TECHNICAL DATA SHEET

Instructions:
1 Kindly do not alter the contents of the cell which contain formulas
2 Click the appropriate TABS to select/go to the respective sheets.
3 Cells/Columns colour coding
Data Contain standard / Formulas / Results
Data to be Entered Manually
Select from Drop down
Resp. Dept. Prepared by

Doc No: PTC-BBT-D-014, Rev. 0 Date Approved by


Generator Protection Panel - Technical Data
Title: 23.06.2017
Sheet
GENERATOR PROTECTION PANEL - TECHNICAL DATA SHEET

Sl. No Description Unit Requirement Data Vendor Confirmation

1.0 GENERAL
1.1 Panel Type Self Standing Panel Yes / No
1.2 Degree of Protection IP-54
1.3 Type of Installation Indoor
1.4 Minimum Ambient Temperature °C 5
1.5 Maximum Ambient Temperature °C 40
1.6 Panel Height mm Vendor to specify
1.7 Panel Width mm Vendor to specify
1.8 Panel Depth mm
Vendor to specify
1.9 Panel Weight kg Vendor to specify
1.10 Auxiliary AC Voltage V 230V, 1Ph
1.11 Auxiliary DC Voltage V DC 110
1.12 Redundant DC Power Supply V DC Required
1.13 Cable Entry Bottom Entry
1.14 Paint Shade RAL 7035
1.15 Panel Labeling As per Manufacturer Standard
1.16 Mimic in Protection Relay Required
1.17 Communication Interface Profibus DP / Ethernet

Page 2 of 3
Sl. No Description Unit Requirement Data Vendor Confirmation

2.0 INTERNAL WIRING


2.1 Wire Insulation - FRLS
2.2 Control Wiring Sq.mm 2.5
2.3 Current Transformer Wiring Sq.mm 4
2.4 Voltage Transformer Wiring Sq.mm 2.5
As per Annex - Design Criteria -
Wire Colour
2.5 Electrical Works
2.6 Wire Marking Ferruled at both ends.
COMPONENTS AND
3.0 ACCESSORIES
3.1 Panel Illumination with Door Switch - Required
Panel Heating with Thermostat
Required
3.2 Control -
3.3 Ventilation - Exhaust Filters
3.4 AC Power Socket Required
3.5 Spare Terminals 20%
3.6 Terminal for CT With Shorting facility
3.7 Test Terminal Block Required
4.0 GENERATOR PROTECTION
4.1 Location In Generator Protection Panel
4.2 Relay Requirement Separate Protection Relay
4.3 Relay Model Vendor to specify
4.4 Make Vendor to specify
4.5 Protection Relay Redundancy Required
4.6 CT and VT Parameters As per HV Single Line Diagram

Page 3 of 3