DESIGN REPORT

PROJECT ID : OPMTD17-008-REPORT
CUSTOMER NAME : Kerry Word Bridge
PROJECT LOCATION : Riverside Mall
DATED OF ISSUED : JANUARY 29, 2018

Design, Fabrication, Supply & Installation of Steel Buildings


Page 1 Of 76

Job No OPSPE16-032-MBS-RE01 Date 20-01-2017


Customer SATO KOGYO Designed By NSP
Project Restaurant Draft By NSP
Address PPSEZ,Posenchey, Checked By NCH

INTRODUCTION

This Design Calculations Package has been prepared using the latest
applicable codes and standards and the latest developments in
engineering practices. A design engineer prepared the calculations and a
building specialist checked the detailing and drafting.

Computer programs, verified and tested by Fuxin Building Systems have been
used where applicable to determine structural requirements. The output of
these programs has been incorporated in this package together with explanation
text where necessary.

For your easy reference, all pages have been numbered and a table of contents
has been provided.

Please use this calculations package in conjunction with the drawings provided.
You can resubmit this package with the drawings to other parties for their
approval as required, or, keep this package for future reference. Fuxin does
not require these calculations to be returned.

For any questions regarding this package please do not hesitate to contact our
office. Fuxin keeps records of reference on design calculations for each
building designed as a part of Fuxin total quality system.

Design/Engineering Department

Fuxin Steel Building


Page 2 Of 76

Job No OPSPE16-032-MBS-RE01 Date 20-01-2017


Customer SATO KOGYO Designed By NSP
Project Restaurant Draft By NSP
Address PPSEZ,Posenchey, Checked By NCH

Table Of Contents

INTRODUCTION.OUT
INTRODUCTION 1 - 1
BUILDING DESIGN DATA
DATA.OUT 3 - 3
BUILDING DESIGN INPUT
INPUT.OUT 4 - 5
RIGID FRAME 11.DXF 6 - 6
COMBINATION.OUT RF-
RF-1-LOAD COMBINATION 7 - 9
1-DEAD LOAD.DXF
RF-1-DEAD LOAD 10 - 10
RF-1-DEAD LOAD-AXIAL
LOAD-AXIAL.DXF RF- 11 - 11
RF-1-DEAD
1-DEAD LOAD-SHEAR.DXF
LOAD-SHEAR.DXF
RF-1-DEAD LOAD-SHEAR RF-1- 12 - 12
DEAD LOAD-MOMENT.DXF
RF-1-DEAD LOAD-MOMENT RF-1- 13 - 13
LIVE LOAD.DXF
RF-1-LIVE LOAD 14 - 14
RF-1-LIVE LOAD-AXIAL
LOAD-AXIAL.DXF RF- 15 - 15
RF-1-LIVE
1-LIVE LOAD-SHEAR.DXF
LOAD-SHEAR.DXF
RF-1-LIVE LOAD-SHEAR RF-1- 16 - 16
LIVE LOAD-MOMENT.DXF
RF-1-LIVE LOAD-MOMENT 17 - 17
RF-1-WIND LOAD-WIND LONG 1 1.DXF 18 - 18
1-AXIAL.DXF
RF-1-WIND LOAD-WIND LONG 1-AXIAL 19 - 19
RF-1-WIND LOAD-WIND LONG 1-SHEAR
1-SHEAR.DXF 20 - 20
1-MOMENT.DXF
RF-1-WIND LOAD-WIND LONG 1-MOMENT 21 - 21
RF-1-VERIFICATION.OUT
RF-1-VERIFICATION 22 - 47
RIGID FRAME 22.DXF 48 - 48
RF-2-LOAD COMBINATION
COMBINATION.OUT 49 - 51
LOAD.DXF
RF-2-DEAD LOAD 52 - 52
LOAD-AXIAL.DXF
RF-2-DEAD LOAD-AXIAL 53 - 53
LOAD-SHEAR.DXF
RF-2-DEAD LOAD-SHEAR 54 - 54
RF-2-DEAD LOAD-MOMENT
LOAD-MOMENT.DXF 55 - 55
LOAD.DXF
RF-2-LIVE LOAD 56 - 56
LOAD-AXIAL.DXF
RF-2-LIVE LOAD-AXIAL 57 - 57
LOAD-SHEAR.DXF
RF-2-LIVE LOAD-SHEAR 58 - 58
LOAD-MOMENT.DXF
RF-2-LIVE LOAD-MOMENT 59 - 59
RF-2-VERIFICATION.OUT
RF-2-VERIFICATION 60 - 76
Page 3 Of 76

Job No OPSPE16-032-MBS-RE01 Date 20-01-2017


Customer SATO KOGYO Designed By NSP
Project Restaurant Draft By NSP
Address PPSEZ,Posenchey, Checked By NCH

S T R U C T U R A L D E S I G N C A L C U L A T I O N S
FOR

SATO KOGYO
PPSEZ,Posenchey, Phnom Penh

PROJECT

Job: OPSPE16-032-MBS-RE01
Restaurant
PPSEZ,Posenchey, Phnom Penh

BUILDING DATA
BUILDING SIZE:
Width (mm) = 20190
Length (mm) = 16980
Back Eave Height (mm) = 8875
Front Eave Height (mm) = 7850
Roof Slope (rise/100) = -5.077:100
BUILDING LOADS:
Roof Dead Load (Kn/m2) = 0.100
Roof Live Load (Kn/m2) = 0.570
Rigid Frame Live Load (Kn/m2) = 0.57
Collateral Load (Kn/m2) = 0
Roof Snow Load (Kn/m2) = 0
BUILDING CODE:
Wind Code = MBMA 10
Wind Speed(mps) = 32
Closed/Open = Closed
Exposure = C
Importance - Wind = 1.00
Importance - Seismic = 1.00
Seismic Zone = A

.
Page 4 Of 76

Job No OPSPE16-032-MBS-RE01 Date 20-01-2017


Customer SATO KOGYO Designed By NSP
Project Restaurant Draft By NSP
Address PPSEZ,Posenchey, Checked By NCH

BUILDING DATA FOR Restaurant

BUILDING SIZE:
Width(mm): 20190
Length(mm): 16980
Back side eave height(mm): 8875 Back side roof slope: -5.077:100
Front side eave height(mm): 7850 Front side roof slope:

LOADING:
Roof Live Load(Kn/m2) : 0.570 Wind Code: MBMA 10
Roof Dead Load(Kn/m2) : 0.100 Building Exposure: C
Roof Snow Load(Kn/m2): 0 Closed/Partial/Open: Closed
Roof Collateral Load(Kn/m2): 0 Wind Speed (mps): 32
Seicmic Zone: A Wind Importance: 1.00

FRAMING:
Left endwall frames: Rigid
Right endwall frames: Rigid
Interior Frames: 4 semi-rigid frames
with interior columns at: 7710.000 13760.00
1 semi-rigid frame
with interior columns at: 13760.00

ROOF SYSTEM:
Roof panel Type: 460A Gauge: 0.5 Color: Fuxin Standard Painting
(SL = Standing Seam Roof; SS = Super Seal)
Clip type: HI (FX = Fixed; FL = Floating)
Clip Height(mm): 90
Gable trim color: Fuxin Standard Painting
Eave trim color : Fuxin Standard Painting

WALL SYSTEM:
Wall panel type: Gauge: Color:
Outside corner trim color: Fuxin Standard Painting
Base trim color :
Opening trim color : Fuxin Standard Painting

FACTORY LOCATED OPENINGS:


Left endwall: none
Front sidewall: none
Right endwall: none
Back sidewall: none

Partial Open Wall Areas:


Left Endwall: None
Front Sidewall: None
Right Endwall: None
Back Sidewall: None
Page 5 Of 76

Job No OPSPE16-032-MBS-RE01 Date 20-01-2017


Customer SATO KOGYO Designed By NSP
Project Restaurant Draft By NSP
Address PPSEZ,Posenchey, Checked By NCH

Column Base Elevations:


Left Endwall: 0 mm
Front Sidewall: 0 mm
Right Endwall: 0 mm
Back Sidewall: 0 mm

Insulation:
Roof: Type = None
Thickness = None
Wire = None
Wall: Type = None
Thickness = None
Wire = None

Roof Extensions (Overhangs):


Left Endwall: 500 mm by 20216 mm
Front Sidewall: 500 mm by 20216 mm
Right Endwall: 500 mm by 16980 mm
Back Sidewall: 1000 mm by 16980 mm

GUTTERS AND DOWNSPOUTS:


Front sidewall gutters(mm): 17980 Front sidewall downspouts: 3
Back sidewall gutters(mm): Back sidewall downspouts:
Color: GL Galvalium Color: GL Galvalium

Translucent Wall Panels: None

Translucent Roof Panels: None

Liner Panels:
Left Endwall: None
Front Sidewall: None
Right Endwall: None
Back Sidewall: None

Anda mungkin juga menyukai