www.sosintl.com 704-752-3534 1
Objectives
Learn how protective relays receive their
information about conditions on the powers system.
Understand the function of various relay
technologies and their limitations.
Understand how relays are integrated together for
total system protection
Diagnose system contingencies given protection
information.
Understand how the different pieces of electrical
equipment are protected.
2
Purpose of Protective Relaying
• Remove the minimum amount of equipment
from the power system
• Limit further damage to equipment
• Minimize danger to people
• Reduce stress on other equipment
• Maintain the integrity and stability of the
remaining system
3
NERC Requirements
System Operators shall be familiar with
the purpose and limitations of protection
system schemes.
Protection schemes must :
Have minimum complexity
Have redundancy
Have proper operation
Have high or fast speed
Have automatic re-closing
4
System Protective Equipment
Purpose of System Protective Equipment:
1. Detect undesired events
2. Take appropriate action
3. Tripping of circuit breakers which isolates the trouble
6
Overlapping Zones
• All power system equipment must be encompassed by at
least one zone
• Zones must overlap to prevent elements from being
unprotected
• Zones may be closed or open
Gen
Gen
7
Overlapping
Protection
ensures that no
part of the
system is
unprotected.
Line Relay CT
Bus Differential
Relay CT
8
Basic Elements of a Protection System
Current & Potential Transformers detect system
conditions and delivers the information to the relays.
Circuit Breakers or other isolating devices separate the
fault from the system.
DC Power does the actual tripping.
CT BRK
9
Protective Relays Information
Sources
1. Direct Current
2. Potential Transformers
3. Current Transformers
10
11
Circuit Breaker Controls
12
Main Bus Pots
13
Potential Transformer (PT)
Potential Transformer Characteristics:
• Standard secondary voltage is 120V phase to phase
• 69V phase to neutral (69 ÷ sq.rt. of 3) or (57.735%) of
phase to phase
• Transforms primary voltage to a level suitable for
metering and relaying
• Provides the first of two basic electrical quantities that
are needed to determine the state of the system
14
Coupling Capacitor Voltage
Transformer (CCVT)
Coupling Capacitor Voltage Transformer
Characteristics:
• Standard secondary voltage is 120V phase to
phase
• Transforms primary voltage to a level suitable
for metering and relaying
• Constructed through series connected
capacitors in combination with a voltage
transformer
• Can be used on busses and transmission lines
15
Coupling Capacitor Voltage
Transformer (CCVT)
16
Current Transformer (CT)
17
Bushing Current Transformer
18
CURRENT TRANSFORMER
19
The secondary current always flows in
the opposite direction from the primary
20
2.2/1
1200/5
Direction of primary current
21
Polarity From
CT
80 160 60 100
turns turns turns turns
X X X X X
1 2 3 4 5
22
Transformer Differential With Y & Delta CTs
Delta
CT
Y - CT
23
46kv
300
phase
shift
13kv 13kv
Shifts
back
24
Phase Sequences
A
• Positive Sequence is
counter clockwise
• Negative Sequence is
clockwise
C B • Zero Sequence is
unidirectional
N
25
Phase-to-Phase (B-C) fault
B C B C
A A
Pre-Fault Voltages Voltages During Fault
26
Phase-to-Ground
(A-ground) Fault
B C B C
A
Pre-Fault Voltages Voltages During Fault
27
46kv
13kv 13kv
28
ZERO SEQUENCE FILTER
The differential
relay has a Y
connection. Fault
current can
return through
the differential
giving a false trip.
29
IEEE Relay Numbers
21 - Distance Relay 59 - Overvoltage
25 - Synchronizing Relay 63 - Pressure Relay
27 - Undervoltage Relay 64 – Ground Relay
49 - Thermal Relay 67 – Directional
Overcurrent
50 - Instantaneous
79 - Reclosing Relay
Overcurrent
81 - Frequency Relay
51 - Time Overcurrent
86 - Lockout Relay
52 - CB Auxiliary
87 - Differential Relay
94 - Auxiliary Relay
30
Protection Technologies
• Fuses
• Electromechanical
• Solid State
• Digital
31
Fuses
Advantages Disadvantages
Simple One shot operation
32
Electromechanical Relays
Electromechanical Electromechanical
Relay Relay
33
Electromechanical Relays
Advantages Disadvantages
Greater input capability
Complicated calibration
Durable
Separate power supply
Allow more complex
protection schemes Large power requirements
Reusable More hardware
Less labor intensive
34
Solid State Relays
Instrument Transformer
Analog Control
Card
Surge Filters
Analog
Card Isolation
Filters
Analog
Card
35
Solid State Relays
Advantages Disadvantages
Allow more Vulnerable to harsh
comprehensive temperatures, moisture,
schemes over voltage & under
Low power requirement voltage
Reduced space Require separate power
requirements supplies
More accurate
Less calibration
Vibration & dust
resistant
36
Digital Relays
Instrument Transformer
Sampling Control
Isolation
A/D чP Filters
37
Digital Relays
Advantages Disadvantages
Remote monitoring & Power quality
setup Susceptible to harsh
Allow most complex environments
scheme
Low power & equipment
requirements
Accuracy
Lower purchase/O&M
costs
Software upgrades
38
Power System Protection
39
Non-Directional Overcurrent - 51
Relay MT = 75 amps
Load = 50 amps
City A
CT CB with Relays
40
Inverse-Time Characteristic
Time
R R
A B
Distance
41
Non-Directional Overcurrent - 51
City A
CB w/ Relays City B
City C
42
Distribution Feeder Protection
Non-directional relaying can be used because fault currents
always flow from sources to loads.
50/51 Fuse
43
Over Current & Residual Ground Relay
44
13kV Overcurrent Relay Settings
51 overcurrent relay can be changed from Tap 1 to
Tap 5.
Some 13kV feeders in a substation have a 600/5 CT.
Examples:
• 600 amps in the primary circuit would produce 5
amps in the secondary. If the tap were on 1,
120 amps in the primary would produce 1amp
in the secondary tripping the circuit breaker.
• The tap raised to 4, would mean that the relay
could allow up to 480 amps in the primary
resulting in 4 amps in the secondary before the
breaker would trip on overcurrent.
45
“Residual” Overcurrent Protection
64, 51N or 51G
I residual = IA + IB + IC = 0 Amperes
A
CB B
C
4 amps
? amps
2 amps 2 amps
46
“Residual” Overcurrent Protection
(“open” CT secondary) 51N or 51G
I residual = IA + IB + IC = 2 Amperes
A
CB B
C
6 amps
? amps
2 amps 2 amps
47
13kV Backup Overcurrent and Ground Relays
The 251 overcurrent relay, the 264 ground relay, and the
25NG1 & 25NG2 are back up relays to the line relays.
48
251
46kv
13kv 13kv
49
51
TU
Timer contacts
50
Power System Protection
51
Transmission Line Impedance
Most transmission line conductors are strands of aluminum
that have steel reinforcement conductors in the center to add
tensile strength.
52
Aluminum Conductor with Steel
Re-enforcement (ACSR)
R XL
XC XC
R - Line Resistance
XL - Inductive Reactance
XC - Capacitive Reactance, line to ground
Capacitance between conductors not shown; usually
negligible for short transmission lines (<50 miles)
54
Distance mho Circle
55
Distance Protection Zones
56
Distance Protection
z Calculation errors
57
Power System Protection
Pilot Protection
58
Carrier uses a combination of a wave trap and a coupling
capacitor potential device to give selective tripping.
59
Wave Traps
60
Line Wave Trap and Coupling Capacitor
61
Pilot Relaying
62
Transfer Trip Communication
Media
63
Fiber Optic Cable Used To Transport
Tripping Signals
64
Transfer Trip Sent To The Line Terminal At The
Other End Of The Line
65
TTX
TTR TTR
66
Permissive Underreach
Transfer Trip (PUTT)
67
Permissive Underreach
Transfer Trip (PUTT)
68
Permissive Underreach
Transfer Trip (PUTT)
69
Permissive Overreach
Transfer Trip (POTT)
70
Permissive Overreach
Transfer Trip (POTT)
71
Phase Comparison Relay Using
Pilot or Carrier
Network T R R T Network
Comparer Comparer
To auxiliary To auxiliary
tripping relay tripping relay
Uses its pilot (or carrier) to compare the phase relation
between current entering one terminal of a transmission-
line section and leaving another.
Carrier current is only transmitted during the half cycles of
the voltage wave when the polarity is positive.
72
Network T R R T Network
Comparer Comparer
To auxiliary To auxiliary
tripping relay tripping relay
The CT’s feeds a network that transforms the CT output into a single
phase output voltage.
The voltage is applied to a carrier current transmitter and to a comparer.
The output of a carrier current receiver is also applied to the comparer.
The comparer controls the operation of an auxiliary relay for tripping the
circuit breakers.
73
Phase Comparison Relay
A B
C D
A Network Voltage at A
For Fault at C or D
carrier-current signal
B transmitted from A to B
for fault at C or D
network voltage at B
C for fault D
carrier-current signal
D transmitted from B to A
for fault at D
E network voltage at B
for fault at C
carrier-current signal
F transmitted from B to A
for fault at C
74
Network Voltage at A Network Voltage at B
A B A
Blocks Blocks Blocks
tripping tripping tripping External
B tries A tries B tries Fault
to trip to trip to trip
A&B A&B
Blocks Blocks
tripping tripping Internal
A&B A&B Fault
try to try to
trip trip
75
Pilot Wire Relaying
zBRK zBRK
zA zB
R R
O O
76
Pilot Wire Relaying
zBRK zBRK
zA zB
R R
O O
77
Power System Protection
Transformer Protection
78
Transformer Protection
The following faults commonly initiate transformer trips:
• Differential
• Time Overcurrent
• Internal Fault Pressure
79
Transformer Protection
63 Sudden Pressure
Tertiary Overcurrent
51 51
Phase
Overcurrent
49 Temperature
Differential
87
80
Differential Protection
81
Differential Zone for a Transformer and Bus
82
Differential Zone Following a Fault
83
Transformer Differential - lines on both sides of the relay
84
The 251 overcurrent
trips on the same path
as the differential relay
which will clear the
transformer.
85
86
Sudden pressure will clear the transformer by tripping an
auxiliary relay.
87
Sudden Pressure Relay
Mechanical device sensing rate of rise of
pressure within the transformer tank
88
Fault (Sudden) Pressure
90
Temperature relay 49 will pick up at a set amount. When
that value is obtained, the relay will initiate a timer. The
timer will run for 1 hour, then trip the bank off line.
Temp. relay
91
Thermocouple
92
RTD
94
Gas Detection
95
Oil Level
z Alarms are common for conservator
tank and main reservoir level
z Sight glasses are used in bushings (No
alarm capability)
96
Oil Flow
z Nutating disks are common transducers for
flow measurement
z Pump status can also initiate low flow
alarms
97
Power System Protection
98
Bus Differential Relays
The bus differential relay normally consist of three overcurrent relays
wired to produce a differential relay.
When the differential CT’s are balanced, no current should flow through
the differential relays. Secondary current will circulate between the line
CT’s. Knowing that the differential relays are over current relays, the
relays themselves would be set to trip at a set amount. Normally the
relays have a 10% variance before they would operate.
A
B
C
C
B
A
99
69KV Bus Differential Relay Zone
z The
Bus diff
100
Shunt Reactor Protection
z Common to use time overcurrent relays
z Reactor faults near phase ends or on the bus
usually are protected with differential schemes
z Circuit breakers are on the non-source side of the
reactors because of the high amount of fault
current they would have to break in case of a
fault
101
Shunt Reactors With Fault Protection
102
Diff
3 3
0 1
8 8
51 51
86
103
Shunt Reactor Protection
z Faults between the capacitor and bus are
detected by conventional overcurrent relays
z Voltage and current surges caused by faults are
dampened by surge protection
z Individual capacitor failures are isolated by
fuses
z Over current or over voltage protection on the
neutral detects multiple capacitor can failures
104
69KV Capacitor Bank And Protection
69KV Capacitor bank
with its Over current,
Current Limiting
device, and
differential protection.
Bank Differential CT
Current Limiting
Device
Over voltage
protection on the
neutral detects
multiple fuse failures
105
Trips & LO 732 Trips & LO 722 Trips & LO 704 230KV
Aux Aux
Aux
OV OV OV
7
0
4
69KV Bus
51 64
106
Power System Protection
Generator Protection
107
Generator Protection
108
Generator Protection
Percentage differential
10% & 25% slopes
Ground fault protection –
A relay set in the neutral of the generator to detect
ground faults
Negative sequence relay (unbalance relay)
• Generator cannot withstand unbalanced conditions
109
Transformer Bus
Generator
R
CV8 Trip
SV SV ICS or
R CV8 Alarm
ICS
110
Generator Protection
Characteristics for a Current Overload (COV) Relay:
• Primarily for bus or feeder faults (not as much for
the unit)
• Voltage controlled over current relay cannot
operate unless the voltage is low
• Current and voltage can be adjusted
independently
• Potential for COV relay comes from the bus
• Overcurrent element can be set below rated load
• Will not operate until a fault reduces the voltage
111
Current – Overload Protection is a back up for bus
or line faults rather than to protect the unit directly.
Transformer A
Gen
Bus Pot
COV
B
112
Generator Rotor Protection
(Rotor Faults)
• Voltage relay used
to detect ground in
floating system
• First ground causes
a trickle effect and
generates alarm
• Second ground
creates a short and
subsequent trip
113
Generator Protection
• Unbalanced currents detected through
negative sequence filters with same
relays
114
Power System Protection
115
Voltage from two sides of the open circuit breaker are fed into the
synchronizing scope. (Bus pot & Line pot).
If the voltages are the same frequency, the scope will not rotate.
If the voltage wave forms are of different frequencies, the scope
will rotate in proportion to the frequency differences.
The needle will always point to the phase angle difference at that
time.
116
Sync-check Relays (Device 25)
A B
f f
V V
117
Sync-check Relays (Device 25)
PL
161KV Bus
Synchronizing Bus Synchronizing Bus supplies
Bus 1 potential bus information to the
synchronizing Scope.
119
Reclosers
• Good for temporary faults
• Number & timing of reclosure attempts is utility
defined
• Does NOT check for fault or trip!
• Usually disabled (blocked) by backup relaying
120
Reclosers
Advantages
• Checks the frequency and power angles
before allowing reclosing
• Maintains generation to load balance
Disadvantages
• Generator instability
• Transformer “through” fault currents
• Safety of the General Public
121
The Circuit Breaker Has A Two Shot Re-closure
CB has two re-
closures.
1. High Speed – The SGR-12
breaker will trip and
close back within CB
about 12 cycles. SGR-12
2. Standard Speed –
The breaker will trip
and close back the
second time in about
30 cycles.
122
SGR-12
Operates a DC contact in the Re-closing Circuit
123
Under Frequency Relays
• Distributed throughout system
• Coordinated with neighboring systems
• Achieves generation to load balance when
manual action by the System Operator is not
fast enough (Major System Disturbances)
• Relief is divided into levels
124
Under Frequency Relay and Load Shedding Auxiliary
Tripping Relay
125
Relay Failure
Types of Relay Failure:
• Current Transformers (CT) and their circuits
• Potential Transformers (PT) and their circuits
• Loss of DC
Short Circuit
Open Circuit
Relay component failure
126
Breaker Failure
z Loss of DC supply
z Open trip coil
z Short circuited trip coil
z Mechanical Failure of Tripping Mechanism
z Failure of Main Contacts to Interrupt
127
Breaker Failure Becomes a Primary Tripping Source
Due To A Loss of Air In 5058
128
Trips all PCB’s
that feeds 5058
Aux
15 cycles 3 cycles
MIN
5058
Trip
BF LR63MTX
Line Relays
129
Breaker Failure
• Detects a trip signal being sent to an isolating
device
• Starts a timer
• Initiates a trip to other devices if the
open/close contact on the isolating device in
question doesn’t change state and non-
directional fault current is still present
• Reacts faster than backup distance relaying
• No communication between substations
130
A BF AA AAA
B BB BBB
C CC CCC
131
Objectives
We learned about how protective relays receive
their information about conditions on the powers
system.
We discussed the function of various relay
technologies and their limitations.
We understand how relays are integrated together
for total system protection.
We diagnosed system contingencies given
protection information.
We understand how the different pieces of electrical
equipment are protected.
132