CT Dimensioning

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
Current Transformers Dimensioning

Protection CT Measuring CT

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Magnetising Curve

10

CT Excitation - BH Curve
Flux Density - B (tesla)

Measured
Knee
Knee'

0
0 1 10
Exciting Current (A-tuns/cm)

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Magnetising Curve

V = 2 ⋅ π ⋅ f ⋅ A ⋅ N ⋅ B = 4.44 ⋅ f ⋅ A ⋅ N ⋅ B
V = induced voltage
f = frequency
A = cross sectional area of magnetic core
N = number of secondary turns
B = flux density
L
I = ⋅H
N
I = magnetising current
L = mean magnetic path
H = magnetising force

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Magnetising Curve

Es tim ate d CT Excitation Cur ve


35

30

25
ExcitationVoltage(V)

20

15

10

5 Knee Point

0
0.00 0.05 0.10 0.15 0.20 0.25

Excitation Cur re nt (A)

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Measuring vs Protection

Measuring CT Protection CT

• Under over current, the CT • In case of over current, the


should limit the secondary CT should maintain the
current to avoid thermal secondary current within
overload of the connected the rated limit to enable
equipment proper protection operation

• At rated burden (cosφ = • At rated burden (cosφ =


0.8) and rated security 0.8) and rated accuracy
factor, the composite error limit factor, the composite
should be > 10% error should be less than
5% or 10%

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Magnetising Curve

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Magnetising Curve
excitation limiting voltage (TPS Class)

10%

100%

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Saturation

Factors affecting CT saturation

 CT ratio
 Core cross-sectional area
 Core design
 Connected burden
 B-H characteristic of core
 Amount of remanent flux
 Fault current & DC offset
 System time constant

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Saturation

Steady-state saturation with a.c. current

Transient saturation with offset current

dφ di
e = −n = −L
dt dt
For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Saturation

IP

φ
saturation flux

IS

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Saturation

Transient CT saturation due to DC component

ISC Short circuit current

DC flux non-saturated

ΦS

Φ
AC flux

Im Magnetising current

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Standards

• IEC/AS 60044-1: Instrument transformers - Part 1 -


Current transformers (ed. 1.2 – 2003)
• IEC/AS 60044-6: Instrument transformers - Part 6 –
Requirements for protective current transformers for
transient performance
• IEC/AS 60044-8: Instrument transformers -Part 8 -
Electronic current transformers
• AS 1675: Current Transformers – Measurement &
Protection (now superseded)
• BS7626 (BS 3938): Specification for current
transformers (now superseded)

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – Equivalent Circuit

n2Zpri ZCT Zwire

1:n Zburden
Iexcitation
Ideal Tx

Xm Rm Zburden

Ipri/n ZCT Zwire

n:1 Zburden
Ideal CT

Iexcitation

Xm Rm
θ
Zburden

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1

Definition of Ratio Error


I sec ⋅ nr − I prim
rerror = 100 ⋅
I prim

Ratio Error (pu)


I s Z sΣlcore
rerror ≅ − sin(α + θ )
2πfµAcore N s I p N p
where
µ = permeabili ty
Xs + Xz
α = atan
Rs + R z
θ
θ = phase angle of excitation
(+ error due to stray capacitance)
For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1

Definition of Angle Error

δ = angle( I sec ) − angle( I prim )

Phase Angle Error (radians)


I s Z sΣlcore
δ ≅− cos(α + θ )
2πfµAcore N s I p N p
where
µ = permeabili ty
Xs + Xz
α = atan
Rs + R z
θ
θ = phase angle of excitation

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class P

Rated Composite Error at ALF IEC/AS 60044-1 / BS3938:


(turn ratio error, iron / copper multiple of rated current at
losses, saturation) which, with rated burden, will
maintain the accuracy
AS 60044: 5P20 5VA IEC/AS 60044-1 / BS3938
specify Rated Burden
AS 1765: 5P 100 F20

Rated Secondary Reference Voltage Accuracy Limit Factor (ALF)


Vref (the RMS secondary voltage (the factor which, when applied
upon which the performance is based) to at rated primary current,
gives the accuracy limit primary
current)
Conversion:
Vref ⋅ I sec = VA ⋅ ALF (Appendix H, AS1675)

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class P

Composite Error:

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class P

Max.
Max. Current
Composite
Accuracy Error at Rated Phase Displacement at Rated
Error at Rated
Class Primary Primary Current
Accuracy
Current
Limit

5P ± 1% ± 60 min. ± 1.8 centiradians 5%

10P ± 3% - - 10%

Accuracy limit based on steady state symmetrical primary current

AS 1675: Current error at rated current with Rb < 0.04 ohm:


Ipri > 100A – 1%
Ipri ∗ 100A – 2%
For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class PR

 New to AS, e.g. 5PR 10VA Ts Rct


 Intended for limiting the remanence
 Additional requirements:
 Saturation flux (ψs)
 Remanent flux (ψr)
 Remanence factor (Kr =100×ψr /ψs < 10%)
 Rated secondary loop time constant (Ts=Ls/Rs) (to be
specified by purchaser)
 Secondary winding resistance (Rct) at 75oC
 Application: current differential protection for
generators, motors, transformers, busbars and
transmission lines.

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class PX

Low leakage flux

Marking, e.g. 5PX 10VA Ek Ie Rct Kx Rb


 Rated turns ratio, turns ratio error < ± 0.25%
 Rated knee point e.m.f. (Ek)
 Maximum exciting current (Ie) at rated knee point
e.m.f. and/or at stated percentage thereof
 Maximum resistance of the complete secondary
winding at a temperature of 75 °C (Rct)

Purchaser may also specify:


 Dimensioning factor (Kx)
 Rated resistive burden (Rb)

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class PX

(similar to BS 3938 Class X


AS 1675 Class PL)

0.05PX 450 R3 10VA Kx Rb


Max. exciting Dimensioning
current (Ie) at factor (Kx) Rated resistive
rated knee point burden (Rb)
voltage
Rated knee point Max. secondary winding
o
voltage (Ek or Vk) resistance (Rct) at 75 C

Turn ratio error within ± 0.25%


AS 1675: or ±50/Ns whichever the greater,
where Ns = number of secondary turns

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class PX

Ek = K x ⋅ ( Rct + Rb ) ⋅ I sn

 Ek = rated knee point emf


 Kx = multiple of Isn at which the CT must perform satisfactorily
 Isn = rated secondary current
 Rb = rated resistive burden
 Rct = winding dc resistance at 75oC

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class PX

Conversion from Class P to Class PX


( Rb + Rct ) ⋅ I sn ⋅ K ssc
Vk =
1.3
Example

600/1, 5P10, 15VA, Rct = 4 Ω, Rb = 15 Ω


(15 + 4) ⋅1 ⋅10
Vk = = 146V
1.3

3000/5, 5P10, 15VA, Rct = 4 Ω, Rb = 15/25 Ω


(15 / 25 + 4) ⋅ 5 ⋅10
Vk = = 177V
1.3
For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 1 – Class PX

Conversion from Class PX to Class P

1.15 ⋅ Vk
K ssc =
( Rb + Rct ) ⋅ I sn
Example

600/1, 0.05PX 150, 15VA, Rct = 4 Ω, Rb = 15 Ω

1.15 ⋅150 ⋅1
K SSC = = 9.1
(15 + 4)

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT – AS 60044 - 6 – Class TP
At rated primary current At rated accuracy limit

Class Phase Displacement Remanence


Ratio Peak
error instantaneous error
Min. Centered

TPY
≤ 10%
(anti-remanence ± 1.0% ± 60 ± 1.8 <10%
during specified duty cycle
air gap)

≤ 10% (ac)
during single energization
TPZ
± 1.0% 180 ± 18 5.3 ± 0.6 with max. d.c. offset at negligible
(linear core)
specified secondary loop
time constant

TPX
≤ 10%
(closed iron core, ± 0.5% ± 30 ± 0.9 no limit
during specified duty cycle
low leakage flux)

TPS specify excitation current limit at excitation limiting


(closed iron core, ± 0.25% secondary voltage (if not, then < excitation current no limit
low leakage flux) at 10% peak instantaneous error of TPX class)
For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning

Operational Accuracy Limit Factor – ALF’

Pi + PN Ri + RN
ALF' = ALF ⋅ = n⋅
Pi + PB Ri + RB

P + PB Ri + RB
ALF = ALF' ⋅ i = ALF'⋅
Pi + PN Ri + RN

Rated CT burden: PN
Internal CT burden: Pi=Ri ⋅ I2N2
Actually connected
burden : PB= RB ⋅ I2N2

with: RB=RL+RR= total burden resistance


RL= resistance of connecting cable
RR= relay burden resistance
For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning

Operational Accuracy Limit Factor – ALF’


I Theory:
ALF ' ≥ K OD ⋅ SC
IN No saturation during BMax XN
total fault duration: K' TF = = 1 + ωTN = 1 +
Where KOD is the total ˆ B~ RN
over-dimensioning factor:
 tM tM 
No saturation for ω ⋅ TN ⋅ TS
− −

K OD ≥ K TF ⋅ K Rem the specified time tM: K ' 'TF = 1+ (e TN − e TS 


 TN − TS 
 
% remanence
K Rem = 1+
100 Practice:
K OD = KTF

Remanence only considered in extra high


voltage systems (EHV)
KTF-values acc. to relay manufacturers‘ guides
For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning

Choice of CT rated power

• Rated burden > total connected burden


• For GIS and MV switchboard with modern
relays/measuring devices, class P 1A CTs
with small rated burden are sufficient, e.g.
5VA, 10VA

Choice of Accuracy Limit Factor

• Relay manufacturer’s recommendation


should be followed + engineering security
factor
• CT performance depends on operational
ALF

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning

Choice of CT Ratio

• CT ratio should be based on the protected object,


however, it may need to be go higher:
• limitation of difference in CT ratio for low impedance
differential protection as recommended by the relay
manufacturer
• Avoid excessive over-dimensioning:
• Imax, switchgear / Ipri-rated > 100 !
• Such CT can damage the relay because there is no CT saturation

If a more precise estimation of the CT performance is


necessary, then RCT and the magnetising curve is required.

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning

Choice of Measuring CT

• For classes 0.1 – 1, the accuracy is based on a total connected


burden between 25% to 100% of the rated burden
• For classes 0.1, 0.2 and 0.2S with rated burden < 15VA, an
extended range of burden can be specified (from 1VA to 100% of
the rated burden)
• For classes 3 and 5, the accuracy is based on a total connected
burden between 50% to 100% of rated burden

• Instrument security factor (FS) defines the maximum secondary


current that will flow under short circuit of primary circuit
• Instrument security factor (FS) is based on the rated burden
• Under-burdened measuring CT can damage connected
instrument during short circuit or overload of the primary circuit

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning
Overcurrent Protection

CT saturation is allowable provided the remaining fundamental current is


higher than I>> setting

Isec, fundamental > I >

Isec,funfamental > I >>

Pn + PCT I >>
ALF' = ALF ⋅ >
P '+ PCT In

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning
Differential Protection
Differential protection should be stable on external faults
High sensitivity for internal fault
Relay
Protected Object Requirement for Internal Faults Requirements for External Faults
Type

min. over min. over


min. saturation min. saturation
dimensioning dimensioning CT symmetry
free time (ms) free time (ms)
KTF KTF

Generator 7UM6 4 0.75 5 1.20

Transformer 7UT6 4 0.75 5 1.20

O/H Line, Cable - 7SD52 3 0.50 5 1.20


with digital
communication 7SD61 3 0.50 5 1.20

O/H Line, Cable -


7SD600 5 1.20 1 1.00 0.75
with pilot wires

Busbar 7SS52 3 0.50 3 0.50

7SS600 4 0.75 4 0.75


For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning
Distance Protection

Zone 1 faults should be cleared without delay


Faults outside Zone 1 should trip after preset delay

CT saturation is allowable CT saturation is allowable only


provided the remaining after the preset time delay for
fundamental current is tripping command
sufficient to trigger Zone 1
operation

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning
CT Requirements – SIPROTEC Catalogue – Part 2

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning
CT Requirements – SIPROTEC Catalogue – Part 2

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
CT Dimensioning
CT Requirements – SIPROTEC Catalogue – Part 2

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
Our Vision

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
High Impedance Differential Scheme

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
High Impedance Restricted Earth Fault

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.
High Impedance Scheme

Through Fault Stability

n2Zpri ZCT Zwire Zwire ZCT n2Zpri

1:n Zstabilise n:1

Ideal Tx
Iexcitation Iexcitation
Ideal Tx

Xm Rm Zrelay Xm Rm

• Stabilising resistor
• Knee point voltage
• Non-linear resistor
• Effective setting

For internal use only / Copyright © Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.