Available
current
sensor 3
and rating
Short plugs for
Breaker
type
time
withstand
Short
time Fixed
digitrip rms
trip unit
1
catalog Interruption Interruption Interruption rating withstand internal (establishes
Frame
amperes
position
1–6
Frame
type
rating at
254 Vac
rating at
508 Vac
rating at
635 Vac
@254/
508Vac
rating
@635Vac
inst
trip
breaker In
rating)
Poles
available 1
800 MDN-408 Narrow 42 42 42 42 42 n/a 200, 250, 300, 3&4
MDN-508 Narrow 50 50 50 50 50 n/a 400, 600, 800 3&4 1
MDN-608 Narrow 65 65 65 65 65 n/a 3&4
MDN-C08 Narrow 100 100 65 20 20 18xIn 3&4
1
MDS-408 Standard 42 42 42 42 42 n/a 3&4
MDS-508 Standard 50 50 50 50 50 n/a 3&4
1
MDS-608 Standard 65 65 65 65 65 n/a 3&4 1
MDS-808 Standard 85 85 85 85 85 n/a 3&4
MDS-C08 Standard 100 100 100 85 85 85 3&4 1
MDS-H08 Standard 130 130 130 85 85 85 3
MDS-L08 2 Standard 200 200 200 2 2 n/a 3 1
MDS-X08 3 6
Standard 200 200 65 30 30 30 3
1200 MDN-412 Narrow 42 42 42 42 42 n/a 200, 250, 300, 3&4 1
MDN-512 Narrow 50 50 50 50 50 n/a 400, 600, 800, 3&4
MDN-612 Narrow 65 65 65 65 65 n/a
1000, 1200
3&4
1
MDN-C12 Narrow 100 100 65 25 25 18xIn 3&4
MDS-X12 Standard 200 200 65 30 30 30 3&4
1
MDS-512 Standard 50 50 50 50 50 n/a 3&4 1
MDS-612 Standard 65 65 65 65 65 n/a 3&4
MDS-812 Standard 85 85 85 85 85 n/a 3&4 1
MDS-C12 Standard 100 100 100 85 85 n/a 3&4
MDS-H12 Standard 130 130 130 85 85 85 200, 250, 300, 3 1
1600 MDN-416 Narrow 42 42 42 42 42 n/a 400, 600, 800, 3&4
1000, 1200,
MDN-516 Narrow 50 50 50 50 50 n/a 1600 3&4 1
MDN-616 Narrow 65 65 65 65 65 n/a 3&4
MDN-C16 Narrow 100 100 65 30 30 18xIn 3&4 1
MDS-516 Standard 50 50 50 50 50 n/a 3&4
MDS-616 Standard 65 65 65 65 65 n/a 3&4
1
MDS-816 Standard 85 85 85 85 85 n/a 3&4
1
MDS-C16 Standard 100 100 100 85 85 85 3&4
MDS-H16 Standard 130 130 130 85 85 85 3 1
MDS-L16 2 Standard 200 200 200 2 2 n/a 3
MDS-X16 3 Standard 200 200 65 30 30 30 3 1
1 Interrupting ratings shown based on breaker equipped with integral Digitrip™ rms trip unit. Interruption ratings for non-automatic breakers are equal
to the published withstand rating. 1
2 Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short time and fixed instanta-
neous trip rating. 1
3 Magnum MDSX current limiting power circuit breaker with fast opening contacts.
4 Product to be tested. Contact Eaton for product rating. 1
5 Breaker applied in a tested fan cooled enclosure.
6 Not released. 1
1
1
1
Table 6. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI continued
rms Symmetrical current ratings kA 50/60 Hz 1 Available
current
sensor
and rating
Short plugs for
Breaker time Short digitrip rms
3 type
catalog Interruption Interruption Interruption
withstand
rating
time
withstand
Fixed
internal
trip unit
(establishes
Frame position Frame rating at rating at rating at @254/ rating inst breaker In Poles
1 amperes
2000
1–6
MDN-620
type
Narrow
254 Vac
65
508 Vac
65
635 Vac
65
508Vac
65
@635Vac
65
trip
n/a
rating)
200, 250, 300,
available
3&4
400, 600, 800,
1 MDN-C20 Narrow 100 100 65 35 35 18xIn
1000, 1200,
3&4
MDS-620 Standard 65 65 65 65 65 n/a 1600, 2000 3&4
1 MDS-820 Standard 85 85 85 85 85 n/a 3&4
MDS-C20 Standard 100 100 100 85 85 85 3&4
1 MDS-H20 Standard 130 130 130 85 85 85 3
MDS-L20 2 Standard 200 200 200 2 2 n/a 3
1 MDS-X20 3 Standard 200 200 65 30 30 30 3
2500 MDS-625 Standard 65 65 65 65 65 n/a 200, 250, 300, 3&4
1 MDS-825 Standard 85 85 85 85 85 n/a 400, 600, 800, 3&4
1000, 1200,
1 MDS-C25
MDS-H25
Standard
Standard
100
130
100
130
100
130
100
85
85
85
85
85
1600, 2000,
2500
3&4
3
1 3200 MDS-632 Standard 65 65 65 65 65 n/a 200, 250, 300,
400, 600, 800,
3&4
MDS-832 Standard 85 85 85 85 85 n/a 3&4
1000, 1200,
1 MDS-C32 Standard 100 100 100 85 85 85 1600, 2000,
2500, 3200
3&4
MDS-H32 Standard 130 130 130 85 85 85 3
1 MDS-X32 3 Double 200 200 4 50 50 50 3
4000 MDS-840 Double 85 85 85 85 85 n/a 2000, 2500, 3&4
1 MDS-C40 Double 100 100 100 100 100 n/a 3200, 4000 3&4
MDS-H40 Double 130 130 130 130 130 n/a 3
1 MDS-X40 3 Double 200 200 4 50 50 50 3
MDN-640 Double 65 65 65 65 65 n/a 3&4
1 Narrow
MDN-840 Double 85 85 65 85 65 n/a 3&4
1 Narrow
MDN-C40 Double 100 100 65 100 65 n/a 3&4
1 Narrow
MDD-X40 Double 200 200 100 100 100 n/a 3
1 5000 MDS-850 Double 85 85 85 85 85 n/a 2500, 3200, 3&4
MDD-X50 Double 200 200 100 100 100 n/a 4000, 5000 3
1 MDS-C50 Double 100 100 100 100 100 n/a 3&4
MDS-H50 Double 130 130 130 130 130 n/a 3
1 MDS-X50 3 5
Double 200 200 4 50 50 50 3
1 1 Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit. Interruption ratings for non-automatic breakers are equal to
the published withstand rating.
Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short time and fixed instanta-
1 2
neous trip rating.
3 Magnum MDSX current limiting power circuit breaker with fast opening contacts.
1 4 Product to be tested. Contact Eaton for product rating.
5 Breaker applied in a tested fan cooled enclosure.
1 6 Not released.
1
1
1
1
1
2000 MD3000 3
1
1 Select the current limiter based on the Magnum breaker frame and current sensor and rating plug as shown.
2 Refer to MDSL current limiter curves for let-through and time characteristics. 1
3 The recommended ratings provide for reduced current let-through and breaker coordination within the trip unit settings. Selection of current limiters
below the recommended ratings shown provides lower current let-through, however, trip unit settings must be considered to avoid nuisance
operation.
1
1
Type Magnum DSL limiters, peak let-through current Type Magnum DSL limiters average melting time-current
characteristics characteristics
3 100
90
80
1000
900
800
70 700
600
1
60 500
50 400
40 300
1
30
200
20
MD3000
1 MD2500
Peak instantaneous let-through current kilo – amperes x 10
10
MD2000 60
MD1600 50
9
8 MD1200 40
MA250
MA800
1
7
6 30 MA300
5 MA600 20 MA400
Time in seconds
4
MA400 MA500
1 3
2
MA300
MA250
10
9
8
MA800
7
MB1200
1
6
5
4 MB1600
1 3
.9 MB2000
.8
1 .7
.6
.5
2
MB2500
MB3000
.4 1
1
.9
.8
.3 .7
.6
.5
.2 .4
1 .3
.2
.1
.09
1 .08
.07
.06
.05
.1
.09
.08
.07
.06
1
.04
.05
.03 .04
.03
.02
1 .02
.01
1
70
1
3
4
5
6
7
8
9
10
20
30
40
50
60
80
90
100
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
100
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
6000
7000
8000
10000
20000
30000
40000
50000
70000
80000
90000
100000
9000
60000
•
used in enclosures)
ANSI C37.16
in UL 891 switchboards.
This provides for improved
1
(preferred ratings, coordination and selectivity
related requirements, for most commercial 1
and application switchboard applications.
recommendations for The instantaneous trip 1
low voltage power circuit function facilitates feeder
breakers and AC power circuit breaker protection 1
circuit breakers) in UL 891 switchboards
• ANSI C37.17 (trip devices with 3-cycle bus bracing. 1
for AC and general purpose This yields reduced energy
DC low voltage power
circuit breakers)
let through to downstream
circuits by eliminating the
1
fault current above the fixed
• ANSI C37.50 (test
procedures for low voltage instantaneous trip point. 1
AC power circuit breaker Magnum SB insulated-
used in enclosures)
•
case circuit breakers have 1
• UL 1066 (standard for low Interruption ratings up to
voltage AC and DC power 150 kA with continuous 1
circuit breakers used in current ratings up to 5000A.
enclosures)
Magnum SB non-automatic
1
Comprehensive enclosure breaker (switch)
solutions
1
The non-automatic Magnum
Magnum SB has proven SB breaker (switch) shares the 1
performance in Eaton same frame and accessories
manufactured switchboards
with the following test
as the circuit breaker. It
does not, however, have the
1
certifications: following:
Trip unit
1
• UL 891 (certified Pow-R-Line •
C low voltage switchboards)
C22.2 No. 31-14 Switchgear
• Sensors
1
• • Overcurrent release
assemblies Like the Magnum SB breaker, 1
Approvals and marks the switch is available in both
• UL listed: Magnum SB
three-pole and four-pole, fixed
and drawout configurations.
1
breaker UL file E52096 and
Cassette UL file E204565
A non-automatic circuit
breaker includes separable
1
• Additional Magnum SB contacts for movement
approvals and certificates between a closed position 1
can be found on www. and an open position, and
eaton.com/magnum an operating mechanism for 1
moving the separable contacts
between the two positions. 1
It cannot be used for branch-
circuit protection.
1
1 D. Interrupting capacity
rating
1 E. Factory equipped
accessories
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
A W C H N E H K L A X
(SRD) 2 = 2A/2B
1 N = None
4 = 4A/4B
Latch check switch/trip unit
metering voltage connection for
6 = 6A/6B digitrip 1150 trip unit
A = 110–127 Vac/Vdc
1 R = 208–240 Vac/Vdc
Bell Alarms Switch (OTS) with
Latch
C = 24 Vdc check 1150 voltage
2a/2b contacts and/or mechanical
1 H
S
= 48 Vdc
= 60 Vdc
trip indicator
switch connection
N = None Upper terminals
Mech. OTS
1 inter- switch
M = None
L = LCS wired
Lower terminals
Upper terminals
Mech. lock for with two
to SRD
1 trip manual
indicator reset
form C
contacts
Y = LCS Wired Lower terminals
to SRD
1 E =
N =
No
Yes
—
No
No
No
C = LCS Wired
External
Upper terminals
M E 32 3 C A DN N NNN W C
Table 8. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI
rms Symmetrical current ratings kA 50/60 Hz 1 Available
3 current
sensor
and rating
plugs for
4 Breaker
type Short
digitrip rms
trip unit
catalog Interruption Interruption Interruption time Fixed (establishes
1 Frame
amperes
position
1–6
Frame
type
rating at
254 Vac
rating at
508 Vac
rating at
635 Vac
Withstand
rating
internal
inst trip
breaker In
rating)
Poles
available
800 SBN-508 Narrow 50 50 35 20 18xIn 200, 250, 300, 3&4
1 SBN-608 Narrow 65 65 42 20 18xIn 400, 600, 800 3&4
SBN-C08 Narrow 100 100 65 20 18xIn 3&4
1 SBS-608 Standard 65 65 65 20 18xIn 3&4
SBS-808 Standard 85 85 85 20 18xIn 3&4
1 SBS-C08 Standard 100 100 85 20 18xIn 3&4
1 SBS-H08 Standard 130 130 130 20 18xIn 3
SBS-E08 4 6
Standard 200 150 65 30 30 3
1 1200 SBN-512 Narrow 50 50 35 25 18xIn 200, 250, 300,
400, 600, 800,
3&4
SBN-612 Narrow 65 65 42 25 18xIn 3&4
1000, 1200
1 SBN-C12 Narrow 100 100 65 25 18xIn 3&4
SBS-612 Standard 65 65 65 25 18xIn 3&4
1 SBS-812 Standard 85 85 85 25 18xIn 3&4
SBS-C12 Standard 100 100 85 25 18xIn 3&4
1 SBS-H12 Standard 130 130 130 25 18xIn 3
SBS-E12 4 Standard 200 150 65 30 30 3
1 1600 SBN-516 Narrow 50 50 35 30 18xIn 200, 250, 300, 3&4
400, 600, 800,
1 SBN-616 Narrow 65 65 42 30 18xIn
1000, 1200,
3&4
SBN-C16 Narrow 100 100 65 30 18xIn 1600 3&4
1 SBS-616 Standard 65 65 65 30 18xIn 3&4
SBS-816 Standard 85 85 85 30 18xIn 3&4
1 SBS-C16 Standard 100 100 85 30 18xIn 3&4
SBS-H16 Standard 130 130 130 30 18xIn 3
1 SBS-E16 4 Standard 200 150 65 30 30 3
2000 SBN-620 Narrow 65 65 65 35 18xIn 200, 250, 300, 3&4
1 SBN-C20 Narrow 100 100 65 35 18xIn 400, 600, 800, 3&4
1000, 1200,
SBS-620 Standard 65 65 65 35 18xIn 1600, 2000 3&4
1 SBS-820 Standard 85 85 85 35 18xIn 3&4
1 SBS-C20 Standard 100 100 85 35 18xIn 3&4
SBS-H20 Standard 130 130 130 35 18xIn 3
1 SBS-E20 Standard 200 150 65 30 30 3
1 Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit.
1 These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15 second interval and a close-open operation,
in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of maintaining the rated
1 3
current for two periods of 1/2 seconds each, with a 15 second interval of zero current between the two periods.
Product to be tested. Contact Eaton for product rating
1 4
5
Magnum SBSE current limiting power circuit breaker with fast opening contacts.
Breaker applied in a tested fan cooled enclosure
1 6 Not released
1
1
1
1
Table 8. Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI continued
rms Symmetrical current ratings kA 50/60 Hz 1 Available
current
sensor
and rating
plugs for
Breaker digitrip rms
type
catalog Interruption Interruption Interruption
Short
time Fixed
trip unit
(establishes
3
Frame position Frame rating at rating at rating at Withstand internal breaker In Poles
amperes
2500
1–6
SBS-625
type
Standard
254 Vac
65
508 Vac
65
635 Vac
65
rating
45
inst trip
18xIn
rating)
200, 250, 300,
available
3&4
4
400, 600, 800,
SBS-825 Standard 85 85 85 45 18xIn
1000, 1200,
3&4 1
SBS-C25 Standard 100 100 85 45 18xIn 1600, 2000, 3&4
SBS-H25 Standard 130 130 130 45 18xIn 2500 3 1
SBS-E25 4 Double 200 150 3 50 50 3
3000 SBS-630 Standard 65 65 65 50 18xIn 200, 250, 300, 3&4 1
SBS-830 Standard 85 85 85 50 18xIn 400, 600, 800, 3&4
SBS-C30 Standard 100 100 85 50 18xIn
1000, 1200,
1600, 2000, 3&4 1
SBS-H30 Standard 130 130 130 50 18xIn 2500, 3000 3
SBS-E30 4 Double 200 150 3 50 50 3
1
4000 SBS640
SBN640
Double
Double
65
65
65
65
65
65
65
65
18xIn
18xIn
2000, 2500,
3000, 4000
3&4
3&4
1
Narrow
SBS-840 Double 85 85 85 72 18xIn 3&4
1
SBS-C40
SBS-H40
Double
Double
100
130
100
130
100
130
72
72
18xIn
18xIn
3&4
3
1
SBN-840 Double
Narrow
85 85 65 72/65 18xIn 3&4 1
SBN-C40 Double
Narrow
100 100 65 72/65 18xIn 3&4
1
SBS-E40 4
Double 200 150 50 50 3&4
1
3
3
current for two periods of 1/2 seconds each, with a 15 second interval of zero current between the two periods.
Product to be tested. Contact Eaton for product rating
1
4
5
Magnum SBSE current limiting power circuit breaker with fast opening contacts.
Not released
1
1
1
1
1
1
1
1
1
1
1
1 MW N 5 12 4 V E A 03 MT 6 M C J 2 Y C N M W X
1
Breaker frame Trip unit and protection,
1 I = Standard or double and external control voltage when
required
N = Narrow or double
Poles and neutral Mounting configuration
1 = narrow
K = Special 1100 Vac ACB (facing front of breaker) and load terminals
NN
22
= Non-automatic (no trip unit)
= 520 LI
3 = Three H = Fixed horizontal 52 = 520 LSI
1 Interrupting Icu 4 = Four (neutral left) V = Fixed vertical 5W = 520i LSIG
R = Four (reserved for L = Drawout horizontal M2 = 520M LSI
4 = 40 kV
1 5 = 50 kV
neutral right) MT
MU
= 520M LSI (24–48 Vdc)
= 520M LSI (120 Vac)
6 = 65 kV Nameplate language
MV = 520M LSI (240 Vac)
1 8 = 85 kV E = English
MW = 520Mi LSIG
Z = 100 kV A = Spanish
MJ = 520Mi LSIG (24–48 Vdc)
1 H = 25 kV
(1100 Vac MWK) Sensor and
MK = 520Mi LSIG (120 Vac)
ML = 520Mi LSIG (240 Vac)
rating plug rating
1 Continuous amperes and NN = None 13 = 1250
ME
MC
= 520M LSIA (24–48 Vdc)
= 520M LSIA (120 Vac)
phasing (facing front of 01 = 100 16 = 1600 MF = 520M LSIA (240 Vac)
1 breaker) 02 = 200 20 = 2000 CT = 520MC LSI (24–48 Vdc)
08 = 800 ABC 05 = 250 25 = 2500 CU = 520MC LSI (120 Vac)
1 10
12
= 1000 ABC
= 1250 ABC
03
04
=
=
300
400
30 =
32 =
3000
3200
CV
CE
= 520MC LSI (240 Vac)
= 520MC LSIA (24–48 Vdc)
16 = 1600 ABC 06 = 600 40 = 4000 CC = 520MC LSIA (120 Vac)
1 20 = 2000 ABC 08 = 800 50 = 5000 CF = 520MC LSIA (240 Vac)
25 = 2500 ABC 10 = 1000 63 = 6300 CJ = 520MCi LSIG (24–48 Vdc)
1 32 = 3200 ABC 12 = 1200 CK = 520MCi LSIG (120 Vac)
41 = 4000 ABC (standard CF = 520MCi LSIG (240 Vac)
1 drawout only)
4N = 4000 AABBCC
C1
C2
= 520MC ARMS LSI (24–48 Vdc)
= 520MC ARMS LSI (120 Vac)
5N = 5000 AABBCC C3 = 520MC ARMS LSI (240 Vac)
1 6N = 6300 AABBCC C4 = 520MC ARMS LSIA (24–48 Vdc)
40 = 4000 ABCABC C5 = 520MC ARMS LSIA (120 Vac)
1 50 = 5000 ABCABC
60 = 6300 ABCABC
C6
C7
= 520MC ARMS LSIA (240 Vac)
= 520MC ARMS LSIG (24–48 Vdc)
C8 = 520MC ARMS LSIG (120 Vac)
1 C9 = 520MC ARMS LSIG (240 Vac)
1W = 1150i LSI (24–48 Vdc)
1 1N = 1150i LSI (120 Vac)
1P = 1150i LSI (240 Vac)
1 1R
1S
= 1150i LSIG/A (24–48 Vdc)
= 1150i LSIG/A (120 Vac)
1T = 1150i LSIG/A (240 Vac)
1
1
1
1
1
1
Magnum IEC breaker product family continued (15 through 25)
MW N 5 12 4 V E A 03 MT 6 M C J 2 Y C N M W X
I = Yes Yes
reset
Yes with
1
24V reset
J = Yes Yes Yes with 1
120V
K = Yes Yes
reset
Yes with
1
240V
reset 1
1
Cassette Magnum IEC breaker product family
E N 32 4 H K N N S NNN W C
5 Interrupt type
Arc hood Door frame and gasket kit
Cassette wiring
A = Arc hood for 690 Vac N = All cassettes
N = Un-wired
1 N = All cassettes
K = Arc hood for 1100 Vac
W = Cassette wired
Future use
Continuous amperes
1 20 = Up to 2000A
Rear terminals N = All cassettes Future use
H = Horizontal stabs
32 = 2500–3000A N = All cassettes
1 41 = 4000A standard frame
(upper and lower
terminals)
40 = 4000A Shutters
1 63 = 5000–6300A
N = No shutters
S = Shutters installed
1 Poles
3 = Three-pole
1 4 = Four-pole
1 1 Exclusionary rules apply. Refer to price list. Confirm all final part
numbers with Eaton. Format structures subject to modifications
1 and additions without notice.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Table 9. Magnum IEC 60947-2 rated air circuit breakers continued
rms symmetrical current ratings kA
1 Available
current
sensor
and
rating
plugs for
3 With-
stand
digitrip
rms trip
Inter- Inter- Inter- rating With- unit
4 rupting
@ 240
rupting
@ 440
rupting
@ 690
Icw
1-Sec @
stand
rating
Fixed
internal
(estab-
lishes Poles
Frame Breaker Frame Vac Vac Vac 440V/ Icw inst breaker KEMA/ avail-
amperes type type Icu = Ics Icu = Ics Icu = Ics 690V 3-Sec trip In rating) KEUR CCC able
5 2500 MWI-625 Standard 65 65 65 65 n/a 200, 250, X X 3&4
MWI-825 Standard 85 85 85 85 65 300, 400, X X 3&4
1 MWI-C25 Standard 100 100 85 85 65 85
630, 800,
1000, 1250, 3&4
1600, 2000,
1 MWI-H25 Standard 125 125 125 85 65
2500
X X 3&4
1 4000
MWI-H32
MWI-64N
Standard
Double 65 65
125
65 65 n/a 2000, X X
3&4
3&4
2500,
1 MWN-64N Double
Narrow
66 66 66 66 n/a
3200,
X X 3&4
4000
1 MWI-641
MWI-84N
Standard
Double
66
85
66
85
66
85
66
85
n/a
n/a
X
X
X
X
3&4
3&4
1 MWN-84N Double
Narrow
85 85 66 85/66 66 X X 3&4
1 MWI-841
MWI-C4N
Standard
Double
85
100
85
100
85
100
85
100
66
n/a
X
X
X
X
3&4
3&4
1 MWN-C4N Double
Narrow
105 105 66 105/66 66 X X 3&4
1 5000
MWI-C41
MWI-85N
Standard
Double
105
85
105
85
85
85
85
85
n/a
n/a 2500,
X
X
X
X
3&4
3&4
3200,
1 MWI-C5N Double 100 100 100 100 n/a
4000, 5000
X X 3&4
1 DEM/DGM
DEM/DGM
Narrow
Narrow
3
3
1000 A
1250 A
1000 V/25 kA/65 kA
1000 V/25 kA/65 kA
Yes
Yes
No/Yes
No/Yes
Three-pole in series
Three-pole in series
Both
Both
IEC 60947-2
IEC 60947-2
1 DEM/DGM Narrow 3 1600 A 1000 V/25 kA/65 kA Yes No/Yes Three-pole in series Both IEC 60947-2
DEM/DGM Narrow 3 2000 A 1000 V/25 kA/65 kA Yes No/Yes Three-pole in series Both IEC 60947-2
1 DEK/DGK Standard 3 2500 A 1000 V/25 kA/85 kA Yes No/Yes Three-pole in series Both IEC 60947-2
DEK/DGK Standard 3 3200 A 1000 V/25 kA/85 kA Yes No/Yes Three-pole in series Both IEC 60947-2
1 DEM/DGM Double narrow 6 4000 A 1000 V/25 kA/100 kA Yes No/Yes Three-pole in series Both IEC 60947-2
DEM/DGM Double narrow 6 5000 A 1000 V/25 kA/100 kA Yes No/Yes Three-pole in series Both IEC 60947-2
1 DEK/DGK Double standard 6 4000 A 1000 V/25 kA/100 kA Yes No/Yes Three-pole in series Both IEC 60947-2
DEK/DGK Double standard 6 5000 A 1000 V/25 kA/100 kA Yes No/Yes Three-pole in series Both IEC 60947-2
1 1 DE is for use in ungrounded applications; DG is for use in grounded applications.
7
1
1
1
1
1
1
1
For IEC applications, Digitrip 520i, Digitrip 520Mi, Digitrip
520MCi or Digitrip 1150i are to be ordered. These trip unit
1
model numbers carries a lower case “i” in the model
designation. This simply indicates that the trip unit complies with 1
IEC requirements in the area of ground fault (earth fault) pickup.
Ground fault pickup is limited to 1200A for UL rated devices. 1
This limitation does not apply to IEC rated devices.
The different models within the family provide for increasing 1
levels of protection and feature options for coordination,
information, diagnostics, and communications: 1
Table 11. Digitrip functionality – Summary of key features and capabilities 1
Functions 520 520M 1 520MC 1 1150+ 1
The trip units themselves are self-powered; no external power Diagram of typical Magnum current sensing, processing, and
is required to operate the protective systems. Current signal tripping system
levels and the control power are derived from integrally mounted
toroidal wound current sensors. The use of toroidal wound
sensors reduces magnetizing currents, resulting in improved Cutler-Hammer
All three parts of the tripping system are discussed in this Toroidal
section. For additional information pertaining to the different trip current
unit models available for all Magnum circuit breakers, refer to sensor
the specific trip unit instructional leaflet (IL70C1036 for 1150+
models and IL70C1037 for 520 models).
7 Typical Magnum DS
Common Digitrip trip unit features A 01 02 03
circuit breaker
1 All Digitrip RMS models offer a wide array of common features. B
These common features ensure unsurpassed versatility, no C Sensors
1 matter which trip unit model is selected. N
G
A B C
• Current Sensors: Three toroidal wound current sensors Note: Alternate ground locations
1 are installed at the rear of the circuit breaker on the lower N may be required to meet installation
terminals. The sensors produce an output current proportional requirements.
1 to the load current. Under preselected conditions of current
magnitude and time, the sensors furnish the trip unit with a
1 •
signal and the energy required to trip the circuit breaker.
Rating Plug: All Magnum circuit breakers use a fixed type
rating plug. The current rating (also known as In) of the rating Current sensors (rear view)
1 plug must match the current rating of the integrally mounted
current sensors. As a safety feature, if the rating plug is
1 removed from the trip unit, the circuit breaker will trip if it sees
load current. There is a viewing window on the back of the
1 breaker that displays the current rating of the installed rating
plug. The rating plug performs several functions:
1 1. It tells the trip unit the rating of the current sensors.
2. It determines the maximum instantaneous setting,
1 which is a function of the current sensor rating.
3. Identifies the trip unit as a UL rated device or
1 IEC rated device. 1
• Intuitive operator interface
1 • Interchangeable models
Self powered device
1 •
• Hand held functional test kit (Digitrip RMS 1150 Model also
has integral testing capabilities)
1 • Status LED: A green light emitting diode (LED), labeled Status,
blinks approximately once each second to indicate that the trip
1 unit is operating normally. This Status LED will also blink at a
faster rate if the Digitrip is in a pickup, or overload, mode.
1 • Cause of trip LED: A red LED on the face of the trip unit
flashes red next to the protection feature to indicate the
1 cause for an automatic trip operation, for example earth fault,
overload or short circuit. A battery in the trip unit maintains the
1 trip indication until the Reset/Battery Test button is pushed. The
battery is satisfactory if its LED lights green when the Battery
Check button is pushed.
1 • Security cover: A tamper-proof Plexiglas® cover sits on the
front of the circuit breaker over the trip unit. The cover is
1 held in place by two cover screws. Security is insured by the
insertion of a standard meter seal through the holes in both of
1 the cover retention screws.
NNote: Refer to the Table 12 for specific programming details associated
with a particular UL or IEC rated Digitrip model.
1 The National Electrical Code (NEC) requires that the maximum ground
fault pickup value not exceed 1200A for UL rated breakers. IEC rated
breakers do not have this current limitation.
Digitrip 520MC
Digitrip 520MC includes all • LDPU Long Delay Pick-up The 520MC is ideally suited for Digitrip 520MC
the features of the Digitrip • SDT Short Delay Trip application on feeder breakers
520M plus an ampere-based • INST Instantaneous Trip and can be used in tandem
communications capability with mains and tie breakers
• GNDT Ground Fault Trip
and the Arc-flash Reduction that are equipped with the
Maintenance System (ARMS). • PLUG Plug Trip full metering and monitoring
The additional features are the • MCR Making Current capability of the 1150+ trip
following: Release unit. The communication
• Communications functions • OTEMP Over Temperature feature requires customer
and data: • HL High Load (LSI only) supplied auxiliary power and
the Ground (Earth) Alarm/
• Transmit LED (Red) • Arc-flash Reduction Power Supply Module in order
indicates trip unit Maintenance System to function.
7 transmitting INCOM signal (ARMS) Functionality- On/
• Device Settable INCOM Off Pickup Levels NNote: Refer to pictures and/or
1 communication Address
from 001 to 999
NNote: Ground (Earth) Alarm/Power
graphics in this section for
additional information and/or
Supply Module is supplied as assistance.
hexadecimal
1 • Bkr Status (Open, Closed,
standard to power trip unit
communications functions. Click here or search
Tripped)
1 • PH1 Phase 1 (A) Current
The 520MC is designed for
applications where some
for ‘70C1037’ on
www.eaton.com,
communication capability of for more detailed
1 • PH2 Phase 2 (B) Current
load and status is required. information on Magnum
• PH3 Phase 3 (C) Current
The 520MC trip unit Digitrip 520, 520M, and
1 • PH4 Neutral Current
communicates current-based 520MC Digitrip trip units
• PH5 Ground Current information and breaker status.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Digitrip 1150+
The Digitrip 1150+ trip unit • Adjustable Instantaneous Contacts Digitrip 1150+
offers advanced protection Pick-up with • Breaker Control (Remote
and power monitoring Instantaneous Off Setting Open & Close via
including harmonics, • Adjustable Ground Fault Communications)
breaker health, waveform Pick-up / Delay (Trip or • Operations Counter
capture, and advanced Alarm) • Test Port with Cover to
communications options. • Undervoltage and receive Digitrip Hand Held
It eliminates the need for Overvoltage Protection Tester
separate metering packages (Trip or Alarm)
which saves cost, space and • Power Receptacle for
• Underfrequency and Auxiliary Power Module to
installation effort. Extensive
Overfrequency Protection power up Trip Unit when
operational information is
(Trip or Alarm) Breaker in Disconnect or
available across the INCOM
communications for increased • Reverse Power (Trip) Remove position 7
remote monitoring and control • Voltage Unbalance • Integral Self-Test
capability. The Digitrip 1150+ Protection (Trip or Alarm) • Accessory Bus for 1
includes the Eaton's Arc- • Phase Rotation (Alarm) Additional Programmable
flash Reduction Maintenance
System (ARMS). For a
• Long Time (Thermal) Contacts 1
Memory Trip • Battery Included to Power
complete discussion of Digitrip
1150+ Trip Unit capabilities, • Overtemperature Trip when LEDs 1
refer to its instruction leaflet the temperature exceeds • Reset/Battery Test
IL70C1036. 85°C Pushbutton 1
• Power and Energy Metering • Communications
The following is a summary of
the 1150+ product features:
Display: Functions and Data 1
• Current (±1% 3-phase,
NNote: The Digitrip 1150+
LSI, LSIG and LSIA
•
Protection
neutral and ground) family of trip units incorporates 1
• Voltage L-L (±1%) two microprocessors in their
Arc-flash Reduction
•
Maintenance System
• Frequency (±0.05 Hz)
design. One processor is devoted
fully to the task of current 1
• Power & Energy (±2%) protection functions. The second
(ARMS) functionality- On/Off
Pickup Levels • Kilowatts (kW) microprocessor provides the
voltage protection, display,
1
• 24 Character, 3-line Digital • Kilowatt Hours (kWH)
communications, metering,
LED Display • Kilovoltamperes (kVAR) harmonic calculations, alarming, 1
• Unit Status LED (Green) • Power Factor and auxiliary relay functions.
Indicator • kVA Hours
These advanced features and the
communications capability require
1
• Programmable Protective • Fixed 15 Minute Demand that auxiliary power be provided by
Settings: for kW, kVAR & kVA the customer to the circuit breaker 1
• I2t and I4t Curves Power Relay Module.
• Sliding 15 Minute
• Adjustable Long Time and Demand for kW or kVA
Click here or search for
1
Short Time Pick-up / Delay • Power Quality and Breaker ‘70C1036’ on www.eaton.
• Moderately Inverse, Very Health Metering and com, for more detailed 1
Inverse and Extremely Monitoring: information on Magnum
Inverse IEEE Curves • Waveform Capture Digitrip 1150 trip units 1
• IEC Curves • % Total Harmonic
• Neutral Protection (Model
LSIG and LSIA Trip Unit)
Distortion 1
• Programmable Alarm
1
1
1
1
1
1
1
1
Table 12. Digitrip trip units for Magnum DS and SB ANSI/UL rated power circuit breaker
7
Trip unit type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ 1
1 Neutral protection (N) Model LSI only Model LSI only Model LSI only Model LSI only
System diagnostics
1 Cause of trip LEDs Yes Yes Yes Yes
Magnitude of trip No Yes Yes Yes
1 information
Remote signal No Yes Yes Yes
contacts
1 Programmable No No No Yes
contacts
1 Electronic operations No No No Yes
counter
1 1 Over and undervoltage alarm or trip, over and underfrequency alarm or trip, voltage unbalance a larm or trip, reverse power trip and phase rotation
alarm are included.
1 2 1200A maximum ground fault setting per UL/NEC.
Table 12. Digitrip trip units for Magnum DS and SB ANSI/UL rated power circuit breaker continued
Trip unit type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ 1
System monitoring
Digital display No 4-Character LCD 4-Character LCD 24-Character LED
7
Current (%) full scale
sensor
No Yes +/– 2% Yes +/– 2% Yes +/– 1% 1
Voltage (%) L to L
Power and energy (%)
No
No
No
No
No
No
Yes +/– 1%
Yes +/– 2%
1
Apparent power kVA
and demand
No No No Yes 1
Reactive power kVAR
Power factor
No
No
No
No
No
No
Yes
Yes
1
Crest factor No No No Yes 1
System communications
Type — INCOM/PowerNet/
Modbus 2 /
INCOM/PowerNet/
TripLink 2 /
1
PROFIBUS 2 Modbus/PROFIBUS
1
2
INCOM network
Typical IBM
compatible
computer
Breaker interface
Monitor (BIM II)
2 4 See view A 7
Twisted Pair.
3
No. 18 AWG 1
Cutoff shield or connect to
Eaton CONI card unused customer terminal— 1
Do not ground
1 1
Typical Magnum 1 4 Res.
circuit breaker with Baud rate
1
Digitrip trip unit 1200 or 9600
(Y) 1
1
001 002
2
3-Digit
1
3
(BL) 4
INCOM address
View A
1
1
1. Refer to master circuit breaker connection diagrams
in Appendix C.
Notice: 100 ohm 1/2W
terminating resistor required
1
on network even if network is
2. Modular telephone connector, Type RJ11, supplied unused 1
by user.
• Auxiliary switch The red flag can be reset by manually pushing it back in.
An auxiliary switch is an optional device providing remote The breaker can be reclosed, even if the flag is not reset. An
electrical indication if the circuit breaker is open or closed. optional Overcurrent Trip Switch (OTS) is available should an
Up to three auxiliary switches can be mounted in one breaker. electrical lockout be required on an overcurrent trip condition.
Each switch has two normally open (“A”) and two normally If the trip unit trips the breaker on an overcurrent condition:
closed (“B”) contacts for a total of 12 available contacts. • Red mechanical trip flag indicator pops out
• OTS contacts change state
Table 17. Auxiliary switch, overcurrent trip switch, and
cell switch contact ratings The OTS Switch is reset by manually pushing in the red trip
flag. When the trip flag is reset, the OTS switch contacts
Control voltages Contact rating inductive load (amperes) return to their normal state.
250 Vac 10
125 Vdc 0.5
250 Vdc 0.25
8
1
1
1
1
1
Mechanical trip
1 indicator
Mechanical accessories
There are numerous optional mechanical type accessories:
1. Operations Counter
2. Off Key Lock
3. Cassette Lock
4. Pushbutton Cover
5. Prevent Close Cover
6. Lockout Cover
7. Cassette Safety Shutters
8. Cassette Cell Switch
9. Door Escutcheon
10. Waterproof Cover 8
11. Mechanical Interlock
• Operations counter 1
The operations counter is a mechanical device used to provide
Motor operator kit a record of the number of circuit operations. It is mounted
1
in the lower right portion of the breaker and can be viewed
through the front cover. 1
• Off key lock 1
The off key lock secures the breaker in the OFF position. It is
mounted in the lower right portion of the breaker and can be
viewed through the front cover. The customer supplies the key 1
lock. The provisions available are for Kirk, Castell, Ronis, CES or
Superior. 1
1
Operations
counter 1
1
OFF 1
key lock
1
1
Motor operator installed in narrow frame circuit breaker 1
1
1
1
Cover mounted key lock and operations counter
1
1
1
1
1
1
8
1
1
1
1
1
1
1 Cassette-mounted key lock
1
1
8
1
1
Cell switch (drawout position indicator) unmounted 1
Door escutcheon and gasket
1
• IP55 waterproof cover 1
A hinged dome-shaped waterproof cover attaches to the
metal compartment door to provide waterproof protection for 1
the breaker.
1
1
1
1
1
Cell switches mounted on cassette
1
1
1
1
1
IP55 waterproof cover 1
1
1
1
1
1
• Mechanical interlock
A family of mechanical interlocks are available to interlock the
closing of two or three Magnum breakers. The mechanical
interlock holds one or more breakers tripped (prevents closure)
when others are closed. A lever assembly is mounted on
each breaker, which interfaces with the pole shaft and the
tripper bar. The lever assemblies are interconnected with either
cables or rods, depending upon the relative orientation of the
breakers. Rods can be used only when the breakers to be
interlocked are vertically stacked. Cables can be used for any
orientation of the breakers. Mechanical interlocks are available
for both fixed and drawout breakers, and in both two-way and
three-way versions.
8
1
1
1
1
1
1
1
1
1
1
1
1
1
Cassette-mounted two-way cable interlock
1
1
1
1
1
1
1
• Altitude factors Table 26. IEC Bus Bar sizes and quantities
All Magnum breakers, including IEC rated breakers, can Maximum
be applied at their full voltage and current ratings up to a service Circuit
current, breaker
maximum altitude of 2000 meters above sea level. When amperes frame
(40 oC (MWN Recommended Bus Bar
installed at higher altitudes, the ratings are subject to ambient) & MWI) quantities and sizes
correction factors. Short circuit current is not affected as long
(in) (mm)
as the voltage is rated in accordance with the information
shown in the table. 800 08 (2) 5x50 (1) .25x3.0
1000 10 (2) 5x60 (2) .25x2.0
Table 24. Altitude rating factors 1250 12 (2) 5x80 (2) .25x3.0
Altitude Voltage Current 1600 16 (2) 5x100 (2) .25x3.0
(meters) correction correction
2000 20 (3) 5x100 (3) .25x3.0
2000 1.000 1.000
2500 25 (4) 5x100 (4) .25x3.0
2150 0.989 0.998
3200 32 (3) 10x100 (3) .25x6
2300 0.976 0.995
4000 40 (4) 10x100 (4) .25x6
2450 0.963 0.993
5000 50 (5) 10x100 (5) .25x6
2600 0.950 0.990
6300 1 63 (6) 10x100 (6) .25x6
9 2750 0.933 0.987
1 6300A only available in Magnum IEC frame
2900 0.917 0.983
1 3050 0.900 0.980 Example 1
3200 0.883 0.977
1 3350 0.867 0.973
3500 0.850 0.970
1 3650 0.833 0.967 (T)
1 Table 25. ANSI Bus Bar sizes and quantities (0.25 in)
Circuit
1 Maximum
services
current,
breaker
frame
(MDS,
amperes MDN,
1 (40 oC
ambient)
SBS,
SBN)
Recommended Bus Bar
quantities and sizes
(in) (mm) in)
(3
1 800 08 (1) .25x3.0 (2) 5x50 Illustration of 2.25in by 3in Bus
1 1000
1200
10
12
(2) .25x2.0
(2) .25x3.0
(2) 5x60
(2) 5x80
Bars stacked to carry 1600 amperes
)
m
m
(60
Illustration of 2.25mm by 60mm Bus
Bars stacked to carry 800 amperes
1
By utilizing this reference Magnum renewal or Time current curves Magnum instruction leaflets
1 list above, you can find many replacement parts (for field replacement
PDF, .dwg, or .stp drawings. Click here or visit www.eaton.
accessories)
1 To access, please visit Click here or visit
www.eaton.com/magnum
com/tcc and select 'Low
Voltage and Medium Voltage
www.eaton.com/magnum, Visit www.eaton.com/
and search ‘Magnum Renewal Power Breakers' from the
1 click on Magnum DS/SB, and
review the 'Drawings' tab. Parts’, for a comprehensive dropdown.
magnum, click on Magnum
DS/SB, and review the
list of renewal or field Wiring diagrams Instructions section on
1 Or use the drawing number
as a search item on
installable parts. the 'Documents' tab.
Search ‘Magnum User
www.eaton.com
1 Manual’ on www.eaton.com,
for up to date Wiring Diagrams
1 on the Magnum IB
(Installation Bulletin).
1
1
Table of contents
800-2000A Narrow frame Cassette (Mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
800-2000A Narrow frame Cassette (Overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
800-2000A Narrow frame Cassette (Accessory dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
800-2000A Narrow frame Cassette (3-pole stab and stab bracing). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
800-2000A Narrow frame Cassette (Door cutout and breaker positions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
800-2000A Narrow frame Cassette (Front mount terminal locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
800-2000A Narrow frame fixed breaker (Overall dimensions and mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
800-2000A Narrow frame fixed breaker (Door cutout and vertical terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
800-2000A Narrow frame fixed breaker (Enclosure and horizontal terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
800-2000A Narrow frame fixed breaker (Optional arc hood). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
800-2000A Narrow frame fixed breaker (Optional front mount terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
800-2000A MDSL Cassette overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
800-2000A MDSL Cassette 3-pole mounting locations dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
1 800-2000A MDSL Cassette 3-pole vertical stab dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
11 800-2000A MDSL Cassette door cutout and breaker positions dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
800-2000A MDSL Cassette accessory dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
1 800-3200A Standard frame universal Cassette (3-pole mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
1 800-3200A Standard frame universal Cassette (Overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
800-3200A Standard frame universal Cassette (Accessory dimensions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
1 800-3200A Standard frame universal Cassette (3-pole vertical stab) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
1 800-3200A Standard frame universal Cassette (3-pole horizontal stab) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
800-3200A Standard frame universal Cassette (Door cutout and breaker positions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
1 800-3200A Standard frame universal Cassette (4-pole mounting locations and overall dimensions). . . . . . . . . . . . . . . . . . . . . . 90
800-3200A Standard frame universal Cassette (4-pole accessory information and vertical stabs). . . . . . . . . . . . . . . . . . . . . . . . 91
1
800-3200A Standard frame universal Cassette (4-pole horizontal stabs and front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
1 800-3200A Standard frame basic Cassette (3-pole mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
800-3200A Standard frame basic Cassette (Overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
1
800-3200A Standard frame basic Cassette (Accessory dimensions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
1 800-3200A Standard frame basic Cassette (3-pole stab and stab bracing). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
800-3200A Standard frame basic Cassette (Door cutout and breaker positions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
1 800-3200A Standard frame Cassette (3-pole mounting locations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
1 800-3200A Standard frame Cassette (Overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
800-3200A Standard frame Cassette (Accessory dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
1 800-3200A Standard frame Cassette (3-pole horizontal stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
1 800-3200A Standard frame Cassette (Door cutout and breaker positions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
800-3200A Standard frame Cassette (4-pole mounting locations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
1 800-3200A Standard frame Cassette (4-pole horizontal stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
1 800-1600A Standard frame fixed breaker (Overall dimensions and mounting locations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
800-1600A Standard frame fixed breaker (Door cutout and vertical terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
1 800-1600A Standard frame fixed breaker (Enclosure and horizontal terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
800-1600A Standard frame fixed breaker (Optional front mount terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
2000A Standard frame fixed breaker (Overall dimensions and mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
2000A Standard frame fixed breaker (Door cutout and vertical terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
2000A Standard frame fixed breaker (Enclosure and horizontal terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
2000A Standard frame fixed breaker (Optional front mount terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
2500-3200A Standard frame fixed breaker (Overall dimensions and mounting locations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
2500-3200A Standard frame fixed breaker (Door cutout and vertical terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
2500-3200A Standard frame fixed breaker (Enclosure and horizontal terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
2500-3200A Standard frame fixed breaker (Optional front mount terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
4000A Double narrow frame Cassette (3-pole mounting locations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
4000A Double narrow frame Cassette (3-pole overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
4000A Double narrow frame Cassette (Accessory dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
4000A Double narrow frame Cassette (Vertical stabs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
4000A Double narrow frame Cassette (Horizontal stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
4000A Double narrow frame Cassette (Door cutout and breaker positions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
4000A Double narrow frame Cassette (4-pole mounting locations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
4000A Double narrow frame Cassette (4-pole overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
4000A Double narrow frame fixed breaker (Overall dimensions and door cutout). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 11
4000A Double narrow frame fixed breaker (3-pole vertical stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
4000A Double narrow frame fixed breaker (4-pole horizontal stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
1
4000A Double narrow frame fixed breaker (4-pole vertical stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 1
4000-5000A Double-wide frame universal Cassette (3-pole mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
4000-5000A Double-wide frame universal Cassette (Overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
1
4000-5000A Double-wide frame universal Cassette (Accessory dimensions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 1
4000-5000A Double-wide frame universal Cassette (3-pole vertical stabs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
4000-5000A Double-wide frame universal Cassette (3-pole horizontal stabs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 1
4000-5000A Double-wide frame universal Cassette (Door cutout and breaker positions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134 1
4000-5000A Double-wide frame universal Cassette (4-pole mounting locations and overall dimensions). . . . . . . . . . . . . . . . . 135
4000-5000A Double-wide frame universal Cassette (4-pole accessory information and vertical stabs). . . . . . . . . . . . . . . . . . . 136 1
4000-5000A Double-wide frame universal Cassette (4-pole horizontal stabs and front view) . . . . . . . . . . . . . . . . . . . . . . . . . . 137
1
4000-6300A Double-wide frame basic Cassette (3-pole mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
4000-6300A Double-wide frame basic Cassette (Overall dimensions). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 1
4000-6300A Double-wide frame basic Cassette (Accessory dimensions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
1
4000-6300A Double-wide frame basic Cassette (3-pole stabs and stab bracing). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
4000-6300A Double-wide frame basic Cassette (Door cutout and breaker positions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 1
4000-6300A Double-wide frame standard Cassette (3-pole mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
4000-6300A Double-wide frame standard Cassette (Overall dimensions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
1
4000-6300A Double-wide frame standard Cassette (Accessory dimensions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 1
4000-6300A Double-wide frame standard Cassette (Horizontal stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
4000-6300A Double-wide frame standard Cassette (Door cutout and breaker positions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
1
4000-6300A Double-wide frame standard Cassette (4-pole mounting locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 1
4000-6300A Double-wide frame standard Cassette (4-pole horizontal stabs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
4000-6300A Double-wide frame fixed breaker (Overall dimensions and mounting locations) . . . . . . . . . . . . . . . . . . . . . . . . . . 150 1
4000-6300A Double-wide frame fixed breaker (Door cutout and vertical terminals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151 1
4000-6300A Double-wide frame fixed breaker (Enclosure and horizontal terminals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
1
1
Document references
1 2C12866 Levering mechanism assembly for replacement parts kit in Magnum low voltage draw out circuit breakers
2C12867 Levering door mechanism replacement parts kit in drawout Magnum low voltage circuit breakers
1 2C12870 Front mounted narrow terminal kits on Magnum (IZM) low voltage circuit breakers and Cassettes
2C12894 Door escutcheon with gasket for Magnum (IZM) low voltage circuit breakers
1 2C12895 Pushbutton cover field option kit for Magnum (IZM) low voltage circuit breakers
2C12896 Instructions for installation of 2A10800G01 and 2A10800G02, arc hood barrier kit (1000V)
1 2C12896 Instructions for installation of 2A10800G11 (3-Pole) and 2A10800G12 (4-pole), fixed arc hood barrier kit
2C12896 Magnum low voltage draw out circuit breaker Cassette arc hood barrier kit 1100V
1 2C12897 Drawout 2500-3200A breaker vertical adapter replacement
2C12897 Vertical adapter kit for Magnum (IZM) fixed low voltage circuit breakers or IEC Cassettes
1 2C12899 Draw out breaker standard/double frame rejection bracket replacement kit
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 4. 800-2000A Narrow frame Cassette (3-pole stab and stab bracing)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 5. 800-2000A Narrow frame Cassette (Door cutout and breaker positions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 6. 800-2000A Narrow frame Cassette (Front mount terminal locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 7. 800-2000A Narrow frame fixed breaker (Overall dimensions and mounting locations)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 8. 800-2000A Narrow frame fixed breaker (Door cutout and vertical terminals)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 9. 800-2000A Narrow frame fixed breaker (Enclosure and horizontal terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 10. 800-2000A Narrow frame fixed breaker (Optional arc hood)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 11. 800-2000A Narrow frame fixed breaker (Optional front mount terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 15. 800-2000A MDSL Cassette door cutout and breaker positions dimensions
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 17. 800-3200A Standard frame universal Cassette (3-pole mounting locations)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 20. 800-3200A Standard frame universal Cassette (3-pole vertical stab)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 21. 800-3200A Standard frame universal Cassette (3-pole horizontal stab)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 22. 800-3200A Standard frame universal Cassette (Door cutout and breaker positions)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 23. 800-3200A Standard frame universal Cassette (4-pole mounting locations and overall dimensions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 24. 800-3200A Standard frame universal Cassette (4-pole accessory information and vertical stabs)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 25. 800-3200A Standard frame universal Cassette (4-pole horizontal stabs and front view)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 26. 800-3200A Standard frame basic Cassette (3-pole mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 29. 800-3200A Standard frame basic Cassette (3-pole stab and stab bracing)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 30. 800-3200A Standard frame basic Cassette (Door cutout and breaker positions)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 35. 800-3200A Standard frame Cassette (Door cutout and breaker positions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 38. 800-1600A Standard frame fixed breaker (Overall dimensions and mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 39. 800-1600A Standard frame fixed breaker (Door cutout and vertical terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 40. 800-1600A Standard frame fixed breaker (Enclosure and horizontal terminals)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 41. 800-1600A Standard frame fixed breaker (Optional front mount terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 42. 2000A Standard frame fixed breaker (Overall dimensions and mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 43. 2000A Standard frame fixed breaker (Door cutout and vertical terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 44. 2000A Standard frame fixed breaker (Enclosure and horizontal terminals)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 45. 2000A Standard frame fixed breaker (Optional front mount terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 46. 2500-3200A Standard frame fixed breaker (Overall dimensions and mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 47. 2500-3200A Standard frame fixed breaker (Door cutout and vertical terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 48. 2500-3200A Standard frame fixed breaker (Enclosure and horizontal terminals)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 49. 2500-3200A Standard frame fixed breaker (Optional front mount terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 50. 4000A Double narrow frame Cassette (3-pole mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 51. 4000A Double narrow frame Cassette (3-pole overall dimensions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 55. 4000A Double narrow frame Cassette (Door cutout and breaker positions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 56. 4000A Double narrow frame Cassette (4-pole mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 57. 4000A Double narrow frame Cassette (4-pole overall dimensions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 58. 4000A Double narrow frame fixed breaker (Overall dimensions and door cutout)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 59. 4000A Double narrow frame fixed breaker (3-pole vertical stabs)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 60. 4000A Double narrow frame fixed breaker (4-pole horizontal stabs)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 61. 4000A Double narrow frame fixed breaker (4-pole vertical stabs)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 62. 4000-5000A Double-wide frame universal Cassette (3-pole mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 65. 4000-5000A Double-wide frame universal Cassette (3-pole vertical stabs)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 66. 4000-5000A Double-wide frame universal Cassette (3-pole horizontal stabs)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 67. 4000-5000A Double-wide frame universal Cassette (Door cutout and breaker positions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 68. 4000-5000A Double-wide frame universal Cassette (4-pole mounting locations and overall dimensions)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 69. 4000-5000A Double-wide frame universal Cassette (4-pole accessory information and vertical stabs)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 70. 4000-5000A Double-wide frame universal Cassette (4-pole horizontal stabs and front view)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 71. 4000-6300A Double-wide frame basic Cassette (3-pole mounting locations)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 74. 4000-6300A Double-wide frame basic Cassette (3-pole stabs and stab bracing)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 75. 4000-6300A Double-wide frame basic Cassette (Door cutout and breaker positions)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 76. 4000-6300A Double-wide frame standard Cassette (3-pole mounting locations)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 80. 4000-6300A Double-wide frame standard Cassette (Door cutout and breaker positions)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 81. 4000-6300A Double-wide frame standard Cassette (4-pole mounting locations)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 82. 4000-6300A Double-wide frame standard Cassette (4-pole horizontal stabs)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 83. 4000-6300A Double-wide frame fixed breaker (Overall dimensions and mounting locations)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 84. 4000-6300A Double-wide frame fixed breaker (Door cutout and vertical terminals)
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Figure 85. 4000-6300A Double-wide frame fixed breaker (Enclosure and horizontal terminals)
1
11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
© 2016 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. CA013002EN / CSSC-1701-3857 All other trademarks are property
April 2017 of their respective owners.