Anda di halaman 1dari 3

Contract No.

PT. PERTAMINA (PERSERO)


DIREKTORAT PEMASARAN

Document No. : NK-DS-INT-005

PT. NINDYA KARYA (PERSERO)

PROYEK PIPANISASI CY III (LOMANIS-REWULU) PHASE 2

DATA SHEET FOR SHUTDOWN VALVE

19/04/2018 For Bid Purpose Only SLP IN NA

Prepared Checked Approved Approved


REV. DATE DESCRIPTION
CONTRACTOR PTP
PROYEK PIPANISASI CY III
PT. PERTAMINA (PERSERO) (LOMANIS-REWULU) PHASE 2
DIREKTORAT PEMASARAN PT. NINDYA KARYA (PERSERO)
DOCUMENT NO TITLE REV PAGE
NK-DS-INT-005 DATA SHEET FOR SHUTDOWN VALVE - 1 dari 3

GENERAL NOTES

1. VTA means Vendor to verify / to provide the correct name, type, model, or value from required item.
2. All Instruments shall be supplied with a 316 SS nameplate with Instrument Tag No. and Model No. permanently inscribed.
3. All non corrosion resistant parts to be painted with manufacturers standard paint system.
4. Vendor to provide Manual Book (Operating & Maintenance Instructions), Material Certificates, Hydrotest Certificate.
5. Hazardous Area Certificate, Ingress Protection Certificate and Functional Test Certificate.
6. Vendor shall be responsible for correct model selection.
7. Fire safe for all ball valves construction shall comply to BS 6755 Part 2 or API 607/ API 6FA.
8. Valve Position Switch Cables are prefered to 2 cable entry 1/2" NPT-F.
9. Internal design of seats and seal shall be renewable.
10. Vendor to provide limit switch complete with local open/ close indicator.
11. Air filter regulator, solenoid valve, manual reset should be installed on SS 316 plate .
12. The closing time of actuated ball valve shall not exceed 3 seconds plus 1 second per inch of valve size.
13. The opening time is 2 seconds (maximum) per inch of valve size.
14. For Paint and Finish, Refer to Document No. CY3-EC-40-SP-003-A4 General Specification for Painting & Protective Coating.
15. Vendor shall be purpose schematic control / shutdown diagram for approval.
PROYEK PIPANISASI CY III
PT. PERTAMINA (PERSERO) (LOMANIS-REWULU) PHASE 2
DIREKTORAT PEMASARAN PT. NINDYA KARYA (PERSERO)
DOCUMENT NO TITLE REV PAGE
NK-DS-INT-005 DATA SHEET FOR SHUTDOWN VALVE - 2 dari 3

1 Tag Number See Page 3 of 3 48 Tag No. Solenoid Valve See Page 3 of 3
GENERAL

2 Service See Page 3 of 3 49 Solenoid Type 3 Way Valve


3 Line No. Equipment No. See Page 3 of 3 - 50 Manual Reset Required
4 P&ID See Page 3 of 3 51 Degree of Protection Ex 'd', Explosion Proof
5 Pipe Size In 12" - ANSI 600#, Sch. STD 52 Hazardous Area Classification Zone 1, Group IIA, T2
PIPE DATA

6 Out 12" - ANSI 600#, Sch. STD 53 Supply Voltage 24 VDC, Loop Power
7 Pipe Material API 5L X46 ERW BE 54 Power Consumption 10 Watts (Max.)

SOLENOID VALVE
8 Pipe Insulation N/A 55 Body Size Number of Ports VTA VTA
9 Process Fluid Premium / Solar / Pertamax 56 Body Material 316 SS
10 Fluid State Liquid 57 Electrical Entry 1/2" NPT-F
2
11 Max. Shut off Pressure 80 kg/cm g 58 Pneumatic Connection 1/2" NPT-F (Vendor shall be responsible
for correct Model No.)
3
12 Flowrate Operating 900 59 Exhaust Bug Screen Yes, Required
PROCESS CONDITION

m /hr
2
13 Pressure Design See Page 3 of 3 kg/cm g 60 Manufacturer Refer to Approved Vendor List
2
14 Operating See Page 3 of 3 kg/cm g 61 Model Number Vendor shall be responsible for correct
Model No.)

15 Temperature Design 60 °C 62 Actuator Type Pneumatic Spring Return


16 Operating 35 °C 63 Single Acting
17 Ambient Temperature (Min./ Max.) 27 - 35 64 Valve Control Station Set Integral
18 Valve Design API 6D 65 Actuator Mechanism Manufacturer Standard
19 Body & Bonnet Material Carbon Steel A216 WCB 66 Operational Position Open
20 Body Type Ball 67 Nitrogen Supply Failure Position Fail Close
21 End Connection 12" - 600# RF 68 Power Failure Position Close
2
22 Flange Facing & Finish ASME B16.5 69 Available Nitrogen Supply (Min/ Max) 2.5 5 kg/cm g
23 Valve Configuration Trunnion Mounted 70 Opening / Closing time (Max) 24 15 second
PNEUMATIC ACTUATOR

24 Bore Size Full Bore 71 Filter & Regulator Required


25 Degree of Rotation 90 degree (Vendor shall be responsible for 72 Actuator Orientation Horizontal
correct Model No.)

26 Fire Safe Design API 6FA 73 Torque Safety Factor 1.3


27 Ball / Disc / Plug Trim Material 316 SS 74 Adjustable Stroking Time VTA
VALVE

28 Stem Material 316 SS 75 Actuator Test Pressure VTA


29 Seat Material 316 SS 76 Handwheel N/A
30 Seat Contact Surface Material RPTFE / Nylon (Vendor to Verify) 77 Paint & Finish See General Notes No. 14
31 Stem Seal Material PTFE (Vendor to Verify) 78 Partial Stroke Test Facility N/A
32 O-Ring Material Viton or RPTFE Based 79 Manufacturer Refer to Approved Vendor List
33 Tightness/Leakage Class Tight Shut off / Class IV 80 Model Number Vendor shall be responsible for correct
Model No.)

34 Painting & Finish See General Notes No. 14 81 Hydro Pressure Yes
35 Manufacturer Refer to Approved Vendor List 82 (As Per API 6D or API 598 )
36 Model Number Vendor shall be responsible for correct Model 83 Leakage Test Yes
TEST

No.)
Shall not exceed ISO 5208 rate A (no
37 Switch Type Hermetically Seal, Beacon Type 84 visible leakage)
38 Tag No. Limit Switch Open See Page 3 of 3 85
39 Tag No. Limit Switch Close See Page 3 of 3
40 Degree of Protection Ex 'd', Explosion Proof
41 Hazardous Area Class. Zone 1, Group IIA, T2
42 Contact Configuration DPDT
LIMIT SWITCH

43 Contact Rating 24 VDC, 2A


44 Cable Entry 1/2" NPT-F
45 Housing Material Manufacturer Standard
46 Manufacturer Refer to Approved Vendor List
47 Model Number Vendor shall be responsible for correct Model