Anda di halaman 1dari 6

TRANSMISSION AND DISTRIBUTION

Using the protection relay in delta-wye


power transformer applications
by George Alexander, Schweitzer Engineering Laboratories

Application of traditional connections such as transformer windings connected in wye and CTs in delta, or transformer windings connected
in delta and CTs in wye, involves no modification of current inputs to differential calculations in the relay.

However, if non-standard connections are


used, e.g. transformer windings connected
in wye and CTs in wye, the current inputs
to the differential calculations in the relay
must be modified to compensate for a
30° shift in the transformer and to subtract
zero-sequence current as necessar y.
To accomplish this, the relay applies a
connection compensation factor for each
winding.

The unit includes five three-phase current


inputs and three single-phase current inputs
for restricted earth fault (REF) protection. It
also includes six voltage inputs. Several
examples for delta-connected high-side
windings and wye connected low-side
windings are shown here. These examples
provide correct settings for two-winding
transformer examples, but can also be
Fig. 1: ANSI standard delta-wye transformer, ABC system rotation, A-B-C connected to H1-H2-H3.
applied to transformers with additional
windings.

The device contains settings for transformer


phase rotation (PHROT), CT connections
(CTCONn), internal/external CT connection
compensation (ICOM), and connection
compensation (TnCTC).

Phase rotation setting (PHROT)


It is recommended that the CT secondary
Fig. 2: System phase angles for DABY connection, ABC system rotation.
circuits are wired to the relay ’s terminal
block such that the system phase is
connected to the same relay phase
(i.e. connect system A-phase to the
relay A-phase). This product uses the
phase rotation setting to determine
negative-sequence current (3I2). The
phase differential element calculations do
not use the phase rotation setting, but the
setting must be correct for one to use the
negative-sequence differential element
Fig. 3: Winding compensation with delta winding as reference.
in the relay, i.e. the system phase rotation
must be known to select the connection
compensation settings properly.

Current transformer connections (CTCONn)


The current transformer connection may
be set for either wye (Y) or delta (D). In
new installations, it is recommended
to use wye-connected CTs whenever
possible to maximise available protection,
simplify overcurrent relay settings, CT
wiring and troubleshooting. If CTs are Fig. 4: Winding compensation with wye winding as reference.

energize - July 2013 - Page 38


TRANSMISSION AND DISTRIBUTION
that use wye-connected CTs. In general,
wye-connected CTs are easier to draw,
wire, and troubleshoot. Using the CTCONn
setting in the relay will automatically
calculate the TAPn setting if MVA is set to
a value other than OFF. If MVA = OFF, the
CTCONn setting can be used for metering
and overcurrent elements.

Internal/external CT connection
compensation (ICOM)
If ICOM = N, the traditional CT connections
external to the relay must be used (e.g.,
transformer windings connected in wye
and CTs in delta, or transformer windings
connected in delta and CTs in wye) to
Fig. 5: ANSI standard delta-wye transformer, ACB system rotation, accomplish the CT and transformer phase-
A-B-C connected to H1-H2-H3. shift compensation. The CTs must be
connected such that the current entering
the polarity marks of the relay windings
are 180° out of phase for load and
external faults. If ICOM = Y, the relay will
compensate internally for the transformer
and CT phase shifts.

Internal connection compensation settings


(TnCTC)

Fig. 6: System phase angles for DABY connection, ACB system rotation. With internal CT connection compensation
enabled (ICOM = Y), the relay can correct
for phase shifts in a transformer or CTs. It
is best to wire all CTs in wye configuration
to maximise available protection, simplify
overcurrent protection, and CT wiring. The
relay setting, CT connection (CTCONn,
where n is the winding input), defines the
CT connection as delta or wye. Where CTs
are connected in wye as recommended,
the relay setting for internal winding/CT
connection compensation (ICOM) will
need to be set to Y to accommodate for
30° phase shifts in the transformer. Setting
Fig. 7: Winding compensation with delta winding as reference. ICOM equal to Y turns on the settings for
connection compensation (TnCTC, where
n is the winding input) to properly account
for phase shifts in transformer winding
connections and CT connections.

The relay can compensate in 30°


increments with a setting range of
0 – 12. A setting of zero applies no phase
shift compensation. A setting of twelve
applies 360° of phase shift compensation,
which results in 0° of compensation but
the removal of zero-sequence currents.
A setting of one applies a 30° phase
shift in the counterclockwise direction
Fig. 8: Winding compensation with wye winding as reference. for ABC system rotation, and a setting of
eleven applies a 330° phase shift in the
counterclockwise direction for ABC system
wye-connected, the relay can provide If CTs are wye-connected, the relay rotation.
phase, negative-sequence, and residual calculates secondar y amps it receives
overcurrent elements for that winding. The by dividing the primary amps by the CT In all of the application examples, the
residual elements respond to 3 I 0, where following assumptions apply:
ratio. If the CTs are delta-connected,
3 I 0 = I a + I b + I c . However, the relay the secondar y amps that the relay  CTs are connected in wye on both
disables residual overcurrent elements receives are larger by √3, the overcurrent sides of the transformer (CTCONS =
automatically if the CTs are connected pick up settings must be adjusted by CTCONT = Y).
for the associated winding in delta. Delta- √3. This can introduce confusion when  The system phases connect to
connected CTs cannot deliver any residual coordinating the relay with downstream complementary labeled bushings on
operating current to the relay. relays (e.g., distribution feeder relays) both the high side and low side of the

energize - July 2013 - Page 40


TRANSMISSION AND DISTRIBUTION
as a result of the opposite CT polarity on
the secondary of the transformer. The CT
secondary current angles in the figure are
the correct angles for a DABY transformer
with ABC phase rotation.

For this example, there are multiple


choices for winding compensation that
will produce the correct 30° shift. The
recommended method is to select
the high-side winding as the reference
winding and shift the low-side currents
by the appropriate amount. In Fig. 3, the
delta winding from neutral to A-phase is
chosen as the reference. The wye current
is adjusted by 30° in the counterclockwise
direction (because of ABC rotation) to
align with the reference. Therefore, setting
TSCTC = 0 and TTCTC = 1 achieves the
Fig. 9: ANSI standard delta-wye transformer, ABC system rotation, C-B-A connected to H1-H2-H3. proper selection of winding compensation.
The appropriate settings are:
PHROT = ABC, CTCONS = Y, CTCONT = Y,
ICOM = Y, TSCTC = 0, TTCTC = 1
A second choice for winding compensation
would be to select the wye winding as the
reference and rotate the delta A-phase by
the appropriate number of degrees to be
in phase with the wye winding A-phase. As
Fig. 4 shows, the A-phase-to-neutral on the
Fig. 10: System phase angles for DACY connection, ABC system rotation. delta winding must be rotated by 330° in
the counterclockwise direction to align with
A-phase-to-neutral on the wye winding.
One might think that the compensation
settings would, therefore, be TSCTC = 11
and TTCTC = 0. However, winding two is
a wye winding with wye-connected CTs;
the proper selection would therefore be
TTCTC = 12 to remove zero-sequence
currents. Setting the winding compensation
to twelve introduces a 360° phase shift and
removes zero-sequence currents. Removal
of the zero-sequence currents is important
because phase-to-ground faults external
to the differential zone of protection could
Fig. 11: Winding compensation with delta winding as reference. cause a false assertion of the differential
element. The false assertion results from
the zero-sequence current source of
the directly grounded or impedance-
grounded wye transformer neutral creating
an apparent, but incorrect, increase in the
secondary phase currents to the relay.
In this case, the appropriate settings would
be: PHROT = ABC, CTCONS = Y, CTCONT = Y,
ICOM = Y, TSCTC = 11, TTCTC = 12
Example 2
For the transformer nameplate drawing
in Fig. 5, ACB phase rotation is assumed
and the highside currents will lag the
Fig. 12: Winding compensation with wye winding as reference. associated low-side currents by 30°. This is
a DABY connection because the polarity
transformer (i.e., high-voltage A-phase associated low-side currents by 30°. This is of A-phase connects to the nonpolarity of
connects to the H1 bushing and low- a DABY connection because the polarity B-phase. Because the CTs are connected
voltage A-phase connects to the X1 of A-phase connects to the nonpolarity of in a wye configuration, the relay must
bushing). B-phase. Because the CTs are connected compensate for the 30° phase shift.
in a wye configuration, the relay must
Application examples The phasor diagram in Fig. 6 shows the
compensate for the 30° phase shift.
A-phase load current flow through the
Example 1
The phasor diagram in Fig. 2 shows the transformer and the 180° shift of the
For the transformer nameplate drawing A-phase load current flow through the A-phase current on the CT secondar y
in Fig. 1, ABC phase rotation is assumed, transformer and the 180° shift of the as a result of the opposite CT polarity on
and the high-side currents will lead the A-phase current on the CT secondar y the secondary of the transformer. The CT

energize - July 2013 - Page 41


TRANSMISSION AND DISTRIBUTION
secondary current angles in the figure are
the correct angles for a DABY transformer
with ACB phase rotation.

For this example, there are also multiple


c h o i c e s f o r w i n d i n g c o m p e n s a t i o n.
The recommended method is to select
the high-side winding as the reference
winding, and to shift the low-side currents
by the appropriate amount. In Fig. 7, the
delta winding from neutral to A-phase was
chosen as the reference. The wye current
must be adjusted by 30° in the clockwise
direction (because of ACB rotation) to
align with the reference. Therefore, setting
TSCTC = 0 and TTCTC = 1 achieves the
proper selection of winding compensation.
The winding compensation setting does Fig. 13: Non-standard delta-wye transformer, ABC system rotation, A-B-C connected
not change, although the phase rotation to H1-H2-H3.
changed. This is because, for ACB rotation,
the phase-angle rotation was adjusted
in the clockwise direction by the TnCTC
setting.

The appropriate settings are:


PHROT = ACB, CTCONS = Y, CTCONT = Y,
ICOM = Y, TSCTC = 0, TTCTC = 1

A second choice for winding compensation


would be to select the wye winding as the
Fig. 14: System phase angles for DACY connection, ABC system rotation.
reference and rotate the delta A-phase
by the appropriate number of degrees to
be in phase with the wye winding A-phase.
As Fig. 8 shows, A-phase-to-neutral on the
delta winding would need to be rotated by
330° in a clockwise direction to align with
A-phase-to-neutral on the wye winding.
Again, as in example 1, the compensation
s e t t i n g s c o u l d b e T S C TC = 1 1 a n d
TTCTC = 12.

The appropriate settings are:


P H R O T = A C B , C T C O N S = Y,
CTCONT = Y, ICOM = Y, TSCTC = 11, Fig. 15: Winding compensation with delta winding as reference.
TTCTC = 12
Example 3

The transformer nameplate in example 3


is exactly like the nameplate in examples
1 and 2, but now the system phase
connections to the H1, H2, and H3 terminals
have changed. A-phase now connects to
H3, and C-phase now connects to H1,
and the system A-phase connects to the
relay IAS input. This is a DACY connection
because the polarity of A-phase connects
to the nonpolarity of C-phase. For the Fig. 16: Winding compensation with wye winding as reference.
nameplate diagram in the example and
ABC system phase rotation, the high-side the secondary of the transformer. The CT the appropriate amount. In Fig. 11, the
currents will lag the associated low-side secondary current angles in the figure are delta winding from neutral to C-phase was
currents by 30°, and the relay must the correct angles for a DACY transformer chosen as the reference simply because
account for this phase angle shift. with ABC phase rotation.
it is at the 12 o’clock position, although
The phasor diagram in Fig. 10 shows For this example, there are also multiple the A-phase could have been chosen
the A-phase load current flow through c h o i c e s f o r w i n d i n g c o m p e n s a t i o n. as the reference again and the same
the transformer and the 180° shift of the The method recommended is to select results would have been obtained. The
A-phase current on the CT secondar y the high-side winding as the reference wye current must adjusted by 330° in the
because of the opposite CT polarity on winding and shift the low-side currents by counterclockwise direction (because of

energize - July 2013 - Page 42


TRANSMISSION AND DISTRIBUTION
ABC rotation) to align with the reference chosen. Therefore, the proper
selection of winding compensation is TSCTC = 0 and TTCTC = 11.

The appropriate settings are: PHROT = ABC, CTCONS = Y,


CTCONT = Y, ICOM = Y, TSCTC = 0, TTCTC = 11

A second choice for winding compensation would be to select the


wye winding as the reference, and rotate the delta C-phase by the
appropriate number of degrees to be in phase with the wye winding
C-phase.

As Fig. 12 shows, the C-phase to neutral on the delta winding would


need to be rotated by 30° in the counterclockwise direction to align
with C-phase-to-neutral on the wye winding and the compensation
settings could be TSCTC = 1 and TTCTC = 12.

The appropriate settings are: PHROT = ABC, CTCONS = Y,


CTCONT = Y, ICOM = Y, TSCTC = 1, TTCTC = 12
Example 4

This transformer nameplate differs from the first three examples in


that the polarity of the H1 winding now connects to the nonpolarity
of the H3 winding. The system A-phase connects to the H1 winding,
and the system C-phase connects to the H3 winding. This is a
DACY connection because the polarity of A-phase connects to the
nonpolarity of C-phase. For the nameplate diagram in the example
and the ABC system phase rotation, the high-side currents will lag
the associated low-side currents by 30°, and the relay must account
for this phase angle shift. The phasor diagram in Fig. 14 shows the
A-phase load current flow through the transformer and the 180°
shift in the A-phase current on the CT secondary because of the
opposite CT polarity on the secondary of the transformer. The CT
secondary current angles in the figure are the correct angles for a
DACY transformer with ABC phase rotation.

For this example, there are also multiple choices for winding
compensation. The recommended method is to select the high-side
winding as the reference winding and shift the low-side currents by
the appropriate amount. In Fig. 15, the delta winding from neutral
to A-phase was chosen as the reference. The wye current must be
adjusted by 330° in the counterclockwise direction (because of ABC
rotation) to align with the reference chosen. Therefore, the proper
selection of winding compensation is TSCTC = 0 and TTCTC = 11.

The appropriate settings are: PHROT = ABC, CTCONS = Y, CTCONT = Y,


ICOM = Y, TSCTC = 0, TTCTC = 11 A second choice for winding
compensation would be to select the wye winding as the reference,
and rotate the delta A-phase by the appropriate number of
degrees to be in phase with the wye winding A-phase. As Fig. 16
shows, A-phase-to-neutral on the delta winding would need to
be rotated by 30° in the counterclockwise direction to align with
A-phase-to-neutral on the wye winding. Compensation settings are
TSCTC = 1 and TTCTC = 12.
The appropriate settings are: PHROT = ABC, CTCONS = Y,
CTCONT = Y, ICOM = Y, TSCTC = 1, TTCTC = 12
Example 5

The transformer connections of Fig. 17 are the same as Fig. 2 for


example 1. However, the CTs connect in the traditional manner
(e.g., transformer windings connect in wye and CTs in delta, or
transformer windings connect in delta and CTs in wye). Because of
the CT connections, internal compensation is not necessary. For the
transformer nameplate drawing in Fig. 17, if ABC phase rotation is
assumed, then the high-side currents will lead the associated low-side
currents by 30°. This is a DABY connection because the polarity of
A-phase connects to the nonpolarity of B-phase. The phasor diagram
in Fig. 2 shows the A-phase load current flow through the transformer.
The high-side current, Ia, connects to the relay’s IAS terminal. The
IAT terminal of the relay connects to Ia – Ib, and the Ia – Ib current

energize - July 2013 - Page 44


TRANSMISSION AND DISTRIBUTION

Fig. 17: ANSI standard delta-wye transformer, ABC system rotation, A-B-C
connected to H1-H2-H3, CTs connected wye-delta.

Fig. 18: System phase angles for DABY connection, ABC system rotation.

shifts 180° on the CT secondary because of the opposite CT polarity on the


secondary of the transformer. The CT secondary current angles in the figure
are the correct angles for a DABY transformer with ABC phase rotation.
T h e a p p r o p r i a t e s e t t i n g s a r e : P H R OT = A B C , C TC O N S = Y,
CTCONT = D, ICOM = D

Conclusions
The relay winding compensation settings provide winding compensations in
30° increments to allow for most transformer applications, including mobile
transformer applications. Care must be taken to connect the CTs and
system phases to the transformer to provide proper targeting and metering
quantities. The following guidelines must be applied whenever possible:
 All CTs should be connected in wye.
 The system phase must be connected to the corresponding relay
phase.
 The Global Phase Rotation Setting (PHROT) must be set to the phase
rotation of the system.
 The system connection diagram, system phase rotation, and
transformer nameplate diagram must be used to determine proper
winding compensation settings.
 The delta connection(s) must be identified as DAB or DAC by using
system phase connections and relay phase connections.
 TnCTC = 12 must be set for any winding that needs no phase angle
correction but is a grounded wye winding with wye-connected CTs.
Important points about delta connections:
 DABY transformers always result in the delta side leading the wye side
for ABC system rotation.
 DABY transformers always result in the delta side lagging the wye side
for ACB system rotation.
 DACY transformers always result in the delta side lagging the wye side
for ABC system rotation.
 DACY transformers always result in the delta side leading the wye side
for ACB system rotation.
SEL commissioning assistant software is available at no charge to help verify
CT connections and compensation settings for SEL-487E relays.
Contact Rudolf van Heerden, SEL, Tel 012 664-5930,
cmd@selinc.com 

energize - July 2013 - Page 45

Anda mungkin juga menyukai