WINTER max.e3-18
GENERAL DATA Supply Side Exhaust Side
Airflow 18000 m³/h 18000 m³/h
Total Heating Capacity 313 kW
Specific Fan Power(SFP)-total for unit 2006 W/m³/s
System COP 14.10
Total power input 22.19 kW
Refrigerant R407C
Unit power supply 400 V/3 ph/50 Hz
Sea level 0 m
The system's Specific Fan Power (SFPe) calculation is based on clean filter and acc. to EN13779
DIMENSIONS AND WEIGHT
Width 2450 mm
Height 2480 mm
Lenght 3800 mm
Weight 2900 kg
PRESSURE DROP
Filter (F6 Microcell Rigid Filters L = 130)
Clean Filter 101 Pa
Dirty Filter for replacing 600 Pa
Supply Side Exhaust Side
Working point pressure drop (clean filters) 101 Pa 101 Pa

Rotary Heat Exchanger 153 Pa 153 Pa


Evaporator 88 Pa
Condenser 35 Pa

Total Internal Pressure Drops 289 Pa 342 Pa


External Static Pressure (ESP) 250 Pa 250 Pa

FILTERS
Class of filtration F6 F6
Total Filtration Area 65.1 m² 65.1 m²
ROTARY HEAT EXCHANGER
Incoming Temperature -18 °C
Incoming Relative Humidity 80 %
Incoming Temperature 22 °C
Incoming Relative Humidity 50 %
Recovered Heat(Total) 259.8 kW
Temp. Eff.(Dry)\Hum. Eff. 71.0 % \ 76.0 %
Outgoing Temperature 10.4 °C
Outgoing Relative Humidity 82 %
Outgoing Temperature -6.4 °C
Outgoing Relative Humidity 99 %
Mass Transfer Humidity 0 l/h 125 l/h
Temperature to frost - °C

DV_Select 3.1 Page: 1 / 3


Date : 16-06-2015
Reference:
Issued by :

MIXING BOX
Supply Side Exhaust Side
Inlet Temp. from Heat Recovery - °C - °C
Inlet Rel. Hum. from Heat Recovery - % - %
Inlet Temp. from Recirculation Damper - °C - °C
Inlet Rel. Hum. from Recirculation Damper - % - %
Outlet temperature - °C - °C
Outlet relative humidity - % - %
Fresh air percentage 100.0 %

EVAPORATOR
Incoming Temperature -6.4 °C Condensation Rate 16.3 l/h
Incoming Relative Humidity 99 %
Outgoing Temperature -10.9 °C
Outgoing Relative Humidity 100 %
Cooling capacity 41 kW

CONDENSER * Warning: condensing temperature lower than minimum compressor cond. temp. Condenser data recalculated with compressor minimum cond. temp.
Incoming Temperature 10.4 °C
Incoming Relative Humidity 82 %
Outgoing Temperature 20.3 °C
Outgoing Relative Humidity 43 %
Condensing capacity 62.3 kW

COMPRESSORS
Quantity 4 n° Compressors COP 4.370
Power supply 400 V/3 ph/50 Hz Operating Current 4 x 5.49 A
Power input 4 x 3.04 kW Full load Current 4 x 145.00 A
Circuits 2 Locked rotor Current 4 x 66.00 A

FAN Supply Side Exhaust Side


Type: Plug Fan - EC Blue
Total Pressure 539 Pa 592 Pa
Fan speed 2110 rpm 1672 rpm
Fan Efficiency 52.5 % 60.4 %
(Static Eff. Impeller incl. motor and controller)
Power absorbed at fan shaft 2 x 2.567 kW 2 x 2.449 kW
Motor Duty 2 x 3.6 kW 2 x 5.4 kW
Motor Efficiency ErP conformity- 2015/EC controller integrated
Full load Current 2 x 5,8-4,6A A 2 x 8,6-6,8A A
K-factor for air flow measuring 197 252
Power supply 400 V/3 ph/50 Hz

DV_Select 3.1 Page: 2 / 3


Date : 16-06-2015
Reference:
Issued by :

SOUND PRESSURE LEVEL (*)


Octavian centre frequency (Hz)
63 125 250 500 1000 2000 4000 8000

(*) Sound Pressure Level-dB(A),


measured at 1m. Distance from the unit in free field(without ducts)

SOUND POWER LEVEL dB(A)


63 125 250 500 1000 2000 4000 8000 SUM
n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. Supply Air Side - Supply
n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. Supply Air Side - Fresh Air
n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. Extract Air Side - Exhaust
n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. Extract Air Side - Extract
n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. Extract Air Side - Surroundings (**)
Sound Pressure Level is measured in acc. to ISO 5136-2003(with ducts)
(**) Surroundings (by ISO 3744: 2006), measured at max.airflow of 0 m³/h