Fire Water Spray Systems Principle Ads by Google

 S Bharadwaj Reddy  Leave a comment

Ads by Google
Like 0 Tweet Share
Share 2 Share 49
Ceiling Water Damage
A Water Spray System, for Fire Protection a di erent variant of Fire Sprinkler System. Such a system is used in places where re is
likely to rapidly spread out of control, within a short duration. Examples of such places, where Water Spray System, for Fire Storage Tank Water
Protection are required are; Transformers, Compressors, Condensate Storage Tanks, LPG bullets and Combustible fuels.
Plant Water

Is it compulsory to have/install, Water Spray System, for Fire Protection? Basement Water

It depends on the type of system, equipment or in ammable liquid, in use. If however, you are using any substance that are highly
in ammable, combustible or catch re and spread quickly. This system is a mandate for you. Categories

How Water Spray System, for Fire Protection, Works? Select Category

Let us take an example to be more speci c and clear. In an oil cooled transformer, the oil is likely to catch re after a certain Ads by Google

temperate is exceeded and instantly the entire transformer will catch re and burn from all sides; even though the transformer is
Ceiling Water Damage
made up of metal. To avoid this, kind re, we use Water Spray System.
Storage Tank Water
Here, there may be multiple metal rings of detectors, a detector is nothing but a temperature sensing element. This detector ring
In Water
is placed next to the most likely sots where the temperature is about to exceed or re is about to take place. Also the, entire
transformer is surrounded by multiple sprays, at multiple levels. A spray is nothing, but a sprinkler without the temperature Spray Foam System
sensing, bulb.

When the re does take place, the detector ring detects this; and gives the signal to the deluge valve or all the sprinkler
surrounding the transformer to start all at once. Hence the entire transformer is ushed with water, to cool it down.

There are two variants of Water Spray System, for Fire Protection:

1) High Velocity Water Spray Systems (HVWS)


2) Medium Velocity Water Spray Systems (MVWS)

High Velocity Water Spray Systems (HVWS):

HVWS, is generally used in oil based systems, having high ash points. The velocity of the water sprays, hitting the system under
re is critical for successful re extinguishing action.
Like our FB Page – Get Updates
Medium Velocity Water Spray Systems (MVWS):
InstrumentationTools
67,478 likes
MVWS, is generally used in oil based systems, having low ash points. The velocity of the water sprays, hitting the system under
re, if it is high, might actually spread the re, and not extinguish it. Hence, the velocity of the water has to be in range.
Like Page Learn More

Advantages of Water Spray Systems

Extinguishes res quickly and prevents res from spreading over a large area. Latest Comments
Minimises the damage caused by re and reduces downtimes, protects the future of your business.
ahmed
High exibility in design and implementation
thanks very much...
Reduces fumes and binds contaminants.
Allows large open areas and thus a more exible use of the premises. Kaushikpatel
Tx bro.. Pleash tel me bro.. FF out put...
Uses water, a natural re extinguishing agent that is available in unlimited quantities at a very low price.
Usama Iskander
Dear Sir i need a Fisher Valve CASCADE
Medium Velocity Water Spray System (MVWS):
CONTROL...

Salah
Fires on Hydrocarbon are more frequent due to the volatility of the hydrocarbon and its property to not dissolve with water and
Very clear and simple explanation, perfect,
lighter than water the re extinguishing of hydrocarbon re with water is not possible. In case of re on Hydrocarbon if the water thank you...
isALL ANIMATION
sprayed, BASICS
due to the light 
weight MEASUREMENT 
of the hydrocarbon CONTROL
it will oat SYSTEMS 
on the water Q & Areignite
and  ELECTRONICS
them to re andELECTRICAL  TOOLS
due to the speed of MORE  
water the re will travel from one place to other place. However for these plant water spray system can be provided as exposure Ashik
protection. That means if any plant is under re the plants nearby shall be kept cool with the water spray system, while plant Ji super keep it up...

under re shall be applied foam. Hoàng


dear sir, I consider if bumps also happen
in case we have PL...
Hence in this case where plant is using hydrocarbon the exposure should be protected with water spray system designed as per
NFPA 15. KESAVA
REALLY THANKS A LOT TO THIS BHARDWAJ
REDDY.BEACAUSE OF HIM S...
This system is mostly used for the protection of the following

Expander & Sale Gas Compressors


O Gas Compressors etc…

Quartzoid Bulb Sprinklers (Q. B. S.) Detection is used to for detection of re which will be connected to deluge valve for auto
operation of the system. Q B Sprinklers shall be of 68 Deg or 79 Deg C or any other temperature depending upon the ambient
temperature of the location of the plant.

For electronic automatic operation of the system the deluge valve shall be provided with pressure sensors, temperature sensors
and annunciation panel.

Operation
Inst Tools Android App
In case of re the Quartzoid Bulb sprinkler shall burst due to heat which allow water in the detection pipe to drain out and in
process allow the Deluge valve to open fully. As soon as the Deluge valve opens the water shall ow through the piping to ow
water to all water spray nozzles mounted on the ceiling of the plant. The water shall be sprayed in solid conical spray pattern to
cover entire area of the plant oor so that the equipment installed shall be kept cool to avoid heat radiation and further ignition of
re.

The re shall be control with the help of the water spray system. Inst Tools IOS App

The indication of operation of the system shall be available on the control panel with Alarming Siren.

Advantages of M.V. Water Spray System

Entire area is ooded with foam, hence very useful for re ghting in hazardous area, plant, storage tanks, etc. where manual
approach is di cult. Language Translate :
Very quick in response.
The re losses is kept low as the area under re get foam blanket and also cooling due to water contain and so chances of Select Language

spreading re is negligible.

High Velocity Water Spray System (HVMS):

High Velocity water spray systems are installed to extinguish res involving liquids with ash points of 65 C or higher. Three
principles of extinguishment are employed in the system – emulsi cation, cooling and smothering. The result of applying these
principles is to extinguish the re within a few seconds.

This system is mostly used for the protection of the following

Transformers, oil lled equipments of power stations


Turbo-alternators and other
Oil red boiler rooms, oil quenching tanks.

Transformer protection shall contemplate on essentially complete impingement on all exterior surfaces except the underside,
which may be protected by horizontal projection.

Transformer present particular design problems for Water spray protection, primarily due to their irregular shape and necessary
clearances to be provided for the high voltage equipment. Generally speaking, there is much more interference with the water
ow on the sides of the transformer than at their top. Due to this reason the protection usually involves a large number of small
capacity projectors than a few bigger ones. Often it will be necessary to put more water on the transformer than required to
achieve complete impingement and total envelopment.

All system components shall be so located as to maintain minimum clearances from live parts.

“Clearance” is the air distance between Water Spray Equipment including piping nozzles and detectors and un-insulated live
electrical components at other than ground potential. The minimum clearance is 900 mm under normal conditions. During the
operation of Water Spray system, they are intended for use as safe.

ALLsprayers
The ANIMATION BASICS in
shall be installed
 MEASUREMENT
rows
 CONTROL
around the transformer andSYSTEMS
 Q & A  . ELECTRONICS
above oil condenser
 ELECTRICAL  TOOLS MORE  
Quartzoid Bulb Sprinklers (Q. B. S.) Detection is used to for detection of re which will be connected to deluge valve for auto
operation of the system. Q B Sprinklers shall be of 68 Deg or 79 Deg C or other temperatures depending upon the ambient
temperature of the location of the plant.

Operation

Also See: Click Here for Deluge Valve Animation

A Deluge system (automatic High Velocity Water Spray System) is a xed re protection system, which totally oods an area with
pressurized water through a system of piping with open nozzles & sprinklers. The system piping is empty until the controlling valve
is activated by a hydraulic or other types of release systems. Deluge valve has an inlet, outlet & priming chamber. The inlet &
outlet are separated from the priming chamber by the valve chamber & diaphragm. In the” SET “position, pressure is applied to
the priming chamber through a restricted prime line .The pressure is trapped in the priming chamber & holds the clapper on the
seat due to the di erential area. When the pressure is released from priming chamber faster than it is supplied through the
restricted priming chamber line, the clapper move & allow the inlet water supply to ow through the outlet into the system and
associated alarm device.

Water spray System are installed to control re & to provide cooling &/or exposure protection to such risks where extinguisher is
always not possible or even desirable e.g. re involving ammable uids having ash points below 650 C (1500 F).

In case of re the Quartzoid Bulb sprinkler shall burst at rated temperature due to heat which allow water in the detection pipe to
drain out and in process allow the Deluge valve to open fully. As soon as the Deluge valve opens the water shall ow through the
piping to ow water to all water spray nozzles mounted on the piping around the transformer. The water shall be sprayed in
Hollow conical spray pattern to cover entire area of the transformer so that the re on the transformer shall cool due to
emulsi cation as well as re get extinguish due to cutting o oxygen due to coverage pattern of the nozzle.

The re shall be control and extinguished with the help of the H. V. water spray system.

The indication of operation of the system shall be available on the control panel with Alarming Siren.

Advantages of HM.V. Water Spray System

Entire Transformer is ooded with water, which extinguish re at earliest as well as avoid further destruction.
Very quick in response.
The re losses is kept low as the area near re get cooling due to water and so chances of spreading re is negligible
ALL ANIMATION BASICS  MEASUREMENT  CONTROL SYSTEMS  Q & A  ELECTRONICS  ELECTRICAL  TOOLS MORE  
WATER CURTAIN SYSTEM

WATER SPRAY NOZZLES

These are similar nozzles as of sprinkler but only di erence is there is no bulb used and they are having open ori ce which could
not hold water pressure.

These nozzles are having threaded inlet and de ector at outlet and tted on the pipe array as same as sprinkler. This system spray
water from all nozzles as the control valve get open and there fore the area under re receive water as well as the adjacent area
also get water and reduces the chances of spreading the re.

Block making
machine
Ad Mustafa Yontar

Book Free Demo at


Home
Ad www.kent.co.in

4-20mA Formulas
and Examples...
instrumentationtools.com

Geared for
WATER SPRAY SYSTEM Adrenaline
Ad www.firefoxbikes.com
The water spray system is basically most useful for various tanks storing hazardous liquids or chemicals.
Why Starting
Current of...
The system consist of water reservoir, a pump of suitable capacity and pressure, delivery main, and distributing pipe array, main instrumentationtools.com

control valve(known as deluge valve), water spray nozzle and heat sensing element. Difference between
Star and Delta...
In case of re the heat sensing element, mainly bulb type sprinklers burst when the rated temperature arrives and causes to open instrumentationtools.com

deluge valve due to pressure di erence. The valve oods complete main and distributed pipes and start spraying from all the Variable Frequency
water spray nozzles at a time. Drive (VFD)...
instrumentationtools.com

Smoke detector Supplier HART


Communication...
Harwest Smoke detector is popular in Euro with high quality for families
instrumentationtools.com

Ad hwsensor.com Visit Site


Allen Bradley SLC
500 PLC...
instrumentationtools.com

Smart Transmitters
LRV & URV...
instrumentationtools.com

Differences
The spray remains under operation till the deluge valve is rest manually. This is most reliable and suitable system for tank Between AC and...
protection as well as exposure protection. instrumentationtools.com

How to Do Loop
Also Read: Fire Water Sprinklers Principle Checks During...
instrumentationtools.com

Advantages of Water Spray System Zigzag


Transformers...

Entire area is ooded with water, hence very useful fore re ghting in hazardous area, basement, storage tanks, etc. instrumentationtools.com

Very quick in response.


The re losses is kept low as the area adjacent to re also get water protection and so chances of spreading re is negligible

Disadvantages of Water Spray System

As entire system get ooded with water the water damage is more.
This system needs through maintenance and periodic checking of automatic operation for reliability during re.

Facebook Twitter Print Email More 48

Your Horoscope 4-20mA Formulas and Correct Filling Weight Why Starting Current of
Prediction Examples Induction Motor is High
Instrumentation Tools Instrumentation Tools
Ad clickastro.com instrumentationtools.com Ad ChemicalQualityExchange instrumentationtools.com

Asphalt Plant For Sale Difference between Star Variable Frequency Drive HART Communication
and Delta Connections (VFD) Working Principle Tutorial Part 1
Instrumentation Tools Instrumentation Tools Instrumentation Tools
Ad NFLG instrumentationtools.com instrumentationtools.com instrumentationtools.com

ALL ANIMATION BASICS  MEASUREMENT  CONTROL SYSTEMS  Q&A  ELECTRONICS  ELECTRICAL  TOOLS MORE  

Anda mungkin juga menyukai