® Battery
NAS Battery Applications
The views expressed in this presentation are the views of the author and do not
necessarily reflect the views or policies of the Asian Development Bank Institute
(ADBI), the Asian Development Bank (ADB), its Board of Directors, or the March 2018
governments they represent. ADBI does not guarantee the accuracy of the data
included in this paper and accepts no responsibility for any consequences of their
use. Terminology used may not necessarily be consistent with ADB official terms. NAS, the NAS logo are trademarks of ©
NGK
2014INSULATORS,LTD., registered
NGK Insulators, Ltd. All in the U.S.
rights reserved
Outline of NGK Insulators, Ltd.
PCS
Container
Controller
Containerized Battery Battery System
200kW (1,200kWh) 800kW (4,800kWh)
© 2017 NGK Insulators, Ltd. All rights reserved 3
Structure of NAS Battery Cell
■Special thin Ceramic Electrolyte realizes ultimate energy density.
(Most space is utilized for Sodium and Sulfur)
Al O
Na+ conduction layer
Sodium
(Na) Beta Alumina
Ceramic
Charge
RELIABILITY &
LONG DURATION COMPACT FAST RESPONCE MAINTENANCE
SAFETY
Operational ambient
Cycle Life : 4500 full discharge Temperature -20C to 55C
Calendar Life : 15 years
Round Trip Efficiency : 75-80%
[MW]
NAS
10
10
Discharge 6 hr or more
Redox Flow
11 System Size ~hundreds of MW
Lead Li-ion
0.1
0.1
Acid Supply Record 530MW/3700MWh
Overseas: 170MW
-2 Domestic: 360MW
1×10
0.01
1×10 -3
0.001
0 2 4 6 8
0 2 4 6 8
Duration [hr]
Power Type
Energy Type
© 2017 NGK Insulators, Ltd. All rights reserved 6
NAS Battery Applications Throughout the Grid
Power Plant
NAS
Naples
installations
Area of
increased renewable
energy generation
Most Typical
Non-Solar Generation
© 2017 NGK Insulators, Ltd. All rights reserved 11
Frequency Control at Miyako Island
■ NAS® stabilize frequency in remote island.
■ NAS® also shift energy and absorbs surplus of PV output during daytime.
Diesel 21.5MW
http://www.okiden.co.jp/environment/report2014/sec7/sec74.htm
PV4MW
NAS
Size of Miyakojima 159 km2 4MW(28.8MWh)
Location 290 km Southwest from
Okinawa(Naha)
Population 52,000people
Sira Sub-station
(20MW) W59(8MW)
E25(8MW)
Musaffah Sub-station
Saudi Border (40MW) GIC(4MW×3sites)
Emirates Energy Award 2015
CISC
MOSG(4MW)
Wathba (12MW)
15
Power
(1)Typical Sunny days
PV Support
10
evening peak
5 NAS+PV Energy Shift
D
0
C NAS Discharge D
-5
C
-10
NAS Charge
0 3 6 9 12 15 18 21 24
Time
Flat Target : 3.3[MW] Discharge during load peak : 5[MW]
20
Smoothing
15 & Energy Shift
10 Energy Shift
5
0
D D
-5
C C
-10
0 3 6 9 12 15 18 21 24
Fluctuated PV
Flat Generation
Battery Power
Charge
Discharge
Generation by Generators
・Whole Day: 632 MWh/day (Δ 104 MWh)
・Evening Peak: 170 MWh/day (Δ 51 MWh)
:Charge :Discharge
2:Substation Application
Photovoltaic
■ NAS battery can provide effective solutions to any issues due to huge
introduction of renewable energy on transmission & distribution grids.
Recommendations:
1) Recognizing battery for grid application as an essential infrastructure for realizing
introduction of further renewable energy and setting up a scheme to share the
cost by people having the benefit.
2) Establishing regulation for grid operator to own battery.
END