Model
PROMET-410I : OCR/OCGR (50/51)(50N/51N) 7.Diagnosis function
PROMET-410V : OVR/UVR/OVGR (59, 27, 64) Auto-diagnostic fault indication to facilitate repair after
PROMET-410D : SGR(50/51)(50N/51N)(64)(67N)(67G)
detection of permanent internal relay fault. Continuous
self-supervision of relay hardware and software for
enhanced system reliability and availability.
1.Equipment (Drawout type)
8.Communication(option)
1) Standard size (H×W×D): 187×110×182mm
2) Weight: 1.3kg
Items Specifications
RS485 Two-wire, Half duplex, isolated (on rear side)
Type
2.Control Power optic port (on front side)
1) Input voltage: AC/DC 110-220V (Free Voltage), Baud Rate 9600/19200bps
AC/DC 20-60V(option) Protocol MODBUS-RTU, DNP3.0, IEC60870-5, Lonworks,
BAC net
2) Power Consumption: 5W or less
1
Recording function
2
Over Current & Earth Fault Relay [50/51x3][50N/51N] PROMET-410I
FEATURES
The multi-OCR is a microprocessor based digital type
protective relay that has 3 phases over current with residual
ground over current detecting function and is provided with
normal-inverse, very inverse, extremely inverse, definite and
instantaneous functions. OCR and OCGR can be set the
functions independently.
The relay has electric current relaying elements, OCR and
OCGR etc Moreover, It enables real-time and remote
supervisory & control by facilitating alignment with central
supervisory system through various communication methods.
It's main functions and features are as follows:
Function
1.Over Current Protection 2.Setting range and characteristic of relay
PROMET performs relay functions by using 4 protection functions
inverse time characteristic curves for electric
current and 1 definite time characteristic curve Relay Relay Pickup set Operation time set
Characteristic
in compliance with IEC-60255 standards. Function type Setting range Step Setting range Step
Instant
1.0~120(A)
Time ,Block 1A 0.04-120s 0.01 Instant
The following is a formula T=
β T
−C × m (I>>)
of inverse time characteristic
α
I −1 10
OCR Normal Inverse
curve for current. (50/51) Delay Very Inverse
0.5~25(A)
Time 0.1A 0.1-50.0 0.1 Extremely Inverse
,Block
α β C (I>) Long inverse
Normal Inverse 0.02 0.14 0 0.1-50.0Sec 0.1Sec Definite time
Very Inverse 1 13.5 0 Instant
Time 0.5~80(A) 0.1A 0.04-120s 0.01 Instant
2 80 0 ,Block
Extremely Inverse (Io>>)
Long Inverse 1 54 0 OCGR Normal Inverse
(50/51N) Delay Very Inverse
The following is a formula Tm 0.1~20(A)
T = 2× Time
,Block
0.1A 0.1-50.0 0.1 Extremely Inverse
of definite time curve for current. 10 (Io>) Long inverse
0.1-50.0Sec 0.1Sec Definite time
3
Over Current & Earth Fault Relay [50/51x3][50N/51N] PROMET-410I
Operating time/curve
10000.00
1000.00
100.00
Time
10.00 50.0
(Sec) 40.0
30.0
20.0
10.0
5.0
1.00
1.0
Tm = 0.5
0.10
0.01
1.0 10.0 100.0
Ratio (I / Is)
1000.00
100.00
Time
(Sec) 10.00
50.0
40.0
30.0
20.0
1.00
10.0
5.0
0.10
1.0
Tm = 0.5
0.01
1.0 10.0 100.0
Ratio (I / Is)
4
Over Current & Earth Fault Relay [50/51x3][50N/51N] PROMET-410I
10000.00
1000.00
100.00
Time 10.00
(Sec)
1.00 50.0
40.0
30.0
20.0
10.0
0.10 5.0
1.0
Tm = 0.5
0.01
1.0 10.0 100.0
Ratio (I / Is)
1000.00
100.00
10.00
Time 1.00
(Sec)
50.0
40.0
30.0
20.0
10
10.0
5.0
1.0
Tm = 0.2
0
1.00 10.00 100.00
Ratio (I / Is)
5
Over & Under Voltage Relay [59x3][27x3][64] PROMET-410V
FEATURES
Up to now OVR and UVR relays were separately set and
also operated but they are compacted in one relay unit,
so very convenient for handling, too.
As assembled with state of art and multifunction, it is
most suitable and applicable to protective coordination.
Volt meter being installed it can be used for measuring.
Electronic indicator can accurately detect troubles, and
surely indicate electric trouble.
It is able to continue self-supervision with auto-
diagnosis of internal faults.
It is able to record the last time fault and event for
statistical analysis.
The setting tap value is memorized by F-RAM, when the
power supply turns off. It is able to confirm each setting
The relay has voltage relay elements, UVR, OVR and tap value by "Enter" key, after the power supply is
OVGR etc Moreover, It enables real-time and remote restored.
supervisory & control by facilitating alignment with central
supervisory system through various communication
methods.
6
Over & Under Voltage Relay [59x3][27x3][64] PROMET-410V
7.Voltage Protection
PROMET410 performs relay functions by using inverse time characteristic curves for
electric current and 1 definite time characteristic curve in compliance with IEC-60255
standards.
β T
T= α
− C × m (OVR, OVGR Type)
V −1 10
8 Tm
T= × (UVR Type)
1 − (V) 2 10
α β C Relay Type
Tm
T = 2×
10
1)Setting range and characteristic of relay protection functions
7
Over & Under Voltage Relay [59x3][27x3][64] PROMET-410V
2)Operating time/curve
Normal inverse for OVR and OVGR Normal inverse for UVR
1000.00
1000.00
100.00
100.00
50.0
Time Time 40.0
(Sec) 50.0 (Sec) 30.0
40.0 20.0
30.0
20.0 10.00 10.0
10.00
10.0
5.0
5.0
Tm=0.2
Tm=0.2
0.10
1.00 1.20 1.40 1.60 1.80 0.10
0.20 0.40 0.60 0.80 1.00
Ratio (V / Vs) Ratio (V / Vs)
10000.00
1000.00
100.00
Time
10.0
(Sec) 10.00 8.0
6.0
4.0
2.0
1.0
1.00
0.2
0.1
0.10
0.01
1.0 10.0 100.0
Ratio (V / Vs)
8
Connection View
The current input will be linked to A, B, C phases using 3 CT, 01, 03 and 05 and N phase will be
connected using the sum of the three phases. If connection is done based on ZCT, electric current input
will be linked to 07 and 08 of ZCT terminal unlike the picture and remaining 02, 04 and 06 terminals
of A, B and C phases will be connected to CT L terminal of A, B and C phases. (Fig. 2)
AC/DC 110-220V free voltage can be connected to power input terminal 16 and 18. Frame ground of
power can be connected to A20 of PROMET. Trip coil will be connected to 09 and 10 : +power is to 09
and -power is to 10.
A
B AC
C or
DC
CB
01 02 03 04 05 06 07 08 16 18
PROMET 410I
RS 485
15
19 17
09 10 11 12 13 14 20
TRIP-
ALM -
ALM -
TRIP+
ALM +
ALM +
1 1 2 2
The voltage inputs will be linked to A, B, C phases using 3 PT(01-06),and N phase will be connected using
GPT(07-08).Vo will be connected using GPT(07-08).(Fig.3)
A
AC
B or
DC
C
GPT
CB CLR
01 02 03 04 05 06 07 08 16 18
PROMET 410V
15
RS 485
17
19
09 10 11 12 13 14 20
TRIP+
TRIP-
ALM +
ALM -
ALM -
ALM +
1 1 2 2
9
Front Panel Layout
Display Panel
LCD Display
16 Char. × 2 Lines
Pickup LED
RUN LED
ALARM LED
10
Dimensional and Panel Cutout size (Unit : mm)
187
187
10
181.4
155.5
166 173
10
4.2
110