By
N.K. BHATI
Copy Right YMPL 1
Course Introduction
• Objectives:
- what is your expectation? Please spell out.
Importance
• Metering system accuracy is governed by
instrument transformers, if used in LT CT or HT
CT/VT systems.( HT3 or HT 4)
• All errors add algebraically.
Meter errors
CT ERRORS
ENERGY METERING
System ACCURACY
VT ERRORS
Importance
• Meters may be of high accuracy, but are instruments
transformers too?,
generally not, may be one class lower.
Large old installed base, meters have been replaced but
CT/PT not changed.
• Accuracy of instrument transformers do change due to
• Aging,
• Environmental effects like ambient temperature,
temperature cycling , humidity etc
• line transients and surges leading to insulation leakage,
shorted turns ,
• fault currents leading to saturation of cores,
• Connected burden, lead length or drop across leads.
Importance
• Higher ratio CTs when used at lower loads,
may have large errors as they may operate at
lower % load.
• With static meters burden being low, if higher
burden CT/PT are used, their performance at
lower burden is questionable, as not even
specified by standards.
• Drop across leads in VTs, depending on burden
connected.
• If a PT or Ct is used for indication only, then
ratio errors are important, phase error doesn’t
matter.
Copy Right YMPL 8
Instrument transformers
• Voltage transformers
• Current transformers
• Combined CT/PT units or metering Units
Voltage Transformers
• Eg.: 12 / 28 / 75 KVp
Testing a VT
• Volt meters 5 VA
• Voltage coils of watt meters and power factor
meters 5 VA
• Voltage coils of frequency meters 7.5 VA
• Voltage coils of kwh, kvar meters 7.5 VA
• Recording – voltmeters 5 VA
• Voltage coils of recording power factor meters
and watt meters 7.5 VA
• Voltage coils of synchroscope 15 VA
Copy Right YMPL 29
Current Transformers
• Resin cast CTs: these are ring type CTs, with polyester
or PVC tape and then cast into resin. Resin works as
insulation as well as provides environmental protection.
Terminals and supporting clamps are also cast in the
resin.
• Accuracy class:
In the case of metering CT s, accuracy
class is typically, 0.2, 0.5, 1 or 3. This
means that the errors have to be within
the limits specified in the standards for
that particular accuracy class. The
metering CT has to be accurate from 5%
to 120% of the rated primary current, at
25% and 100% of the rated burden at the
specified power factor.
Design aspects….principle
With the secondary winding connected to the burden, and a
primary current (Ip) flowing, an alternating flux is induced in the
core.
This flux is of just sufficient value to induce in the secondary
winding an emf (Es), again of just sufficient magnitude to pass a
secondary current (Is), through the secondary circuit such that
there is absolute equality between the primary and secondary
ampere turns and precise phase opposition between them.
Np. Ip =Ns. Is
where
Np = No. of primary turns.
Ns = No. of secondary turns.
Calculation of errors
RATIO ERROR.
(Im Sin δ + Iw Cos δ)
% R. E. = -
100----------------------------------------
Ip
PHASE ANGLE ERROR
Im Cos δ – Iw Sin δ
P. E. = 3438 ------------------------------------ minutes
Ip
WHERE,
δ = OVERALL SECONDARY POWER FACTOR ANGLE.
Im = MAGNETIZING COMPONENT OF EXCITING CURRENT.
Iw = WATT-LOSS COMPONENT OF EXCITING CURRENT .
Ip = ACTUAL PRIMARY CURRENT.