558 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 2002

Enhancement of Power Transfer Capability


of Existing 400kV Transmission Lines
Rajiv Gandhi, Anish Anand, Y. K. Sehgal, M. Krishnakumar and Anand Mohan

Abstract--The Indian Power sector has ambitious plan to add II. NEW TECHNOLOGIES FOR IMPROVEMENT OF
about 100,000 MW generating capacity in the next 10- 12 years. STABILITY LIMITS AND OTHER CONSIDERATIONS
A great proportion of this would be generation confined to coal
pitheads in Eastern Region and hydro generation in North While enhancing the thermal limit of the existing lines or
Eastern region and Northern region. To meet the power choosing high thermal capacity conductor or multiple
evacuation needs of such large generation expansion; a
judicious decision considering optimum utilisation of right of conductor line, various aspects like voltage instability and/or
Way and existing transmission infrastructure is of great angular instability need to be examined. These two aspects
significance. Enhancing capacity of existing transmission lines, are related with the line length, hence line reactance, strength
therefore, is considered as one of the alternatives. The paper of the parallel/underlying transmission network and the
presents salient studies conducted by in this regard and strength of the termination points. Therefore, before making
examines various possibilities. any effort to enhance the capacity of the line, there is a need
to analyse these aspects in detail. Generally, to take care of
Index Terms—Series Compensation, Uprating, Weather
angular stability problem as well as voltage instability issue,
Predicted Thermal rating systems
application of series compensation on long lines, Static Var
Compensators (SVC) and other type of FACTS devices like
I. INTRODUCTION
TCSC, Controlled Shunt Reactor (CSR) etc. are nowadays in
use in the transmission network. These power electronic
The power transfer capability of an AC transmission line is
devices facilitate enhancement of power transfer capacity of
influenced by:
EHV lines by providing adequate reactive power support as
well as reduction in line reactance.
(a) Stability limit: This limit depends on voltage class, line
length and power system network configuration.
While enhancing the power transfer capacity of line,
another important aspect need to be considered is
(b) Thermal limit: This limit depends on the type of
transmission losses at different power order at 400KV level
conductor, its sag-tension characteristics, maximum
and compare it with next higher voltage level like 765kV. As
permissible conductor temperature, ambient temperature and
such with the increase in loading (current, I), transmission
other environmental factors.
losses increase in proportion to the square of the current (I2
R). Therefore, economic benefit of increase in line rating
For the Indian 400 kV transmission lines having lengths
along with the increase of line loss need to be compared with
more than 200 kms, stability limit has been the factor
the cost of higher voltage level line.
determining safe power carrying capability. For lower
voltage class lines having lower lengths however, the power
III. ENHANCEMENT OF THERMAL RATING
flow capacity generally is dependent on its thermal limits.
OF TRANSMISSION LINES
The power transfer capability of existing transmission
system can be enhanced through (i) improvement of stability
A. Weather Predicted Thermal Rating Systems
limits and (ii) current uprating.
Increasing thermal limits of the existing facilities along
Thermal rating of a transmission line is influenced by
with improved stability limits achieved by introduction of
FACTs, series compensation etc can yield encouraging factors such as ambient temperature, maximum permissible
conductor temperature for the type of conductor used, wind
solutions for optimising Right of way and new investments.
velocity, solar radiation, solar absorption & emissivity
Various alternatives possible in this direction have been
coefficients etc. Since all these variable conditions /
examined and discussed in this paper. parameters do not usually attain their peaks simultaneously,
their exists scope of possible increase in thermal capacity of
the lines if realistic / justifiable parameters are identified. In
various countries, power utilities have now started use of
Authors are with Power Grid Corporation of India Ltd. (A Govt. Of India weather predicted thermal -rating systems instead of using
Enterprise), New Delhi-1110016
INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 559

conventional static or book ratings based on conservative 1000


assumptions used earlier. It has been found that increase in

Current Carrying Capacity


900
power flow capacity by around 10% is generally possible 800
though not 100% of the time by adopting weather predicted 700
systems. 600

(Amp)
500
As per Planning Criteria [2] presently in force, the 400
following factors are considered for calculation of current 300
carrying capacity / thermal rating of transmission lines: - 200
100
Solar radiation 1045 watts/sqm 0
Solar Absorption coeff. 0.8

0
0

45

50
00
50
25

75
Emmissivity coeff. 0.45

10

12
10
Wind velocity 2 kms/hr Solar Radiation (W/sq.m)
Ambient temperature 45 degC
Fig. 2. Conductor current carrying
However, these parameters considerably vary with time of
capacity: Varaition w.r.t Solar
the day, days and seasons in a year. Analysis of variations in
thermal rating of 400 kV line w.r.t. variations in influencing Radiation
parameters (i.e. ambient temp., solar radiation, wind From the results, it is observed that ambient temperature
velocity, solar absorption coeff., emmissivity coeff., maxm. has a major impact on current carrying capacity of the line.
conductor temp.) have been conducted using in-house As this can be predicted to a good degree of accuracy based
developed software and salient results are indicated in Fig. 1 on actual measurements (for operation) and past
to 5. climatological data (for planning), this can be effectively
1200 utilized to identify thermal rating of lines in different time of
a year. Similarly, variations in solar radiations due to time of
day, month/season etc. can also be utilized as peak load
hours do not necessarily coincide with time of maximum
1000 solar radiation

1800
Current Carrying Capacity (Amp)

800 1600

1400
Current Carrying Capacity (Amp)

600
1200

1000
400
800

600
200
400

200
0
20 25 30 35 40 45 50 0
25
0

Ambient Temp (degC)


Wind Velocity (Km/hr)
Fig. 1. Current carrying capacity:
Variation w.r.t Ambient temperature
Fig. 3. Current carrying capacity:
Variation w.r.t wind velocity
560 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 2002

to increase the thermal limits of lines also where such


devices are installed so that the power transfer capacity in
those transmission corridors can be enhanced to maximum
900 possible limits in an economical manner. Enhancing
800 maximum operating temperature limit is one of the feasible
Current Carrying
Capacity (Amp)

700 solutions.
600
500 Salient observations and results of the study conducted [8]
400 in this direction for 400 kV lines are presented in Fig. 6
and Table I & II.
300
200
100
0 1400

Current Carrying Capacity


0.23 0.5 0.8 0.97 1200

Absorption Coeff 1000

(degC)
800
Fig. 4. Current carrying capacity: 600
Variation w.r.t Absorbtion 400
coefficient 200
0
760 65 75 85 95 115 125
Current Carrying Capacity

740 Max Permissible Temp (deg C)


720
700 Fig. 6. Current carrying capacity:
680
Variation w.r.t max permissible
(Amp)

660
640 conductor temperature
620
600
580 Table-I
560
540
Conductor Current carrying Thermal rating
0.23 0.45 0.75
Temperature capacity of
Emmisitivity Coeff Conductor
Fig. 5. Current carrying capacity: (Deg C) (Amp) (MVA)
Varaition w.r.t emissitivity
coefficient 75 614 851 (Base)
85 787 1090 (128%)
95 923 1280 (150%)
B. Enhancement Of Maximum Permissible Conductor
Temperature Limit Table - II

During the initial development of 400kV transmission Conductor Conductor sag


system in India where the line lengths were more than 200 Temperature for 400 m span
kms and the network was in developing stage, stability limit (Deg C) (m)
was the determining factor for the safe power carrying
capacity of transmission lines for operational as well as 75 12.87 (Base)
planning purposes. As such the thermal limit has not been a 85 13.26(+0.39 m, 3%)
constraint. In late 70’s, the maximum permissible ACSR 95 13.65 (+0.78 m, 6.1%)
conductor temperature was fixed at 65 deg.C (17/20 deg. C
more than the maximum ambient temperature of 48/45
deg.C). In mid 80’s this temperature was increased to 75 T The increase in thermal rating is 28 % & 50 %
degrees with the development of system network and this respectively for 85 & 95 degree C maximum operating
practice has been followed till recently for planning & temperature for ACSR MOOSE used for 400 kV lines
design of EHV transmission lines in the country. and the sag increase is also nominal and this can be
catered to either by reducing the span or increasing the
The stability limits of lines are now being enhanced by tower height nominally for new lines. The cost impact
means of series compensation, FACTs etc. It is advantageous on account of this is also of the order of 1% & 2 %
INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 561

respectively for 85 & 95 degree C conductor temperature. of the conductor and also results in increasing the current
Considering the advantages, POWERGRID has decided to carrying capacity.
adopt 85 deg C as the conductor temperature limit for all its
under construction/future 400 kV transmission lines. The iii. ACSS & GAP CONDUCTORS
adoption of 95 deg C is proposed to be taken up on case-to-
case basis based on power flow requirement estimated at ACSS is Aluminium conductor steel supported. The
planning stage. construction is similar to standard ACSR except that the
Aluminium strands are fully annealed. Under typical
The possibility of increasing the permissible operating conditions, ACSS allows the entire mechanical
maximum operating conductor temperature for the existing load to be carried by the steel core. Some of the major
400 kV lines is also being examined by POWERGRID on advantages of ACSS are improved conductivity and better
case-to-case basis. This involves detailed study of existing self-damping characteristics. Since the Aluminium strands
ground profiles and tower spotting to assess whether do not take any mechanical load, the conductor may be
additional margins in ground clearance are physically operated at temperatures in excess of 200 deg .C without loss
available. Utilisation of ground clearance margins physically of strength.
available and also by adopting methods like re-tensioning or
re-conductoring with alternate low sag conductor in critical The technology of GAP conductor is similar to ACSS
spans can prove to be an economical solution to improve conductor, the only difference being that a small gap is
thermal rating of the lines. maintained between the steel and Aluminium layer and the
conductor is strung by tensioning the steel core only. Hence
C. Uprating Of Existing Lines under all operating conditions, the mechanical load is carried
by steel core only and conductor may be operated at
ACSR is the most common type of conductor used for temperatures in excess of 200 deg. C.
EHV transmission lines in India as well as other countries. It
is a relatively low technology item and its performance has iv. INVAR CONDUCTORS
been quite satisfactory in Indian transmission system.
However these have limitations in operating at temperatures INVAR Conductor consists of core of alloy of iron and
beyond 95 deg C and also the sag varies at a relatively higher nickel which has an extremely low co-efficient of thermal
proportion with temperature. Therefore such conductors expansion of about 1/3rd that of conventional steel wire. The
cannot be adopted for current capacities beyond certain outer aluminum alloy layers of INVAR conductors are
limits. thermally annealed. As such INVAR conductors can
operate at temperatures in excess of 200 deg. C. Above
Uprating of existing transmission lines to enhance thermal certain transition temperature all mechanical load is
limits can be accomplished by re-conductoring the existing transferred to INVAR core and hence at temperature above
line with conductor types having high current carrying this transition temperature INVAR conductors have less sag
capacity, high temperature endurance, compatible sag– compared to ACSR conductors. Typical temp v/s sag curve
tension characteristics etc. Custom made conductors to suit of INVAR conductors are exhibited in Fig- 7.
specific applications can be selected. Various new
technology conductor types used by other World utilities
15
have been subjected to detailed study and possibility of
adoption for uprating of existing lines have been examined. 14

The conductor types thus examined were: 13

i. AAAC 12
Sag (m)

11 Existing 400kV sag 65deC


AAAC is a stranded conductor of good conductivity, high
tensile strength and corrosion resistant Aluminium alloy. The Existing 400kV sag 75degC
10
AAAC offer improved strength to weight ratio resulting in ZTACIR 410
lower sag, lower electrical losses owing to lower ac 9 ZTACEIR 400
resistance and superior corrosion resistance. . STACIR 480
8
ii. COMPACT CONDUCTORS 25 50 75 100 125 150 175 200
Temp (degC)
Compact Conductor is an ACSR conductor with
Fig. 7. Sag vs Temp of various INVAR
Aluminium wires/strands shaped in the form of a trapezoid.
conductors
Due to greater compactness of trapezoid wires, more
Aluminium is present in the conductor compared to same The important design considerations for uprating are: -
diameter ACSR conductor. This reduces electrical resistance
562 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 2002

i. Mechanical loading with alternate conductors does required to be analyzed for current carrying capacities,
not exceed the design loads of existing tower sag-tension characteristics, mechanical loading on
structures. structures, operating temperature limits , line losses etc
ii. Sag of the conductor should be less than or equal to to arrive at a techno economically suitable selection
the existing conductor sag. satisfying the above mentioned requirements.
iii. Techno economic evaluation should be carried out
for each case. Salient results of studies carried out for conductor
selection for uprating of 400 kV transmission lines are
A wide range of alternative types & sizes of conductors presented in Table - III
(having different stranding ratios, diameter etc) are

Table- III Comparison of Uprating Options

Alternatives Operating temperature Thermal rating Cost of re- Cost per Avg line loss Additional cost of re Ratio of % Increase in
w.r.t permissible Sag (deg. in MVA after conductoring in Rs MVA in Rs in MW for -conductoring as a enhanced power flow over
C) uprating lacs/km lacs for 100kms line % of standard line capacity to standard line
100kms line (loss factor- cost Additional cost
0.5215)

ACSR
Moose 75 1702
Avocet/TW
(Compact) 100 2768 27.3 2.6 43.7 52.2 1.2 62.6
AAAC
Moose 95 2800 16.3 1.5 9.5 31.1 2.1 64.5
ACSS-
Cardinal 125 3312 48.6 3.0 75.1 92.8 1.0 94.6
60
ZTACEIR
400 (Invar) 165 3534 69.9 3.8 117.1 133.5 0.8 107.6

IV. CONCLUSIONS

To take care of power transfer requirement of any VI. REFERENCES


transmission corridor, power flow under normal condition
as well as under contingencies as stipulated in the CEA’s [1]. House & Tuttle, “Current carrying capacity of ACSR”, IEEE, 1959
[2]. CEA, “Manual on transmission planning criteria”, June 1994
manual on transmission planning criteria must be within [3] The Aluminium Association, USA, “Aluminium Conductor
the capacity of the line. As discussed in the paper, power Handbook”, 1982
transfer capacity is limited due to thermal, angular stability [4] T.O.Seepa, M.Clements et al., “Application of real time thermal
and voltage stability considerations. There are various ratings for optimising transmission line”, Cigre 2000, 22-301
new technology options available now to enhance thermal [5] R.Stephen, D.Muftic, “Determination of thermal ratings and uprating
methods for existing investment and operating decisions”, Cigre
limits of existing transmission lines and adoption of such 2000, 22-305
options would facilitate conservation of right of way, [6] M.Krishnakumar, "Upgrading of transmission lines - Design
reduced environmental impact and reduction in considerations, constraints & feasible solutions"-International
Seminar on Uprating /Upgrading of Transmission Lines organised
construction time. While adopting any such means to by CBIP & EMC at New Delhi in March'95 .
update the thermal capacity of the line, detail studies for [7] S.C.Parakh, M.Krishnakumar et al "Upgrading V/S Uprating - A
angular and voltage instability need to be carried out for Techno economic Analysis." Third Afro-Asian Conference on
each specific transmission corridor. To take care effect of Power Development held at Kathmandu, Nepal in March'96.
[8] Rajiv Gandhi, Anish Anand, M.Krishnakumar, D.chowdhury,
line reactance alternate devices to give static and dynamic Anand Mohan “Enhancement Of Maximum Permissible Conductor
reactive power support or change in static and dynamic Temperature Of 400 kV Transmission Lines” Presented In Council
line reactance may be required through FACTS. In Of Power Utilities Conference, 2001
addition increase in power flow would be associated with [9] South wire Company, 1994 “Overhead Conductor Manual”
increase in transmission losses. Therefore, before taking [10] Product Catalogues of Hitachi Cable Ltd, Japan, Sumitomo etc.
[11] D.A.Douglass, T.O.Seepa, Y.Motlis., “IEEE’s approach for
decision, various aspects like cost-benefit, conservation of increasing transmission line ratings in North America” , Cigre 2000,
Right-of-Way etc. need to be considered. 22-302