Anda di halaman 1dari 10

Soil Dynamics and Earthquake Engineering 23 (2003) 313–322

www.elsevier.com/locate/soildyn

Dynamic characteristics of a base isolated building from ambient


vibration measurements and low level earthquake shaking
C.E. Venturaa,*, W.D. Liam Finnb, J.-F. Lordc, N. Fujitad
a
Department of Civil Engineering, The University of British Columbia, 2324 Main Hall, Vancouver, Canada 761-0396
b
Anabuki Chair of Foundation Geodynamics, Kagawa University, Japan
c
Department of Civil Engineering, The University of British Columbia, Canada
d
Anabuki Chair of Foundation Geodynamics, Kagawa University, Japan
Accepted 2 September 2002

Abstract
Ambient vibration tests were conducted on a base-isolated apartment building in Takamatsu, Japan, to determine the mode shapes and the
associated natural frequencies and damping ratios at very low levels of excitation. The latest developments in signal analysis for modal
decomposition are used to analyze the ambient response data. A finite element model of the building and isolators was calibrated and refined
using the experimental results from the ambient vibration tests. This model was then used to simulate the recorded response of the building
under excitation from a small earthquake. The finite element model, calibrated by ambient vibration data and the low level of earthquake
shaking, provides the starting point for modelling the non-linear response of the building when subjected to strong shaking.
q 2002 Elsevier Science Ltd. All rights reserved.
Keywords: Base-isolated building; Ambient vibration tests; Modal characteristics; Model updating; Signal analysis

1. Introduction and objective of study point for realistic computational models for the non-linear
analysis of structures under strong ground shaking corre-
Ambient vibration tests were conducted on a base- sponding to Level 2 motions, specified for strong shaking in
isolated building in Takamatsu, Japan, to determine its the Japanese Code.
dynamic response characteristics under very low levels of
excitation. The study was a joint research venture between
Kagawa University, Takamatsu, Japan, the University of 2. Description of the building
British Columbia, Vancouver, Canada, and Anabuki
Komuten of Takamatsu, Japan. The natural frequencies, The Wakabaryo Building is a base-isolated six-storey
modal damping and mode shapes of the building were reinforced concrete frame building. The lateral force
determined in the longitudinal, transverse and torsional resisting structural system consists of concrete shear walls
directions in order to provide data for the calibration of a in the transverse direction and concrete moment frames in
finite element model of the building in its initial state before the longitudinal direction. The superstructure is supported
the onset of strong shaking. The primary objective of the on 12 rubber base isolators. Each base isolator has a
study is to provide a starting point for tracing the evolution diameter of 0.80 m and a height of 0.42 m. The footings
of the non-linear response of the building under strong under the isolators are supported on circular reinforced
shaking, using the computer program ETABS [1]. concrete caissons, 18 m long, 1.8 m in diameter and are
The dynamic characteristics at low levels of shaking connected by deep reinforced concrete beams (depth ¼ 1.5
correspond to elastic response and therefore may be m). Therefore, it is reasonable to assume for finite element
appropriate for the analysis of the building response to the modelling purposes that the foundation can be considered
Level 1 motions specified for the serviceability design level fixed against rotation. Two different views of the building
in recent Japanese codes. They also provide the starting are shown in Fig. 1. A 6.84 m high mechanical equipment
room, which houses a 3 ton water storage tank, can be seen
* Corresponding author. at one end of the building above the roof level. A close up of
0267-7261/03/$ - see front matter q 2002 Elsevier Science Ltd. All rights reserved.
PII: S 0 2 6 7 - 7 2 6 1 ( 0 2 ) 0 0 2 0 8 - 7
314 C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322

Fig. 1. Views of the Wakabaryo building. Fig. 2. Details of base-isolation system: (a) the base isolator itself along
with a strong motion accelerometer; (b) the emergency exit.
the base-isolation system is shown in Fig. 2(a). Fig. 2(b)
shows how the entrances to the building have been designed the building. A modal identification of the structure was
to prevent any contact of the stairs with the ground and to
developed from the ambient vibration data using state-of-
ensure proper performance of the base isolation system. A
the-art modal analysis techniques. This section describes the
plan view and an elevation of the building are shown in
experimental work and the data analyses.
Fig. 3 along with some pertinent dimensions. Storey heights
are as follows: first and second floors, 3.31 m; third through
fifth floors, 2.76 m; and sixth floor, 2.81 m. Immediately 3.1. Instrumentation
after construction in 1996, the building was permanently
instrumented with strong motion accelerometers. This The ambient responses of the building were measured
instrumentation has already recorded the motions from a with a 10-channel data acquisition system using EpiSen-
magnitude 5.4 earthquake that occurred in the Wakayama sor Model FBA ES-T force balanced accelerometers,
Prefecture on August 21, 1999. This earthquake induced connected by shielded cables to a 16-bit signal condi-
ground accelerations of less than five gals at the base of the tioner and A/D converter (Kinemetrics, VSS3000). The
building [2]. EpiSensor ES-T can be uni-axial or tri-axial. Both types
were used during the ambient vibration testing of the
building. Its range of operation is user selectable at
3. Experimental study ^ 0.25, ^ 0.50, ^ 1.0, ^ 2.0, or ^ 4.0 g. The range of
^ 0.50 g was selected for the study. A laptop computer
The experimental study consisted of a series of ambient was used for data acquisition and data storage. For each
vibration measurements at selected locations throughout set-up, the data was recorded for a period of 20 min at
C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322 315

Fig. 3. Typical plan and elevation of the Wakabaryo building.

a rate of 200 samples per second (sps), thus resulting in assumption of the analysis of these ambient vibrations
a Nyquist frequency of 100 Hz. is that the inputs causing motion have white noise
In order to capture the transverse, longitudinal, and characteristics in the frequency range of interest. This
torsional modes of the building, three uni-directional assumption implies that the input loads are not driving
horizontal accelerometers were used on each floor. Two the system at any particular frequency and therefore any
reference sensors were placed on the roof (one in each identified frequency associated with significant strong
direction). The locations of the accelerometers are response reflects structural modal response. However, in
shown in Fig. 4. A total of four separate set-ups were reality, some of the ambient disturbances, such as, for
needed to measure the motions at each floor of the instance, an adjacent machine operating at a particular
building. frequency may drive the structure at that frequency. In
this case, the deformed shapes of the structure at such
3.2. Analysis of ambient vibration data driving frequencies are called Operational Modes. This
means that a crucial requirement of methods to analyze
During normal operating conditions, a building is ambient vibration data is the ability to distinguish the
regularly subjected to ambient vibrations generated by natural structural modes from any imposed operational
wind, occupants, ventilation, etc. The fundamental modes.
316 C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322

Fig. 4. Accelerometer sensor locations: (a) ground floor; (b) floors 1 through 6; (c) roof level.

The computer program ARTEMIS Extractor [3] was used matrices obtained from the measurements. The results of
to perform the modal identification of the structure. In order the decomposition are a set of singular values and
to increase confidence in the modal identification results, associated singular vectors. The singular values are
two independent analysis techniques were used with the estimates of the auto spectral density of the component
same vibration data: frequency domain decomposition SDOF systems, and the singular vectors are estimates of
(FDD) and stochastic subspace identification (SSI) [4,5]. the mode shapes. The FDD technique involves the
The objective of using two modal identification techniques following main steps: (a) estimate spectral density
is to cross-validate the results. The FDD technique, as matrices from the measured time series data; (b) perform
applied, easily identifies frequencies and peak responses, a SVD of the spectral density matrices; (c) if multiple
which may be associated with either structural or oper- data sets are available, average the singular values of from
ational modes. However, when viewing animated mode all data sets and display the results in graphical form; (d)
shapes, it is usually possible to identify structural modes. On scan the curves of singular values and ‘peak pick’ the
the other hand, the SSI technique can discriminate reliably frequencies of interest and estimate the corresponding
between structural and operational modes but it requires mode shapes at each frequency of interest using the
very lengthy calculations. information contained in the singular vectors of the SVD.
The essence of the FDD technique is to perform an A further refinement of the FDD, the enhanced frequency
approximate decomposition of the measured system domain decomposition (EFDD) method in ARTEMIS , uses
response into a set of responses of independent single the modal estimates from the FDD technique to identify the
degree of freedom (SDOF) systems, one for each mode. bell-shaped spectral functions of the SDOFs. From these
The decomposition is performed by a singular value functions, it estimates additional modal parameters such as
decomposition (SVD) of each of the spectral density modal damping.
C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322 317

The principle behind the stochastic subspace iteration Table 1


(SSI) technique is to fit the vibration data in the time domain Fundamental periods of the building
with a parametric model. The parametric model is a Mode no. Period (s) MAC
mathematical model where parameters can be adjusted to
replicate the raw time series accurately. The parameters FDD SSI
should be chosen so that the deviation between the predicted
1 0.43 0.42 0.94
response and the measured response is minimum. By using
2 0.37 0.36 0.98
the transfer function of the mathematical model, the natural 3 0.32 0.31 0.99
frequencies, damping ratios, and mode shapes can be 4 0.14 0.14 0.71
extracted. 5 0.13 0.13 0.95
Details of the FDD and the SSI techniques may be found 6 0.11 0.11 0.97
in Refs. [4,5].

the different structural elements is rather low. Since


4. Experimental results the damping of the base isolators is highly dependent on
the strain induced by the lateral shaking, at low levels of
The ARTEMIS Extractor FDD Peak Picking editor strain the associated damping for each isolator is rather
displays singular values of the spectral density matrices small. The implication of this is that the overall damping of
(Fig. 5). The peaks represent either structural modes or the system could be considered for practical purpose as
operational modes. The structural frequencies were esti- proportional or classical damping, and thus, the associated
mated as described in the previous section and are mode shapes of the system are essentially identical to the
identified in Fig. 5. The values of these frequencies/periods modes of the system without damping. As the levels of
are also given in Table 1. The structural mode shapes and shaking increase, the strains of the isolators will increase
frequencies were also estimated using the SSI technique. and, consequently, the damping of the isolators will
The correlation between the FDD and SSI modes can be increase. The overall damping of the system will become
quantified using the modal assurance criterion (MAC) [6]. of the non-proportional or non-classical type, and the
The correlation between all of the modes estimated by both associated mode shapes could become complex-valued
techniques is presented in Table 2. The MAC value for vectors. In such a case, the traditional modal superposition
each mode can also be found in Table 1. A MAC index of method of analysis is no longer applicable, and alternative
above 0.7 was obtained for the first six modes indicating a methods of analysis need to be used for evaluating the
good correlation between both techniques. The first six seismic response of the structure. The modal identification
structural modes of the building are well defined in the of the ambient vibration data performed with the program
transverse, longitudinal, and torsional directions. ARTEMIS resulted in low modal damping values. Further-
Elevations, plans, and oblique views of the mode shapes more, the identified mode shapes, when animated, look like
are shown in Fig. 6. stationary waves, which is a good indicator that all the mode
The damping ratios obtained using EFDD and SSI are shapes are real valued. Had the mode shapes been complex-
presented in Table 3. They represent the amount of damping valued, each would have appeared as a traveling wave
in the building for the displacement generated by each propagating from the base of the structure to the roof. But
mode, hence the small damping values. It is generally that was not the case during the analysis of the ambient data.
accepted that at ambient levels of shaking, the strain of It can then be concluded that at the levels of ambient
vibration, a base isolated building behaves essentially as a
classically damped system.

Table 2
MAC matrix

FDD (s) SSI (s)

0.42 0.36 0.31 0.14 0.13 0.11

0.43 0.94 0.02 0.31 0.24 0.14 0.06


0.38 0.23 0.98 0.23 0.11 0.03 0.02
0.32 0.37 0.38 0.99 0.24 0.03 0.06
0.14 0.49 0.1 0.18 0.71 0.49 0.23
0.13 0.08 0.02 0.13 0.09 0.95 0.34
0.11 0.06 0.04 0.06 0.07 0.29 0.97
Fig. 5. Singular values of the spectral density matrices.
318 C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322

Fig. 6. Elevations, plans, and oblique views of the first six mode shapes of the building obtained experimentally.

5. Finite element model calibration elevations were defined at the centreline elevation of the
girders; (2) the building masses were lumped at the floor
The computer program ETABS Non-linear, Version 7.1 level; (3) the floor diaphragms were rigid in plane; (4) the
[1], was used to develop a finite element model of the base was assumed fixed because of the foundation
Wakabaryo building. The ETABS model was idealized as an
assemblage of area, line, and point objects. These objects Table 3
Damping ratios of the building
were used to represent different objects such as columns,
beams, walls, and slabs. Three-dimensional mode shapes Mode no. Damping (%)
and frequencies, modal participation factors, direction EFDD SSI
factors and participating mass percentages can be evaluated
using either eigenvector or Ritz-vector analysis. In this 1 3.91 ^ 1.53 6.21 ^ 0.614
2 5.86 ^ 0.843 3.66 ^ 0.368
study, the frequencies and corresponding mode shapes were 3 5.08 ^ 0.595 2.93 ^ 0.454
evaluated using Ritz-vector analysis [7]. 4 2.90 ^ 2.56 4.20 ^ 0.324
A few assumptions were made in order to build the 5 3.23 ^ 1.70 4.02 ^ 0.468
6 6.26 ^ 0.841 4.69 ^ 0.621
analytical model of the Wakabaryo building: (1) the floor
C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322 319

structures; (5) beam to column connections were fixed Table 4


(moment resisting frame assumption); (6) shear walls and Comparison of periods from experimental data and ETABS model
floor slabs were modeled as plate elements; (7) the Mode no. Experimental period (s) Analytical period (s)
base isolators were modeled as line elements with two
translational and one vertical spring stiffnesses; and (8) no 1 0.43 0.42
rigid-offsets were used to model beam-to-beam and beam- 2 0.37 0.40
to-column connections. 3 0.32 0.35
4 0.14 0.11
The specified concrete strengths used in the model for
5 0.13 0.09
the columns, beams, slabs, and walls are 24.7 MPa for 6 0.11 0.08
floors 1 – 3 and 23 MPa for floors 4 to the roof. Grade
400 reinforcing steel was also used in the model. A as in-fill walls. A stiffness modifier coefficient of 0.2 was
partition load of 120 kg/m2 was added to simulate the used (i.e. 20% of Ig was used) for these walls.
ceiling loads and other partitions present in the building. In order to achieve a good correlation between the
The weight of the concrete slabs was adjusted accord- experimentally determined modal characteristics and
ingly to accommodate this increase. The 3 ton water those from the finite element model, it is very important
tank, located in the mechanical equipment room, was to select the appropriate stiffness of the isolators for low
modeled approximately as a uniformly distributed mass levels of shaking. The design stiffnesses for earthquake
over the plan area of the mechanical equipment room. design were supplied by the manufacturer, but these are
The total weight of the modeled structure is about not appropriate for ambient motions. At the low level of
3800 ton. Lastly, the longitudinal walls were considered vibration at which the building test was conducted, the
isolators behaved almost like rigid links. Therefore, the
isolator’s stiffness proposed by the manufacturer had to
be increased significantly in order to match the modal
characteristics obtained from ambient vibration data with
the analytical ones. The appropriate ambient vibration
stiffness was 80 kN/mm. As a reference, the initial
manufacturer’s stiffness was 8.75 kN/mm.
The model of the building is shown in Fig. 7. The
fundamental frequencies/periods are presented in Table 4
and the corresponding mode shapes are shown in Fig. 8.
The short stubby lines under the building show the
directions of the deformation of the isolators. By
comparing Figs. 6 and 8, it can be seen that there is
good correspondence between experimental and analyti-
cal mode shapes. Since the results are satisfactory, the
model is thought to be a good representation of the real
the building (or ‘of reality’).

6. Response due to low level earthquake shaking

The response of the Wakabaryo building was recorded


during a magnitude 5.4 earthquake that occurred on August
21, 1999. The response of the building during the
earthquake was compared to its ambient vibration response.
The frequency response function (FRF) of the earthquake
records is shown in Fig. 9. It can be observed that the natural
frequency of the building dropped from 2.34 to 2.05 Hz in
the first transverse mode, from 2.66 to 2.36 Hz in the first
torsional mode, and from 3.16 to 2.60 Hz in the first
longitudinal mode. This reduction in frequencies indicates
that the stresses and displacements generated in the isolators
have reduced their stiffness and therefore increased the
period of the building. This is the expected action of the
Fig. 7. ETABS model of the Wakabaryo building. isolators as the level of shaking increases.
320 C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322

Fig. 8. View of the first six mode shapes of the building obtained analytically.

The ground motions recorded at the foundation level structural response of the model and the recorded
of the building were used as inputs for a non-linear earthquake data on the building was obtained. The initial
time-history analysis of the ETABS model. The computed stiffness of the force-displacement curve of the isolator
responses of the floor immediately above the isolator and needed to be adjusted to represent the average properties of
the response of the roof level were compared with the the isolators for the strain levels at which the isolators were
measured motions at these same levels during the earth- being initially deformed during the earthquake. The bi-
quake. To this end, the stiffness of the isolators was linear link properties used to model the isolators are listed in
modified until a good match between the computed ETABS Table 5. A comparison of the acceleration response spectra
C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322 321

for calculated and measured motions in the transverse and


longitudinal directions, at the ground floor and roof levels, is
shown in Fig. 10. A good match was obtained for the
transverse direction and an acceptable match was obtained
for the longitudinal direction. This indicates that the ETABS
model is a good representation of the existing structure.
The next step in the present ongoing study will be to
analyze the response of the building to the strong motion
input used for design, and to subject the model to other
extreme levels of shaking in order to understand better the
Fig. 9. FRF of earthquake record. behavior of the base isolation system and the superstructure.
Table 5
Isolator properties used for calibrating the ETABS model to the Wakayama earthquake

Direction Linear properties Non-linear properties

Effective stiffness (kN/mm) Effective damping (%) Stiffness (kN/mm) Yield strength (kN) Post-yield strength ratio

X 80 0.25 60 128.4 0.022


Y 200 0.25 65 128.4 0.022
Z 2500 0.18 – – –

Fig. 10. Comparison of acceleration response spectra of measured and calculated floor responses.
322 C.E. Ventura et al. / Soil Dynamics and Earthquake Engineering 23 (2003) 313–322

7. Conclusions and support of Mr Yasuo Asakura and Mr Tadaharu


Manabe of Anabuki Komuten were crucial to the success
The fundamental periods and corresponding mode of the project. Mr Estuardo Ventura of Vancouver provided
shapes for the Wakabaryo apartment building in Takamatsu, invaluable assistance in carrying out the tests. Ambient
Japan, were determined experimentally using ambient vibration research conducted by Dr Carlos E. Ventura at
vibration measurements. Two techniques were used to the University of British Columbia is supported by the
derive the modal characteristics of the structure: the FDD Natural Science and Engineering Research Council of
and the SSI. The first six mode shapes were obtained both Canada.
graphically and numerically.
The damping ratios were obtained using the EFDD and the
SSI techniques. It was recognized that a base-isolated structure
should have non-classical damping, but considering the low References
level of vibration, the isolators act almost as rigid links and
classical damping can be considered as a valid assumption. [1] Computers and Structures Inc. (CSI). ETABS User’s manual. Berkeley,
The modal parameters obtained experimentally were California; December 1999; www.csiberkeley.com.
[2] Ventura CE, Finn WDL. Ambient vibration measurements of four
used to calibrate a finite element model of the building. The
buildings in Kagawa prefecture, Japan. UBC Earthquake Engineering
initial stiffness of the isolators required to replicate the and Anabuki Chair of Foundation Geodynamics; 2000.
ambient response was 80 kN/mm. Analysis of the calibrated [3] Structural Vibration Solutions ApS. ARTEMIS Extractor, Release 3.0.
model using recorded low level input motions resulted in User’s Manual, Alboorg, Denmark; 2001; www.svibs.com.
response spectra in good agreement with the spectra of the [4] Brincker R, Zhang L, Andersen P. Modal identification from ambient
recorded motions in the structure responses using frequency domain decomposition. Proceedings of the
18th International Modal Analysis conference (IMAC), San Antonio,
The finite element model, calibrated by ambient vibration
Texas; 2000.
data and verified for a low level of earthquake shaking, [5] Brincker R, Andersen P. Ambient response analysis of the heritage
provides the starting point for modeling the non-linear court tower building structure. Proceedings of the 18th International
response of the building when subjected to strong shaking. Modal Analysis conference (IMAC), San Antonio, Texas, vol. II.;
2000.
[6] Allemang RJ, Brown DL. A correlation coefficient for modal vector
analysis. Proceedings of the First International Modal Analysis
Acknowledgements
Conference (IMAC), Orlando, Florida; 1982.
[7] Chopra AK. Dynamics of structures: theory and applications to
The financial and logistical support provided by earthquake engineering, 2nd ed. Upper Saddle, New Jersey: Prentice
Anabuki Komuten is gratefully acknowledged. The interest Hall; 2001.

Anda mungkin juga menyukai