Tutorial 5.
.
3 q s 42 kW
1 .
2 Space ql 42 kW
Cooling coil Reheater 24oC SHF 0.5
50% RH
1 2 24o
9o
35 26
or: h2 h1 c p (t2 t1 ) t2 9 17.8 oC
1.02
. . . . 47.5 35
Heat load: q s ql m a (h3 h2 ) m a 6.72 kg/s
42 42
MEC4417 TUTORIAL 5. K. S. ONG
4 Q2.
2. Using tdb to choose between outdoor air or return air may not be the most energy efficient selection. For example, when
outdoor air temperature exceeds that for return air, the latter appears to be a better choice due to its lower temperature.
However, the warmer and less humid outdoor air is likely to require less energy to cool than the return air. For this reason,
using enthalpy instead of Tdb might be a better option with some limitations which this problem is designed to illustrate.
Suppose that the temperature setting of outlet air from the cooling coil is 10oC and that the outlet air is essentially saturated
when dehumidification occurs in the coil. If the condition of return air is 24oC and 40 % RH and the outdoor conditions are
26oC and 30 % RH, would return air or outside air be the preferred choice? Explain why.
2 3
1 A/C
Zone
4
Tdb
MEC4417 TUTORIAL 5. K. S. ONG
5 Q2 (contd).
2 3 h4
1 A/C h1
Zone h3 40%
4
4
30%
3
1
h1 40.5 kJ/kg
10o 24o 26o
h4 42.0 kJ/kg
h3 29.2 kJ/kg
.
qt
100% return air used: .
h4 h3 42.0 29.2 kJ/kg = 12.8 kJ/kg
ma
.
qt
100% outside air used: .
h1 h3 40.5 29.2 kJ/kg = 11.3 kJ/kg
ma
100% outside air better.
MEC4417 TUTORIAL 5. K. S. ONG
6 Q3.
3. A terminal reheat system has a supply air flow rate of 18 kg/s and currently operating with 3 kg/s of outside air at 28oC db
and 30 % RH. The combined sensible load in the space is 140 kW and the latent load is negligible. The temperature of the
supply air is constant at 13oC. The space thermostats are then changed from 24 to 25oC. What is the (a) rate of heat removal
in the cooling coil before and after the change and (b) the rate of heat supplied at the reheat coils before and after the
change? Assume that the space sensible load remains constant at 140kW. [+ 15 kW in cooling rate, + 18 kW in heating rate].
. .
m1 3kg/s q s 140 kW
t3 =13oC .
. . . . ql 0
t1 =28oC m2 m3 m4 m5 18 kg/s
30% RH 2 3 4
1 A/C Reheat
h1
6 . Zone
.
q coil q reheat 5
SHF
h2 1
room SHF h5,6
o
t5 =24 25 C .
coil SHF 2 m a1
h3 .
ma6
Tdp (5,6)
3 4
13o 24 25
. . .
q coil m6 (h6 h3 ) m1 (h1 h3 )
. . .
q coil m6 [(h6 25o C h3 ) (h6 24o C h3 )] m6 [h6 25o C h6 24o C ]
.
= m6 c pa [(25 24) (18 3) x 1.02 x (25 24) 15 kW
. .
q reheat m3 c pa (t4 t3 )
. . 140
From q space m3 c pa (t5 t4 ) t 4 t5 16.22o C [for t 5 = 24oC]
18 x 1.02
= 17.22oC [for t 5 = 25oC]
. .
q reheat m3 c pa (17.22 16.22) 18 x 1.02 x 1.0 18 kW
When zone temp is changed from 25 to 24oC, conditions of air entering the cooling coil would change. This
would change the coil capacity.
. .
q s 500,000 Btu/hr, ql 50,000 Btu/hr
115oF Space
1 72oF 2
. 30% RH
V ?
500,000
SHF 0.91
500,000 50,000
0.91 SHF h1
Pt 2: Space condition at 72oF/30% h 2 = 22.8
Line // SHF = 0.91 & supply air at 115o F Pt 1: h1 = 34.3, 1 = 14.62
1
Total heat loss: h2
. . . 500,000 50,000
q m a (h1 h2 ) ma 47,826 lb/hr
(34.3 22.8) 2
Volumetric air flow:
. . 47,826 x 14.62
V a m a 1 11,654 cfm 72o/50% 115o
60
5 TR
h w = 1150
mw ? .
qt 200,000 Btu/hr
40o F/20% 120oF
1 x s
1000 cfm 72o F/30%, SHF = 0.8
Heater Humidifier
0 r
. . Space
q furnace q hum
(a)
0.8
SHF = 0.8 & t s = 120o F point s = 120oF db/74o F wb
hs
h s = 37.2, s =14.78
Point r at 72o F/30% h r = 22.8 hr s
.
. qt 200,000 . r
ms 13,889 lb/hr = m1
hs h r (37.2 22.8)
. . 13,889 x 14.78
V s ms s 3,421 cfm
60
74oF/30% 120oF
(b) 0.8
Fresh air condition 0 at 40 F db/20 F wb o =12.61
o o hs
. 1150 hx
. Vo
1,000 x 60
mo 4,758 lb/hr s
o 12.61 h1
r
.
mr 13,889 4,758
0.66 x
. 13,889 1
m1 0
. .
(c) m w m s (Ws Wx ) 13,889 (0.0075 0.0036) 54.2 lb/hr
. .
(d) q furnace m1(hx h1) 13,889 (32.8 18.6) 197,224 Btu/hr