Anda di halaman 1dari 1

Page 1 of 1

2 COMPRESSOR AIR COOLED FLOODED SCREW


CHILLER RATING
Project 210Tr nominal_193.6TR rated_AC Flooded Screw_Twin Date: 29/12/17
Compressor_HE-1
Customer
Location

Model Specifications
Model No. LCA2-210X55X56H
Actual Capacity 193.6 TR
Compressor Input power 243.4 KW
Refrigerant R134a
Expansion Valve Electronic Type

Evaporator
Leaving Temperature 6.00 °C
Entering Temperature 12.00 °C
Delta T 6.00 °C
Flow Rate 97.92 cmh
Evaporator Pressure Drop 49.3 kpa
Fouling Factor 0.0000440 M2 °K/W
Max Operating Pressure 150 psig (Water Side)

Condenser
Ambient Temperature 40.0 °C Altitude From Sea Level : 0.000 mtr
Total Heat Rejection 262.8 TR
Fan Quantity 12
Fan Motor Power (each) 2.500 KW
Fan Motor Power (total) 30.00 KW
Air Flow Rate 295626 CMH
Electrical Data
Volts/Phase/Hertz 415/3/50.0
Full Load Current 448.39 A
Starting Current 627.40 A
Voltage Range 360-440 V

Physical Data
Operating Weight 7350 kg
Refrigerant Charge 170 kg
Length 7082 mm
Width 2235 mm
Height 2457 mm
Compressor Type Semi Hermetic Screw
Compressor Quantity 2
Compressor Motor Speed 2950 rpm
Part Load Data "Rated in accordance with AHRI standard 550/590"
% LOAD AMBIENT ( °C) CAPACITY (TR) COMPR (KW) UNIT EER ** (Btu/Wh) kW/tonR *
100.00 40.0 193.6 243.4 8.500 1.257
90.00 36.4 174.3 199.6 9.110 1.146
80.00 32.7 154.9 153.4 10.14 0.9901
75.00 30.9 145.2 126.6 11.13 0.8717
70.00 29.1 135.5 116.8 11.08 0.8621
60.00 25.4 116.2 96.15 11.05 0.8277
50.00 21.8 96.80 64.50 14.61 0.6663
40.00 19.3 77.44 50.87 14.11 0.6569
30.00 16.9 58.08 35.78 13.73 0.6160
25.00 15.7 48.41 28.48 13.36 0.5883
PLV * = 0.7304 kW/tonR (* kW/tonR & IPLV/PLE figures are without condenser fan power)
** EER figures are with condenser fan power

Blue Star Chiller Selection Software Version 5.2