CT RATIO SELECTION CALCULATION
Rated Power 25 MW
Rated Voltage 11 KV
__________________________________________________________________________________________________________________________________
Format No.: DDIT3009
REV./Date : A/08.12.2005
Page: Document No. Rev.No.
3 of 3 Information #1 0
PROTECTION CLASS CT DETAIL
Since, PS class CT’s are selected for protection purpose, there is no need for burden calculation at rated conditions;
however it should be ensured that at plant fault level, CT’s do not saturate. Hence the knee-point voltage of CT’s shall
be designed as follows:
The Rct value is subject to change and shall be confirmed by the CT manufacturer and hence the value of Vk shall be
accordingly governed by the above formulae. In any case, the CT shall be designed to have Vk such that it does not
saturate at system fault level of 40 kA for 3 Seconds.