Arrange to submit the existing approval with DEWA's stamp

PROJECT: Maya DETAILS OF CONNECTED LOAD / MAX. DEMAND LOCATION:Service room


PLANNED COMPLETION DATE: OWNER: Maya
SMDB-T-NE-C1-G-F2 CONSULTANT:

RATING-AMPS PVC/XLPE CABLE SIZE ECC CONNECTED LOAD PROPOSED KWH


CIRCUIT/ SP FAULT SIZE KW MEETERING REMARKS
FEEDER / F/S/ MCCB MCB DUTY 2/4X 2/3/4C R-PH Y-PH B-PH TOTAL 1-PH 3-PH 3-PH CT
DB.NO. TP ISOL. KA SWA/PVC 1C mm 1C KW KW KW KW {1} {2} {3} {4}
mm mm
400
INCOMER TP 350 35 4C X 300 150 1 300/5A

OUTGOINGS:
DB-L-SH-02 TP 40 25 XLPE/SWA/PVC 10 10 2.37 2.51 2.34 7.22
DB-P-SH-02 TP 160 125 25 XLPE/SWA/PVC 50 25 22.44 21.07 20.55 64.07
Spare TP 100 Subjected to DEWA's approval 15.00 15.00 15.00 45.00
Spare TP 125 16.59 17.82 18.51 1
52.92

TOTAL CONNECTED LOAD PER PHASE 56.40 56.40 56.40 169.21 1

MAX. DEMAND: 143.83 KW AT 85% DIVERSITY TOTAL CONNECTED LOAD (3PH) 169.21 KW
CONTRACTOR: BRIGHT ELECTRICAL WORKS
TELEPHONE: 3856557
FAX: 3856553 (1) 20-80A (2) 30-90/120A (3) 100-160A (4) ---/----
PROJECT: Maya Lounge LOCATION:Service Room
DB-L-SH-02 LOAD DISTRIBUTION SCHEDULE
FED.FROM:SMDB-T-NE-C1-G-F2 Page : 1 of 1

RATING RATING MCB CCT. ECC. CONNECTED LOAD / POINTS LOAD PER CIRCUIT-WATT

OF OF SL. CIR. RTG. WIRE WIRE ROOM / AREA C EX. CHA 13A 15A COO WATT/ REMARKS
INCOMER ELCB NO. NO. AMP. SIZE SIZE LTG. FAN FAN NDL S/O S/O W/H KER ISOL FCU AC UNIT R Y B

LER
1 R1 10 2.5 2.5 Band Stage 19 40 760
1 2 Y1 10 2.5 2.5 Indoor Seating 24 40 960
40A 3 B1 10 2.5 2.5 Dinning 22,2 20/100 640
4P 4 R2 10 2.5 2.5 Indoor Seating 23 20 460
100mA 5 Y2 10 2.5 2.5 Kitchen 3 50 150
6 B2 10 2.5 2.5 Kitchen 6 50 300
4P 40 A ISOLATOR

2 7 R3 10 2.5 2.5 Kitchen 15 50 750


40A,4P 8 Y3 20 2.5 2.5 SIGN BOARD 1000 1000
100mA 9 B3 20 2.5 2.5 SIGN BOARD 1000 1000
3 10 R4 20 4 2.5 Indoor Seating 1 400 400
40A,4P 11 Y4 20 4 2.5 KITCHEN FCU 1 400 400
100mA 12 B4 20 4 2.5 Indoor Seating 1 400 400

CABLE SIZE : 4C X 10 mm2 CU XLPE /PVC/SWA/PVC+1Cx10 mm2 CU PVC ECC TOTAL 2370 2510 2340 7220
' S ' -SPLIT TYPE UNIT. ' W ' -WINDOW TYPE UNIT.

CABLE SIZE : 4 x 1C mm2 CU PVC/SWA/PVC + 1Cx mm2 CU PVC ECC


PROJECT: Maya Lounge LOCATION:Service Room
DB-P-SH-02 LOAD DISTRIBUTION SCHEDULE
FED.FROM:SMDB-T-NE-C1-G-F2 Page : 1 of 1

RATING RATING MCB CCT. ECC. CONNECTED LOAD / POINTS LOAD PER CIRCUIT-WATT
OF OF SL. CIR. RTG. WIRE WIRE ROOM / AREA C EX. CHA 13A 15A 20A WATT/ REMARKS

INCOMER ELCB NO. NO. AMP. SIZE SIZE LTG. FAN FAN NDL S/O S/O W/H S/O ISOL FCU AC UNIT R Y B
LER
1 R1 20 4 2.5 Band Stage 4 200 800
1 2 Y1 20 4 2.5 Band Stage 4 200 800
40A 3 B1 20 4 2.5 Band Stage 4 200 800
4P 4 R2 32 4 2.5 Bar Counter 8 200 1600 Ring
30mA 5 Y2 20 4 2.5 ICE Machine 1 1000 1000
6 B2 20 4 2.5 CHILLER Each socket in seperate circuit 2 644 1288 RING
2 7 R3 32 3667
40A,4P 8 Y3 TP 40 10 6 DISH WASH 1 11000 3667
100mA 9 B3 3666
10 R4 20 4 2.5 DOUGH MIX 1 644 644
3 11 Y4 20 4 2.5 Water Heater 1 1500 1500
4P 125 A ISOLATOR

40A 12 B4 20 4 2.5 Fridge 1 368 368


4P 13 R5 20 4 2.5 HOT CUPBOARD 1 1500 1500
30mA 14 Y5 20 4 2.5 Fridge 1 368 368
15 B5 20 4 2.5 Ice cream Machine 1 1000 1000
16 R6 20 4 2.5 Indoor Seating 2 200 400 FLOOR BOX
4 17 Y6 20 4 2.5 Indoor Seating 2 200 400
40A 18 B6 20 4 2.5 Indoor Seating 4 200 800
4P 19 R7 20 4 2.5 COMB OVEN 1 2000 2000
30mA 20 Y7 20 4 2.5 HOT CUPBOARD 1 1500 1500
21 B7 20 4 2.5 ESP 2 600+200 800
5 22 R8 32 3667
40A,4P 23 Y8 TP 40 10 6 OVEN 1 11000 3667
100mA 24 B8 3666
6 25 R9 25 2000
40A,4P 26 Y9 TP 32 6 4 Deep Fryer 1 6000 2000
100mA 27 B9 2000
7 28 R10 20 1500
40A,4P 29 Y10 TP 32 6 4 COFFE 1 4500 1500
100mA 30 B10 1500
8 31 R11 20 1666
40A,4P 32 Y11 TP 32 6 4 EXHAUST FAN 1 5000 1666
100mA 33 B11 1666
9 34 R12 3000
40A,4P 35 Y12 TP 40 SPARE 1 10000 3000
100mA 36 B12 3000
CABLE SIZE : 4C X 50 mm2 CU XLPE /PVC/SWA/PVC+1Cx25 mm2 CU PVC ECC TOTAL 22444 21068 20554 64066
' S ' -SPLIT TYPE UNIT. ' W ' -WINDOW TYPE UNIT.

CABLE SIZE : 4 x 1C mm2 CU PVC/SWA/PVC + 1Cx mm2 CU PVC ECC


1) DRAWINGS ARE NOT TO BE SCALED STATED
DIMENSIONS ONLY ARE TO BE TAKEN

2) ANY CONSISTENCY OR DISCREPANCY IS TO


BE BROUGHT THE ATTENTION OF & RESOLVE

NOQTY KITCHEN AREANOQTY KITCHEN AREA


BY THE ARCHITECT/DESIGNER BEFORE THE
WORK IS PUT IN HAND

3) ALL DIMENSIONS TO BE CHECKED ON SITE


BEFORE COMMENCING WORK

LEGEND:
3.9m HEIGHT
GLASS WALL EXISTING WALL
SERVICE ENTRY GLASS WALL
8140
GYPSUM WALL
SINGLE POWER SOCKET
FLOOR BOX
8

F/B
R7/DB-P-SH-02
@140cm
1810

Y5/DB-P-SH-02
18
@40cm 10
@140cm R5/DB-P-SH-02
GREASE TRAP @40cm, 20 A
4
AUTOMATIC DOING AG2 FREEZER D
ROOM
16

AG2
D
3175 12 Y7/DB-P-SH-02
R4/DB-P-SH-02
LEGEND 11
@140cm
@40cm, 20 A

Single Socket
18

Double Socket 8385 1


Y4/DB-L-SH-02 KITCHEN
13 14
FCU 77m²
Isolator Vegetable

Date:
D DATA
Preparation area
B5/DB-P-SH-02
RYB8/DB-P-SH-02
3.9m HEIGHT REMARKS
@40cm
/DB-P-SH-02
DIVIDER
27
@140cm, 20 A GLASS WALL
@40cm Hand Wash
Fish DAILY
1500
Preparation area STORES
3
B4/DB-P-SH-02
8
16 @40cm
MAIN ENTRY Y4/DB-P-SH-02 2539
SERVICE ENTRY W/H B2/DB-P-SH-02 10801
@40cm
1600
SPACE TABLE
Meat
100 2 Preparation area
15 & RACK

10850 6800 @40cm


16 19

B4/DB-L-SH-02
Rack
FCU 20 17090
R2/DB-P-SH-02 M.DB. DB-L-SH-02 DB-P-SH-02 Network Box
R1/DB-P-SH-02 @40 SMDB-T-NE-C1-G-F2 15
28
SPACE TABLE

785 RYB11/DB-L-SH-02
@10cm
D EXHAUST (FEATURE PROVISION) 16
21 RYB9/DB-P-SH-02
F/B Electrical / Service Room 7 Dish Wash
@40cm, 20A
RYB3/DB-P-SH-02
@40cm, 20A 23
RYB10/DB-P-SH-02 Pot Wash POWER DAMPER
R4/DB-L-SH-02 6
FCU R2/DB-P-SH-02
BAR COUNTER @40cm, 20A @ CEILING
26 24 25 24 21
@80cm Y2/DB-P-SH-02 Storage
Cabinet
28

D @40cm 9
D Double Mop
5 Sink
Double Sink Sink 22

Y1/DB-P-SH-02 F/B
SHOP NO 2 Hand Wash
Window

TOTAL AREA
297m²
@10cm Drop down B7/DB-P-SH-02
8745 INDOOR SEATING F/B
ESP B6/DB-P-SH-02
F/B
@40cm
D
ENTRY 2 MEP CONTRACTOR
BAND STAGE

2523

3.9m HEIGHT
R1/DB-P-SH-02
R6/DB-P-SH-02
GLASS WALL BRIGHT ELECTRICAL WORKS
@10cm DINNER 70 PAX INCL BAR INDOOR SEATING
F/B
D F/B

1811
CLIENT :

Al maya restaurant
Y6/DB-P-SH-02
@40cm

PROJECT :
26445
3.9m HEIGHT SHOP-02
ENTRY 1
GLASS WALL
3.9m HEIGHT
GLASS WALL DRAWING TITLE :
PROPOSED POWER LAYOUT

COPYRIGHT: REGAL INTERIORS LLC.


Location
BUSINESS BAY
PROPOSED POWER LAYOUT Drawn by Drawing no:
RAM REG-ZAE- 9
Checked by rev no:
BS
Scale Date: Job no
FEB 17 W-17-4
1) DRAWINGS ARE NOT TO BE SCALED STATED
DIMENSIONS ONLY ARE TO BE TAKEN

2) ANY CONSISTENCY OR DISCREPANCY IS TO


BE BROUGHT THE ATTENTION OF & RESOLVE
BY THE ARCHITECT/DESIGNER BEFORE THE
WORK IS PUT IN HAND

3) ALL DIMENSIONS TO BE CHECKED ON SITE


BEFORE COMMENCING WORK

3.9m HEIGHT LEGEND:


GLASS WALL
EXISTING WALL
SERVICE ENTRY
GLASS WALL
8140

GYPSUM WALL
SINGLE POWER SOCKET
FLOOR BOX
B2/DB-L-SH-02 R2/DB-L-SH-02
F/B
1810

FREEZER
ROOM

3175

8385 KITCHEN
77m²
3.9m HEIGHT
DIVIDER
GLASS WALL Date: REMARKS
DAILY
1500 STORES

MAIN ENTRY 2539


SERVICE ENTRY 10801

100 1600
10850 6800

17090
Y1/DB-L-SH-02
R1/DB-L-SH-02
M.DB. DB-L-SH-02 DB-P-SH-02 Network Box
SMDB-T-NE-C1-G-F2

965 2524 2602

Electrical / Service Room


771
R3/DB-L-SH-02
LED STRIP LIGHT
BAR COUNTER
(Shelf & triangular shelf)

Y2/DB-L-SH-02
SHOP NO 2 Window

TOTAL AREA
297m²
Drop down

8745 INDOOR SEATING


ENTRY 2
BAND STAGE
MEP CONTRACTOR

3.9m HEIGHT
GLASS WALL
B1/DB-L-SH-02
DINNER 70 PAX INCL BAR INDOOR SEATING BRIGHT ELECTRICAL WORKS

LED STRIP LIGHT LED STRIP LIGHT


(4.8mx1.4m all sides) (4.8mx1.4m all sides)

CLIENT :

Al maya restaurant
B3/DB-L-SH-02
SIGN BOARD
26445 PROJECT :
Y3/DB-L-SH-02 3.9m HEIGHT
SIGN BOARD ENTRY 1
GLASS WALL
SHOP-02
3.9m HEIGHT
GLASS WALL
DRAWING TITLE :
PROPOSED LIGHTING
LAYOUT
COPYRIGHT: REGAL INTERIORS LLC.
Location
PROPOSED LIGHTING LAYOUT BUSINESS BAY
Drawn by Drawing no:
RAM REG-ZAE- 9
Checked by rev no:
BS
Scale Date: Job no
FEB 17 W-17-4

Anda mungkin juga menyukai