1) Bend Radius
In spaces with UTP terminations, cable bend radii shall not be less than four
times the cable diameter for outlet cable.
2) Pulling Tension
The maximum pulling tension for a 4-pair 24-AWG UTP cable should not
exceed 110 N (25 lbf).
A conduit passes the mandrel test if the test mandrel passes through
the entire length of the conduit without: