Technical requirements for
 Technical requirements for medium- ___________________
medium-voltage 1
transformers
voltage transformers for use with SINVERT central inverters

SINVERT

Technical requirements for medium-


voltage transformers for use with
SINVERT central inverters
Application manual

04/2012
A5E03827321-02
Legal information
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

NOTICE
indicates that an unintended result or situation can occur if the relevant information is not taken into account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG A5E03827321-02 Copyright © Siemens AG 2012.


Industry Sector Ⓟ 04/2012 Technical data subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Table of contents

1 Technical requirements for medium-voltage transformers ......................................................................... 7


1.1 Rated voltages and low-voltage infeed..........................................................................................7
1.1.1 Rated voltages ...............................................................................................................................7
1.1.2 Low-voltage and high-voltage winding...........................................................................................7
1.1.3 Interconnection of the components................................................................................................8
1.2 Voltage peaks and filtering.............................................................................................................9
1.2.1 Transformer design........................................................................................................................9
1.2.2 Design of surge arresters (AC-side) ..............................................................................................9
1.3 Short-circuit voltages .....................................................................................................................9
1.4 Types of construction...................................................................................................................10
1.5 Special requirements for oil-immersed transformers ...................................................................10

Technical requirements for medium-voltage transformers for use with SINVERT central inverters
Application manual, 04/2012, A5E03827321-02 5
Table of contents

Technical requirements for medium-voltage transformers for use with SINVERT central inverters
6 Application manual, 04/2012, A5E03827321-02
Technical requirements for medium-voltage
transformers 1
1.1 Rated voltages and low-voltage infeed

1.1.1 Rated voltages


The rated voltage is dimensioned to the respective low voltage dependent on the inverter
type:

Inverter Rated voltage


SINVERT TL 500/1000/1500/2000 328 V
SINVERT PVS 500/1000/1500/2000 288 V
SINVERT PVS 585/1170/1755/2340 340 V
SINVERT PVS 600/1200/1800/2400 370 V
SINVERT PVS 630/1260/1890/2520 370 V

1.1.2 Low-voltage and high-voltage winding


/RZYROWDJH +LJKYROWDJH
ZLQGLQJ9$& ZLQGLQJN9$&

,QYHUWHU
VXEXQLW N:

&RQQHFWLRQRI
PHGLXPYROWDJHV\VWHP
VZLWFKJHDU

,QYHUWHU
VXEXQLW N:

/RZYROWDJH +LJKYROWDJH
ZLQGLQJ9$& ZLQGLQJN9$&

Figure 1-1 Configuration example of a medium-voltage transformer 1200 kVA


(370 V / 370 V / 21 kV)

Technical requirements for medium-voltage transformers for use with SINVERT central inverters
Application manual, 04/2012, A5E03827321-02 7
Technical requirements for medium-voltage transformers
1.1 Rated voltages and low-voltage infeed

● A separate isolated low-voltage and high-voltage winding is required for each inverter
subunit.
● If several low-voltage windings are available (four-winding transformer design), the
transformer must be suitable for use with asymmetrical load of the low-voltage and high-
voltage windings.
● The high voltage is selected between 8 kV and 66 kV dependent on country-specific,
grid-operator-specific, and project-specific requirements.

Note
The country-specific grid frequency, standards and regulations, as well as the stipulations
of the local grid operator must be complied with.

1.1.3 Interconnection of the components


,QYHUWHUVWDWLRQ

,QYHUWHUV
6,19(57396

0HGLXPYROWDJHWUDQVIRUPHU

0HGLXPYROWDJHVZLWFKJHDU

Figure 1-2 Basic principle of interconnecting components in the inverter station


in a configuration with SINVERT PVS 2000 or SINVERT PVS 2400 inverters

Technical requirements for medium-voltage transformers for use with SINVERT central inverters
8 Application manual, 04/2012, A5E03827321-02
Technical requirements for medium-voltage transformers
1.2 Voltage peaks and filtering

1.2 Voltage peaks and filtering

1.2.1 Transformer design


● The technical design of the transformer must be suitable for operation with pulsed
inverters.
● The voltage peaks can reach ±1500 V to ground (pulses). The rms value of the voltages
to ground must not exceed 800 V.
● The low-voltage winding must be designed for gradients dU/dt up to max. 500 V/ µs to
ground.
● For dry-type transformers, a shield winding (dU/dt filter) between the low-voltage winding
and the high-voltage winding can be dispensed with by means of appropriately
implemented design measures.
● Overvoltage protection in accordance with VDE 0101, Section 5.2.2.7 (spark gaps to VDE
0532-14) is required for all transformers.

1.2.2 Design of surge arresters (AC-side)


● The surge arresters must be suitable for pulsed operation.
● The surge arrester must be effectively designed for voltages of ±1500 V and 800 V AC.
One surge arrester must be installed per phase.
● It must be ensured that no grounding or artificial neutral point is caused by this
installation.

1.3 Short-circuit voltages


● The short-circuit voltage Uk must be selected at 6%. In doing so, 5.4% to 6.6% must be
maintained.
● With four-winding transformers, the short-circuit voltage between the low-voltage
windings must be 10%.
● If the high-voltage winding is not connected, the measurement is carried out by short-
circuiting one low-voltage winding, and voltage infeed at the second up to the rated
current.
● For thermal dimensioning, the respective site conditions and isolation classes must be
taken into account.

Technical requirements for medium-voltage transformers for use with SINVERT central inverters
Application manual, 04/2012, A5E03827321-02 9
Technical requirements for medium-voltage transformers
1.4 Types of construction

1.4 Types of construction


● The permissible types of construction are Dy5Dy5 and Dy11Dy11.
● The neutral point must not be brought out on the low-voltage side.
● At least 5 voltage levels must be brought out on the high-voltage side:
-5.0%, -2.5%, rated voltage, +2.5% and +5%

Note
In the case of thin-film modules, a range of up to -15% may be required, depending on
the manufacturer.

● Since it is an infeed transformer, the rated voltage must be 5% higher than the rated grid
voltage (rated grid voltage 20 kV, rated transformer voltage 21 kV).
● When using the transformer in conjunction with the Siemens 8DJH switchgear, the rated
voltage of the transformer must not exceed 24 kV.

1.5 Special requirements for oil-immersed transformers


If oil-immersed transformers are used, oil sumps must be provided and acceptance-tested by
an appointed person depending on the location of use (water regulations). In water reserves,
special permits must be obtained for transporting and using oil sumps.
With oil-immersed transformers, a suitable dU/dt filter shield winding must be provided
between the low-voltage and high-voltage winding. This must be grounded on the tank.

Technical requirements for medium-voltage transformers for use with SINVERT central inverters
10 Application manual, 04/2012, A5E03827321-02
Service & Support
Download catalogs and information material:
www.siemens.com/sinvert/infomaterial

Newsletter - always up to date:


www.siemens.com/sinvert/newsletter

E-Business in the Industry Mall:


www.siemens.comindustrymall

Online-Support:
www.siemens.com/sinvert/support

Contact for all technical information:


Technical Assistance
Tel.: +49 (911) 895-5900
E-Mail: technical-assistance@siemens.com
www.siemens.com/sinvert/technical-assistance

Siemens AG Subject to change without prior notice


Industry Sector Order No.: A5E03827321-02
Postfach 23 55 © Siemens AG 2012
90713 FÜRTH
GERMANY

www.siemens.de/industry

Anda mungkin juga menyukai