M-0329B LTC
Backup Control
M-0329B Backup Control
CONTROLS
• Fully transient protected and operates within ±1% voltage accuracy over
a temperature range of –40° to +80° C
–1–
The M-0329B LTC Backup Control provides the extra protection that can save your customers from the hazards
and inconvenience of excessively high or low voltage. Defective LTC tapchanger controls can cause either too
high or too low a voltage along the line, possibly damaging customers' motors, computers or televisions. Even
when the control is operating properly, customers close to the transformer may receive dangerously high voltage
as the line drop compensator attempts to maintain a constant voltage under heavy load at a central point on the
distribution line. The Beckwith Electric M-0329B LTC Backup Control can be installed as a solution to both of
these problems.
The LTC Backup Control will prevent a defective LTC tapchanger control from running the voltage outside the
upper and lower voltage limits and, in addition, will prevent the line drop compensator from raising the voltage too
high under full load or overload conditions. Setting the voltage bands on the M-0329B slightly wider than the
transformer control limits will assure that a failed control will not result in a runaway LTC transformer. Under full
or overload conditions, the control automatically takes over as an upper voltage limit control, not affected by load
current, to prevent damage to equipment close to the transformer. While the Block Raise contact prevents a raise
operation, a Lower contact forces the tapchanger down if the primary voltage should subsequently rise.
Features
Block Raise and Block Lower voltage levels are set by accurately calibrated BANDCENTER and BANDWITH
controls, similar to those found on LTC transformer controls.
BLOCK RAISE/LOWER and LOWER LEDs indicate backup control status.
Block Raise, Block Lower, Lower and Alarm contacts provide outputs to drive external components.
Inputs
Power: 90 to 140 V ac, 50/60 Hz, 2 W at 120 V ac
Voltage: Less than 0.2 VA burden at 120 V ac input
LED Indicators
The BLOCK RAISE/LOWER LED will light to indicate when the voltage is outside the band.
The LOWER LED will light when the voltage exceeds the Block Raise level for an adjustable time period.
Output Contacts
Output Contacts: Contacts are rated at 2 A at 120 V ac.
Blocking Contacts: Contacts will operate within 0.2 seconds after a voltage excursion to prevent the transformer
control from causing another tapchange.
Alarm Contacts: After a fixed 3 minute time delay, if the voltage excursion is still present, the alarm is activated
to indicate control failure.
Environmental
Temperature Range: Operates within ±1% voltage accuracy as per the following:
IEC 68-2-1 –40° C 96 hour duration
IEC 68-2-2 +80° C 96 hour duration
IEC 68-2-3 +40° C 93% RH 96 hour duration
Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.
Transient Protection
Input and output circuits are protected against system transients. The M-0329B will pass all the requirements
of ANSI/IEEE C37.90.1-1989, which defines oscillatory and fast transient surge withstand capability. All
inputs and outputs will withstand 1500 V ac to chassis or instrument ground for one minute. Voltage inputs
are electrically isolated from each other, from other circuits, and from ground.
All faces of the relay, with the chassis solidly grounded, have been exposed to Radio Frequency Immunity
testing and have successfully passed with a field intensity of 20 V per meter at typical utility frequencies of
144 MHz, 438 MHz, and at 450 MHz.
Physical
Size: 5–3/4" high x 8–3/4" wide x 3–1/2" deep (14.6 cm x 22.2 cm x 8.9 cm)
Approximate Weight: 3 lbs (1.4 kg)
Approximate Shipping Weight: 5 lbs (2.3 kg)
– This sign warns that the area is connected to a dangerous high voltage, and you
must never touch it.
– This sign means that you should refer to the corresponding section of the operation
manual for important information before proceeding.
1.1 Introduction
Defective tapchanger controls can create either The amount of Deadband between the Block Raise
too high or too low a voltage along the line, possibly and the Lower levels can be selected by the
damaging customer's motors, computers or customer, using a switch on the side of the unit.
televisions. Even when the control is operating The BANDCENTER dial has settings from 100 V
properly, customers close to the transformer may rms to 140 V rms that allow the relay to match any
receive dangerously high voltage as the line drop transformer control.
compensator attempts to maintain a constant
voltage under heavy load at a central point on the Above the Block Raise level, the relay will detect
distribution line. The Beckwith M-0329B LTC voltage above the Lower setpoint. This point is at a
Backup Control can be installed as a solution to fixed level above the Block Raise, and will initiate a
both of these problems. lower tapchange operation if exceeded for an
adjustable amount of time (1 to 30 sec) as set on
Designed to replace the Beckwith M-0029 LTC the TIME DELAY control.
Control Backup Relay as well as the M-0145 First
Customer Protector, the single-phase, solid-state Blocking contacts on the M-0329B will operate
M-0329B has three main functions: within 0.2 seconds after a voltage excursion to
prevent the defective transformer control from
1. Prevent a defective LTC tapchanger
control from running the voltage outside causing another tapchange. After a fixed 3 minute
the upper and lower voltage limits. time delay, if the voltage excursion is still present,
the ALARM contact is activated to indicate control
2. Prevent the line drop compensator from failure.
raising the voltage too high under full
load or overload conditions. Under full or overload conditions, the M-0329B
automatically takes over as an upper voltage limit
3. Lower the voltage if the regulated voltage
control, not affected by load current, to prevent
goes above the Block Raise setpoint by
damage to equipment close to the transformer.
a fixed bandwidth, as shown in Figure 1.
While the Block Raise contact prevents a raise
operation, a Lower contact forces the tapchanger
The Block Raise and Block Lower voltage levels down if the primary voltage should subsequently
are set by accurately calibrated dials, labeled rise.
BANDCENTER and BANDWIDTH, similar to those
found on LTC transformer controls.
LOWER
FIXED DEADBAND
V BLOCK RAISE
BR
1/2 BW
ADJUSTABLE
VC BANDWIDTH BANDCENTER
1/2 BW
V BLOCK LOWER
BL
–1–
M-0329B Instruction Book
2.1 Installation
The mounting and outline dimensions are shown The ALARM contacts should be used to alert
in Figure 2, and the external connections in Figure 4. system operators that a problem has occurred and
that the LTC transformer or regulator is not
■ NOTE: TB refers to Terminal Block numbers operating. It must be recognized that the ALARM
shown in Figure 4 External Connections. contacts may operate under conditions of heavy
load using the two-wire connections and the line
The M-0329B can be connected as a two-terminal drop compensator.
device, by paralleling the Power Input (TB1-1 to
TB1-2) and the Voltage (Sensing) Input (TB1-3 to The output blocking contacts should be connected
TB1-4). With this connection, the BANDCENTER in series with the raise and lower contacts from the
and the BANDWIDTH controls can be set so that LTC control. In some control circuits, a timing relay
an upper voltage and a lower voltage limit are is used. There, the blocking contacts should be in
established at the desired levels. The M-0329B will series with the timing relay contacts. The blocking
block any further tapchanger raise operations when relay contacts should not be connected to drop out
the regulated voltage exceeds the upper voltage the motor starter relay once it is sealed in for a
limit. Also, if the voltage drops below the lower tapchange, since most tapchangers should not be
limit, the M-0329B will block any further lower stopped until the tapchange is completed. An
operations. Additionally, if the voltage level exception to this is a spring-driven tapchanger that
increases above the upper limit (Block Raise) the may be stopped at any time. Figure 6 shows the
M-0329B will lower the voltage, protecting connections for using the M-0329B with most of
customers from excessively high voltage levels. the Beckwith Tapchanger and Regulator Controls.
The M-0329B also provides the First Customer
Protection function that previously required a When power is suddenly changed from raise to
separate relay. If the LDC raises the local voltage lower, motors with centrifugal starters will continue
due to heavy load current, the M-0329B will protect to run in the wrong direction without reversing. A
nearby customers from high voltage, and will act defective control timer, for example, could lead to
as an LTC control around the upper voltage limit. this type of runaway situation. Here, the M-0329B
will open up the wrong connection if connected as
On controls where compensated voltage from the described above. The circuit of Figure 7 may be
line drop compensator is available, the M-0329B used instead, where timer relay KX permits the
can be connected as a four-wire device. The Power motor to stop regardless of its direction. It is
Input should be connected to a 120 V ac source assumed that the motor will start in the right direction
and the Voltage Input is then connected to the once it has stopped.
LDC compensated voltage.
Since sudden changes in the transformer primary
voltage may move the secondary voltage outside
the range of the LTC control and the M-0329B, a 3
minute timer is provided to allow a normal control
to correct the voltage. After 3 minutes of abnormal
voltage, the M-0329B ALARM contact will indicate
an abnormal condition. The BLOCK RAISE/
LOWER LED will be on, the ALARM relay contacts
TB1-14 to TB1-15 will be closed and TB1-15 to
TB1-16 will be open. The ALARM contacts will
also indicate an alarm condition if the AC power to
the M-0329B fails.
–2–
M-0329B Instruction Book
1-1/8" Max
(2.86 cm)
2-3/8"
(6.03 cm)
TB1
8-1/4"
(20.96 cm)
1/2"
(1.27 cm)
4-3/4"
4-3/4" (12.07 cm)
(12.07 cm)
5-3/4"
(14.61 cm)
1/4"
(.64 cm)
7-3/4"
(19.69 cm)
8-3/4"
(22.23 cm)
–3–
M-0329B Instruction Book
The M-0329B LTC Backup Control is listed to UL the figure below. The wire should be No. 16 AWG
Standards for Safety by Underwriters Laboratories inserted in an AMP #51864-1 (or equivalent)
Inc. (UL). To fulfill the UL requirements, terminal connector, and both screws tightened to 16 inch-
block connections must be made as illustrated in pounds torque.
16 AWG
AMP #51864-1
or equivalent
Tighten to 16 inch-pounds
Figure 3 Wire Terminations for External Connections as Required for UL Listing
TB1
1 120 V ac Power Input Hot
2 120 V ac Power Input Neutral
3 Voltage (Sensing) Input Hot
4 Voltage (Sensing) Input Neutral
5
BLOCK
6 • RAISE
7
8
BLOCK
9 • LOWER
10
11
12 • LOWER
13
14
15 • ALARM
16
■ NOTE: All contacts are shown in the inactive (normal) condition, i.e. the output contact between TB1-14
and TB1-15 is open for the No Alarm condition and will close to indicate an Alarm Condition.
–4–
M-0329B Instruction Book
4.1 Application
The M-0329B can be used in many applications Raise (BLK R) and the Block Lower (BLK L)
not related to LTC backup for a very accurate outputs can be used as overvoltage and
overvoltage and/or undervoltage relay. The Block undervoltage outputs, respectively.
TB1 TB1
1 1
120 V POWER
120 V 2 2
M-0329 3 M-0329
3
LDC VOLTAGE
4 4
MOTOR
SUPPLY
TAPCHANGER CONTROL
90 *11 1
120 Vac
R LOWER POWER
R *12 2
6 3
Voltage
BLK RAISE
c 4
7
9 14
Alarm
L BLK LOWER 15
10
L 90 B.U.
84R 84L
■ NOTE: *If first customer protection is not required, delete these connections.
–5–
M-0329B Instruction Book
TCC CONNECTIONS
M- 0067/M- 2067 7 8 9
M- 0271(TB1)/M- 2271 5 9 6
M- 0270/M- 2270 5 9 6
M- 0278(TB2)/M- 2278(TB3) 10 9 11
M- 0323 L J C
M- 0324/M- 2324 25 V2 23
M- 0338 10 9 11
M- 0339/M- 2339(TB4) 10 9 11
M- 0345 2 V1 3
M- 0355/M- 2355 R3 Vm L3
–6–
BL BR BL BR
Figure 7
2 2 5 1 1
BL BR * M-0329B K2 8
3 3 Block Raise.
L L * M-0329B K3 M-0329 K3
2 6 KX KX
3 B R * * 2 Block Lower. Block Lower
3 1
2 9
–7–
** Timer Relay Contact
shown before timing out.
BR
KX BL
L R
4 4
KX New Timer Relay - Delay on pickup to assure motor stops before powering in reverse direction.
R,L Existing Raise and Lower.
BR, BL New Block Raise and Block Lower Relays.
O Terminals on M-0329B Backup Relay.
AC/DC Converter
5.1 Adjustment
The Voltage Input, TB1-3 to TB1-4, is the voltage
that the M-0329B will monitor to provide the voltage
Accurately calibrated dials, labeled BANDCENTER protection functions described previously. The input
and BANDWIDTH, set the Block Raise and Block protection circuitry for the Sensing Input is the
Lower voltage levels. The dials on the M-0329B same used for the Power Input. Transformer T2
cover are calibrated in volts for use with a 120 V ac steps down the input level to a lower level used by
nominal voltage. the Ac/Dc Converter. U2-1, U2-7 and associated
circuitry form a precision active full-wave rectifier/
The following equations will assist the user in
filter that converts the ac Sensing Input to a dc
choosing the correct setpoints for the M-0329B.
voltage that is proportional to the average voltage
VBR = the Upper Voltage Limit (Block Raise) desired. level of the Sensing Input. This dc level at U2-1 is
offset by the BANDCENTER adjustment network,
VBL = the Lower Voltage Limit (Block Lower) desired. consisting of R3, R16, R17, R15 and R14; so that
the voltage at U2-1 equals +5.0 V dc when the
The Base Voltage is 120 V ac. Sensing Input level is equal to the setting of the
VBR + VBL BANDCENTER dial. Any variation of the input level
The Bandcenter Voltage VC = (1) from the BANDCENTER setting will cause the U2-1
2 voltage to deviate from +5.0 V dc by approximately
0.072 V dc/%.
The Bandwidth VBW = VBR - VBL (2)
Level Detectors
The Level Detector circuits compare the dc voltage
from U2-1 to dc levels set by the BANDWIDTH
6.1 Theory of Operation control. R21 and R4 are used in a voltage-divider
circuit to establish the bandwidth. The voltage
Refer to Figure 8, Schematic and Figure 9, Block across R21 and R4 is centered around +5.00 V dc
Diagram. so that a symmetrical band is formed around the
BANDCENTER setting. If the U2-1 voltage rises
Power Supply above the voltage at U2-9, the output at U2-8 goes
high to block any further raise operations of the
The Power Supply converts the 120 V ac power tapchanger. If the voltage drops below the level at
input to the dc voltages required for the M-0329B U2-12, the voltage at U2-14 goes high, blocking
circuitry. Components C1 and RV1 are used to any further lower operations of the LTC. When the
suppress transverse-mode transients on the input. U2-1 output voltage exceeds the level at U3-6, the
RV2 and RV3 are common-mode suppressors that voltage at U3-7 goes high, lighting the LOWER
allow up to 1500 V rms common-mode voltage but LED and initiating a lower operation. R23 through
will clip any transients above this level. T1 converts R28 provide a small amount of hysteresis at each
the 120 V ac input to 36 V ac, center-tapped at of the voltage levels in order to avoid oscillations in
T1-4. T1 also employs a Faraday shield that isolates the level detector outputs.
the secondary windings from common-mode
transients on the primary.
Power Supply Monitor
Diodes CR1 through CR4 form a full-wave recti- The Power Supply Monitor is used to delay the
fier that produces +24 V dc and -24 V dc from operation of the BLK R, BLK L, and LOWER relays
the secondary of T1. Capacitors C2 and C3 filter for approximately 2 seconds when power is applied.
the ac ripple off the +24 V dc; C7 smooths out This eliminates any relay chatter when the M-0329B
the -24 V dc. VR1 is a zener diode that clips off, is put in service. Also, this circuit monitors the level
to a safe level, any transients that may remain of the Power Input and disables the above relays if
on the +24 V dc, protecting U1 and U5. the voltage level is below 75 V ac.
–8–
M-0329B Instruction Book
–9–
M-0329B Instruction Book
TP21
-24V +24V
120VAC TP2 TP1
U5
CR1 CR2 R6 LM317
TB1-1 T1 10 3 2 JP1
1 F1 1 U-0256 11 VIN VOUT
HOT +15V
2W,5 C2 C18 C19 C4
ADJ
4 1N4004 1N4004 + C3 R102 1uf
1A C1 RV1 VR1 .05uf .01uf .01uf
CR3 CR4 1N5365B 600V 470uf 50V 124 50V 50V
2 8
TB1-2 .01uf 250V 36V 50V 1/4W,1 R103
1
2 125V 1.37K
NEUTRAL
6
1N4004 1N4004
1/4W,1
RV2 U1
1KV R9 LH0070
1.5K JP2 1 2
-15V IN OUT +10V
GND
2W,10 C5 C6
C7 VR3 .01uf .01uf
RV3 470uf +
50V 50V
275V CMZ5929B
50V 15V
(1N965B) R21
3
102
X1
1/8W,1
TP12
+10V
R18
1.78K
1/8W,1
+10V -15V
TP3 TP4 TP5
X2
8
7
6
5
4
3
2
1
S1
DPST
13
12
14
15
16
10
11
9
TP7
R2 R12
100K 66.5K
1/8W,1 1/8W,1
U3B
U2A TLC274 R44
C13 R23 6
3 LM224 - 7 3.9K
R10 R11 .68uf 1K 5 X3
+ 1
+
49.9K 24.9K R13 50V 2 1/4W,5
- 1/4W,5
1/8W,1 1/8W,1 24.9K
C12 1/8W,1 R24
CR6 3.3uf R14 330K
CR5 CR9 CR10
1N4004 50V 182K 1N4148 1/8W,5
1/8W,1 1N4148
+15V TP6
POT. 1N4004
C10 U2C
R25 9 LM224 CR12
INPUT U2B
- 8
1K 10 + X4
4
X6
X7
Figure 8 Schematic
–10–
M-0329B Instruction Book
R4 R3 R5
D X-0329B B
500 2K 500K
FRONT PANEL
CONNECTIONS J2
J1
1
2
3
1
2
3
4
5
6
P1 P2
1
2
3
+10V
+15
X1
R35 R36 R37
53.6K 56.2K 2.37
1/8W,1 1/8W,1 1/8W,1
TP10
R22
1.87K
1 / 8 W, 1
R16
R15 750
50K
1/2W,20 1/8W,1
R17
200
1/2W,20
2N2222A
CR15 R43
2
TP9 R38 5.1K 1
10K TB1-13
1/4W,5
U3D 1N4004 13
X2 1/4W,5
3
CR14 TLC274
U4D MMBD1501/A 13
12 R39 14 R80
11 10M 12
+15V +24V 13 TB1-12
1/4W,5 12 LOWER
4081 TP11 C16
4.7uf K1 4
R40 5
CR11 R29 63V 100K
100K CR16 3
1N4148 TB1-11
1/4W,5 1
R31 1/4W,5 +24V
11
680K
R41 1N4148 2
1K T75-24VDC
1/4W,5 1/4W,5
R30 +15V
267K +15V
1/8W,1 C14
TB1-7
R32 +15V 7
.1uf 510K
50V 1/4W,5 2N2222A
4
14
3 U4C U4B Q3
1 8 R46 TB1-6
2
5 BLOCK
2 10 4 15K 1 6
+10V
U3A 9 6 RAISE
1/4W,5 K2 4
TLC274
11
3
4 0 8 1 5
4081
7
CR17 3
+ 1 TB1-5
C15 R45
4.7uf 100K 5
R33
25V 100K 1/4W,5 1N4148 2
T75-24VDC
1/4W,5
R34 CR25
2K
1 / 4 W, 5 +24V
LED TB1-10
LOWER
BLOCK RAISE / LOWER 10
CR24
Q4 2N2222A
X3 U4A
1 R48 TB1-9
2
5
4081 CR18 3
R47
1 TB1-8
100K
1/4W,5 8
VR4 1N4148 2
+24V T75-24VDC
+15V
2N2222A
Q5
CR22 R54
2
TLC274 16
9 - R81
8 ?
1
X5 +
FUTURE
C17
4.7uf TB1-15 BLOCKING
63V R52 15
182K
1/8W,1 K4 ALARM
4
R56 5
CR23 3
1 TB1-14
3.9M +24V 14
1/4W,5 2
1N4148
X6 T75-24VDC
X7
–11–
M-0329B Instruction Book
–12–
M-0329B Instruction Book
7.1 Maintenance
Due to the extremely sophisticated nature of the ■ NOTE: Units returned with only a blown fuse
circuitry in the M-0329B, field repair is not are not covered by warranty and a
recommended. All units are fully calibrated at the nominal repair charge will be made for
factory prior to shipment; there is not need to re- replacement of the fuse. Please check
calibrate a unit prior to initial installation. Calibration the fuses before returning the M-0329B
is only required after a component is replaced. In for repair in order to avoid unnecessary
the event that a unit does not operate properly, it repair charges.
should be established that the problem is caused
by malfunction of a Beckwith unit and not caused To help in analyzing the problem, a complete
by an external fault or wiring error. Once this is description of the malfunction and conditions
assured, the entire unit should be returned to leading to the failure should be included with the
Beckwith Electric. Pack the unit carefully (in the unit.
original carton if possible), assuring that there is
adequate packing material to protect the contents. However, if you choose to repair the unit, it is
necessary to be completely familiar with the circuitry
■ NOTE: Any equipment returned for repair must involved, and have an adequate understanding of
be sent with transportation charges field effect devices. Be sure to carefully read the
prepaid. The equipment must remain
WARNING page at the beginning of this manual.
the property of the user. The warranty is
void if the value of the unit is invoiced to It is suggested that first a visual inspection be
Beckwith Electric at the time of return or made for any component that does not appear
if the unit is returned with transportation normal or appears to have overheated. Analysis of
charges collect. the circuit will then often lead to the cause of the
failure and components that need to be replaced.
If under warranty, units will be repaired rapidly and
returned at no cost and with return transportation If no obvious problems exist, it is suggested that
paid if the fault is found to be due to workmanship the TEST and CALIBRATION PROCEDURES be
or failure of material. If a unit is under warranty and followed until a portion of a circuit is detected
express shipment for return of the repaired unit is which does not perform as expected or until a
requested, shipping charges will be billed at the calibration point is found which will not meet
current rate. If the fault is due to abuse or misuse, requirements. These procedures should lead to a
or if the unit is out of warranty, a modest charge will determination of the defective component.
be made. Repair can normally be expected to take
two weeks, plus shipping time. If faster service is
required, it should be requested at the time of
return.
–13–
M-0329B Instruction Book
Please refer to the WARNING page at the beginning 3. A high impedance true rms digital
of this manual before proceeding. multimeter with an ac accuracy of at
least ±0.02% of reading, Fluke 45 or
Refer to Figure 10 for the test setup. equivalent.
4. Solder sucking syringe or solder wick.
Equipment Required
1. A stable 60 Hz source with fixed 120 V 5. Soldering iron - Weller Controlled Output
rms and proper load regulation so that Soldering Station Model MTCPL, 60 W,
the amplitude does not change more 120 V, 50/60 Hz or equivalent with
than 0.05 V rms when the relays are grounded tip.
energized or the functional indicator 6. An accurate stopwatch.
lamps are on.
2. A variac, 0 to 140 V adjustable
transformer.
2 120 V rms
•H FIXED
3 • N
INPUT
4 •
5 •
Block Raise •
6 •
7
M-0329B
INPUT
8 • ADJUSTABLE
Block Lower H
9 • 0 V TO 140 V ac
SUPPLY
10 • N
VARIAC
11 •
Lower
12 •
13
14
Alarm
15 120 V lamp or relay coil
for functional indicator.
16
–14–
M-0329B Instruction Book
–15–
M-0329B Instruction Book
Removing the Printed Circuit Board 2. Remove the old component and discard.
1. Remove the cover by loosening the four 3. Remove the excess solder using the
acorn nuts. solder syringe or wick, leaving the hole
2. Remove the four screws that hold the or pad clear to facilitate insertion of the
transformers to the base plate. new component.
Location of
Re ading Type of Wave form
Te s t Points
TP1 15 V K0.8 DC
TP4 10 V K.02 DC
TP6 15 V K0.8 DC
TP9 14 VK0.5 DC
–16–
M-0329B Instruction Book
Conditions
1. All terminals are open circuited.
2. Measurements are made with a Fluke
45 digital multimeter.
TB1- 5 TB1- 6 20 M 00
TB1- 8 TB1- 9 20 M 00
TB1- 11 TB1- 12 20 M 00
TB1- 15 TB1- 16 20 M 00
–17–
M-0329B Instruction Book
–18–
M-0329B Instruction Book
11.1 Calibration
–19–
M-0329B Instruction Book
PARTS LIST
This list includes all electrical and mechanical parts which could conceivably either require replacement or
be lost. The COMPONENT DESIGNATION is the same as that appearing on schematics or referred to in
Instruction Books.
The BECO NUMBER refers to an index maintained by the company. This lists the currently available device
which may be substituted even though the device originally supplied is obsolete and no longer available. Parts
marked by an asterisk* are not available from other sources. Either the original component or a current
substitute will be carried in stock by Beckwith Electric.
Parts not marked with an asterisk are normally available from an electronics components house. Those parts
or a current substitute will normally be available from Beckwith Electric stock.
In either case, when parts are ordered from Beckwith Electric, we will be responsible for supplying the current
replacement in the shortest possible time.
Sufficient detailed description is also given to permit purchasing from an electronics parts house, providing
the part is of equal or better quality to insure reliable operation. This may require some interpretation of
specifications which may be avoided by direct purchase from Beckwith Electric using the BECO NUMBER.
Note that in a few instances, components are selected in final test. Procedures described in the TEST
PROCEDURES Section must be followed in replacing these components.
COMPONENT BECO
DESCRIPTION
DESIGNATION NUMBER
COMPONENT BECO
DESCRIPTION
DESIGNATION NUMBER
F1 420-00719 Fuse, 1 A
–21–
M-0329B Instruction Book
COMPONENT BECO
DESCRIPTION
DESIGNATION NUMBER
R43 340-00065
–22–
M-0329B Instruction Book
COMPONENT BECO
DESCRIPTION
DESIGNATION NUMBER
–23–
M-0329B Instruction Book
COMPONENT BECO
DESCRIPTION
DESIGNATION NUMBER
REV. A
–24–
Legal Information
Patent Indemnification
The Seller shall not be liable for any property
The units described in this manual are covered by damages whatsoever or for any loss or damage
U.S. Patents, with other patents pending. arising out of, connected with, or resulting from
Buyer shall hold harmless and indemnify the Seller, this contract, or from the performance or breach
its directors, officers, agents, and employees from thereof, or from all services covered by or furnished
any and all costs and expense, damage or loss, under this contract.
resulting from any alleged infringementof United In no event shall the Seller be liable for special,
States Letters Patent or rights accruing thereform or incidental, exemplary, or consequential damages,
trademarks, whether federal, state, or common law, including but not limited to, loss of profits or
arising from the Seller’s compliance with Buyer’s revenue, loss of use of the equipment or any
designs, specifications, or instructions. associated equipment, cost of capital, cost of
purchased power, cost of substitute equipment,
facilities or services, downtime costs, or claims or
All rights reserved by Beckwith Electric Co., Inc. No reproduction may be made without prior written approval
of the Company.
BECKWITH ELECTRIC CO., INC.
6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A.
PHONE (727) 544-2326 • FAX (727) 546-0121
E-MAIL marketing@beckwithelectric.com
WEB PAGE www.beckwithelectric.com