Anda di halaman 1dari 3

DOCUMENTO SIGNA:

HOJA DE DATOS
SIGNA-N63-PI-HD-007
DOCUMENTO eB:
PROYECTO AFE- 952
CHM-PCH-LIN-IM-011
INGENIERÍA BÁSICA Y DETALLE
LÍNEA DE PRODUCCIÓN DRO REVISION ACTUAL:

TITULO: 0
FECHA DE EMISION:
HD TRANSMISOR INDICADOR DE PRESIÓN 12/10/2014
HOJA 1 DE 2

LISTA DE MODIFICACIONES

FECHA REVISION MOTIVO PARA LA REVISION MODIFICACIONES

12/10/2014 0 Emitido para Licitacion, SIGNA SRL

Elaborado por: Revisado por: Aprobado por:


J.S.C. D.S.V. J.A.A.
FECHA 10-Dec-14 FECHA 10-Dec-14 FECHA 10-Dec-14
FIRMA FIRMA FIRMA
DOCUMENTO SIGNA:
HOJA DE DATOS
SIGNA-N63-PI-HD-007
DOCUMENTO eB:
PROYECTO AFE- 952
INGENIERÍA BÁSICA Y DETALLE CHM-PCH-LIN-IM-011
LÍNEA DE PRODUCCIÓN DRO REVISION ACTUAL:

TITULO: 0
FECHA DE EMISION:
HD TRANSMISOR INDICADOR DE PRESIÓN 12/10/2014
HOJA 2 DE 2

1 Tag. No. See Table


2 Function Record □ Digital Indicator ■ Control □ Blind □ Trans ■
Other_______________________________________________________
3 Case MFR STD ■ Nom. Size ____________ Color: MFR STD ■ Other: ______
4 Mounting Flush □ Surface □ Yoke □ Other: _________________
5 Enclosure Class General Purpose □ Weather Proof ■ Explosion Proof ■ Class I Div 1.
GENERAL
For use in Intrinsically Safe System Other ____________________
6 Power Supply DC 24 Volts
7 Chart Strip ______ Roll ______ Fold _______ Circular ________ Time Marks ___________
8 Chart Drive Speed ______________________________ Power ________________________________
9 Scales Type ________ Pressure psig Temperature ____________ Flow __________
Range 1 2 _____________ 3 ______________ 4 _____________________
10 Operatin Conditions Fluid: Natural gas Norm Temp Range: 80º - 100º F Pressure Range: 1324 psig
PROCESS 11 Desing Conditios Max Temperature: 190º F Max. Pressure: 1334 psig
12 Site Conditions Ambient Temperature : 30º -62º F Site Elevation: 461 msnm
13 Transmitter 4 -20 mA ■ 10 - 15 mA □ 21 - 103 kPa (3 15 psig) □ Other ■ HART
XMTR
14 Output Accuracy: ± 0.1 % Span Rangeability: 100 : 1
15 Control Modes P = Prop. (Gain) I = Integral (Auto Reset) D = Derivative (Rate)
Sub: S - Slow F - Fast
P □ PI □ PD □ PID □ IF □ DF □ IS □ DS □
Other __________________________________________________________________
CONTROLLER 16 Action On Meas. Increase Output: Increases □ Decreases □
17 Auto-Man Switch None □ MFR STD □ Other _______________
18 Set Point Manual □ External □ Remote □ Other _______________
19 Manual Reg. None □ MFR STD □ Other _______________
20 Output 4 - 20 mA ■ 10 - 50 mA □ 21 - 103 kPa (3 - 15psig) □ Other _______________
21 Service Gage Press. ■ Vaccum □ Absolute □ Compound □
22 Element Type Diaphragm ■ Helix □ Bourdon □ Bellows □ Other _____
23 Element Material 316 S.S. ■ Ver. Copper □ Other ______________________
24 Range Fixed ■ Adj. Range See table
ELEMENT
Overrange Protection To ___________________________________________________
25 Process Data Press.: Normal ____________ Element Range _________
26 Process Connection 1/4 in. NPT □ 1/2 in. NPT ■ Other ____________________________
Location: Bottom ■ Back □ Other ____________________________
27 Alarm Switches Quantity _____________________ Form _________________________ Rating ________________
28 Function Press. □ Deviation □ Contacts To ___________________ on Inc. Press.
29 Requirement Filt_Reg. □ Sup. Gage □ Output Gage □ _____________ Charts
OPTIONS
Diaph. Seal □ Type _______________ Diaph ______________ Bot. Bowl _______________
Conn. __________ Capillary: Length _______________ Mtl. ____________________________
Other: See note 2 ■ Mounting Brackets for 2" pipe (Instrument rack) ■
MANUFACTURER 30 Mfr & Model ROSEMOUNT 2088G4S22A1M5B4E5Q4S5
Typical Integral
CODE 31 Manifold Model 3 0 6 RT2 2 BA1 1
Number

QTY TAG OP. PRESS (PSIG) CALIBRATED RANGE (PSIG) LOCATION P&ID

1 PIT-0824 1334 0-4000 4"-0.438-B(FH-9)-0824 SIGNA-N63-PD-PID-002


1 PIT-0811 1334 0-4000 8"-0.719-B(FH-9)-0811 SIGNA-N63-PD-PID-002
1 PIT-0813 1332 0-4000 6"-0.562-B(FH-9)-0813 SIGNA-N63-PD-PID-002
1 PIT-0812 1332 0-4000 6"-0.562-B(FH-9)-0812 SIGNA-N63-PD-PID-002
1 PIT-0221 1324 0-4000 6"-0.432-B(FH-9)-0221(linea existente) SIGNA-N63-PD-PID-002
1 PIT-0819 1020 0-4000 8"-0.719-B(FH-9)-0819 SIGNA-N63-PD-PID-002
1 PIT-0823 1334 0-4000 4"-0.438-B(FH-9)-0823 SIGNA-N63-PD-PID-002
1 PIT-7007 1334 0-4000 2"-0.218-B(FG-1)-7007 SIGNA-N63-PD-PID-003
Notes:
1. All instruments must be submitted with the respective certification with which the computer account (UL, FM, etc.)
2. Process connection 2 way block and bleed needle valve 1/2" NPT.
3. if the well is a single arm disregard the PIT belonging to the Short side. (LC)