Anda di halaman 1dari 5

Design of a water flow and usage meter

S Botha, LA Meijsen, GP Hancke and BJ Silva


Department of Electrical, Electronic and Computer Engineering
University of Pretoria
Pretoria, South Africa
Corresponding author: silva.bjc@gmail.com

Abstract— South Africa could potentially face a shortage of meter generally only have a five year life expectancy. The
water in the near future. Efficient and low cost methods to magnetic flow meter is the next generation of meters that the
determine water usage are vital to help prevent this issue. Flow municipalities and water utilities will employ as the life
and usage meters are necessary to ensure accurate usage expectancy is much greater and these meters which are located
readings. An electromagnetic flow meter and a water usage meter
outside the pipe, thus there is no maximum pressure and head
were developed. The designed module can be implemented on a
standard water pipe at residential areas. The developed system loss to consider. The meter that designed in this paper is an
harvests energy using a solar panel. ultrasonic flow meter. Ultrasonic flow meters are usually used
in industrial, sewage and medical fields. Their non-invasive
Keywords— water flow meter; water usage; water supply. feature makes them popular for pipe systems that are large and
I. INTRODUCTION already existing. The problems addressed in this work are the
design of an electromagnetic water flow meter and a water
By the year 2020 South Africa could experience a critical usage meter that harvests energy from the sun. The proposed
shortage of water as a result of water demand from consumers system is completely independent of any external power
exceeding the water supply [1]. Therefore water utilities and sources.
municipalities would be required to perform appropriate The rest of this paper is organized as follows: some
planning and water management to avoid water usage background to put the proposed system in context is presented
restrictions in the future. Measurements from flow meters in Section II; an overview of the proposed system is given in
allow the water utility to make day-to-day decisions and long- Section III; the design and implementation are discussed in
term planning for the future, as well as charging customers for Section IV; the results are presented and discussed in Section
water used. Measurements are done by employees of the water V; and in Section VI, the paper is finally concluded.
utility and/or municipality. This introduces a human error
factor which could result in incorrect charges of customers and II. BACKGROUND
also affect future planning. Thus the problem addressed in this A. Electromagnetic flow meters
work was to eliminate the human error through sending the
An electromagnetic flow meter uses the principle of
water usage measurement directly to the water utility, hence
Faraday’s law of induction [8] which states that a potential
improving the service delivered to customers. Furthermore, difference can be measured across two electrodes in a fluid
Internet-of-Things (IoT) and Wireless Sensor Networks when a magnetic field is induced perpendicularly to the
(WSNs) [2] are ubiquitous and make lot of different electrodes. The electrodes have to be placed in the pipe and
monitoring applications possible [3], especially in harsh need to be in contact with the fluid in the pipe. When there is
environments, where water usage has to be monitored as well an electromagnetic field across the pipe the ions in the fluid
[4], [5]. The hardware platforms needed to develop these separate, into positive and negative ions, and induce a potential
applications need to be taken into consideration as well [6], difference across the electrodes. Therefore the fluid in the pipe
[7]. has to be a conductive fluid. To produce an electromagnetic
field across the pipe a Helmholtz coil will be implemented. A
Municipalities and water utilities generally own read and Helmholtz coil is used in order to create a uniform
maintain water meters. Currently employees are required to electromagnetic field across the pipe, to ensure that the ions in
drive to each and every meter owned in order to collect water the liquid will be separated evenly. This is important as
usage reading ideally on a monthly basis. Positive complete separation of the ions in the liquid is needed, to
displacement (PD) meters are usually used as they are measure the correct potential difference across the electrodes.
relatively accurate at low to moderate flow rates, which is the In order to reduce power consumption the magnetic field will
case in residential and small commercial applications, and be driven with a DC signal instead of the conventional AC
they are economical. signal.
To produce an electromagnetic field across the pipe a
However, due to the rotating parts and seals inside the flow Helmholtz coil can be implemented as in [9]. A Helmholtz coil
meter, as well as the built in strainer, some maintenance is can be used in order to create a uniform electromagnetic field
required from time to time to guarantee accuracy as these across the pipe, to ensure that the ions in the liquid will be

978-1-5090-3474-1/16/$31.00 ©2016 IEEE 6211


separated evenly. This is important as complete separation of and its error accuracy curve for the V110 KSM volumetric
the ions in the liquid is required, to measure the correct meter can be found in the datasheet in reference [12].
potential difference across the electrodes. Helmholtz coils are
often used with low frequency requirements, for example it is
used for treatment of soybeans in [10]. Such a coil is illustrated III. OVERVIEW OF THE SYSTEM
in Fig. 1. Fig. 2 shows the functional diagram of the water usage
meter and Fig. 3 shows the concept design of the final circuit of
the water flow meter.

Fig. 1. Example of a Helmholtz coil [8].

A Helmholtz coil consists of two coils placed parallel to one


another. Each coil has the same diameter and the same number
of turns. Both coils are wound in the same direction (wound in
series) and the copper windings continue from the first coil Fig. 2. Block diagram of proposed water usage meter.
onto the second coil. The windings on the coil were wound
with an insulated copper wire. A magnetic field is created The system was powered by a renewable energy source
when a charge is in motion, where charge is the current in the Functional unit (FU) 1. The output of the renewable energy
coils. The electromagnetic field is generated between the coils source (FU1) was stored in a storage battery (FU2). In order to
where the linearity and strength of the magnetic field is power the processing unit (FU4), the flow meter (FU5) and its
directly related to the distance between the two coils and the circuitry and the communication module (FU7), power
current through them. converters (FU3) was required to deliver the correct voltage
and current ratings using the storage battery’s (FU2) output as
B. Water usage meters input power. Data was received and send from the processing
There are many types of flow meters used to measure the unit (FU4) to the flow meter (FU5) through an engineering
flow rate of the liquids and gasses; however this literature interface, where the processing unit (FU4) processed and
study will focus on three flow meters that are able to measure manipulated the data received in order to convert measured
low to moderate flow rates of cold potable water, which is the flow rates to the amount of water used. The flow meter (FU5)
case in residential and small commercial applications, was investigated and a suitable meter was designed and
typically between the ranges of 15 l/h (liters per hour) to 4,500 manufactured. The user interface (FU6) ideally consisted of a
l/h. push button and a liquid crystal display (LCD) screen and
Municipalities and water utilities prefer to use the PD enabled the user to read off the water usage measurements
meters, also known as volumetric meter, as these meters are locally. The processing unit (FU4) also 4 communicated with
relatively accurate at low to moderate flow rates, and they are the communication module (FU7) to send water usage
rather inexpensive. The PD meter measures the volume of the measurements a recipient (FU8).
fluid, which is accomplished by its “bucket” shaped design.
Most PD meters consist of multiple “buckets” that are both
valved and geared together, so that whilst some buckets are
filling up, the others are emptying. The driving force of this
action comes from the stream as a pressure drop.
There are many different types of PD meters used to
measure fluid which include reciprocating piston, rotating
discs, sliding vanes, rotational vanes, oval gear, nutating discs,
metering pumps and lobed impellers. However, in this text,
the volumetric meter with semi-positive rotary piston type
(V110T KSM) will be the focus. This PD meter caters for
flow ranges of 15 l/h to 7000 l/h at which readings meet the
criteria for accuracy of water meters of WWA which states
that meter’s measured error at low flow should not exceed 5%,
and at high flow should not exceed 2% [11]. The typical flow Fig. 3. Concept circuit design of magnetic flow meter.

6212
The processing unit is a microcontroller. The to propagate along the path length in the measured flow. The
microcontroller is both the central controlling unit as well as ultrasonic frequency typically used to measure the flow of fluid
the time difference collection module. The microcontroller ranges between 0.4 to 2 MHz. For a short propagation path
selected for this work was the PIC32MX795F512L, as it has length the transducer frequency selected should be in the high
the ability to realize functions such as generating, collecting relative high range [13].
and processing the signals, accounting the time of the forward
(downstream) and reverse (upstream) direction transmission, The ultrasonic transducers that were selected had both
calculating the flow rate, as well as communicating with transmitting and receiving properties, and are waterproof, thus
external communication link and user interface. the impedance matching layer is matched with that of water.
The transducers also have a center frequency of 1.2 MHz, and
IV. DESIGN AND IMPLEMENTATION bandwidth of 0.1MHz. As mentioned, the ultrasound intensity
is reduced when the beam spread increases and with a wide
This section contains information on the design and bandwidth. From the datasheet the beam angle is 8 degrees
implementation of the proposed system. which was assumed to be the beam spread. The features of the
A. Electromagnetic flow meter design transducer include that its maximum operating temperature is
When designing the Helmholtz coil the magnetic field in and that its maximum pressure it is 1.6 MPa. Additionally from
the center of the coil is of the utmost importance as this would the datasheet its minimum parallel impedance is Ω and its
be the maximum magnetic field generated. Using Equation 1 electrostatic capacity is pF. These impedance values were
and setting z = 0, as the magnetic field in the center is of assumed to be the impedance of the transducer during both the
concern, the following formula is: transmitting and receiving operation mode. Furthermore, the
transducer is threaded at the end to ensure that transducer is
8 0 IN secure and stable when inserted in the structure of the flow
 3
 (1) meter, and the casing of the transducer is made of copper, thus
r it’s electrically conductive. The transducers are found in the
5 2
datasheet in reference [14].
where β is the magnetic field strength in the center of the two As mentioned, in the near field the sound field’s state of
coils (in T), µ0 is the permeability of air (in Henrys/m), r is the uniformity is affected by the constructive and destructive
coil radius (in m), I is the current (in A) and N is the number of interference. This is not considered as the optimal field to
turns per coil. Equation 1 gives the total strength of magnetic operate in, thus the distance (N) from the face of the transducer
field induced by both the coils. The magnetic field produced by where the near field end and the far field begins should be
the Helmholtz coil is directly proportional to the number of calculated. This was calculated for the transducer as follows:
turns on each coil and the amount of current sent through the
coils. The final design of the Helmholtz coil is illustrated d 2 F 0.0142 1.2 106
below. N   0.0397m  4cm (2)
4c 4 1480

Thus the far field is located approximately 4cm away from


the face of the transducer where a uniform and intense wave is
developed. The piping structure of the time-transit UFM was
designed such that the distance at which the far field begins
will be the same distance between the transducer and the inlet
and outlet for flow.
The piping structure was designed so that the inlet and
outlet for water are both at an angle of 45 degree angle to the
sensor path, and that the ultrasonic beam travelling distance is
approximately 310 mm. The piping structure should ideally be
made out of standard steel piping and electrically insulated
bushers are required to isolate the transducers from the piping
structure. Although, the piping structure used in the designed
Fig. 4. Final design of the Helmholtz coil. flow cell transit-time UFM was copper piping due to the 45
degree elbows that were available only in copper. In Fig. 5 the
B. Water usage meter design piping structure of the designed flow meter with dimensions is
The time-transit UFM is made up of the transducers and the shown. The inlet and outlet’s length is times the pipe’s
main measuring unit. The transducers selected will directly diameter, as that is the suggested length to stabilize the flow
influence the stability and accuracy of the meter, thus it is an before it enters the sensor path.
important factor to consider. When looking at the physics of
sound wave, it is evident that there are factors to consider,
when choosing an ultrasonic transducer. The type of transducer
selected is thus dependent of the ultrasonic frequency required

6213
B. Energy harvesting results
Fig. 8 shows the measured potential difference across the
terminals of the battery, whilst the battery was charged using
the designed charging circuitry. The black dotted line is the
trend curve of the rate of charge. Between 09:00 and 11:30 the
battery had a 30W TV as a load and from 11:30 until 17:00
there was no load connected to the battery.
Fig. 5. Designed flow cell time-transit UFM with dimensions.

C. Energy harvesting
A 10W solar panel is connected to a battery, which is
charged during the day when exposed to sunlight. This serves
as the energy harvesting component of the system, illustrated
in Fig, 6.

Fig. 8. Measured voltage across the battery.

Regarding the battery charging circuit; when the battery


was under load almost no charging of the battery occurred, but
no charge was lost. No charge of the battery was lost, because
there was a voltage gain from 12.4V to 12.5V (seen in Fig. 8)
whilst the load was connected. When the load was
Fig. 6. Illustration of energy harvesting component of the system. disconnected after 11:30 the charging rate increased and was
more effective. Because the voltage across the terminals of the
V. RESULTS AND DISCUSSION battery increased, the rate of charging decreased as this
decreased the charging current.
A. Flow meter accuracy
The objective of this experiment was to test and verify that VI. CONCLUSION
the flow meters accuracy meets the proposed accuracy This paper presented the design and implementation of a water
specification of 85% or more, over a range of flow rates. The flow and usage meter. A Helmholtz coil was designed and
experimental setup and testing equipment is seen in Fig. 7 built for the purpose of producing an electromagnetic field
below. By adjusting the flow rate of the water with the valve across the water pipe. Two electrodes were placed in the water
that is attached to the pump for specific time interval, the pipe 900 to the magnetic field in the water pipe. The signal
designed meter’s accuracy was tested over a range of flow received from each of the electrodes went to a small signal
rates. This was done by comparing the reading of the designed
analysis circuit. In the small signal analysis circuitry the
meter to that of the V110 KSM volumetric meter that is used as
signals underwent filtering to remove unwanted noise from the
a control meter.
signal and underwent amplification. After the amplification
stages an ADC was done to the signal with the use of
software. The ADC of the signal was then manipulated to
relate the received value from the electrodes to the rate of flow
of the water. In future work we could consider how to better
interconnect these meters to wireless sensor networks, which
would allow for remote monitoring, device localisation [15],
while also considering how to secure device computation, e.g.
using tamper proof tokens [16], communication [17] and
location [18].

Fig. 7. Experimental setup.

6214
REFERENCES [Online]:http://www.google.com/patents?id=mgo7AAAAEBAJ&printse
c=abstract&zoom=4#v=onepage&q&f=false.
[1] Times Live Article: “Water crisis”. [Online]
:http://www.timeslive.co.za/local/articles913892.ece/Water-crisis-by- [10] S.R. Gyawali, “Design and construction of Helmholtz coil for
2020, [Last Accessed 03/04/2016]. biomagnetic studies on soybean‟, pp. 38-56, Aug. 2008.
[2] A. Abu-Mahfouz and G.P. Hancke, “An efficient distributed localisation [11] Don D. Ratnayaka, Malcolm J. Brandt, K. Michael Johnson, CHAPTER
algorithm for wireless sensor networks: based on smart reference- 16 - Valves and Meters, Water Supply (Sixth Edition), Butterworth-
Heinemann, Boston, 2009, Pages 599 - 629, 2009.
selection method”, International Journal of Sensor Networks, vol. 13,
no. 2, pp. 94 - 111, May 2013. [12] Leon Scholtz, Contracts Manager at Elster Kent Metering, Product
information specifications for Non-metallic products, 06/04/2012.
[3] A. Kumar and G.P. Hancke, “Energy Efficient Environment Monitoring
System Based on the IEEE 802.15.4 Standard for Low Cost [13] Y. Wang, "Development of multi-path ultrasonic flow meter based on
Requirements,” IEEE Sensors Journal, Vol.14, No.8, pp.2557-2566, embedded system," IEEE International Conference on Control and
August 2014. Automation (ICCA), pp. 689-692, 2010.
[4] C.P. Kruger and G.P. Hancke, “Implementing the Internet of Things [14] Donald A Neamen; Chapter 6 – Basic BJT amplifiers, Microelectronics
vision in industrial wireless sensor networks,” IEEE International – Circuit Analysis and Design (Third Edition), McGraw-Hill
Conference on Industrial Informatics, pp.627-632, July 2014. Companies, New York, pp. 369 – 561, 2007.
[5] B. Silva, R. M. Fisher, A. Kumar and G. P. Hancke, “Experimental Link [15] A.M. Abu-Mahfouz and G.P. Hancke. “ns-2 Extension to Simulate
Quality Characterization of Wireless Sensor Networks for Underground Localization Systems in Wireless Sensor Networks”, IEEE Africon
Monitoring,” IEEE Transactions on Industrial Informatics, vol. 11, no. 2011, September 2011.
5, pp. 1099-1110, Oct. 2015. [16] K. Markantonakis, M. Tunstall, G.P. Hancke, I. Askoxylakis and K.E.
[6] C.P. Kruger and G.P Hancke, “Benchmarking Internet of things Mayes, “Attacking Smart Card Systems: Theory and Practice”, Elsevier
devices,” IEEE International Conference on Industrial Informatics, Information Security Technical Reports, Vol. 14, No. 2, pp. 46-56, May
pp.611-616, July 2014. 2009.
[7] R. Fisher, L. Ledwaba, G.P. Hancke and C. Kruger, “Open Hardware: A [17] W.D. Chen, G.P. Hancke, K.E. Mayes, Y. Lien and J-H. Chiu. “Using
Role to Play in Wireless Sensor Networks?,” Sensors, 15(3), pp. 3G Network Components to Enable NFC Mobile Transactions and
6818-6844, 2015. Authentication”, IEEE International Conference on Progress in
Informatics and Computing (PIC 2010), December 2010.
[8] M.K. Bevir, “The theory of induced voltage electromagnetic
flowmeters”, J. Fluid Mechan., 1970, 43, (3), pp. 577–590. [18] G.P. Hancke, “Distance Bounding for RFID: Effectiveness of Terrorist
[9] Pulsed DC constant magnetic flowmeter, by Freund, Jr (1982 April 20). Fraud in the Presence of Bit Errors”, IEEE RFID-TA, pp. 91-96,
4325261. November 2012.

6215

Powered by TCPDF (www.tcpdf.org)

Anda mungkin juga menyukai