Slope Characteristics Setting in Differential Page

Relay Type Characteristics Bias Equation Ibias calculation Relay Settings


Method (if required)
ABB : RET 670 NA
IdMin : 0.3
Id_Unres :8

Slope From Base Endsection1 : 1.25


> IIpI or IIsI
Point SLP_Section_2 : 40 %
Endsection2 : 3.0

SLP_Section_3 : 80 %

Relay Type Characteristics Bias Equation Ibias calculation Relay Settings


Method (if required)
Siemens : 7UT NA
87-1 Pickup : 0.44
87-2 Unrest :5
87_Base_Point_1 : 0.63
Slope From X Axis ( IIpI + IIsI )
87 Slope_1 : 25%

87_Base_Point_2 : 2.82

613 87 Slope_2 : 50 %
Relay Type Characteristics Bias Equation Ibias calculation Relay Settings
Method (if required)
Areva/Schnider Ibias for Slope 1: Idiff > : 0.2

Idiff>> : 6.0
Slope From Base ( IIpI + IIsI ) / Ibias (Slope1) : 0.1
Point 2
m1 : 0.3
Ih, m2 :4

: P63x (Pickup/2) m2 : 0.7


Relay Type Ibias calculation
Characteristics Method
Bias Equation (if required) Relay Settings
Alstom : KBCH NA
Idiff > : 0.5

Idiff>> : 10

Slope From Base ( IIpI + IIsI ) /


Point 2
m1 : 0.2

Ih, m2 :1

m2 : 0.8

Relay Type Ibias calculation


Characteristics Method
Bias Equation (if required) Relay Settings
ER : Duobias NA
Pikcup : 0.25

Id>> :7

Slope Through
Orgion
Slope1 : 20 %

Slope knee point : 3.9

Slope2 : 100
Relay Type Characteristics Bias Equation Ibias calculation Relay Settings
Method (if required)
SEL : SEL 387 NA
O87P : 0.3

U87P :5
Slope Through ( IIpI + IIsI ) /
Orgion 2
SLP1 : 20%
IRS1 :3
SLP2 : 50 %
Relay Type Characteristics Bias Equation Ibias calculation Relay Settings
Method (if required)
SEL : SEL 587 NA
O87P : 0.3

Slope Through ( IIpI + IIsI ) / U87P :5


Orgion 2
SLP1 : 20%
IRS1 :3
SLP2 : 50 %

Relay Type Characteristics Bias Equation Ibias calculation Relay Settings


Method (if required)
SEL : SEL 787 NA
O87P : 0.3

U87P :5

Slope Through
( IIpI + IIsI )
Orgion
SLP1 : 20%

IRS1 :3

SLP2 : 50 %
Relay Type Characteristics Bias Equation Ibias calculation Relay Settings
Method (if required)
GE : SR 745 User have to to
Pickup : 0.3
calculate the

Line segments > IIpI or IIsI values as known


Slope1 : 25%
in Line segment
Kneepoint :3

column Slope2 : 50 %
Relay Type Bias Equation
Characteristics Method Ibias calculation (if Relay
required)
Settings
Areva/Schnider Slope Through ( IIpI + IIsI ) /
: P64x Origin 2 Is1 > : 0.2
Is-Hs2>> : 8.0

k1 : 0.3
Is2 :1
k2 : 0.8

Relay Type Ibias calculation


Characteristics Method
Bias Equation (if required) Relay Settings
SEL : SEL 487E User have to to
O87P : 0.3

calculate the U87P : 10

Line segments ( IIpI + IIsI ) values as known


SLP1 : 15%
in Line segment

column SLP2 : 30%


Slope 2 Settings (SEL 487E)

Line Segments

IBias (P.U) Gradient %

(Pickup) 0.3 0
(Pickup/Slope2) 1 (Slope2) 30
((Pickup/Slope2)+3) 4 (Slope2) 30
((Pickup/Slope2)+5) 6 (Slope2) 30

Relay Type Ibias calculation


Characteristics Method
Bias Equation (if required) Relay Settings
ABB : RET 543 User have to to Basic setting : 30%
Starting ratio : 50%
Slope From Base ( IIpI + IIsI ) /
calculate the Turn Turn Point 2 : 1.25
Point 2
Turn Point 1 : (Basic setting/ starting ratio) 0.6
Inst. Setting : 30
point 1 values
Line Segments (GR 745)

IBias (P.U) Gradient %

(Pickup/ Slope1) 1.2 (Slope1) 25


(Kneepoint) 3 (Slope2*Kneepoint) 1.5

(Kneepoint) 3 (Slope2) 50

(No setting available)12 0


Slope 1 Settings

Line Segments (SEL 487E)

IBias (P.U) Gradient %

(Pickup) 0.3 0

(Pickup/Slope1) 2 (Slope1) 15

((Pickup/Slope1)+2) 4 (Slope1) 15

((Pickup/Slope1)+4) 6 (Slope1) 15