2400
All Posi-STRUT® components should be strapped and
stacked vertically with the bottom chord clear of the
ground, supported on bearers located directly under
web points. Posi-STRUTS® may be stacked on top of
each other with bearers aligned as closely as 300
possible to web panel points.
Posi-STRUTS® should not be left exposed to weather for
extended periods of time without adequate protection. If
covered, ensure adequate air circulation around the trusses.
Bearers as close as
Fig. 2
possible to web points.
1200
2400
300
Bearers as close as
possible to web points.
Fig. 3
600
600
2400
5
SET OUT AND PLACEMENT Trimming limitations for Posi-PLUS®
Posi-STRUTS® are generally placed perpendicular to Posi-PLUS® members may be trimmed at either end to
load bearing supporting walls and should be located so within a minimum distance of 90 mm from the
that distance between them does not exceed the Posi-STRUT® web.
designed spacing.
90mm minimum clearance
Care should be taken to place the Posi-STRUTS® the
right way up. Unless marked otherwise Posi-STRUTS®
are always manufactured so that Posi-Web starts at the
top chord at each support point. There are occasions
where it is necessary to design and manufacture
Posi-STRUTS® with the first web starting at bottom chord
level. In this case trusses will be marked “THIS WAY UP”.
6
Where there are larger openings in the upper storey wall CASE 2. Single Storey - for a single storey construction
which cause a concentrated load on the Posi-STRUT® or where continuous support for the end F-Frame is not
F-Frame, a suitable timber vertical member should be available, frames using Posi-JOIST® detail may be
inserted between the top and bottom chord under the used provided the roof load (EL) does not exceed that
point load to transfer it down to the wall below. specified in Table 6, and that pier spacing does not
exceed 1200 centres.
Note: 1. Posi-STRUT® chords and F-Frame chords may
be considered to act in conjunction with wall Table 6. Effective Length of Roof Supported. (EL)
plates to form a double plate or ribbon plate.
Posi-JOIST® Sheet Roof Tiled Roof
2. Where openings are positioned in end walls, (mm) (mm)
End Size
lintels are to be sized in accordance with
AS1684. PJE25 7200 3600
Upper storey wall PJE30 7200 3600
PJE40 7200 3600
Studs carrying
concentrated loads Where the effective length of roof supported exceeds
that specified in Table 6, use either solid timber or
laminated ConstructaBEAMS to support end wall and
roof loads. Bearer sizes to be taken from AS1684-1999,
relevant State Timber Framing Code or refer Gang-Nail
Span Charts for laminated ConstructaBEAMS or
Opening AutoBEAM.
X
Standard
Posi-STRUT®
floor truss
X
Lintel to
AS1684
Timber verticals
to be placed
under studs
where effective
length of roof
supported by
upper storey
wall is greater Solid timber or laminated Common
than specified ConstructaBEAM bearer Posi-STRUT®
Lower storey wall in Table 5. Overhang supported by brick piers Overhang
Trim
Plasterboard
Posi-JOIST END 30 (PJE30)
WARNING (Typical)
Where stair wells or other voids are located adjacent 50 62
external walls, the stability of the external wall should be
checked by a structural engineer.
Generally, F-frames may be
1200 max. 1200 max. 1200 max.
used to support upper walls of
two storey construction at end
walls where floor and ceiling Upper
acts as a diaphragm to restrain storey Posi-JOIST END 40 (PJE40)
the external wall against lateral
(Typical)
loads. Opening
50 20
However, F-frames should not
be used whenever supporting Do not use
F-frame, Floor
external walls that have an solid bearer
opening for a void area or or standard
Posi-STRUT 1200 max. 1200 max. 1200 max.
staircase as shown. In these
cases, the external walls are
Lower
required to be designed by a storey
Internal
structural engineer. wall
7
CASE 3. Building with Hip Ends - Both of the above SUPPORTING NON-LOAD
two cases apply, provided the truncated girder truss
station does not exceed the effective length of roof BEARING WALLS
supported specified in Table 5. Walls Perpendicular to Posi-STRUTS®
Walls placed perpendicular to the Posi-STRUTS® require
Overhang
no additional support. However, for braced walls with
Truncated girder station
bracing capacity of up to 3.0 kN/m and 2700mm high,
Truncated fix each end of bracing wall using 2/90 x 35 F5 under
girder truss
battens with M10 bolt and washer.
8
Walls Parallel to Posi-STRUTS® External brickwork
Load bearing or non-load bearing stud wall
a) Platform Flooring
Walls placed parallel to the Posi-STRUTS® do not
require additional support where a platform floor is to be
used and the flooring material is capable of supporting
walls. However, for braced walls with bracing capacity
of up to 3.0 kN/m and 2700mm high, fix each end of
bracing wall using 2/90 x 35 F5 under battens with M10
bolt and washer.
Bracing wall M10 bolt and washer Truss to be supported
on bottom chord
Double truss
centred under
partition wall Timber block nailed to end web Concealed beam
Fitted Flooring Figure ‘X’
Double trusses used under non-load bearing internal
partition walls should be located such that the partition is Recommended Timber Blocking Sizes
bearing equally on both trusses. Flooring and strong- Posi-STRUT Depth 200 250 300 400
backs should be fixed to both trusses.
Strongback Size 90 x 35 120 x 35 140 x 35 190 x 35
SUPPORT DETAILS
Timber End Block for Top Chord Supported
Posi-STRUT® Bottom Chord Support Posi-STRUTS®
Posi-STRUTS® may be supported on their bottom chord
as shown Support width GQ - 75 x 100
35 mm - 60 mm
Load bearing wall
Support width
Support width
Figure ‘Y’.
9
Posi-JOIST® Bottom Chord Support Posi-JOIST®
Posi-JOISTS® should only be supported on their bottom
chord as shown.
External brickwork
Truss to be supported
on bottom chord
Fixing to Internal Walls
®
Posi-PLUS Bottom Chord Support When Posi-STRUTS® are to be supported by internal
Load bearing wall walls place Posi-STRUTS® side by side and fix as above
or butt together using a 50 x 100 mm Strapnail to connect
Waling plate or lintel Posi-STRUTS®.
50 x 100mm Strapnail or
4T5 (43 x 120mm) Tylok
Trip-L-Grip
90 x 35mm block
10
Fixing to Internal Walls b) Bracing Wall
a) Non-bracing wall Where internal walls are designed as bracing walls,
trusses should be fixed to the top plate using structural
If internal walls are not designed as bracing walls, fix the connections of equivalent strength to the bracing
truss with the INTERNAL WALL BRACKET with nails at strength of that particular bracing wall. The connection
the top of the slots to allow for truss settlement as it should also allow the truss to deflect vertically when it is
is loaded. Brackets are fixed at 1.8m centres along loaded.
unsupported sections of the wall. Where trusses are
parallel to walls, trim between the bottom chords and fix Truss Parallel to Bracing Wall
brackets to the trimmer. Where internal walls are stable Nailing plates or framing anchor (legs not bent)
in their own right, no Internal Wall Brackets are required. to either end of nogging with 6/2.8mm diameter
nails to each face.
Truss Parallel to Non-Bracing Wall 90 x 35mm blocking
connected to
Internal Wall Bracket Shear blocks nailed Posi-STRUT with
nailed at top of slot. or bolted as per 6/2.8mm diameter nails.
Leave gap between Table 7.
nail head and bracket
90 x 35mm to allow for vertical
movement of truss Nogging
on loading.
Posi-STRUT
Gap to truss
Internal Wall
Bracket nailed
Internal Wall Bracket at top of slot.
nailed at top of slot. Leave gap between
Leave gap between nail head and
nail head and bracket bracket to allow
to allow for vertical for vertical
movement of truss movement
on loading. of truss on
loading.
90 x 35mm
Gap to truss
Type of Number of Type A or Type B bracing units in braced wall (Refer AS1684 Part 4)
Connection Unseasoned Timber Seasoned Timber
J2 J3 J4 JD4 JD5 JD6
Type A Type B Type A Type B Type A Type B Type A Type B Type A Type B Type A Type B
Nails
4/3.05ø 1.6 N 1.1 N N N 1.1 N N N N N
6/3.05ø 2.1 1.1 1.5 N 1.1 N 1.6 N 1.2 N 1.0 N
4/3.33ø 1.9 N 1.3 N N N 1.3 N 1.1 N N N
6/3.33ø 2.4 1.2 1.7 N 1.2 N 1.8 N 1.5 N 1.1 N
Bolt Size
M10 2.5 1.3 2.2 1.1 1.7 N 2.0 1.0 1.6 N 1.3 N
M12 3.3 1.6 2.6 1.3 2.1 1.0 2.4 1.2 1.9 1.0 1.5 N
Screws
2 No.14 Type 17 3.2 1.6 2.3 1.2 1.6 N 2.3 1.2 1.6 N 1.2 N
3 No.14 Type 17 5 2.5 3.3 1.7 2.5 1.2 3.3 1.7 2.5 1.2 1.8 N
N - Not Suitable
11
Fixing to Steel Beam Table 8. Timber Blocking Size Required
Note: Posi-PLUS® Timber Blocking Size
1. Size of packers and timber fixing plate to suit steel PP 250 deep 120 x 35
flange width.
PP 300 deep 140 x 35
2. Timber fixing plate is to be contained within the steel
beam flange so as to restrain any vertical loads
induced by Posi-STRUT® trusses.
Posi-TRUSS®
Skew nail top flange Packers 70 x 35 or 70 x 45mm softwood
to fixing plate fastened securely to steel web
WRONG WRONG
Timber blocking fitted between each Posi-PLUS and nailed securely to Posi-PLUS timber
Refer Table 8 for member size
12
Table 9. Recommended Strongback Sizes Table 10. Splice Plate Sizes
Posi-STRUT Strongback Joint GN Plate Tylok Plate
200 250 300 400 Size Type Type & Size
Depth Type & Size
Strongback 90 x 35 Single GE75150 6T10
90 x 35 120 x 35 140 x 35 190 x 35 120 x 35 Single GE75150 6T10
Size
140 x 35 Double GQ50150 6T5
Strongback fixing and splice 190 x 35 Double GQ63150 8T7
Timber splice plate fixed to
Strongback with 5/3.15 dia. When strongback location changes, the strongback must
nails each side of splice
run through to the next Posi-STRUT® and be connected
Splice plate.
Same size and
to the side as per detail following.
grade as Strongback
Connection of strongback to Posi-STRUT® at
change of span
Strongback
fixed to
3/3.15 dia. nails Posi-STRUT®
vertical web
Strongback
Timber
splice plate
Strongback
Strongback
1 screw into
top and bottom
2 screws to face chord of Posi-STRUT
of strongback
Note:
1. All screws MiTek 14 gauge x 30mm.
2. Do not over tighten screws.
Splice plate as
specified in Table 10
13
STAIR OPENINGS
Where openings are required on the upper floor for
stairwells, one or more shorter Posi-STRUTS® may be
used and supported on headers fixed to adjacent
Posi-STRUTS®.
The header beam maybe supported on double
Posi-STRUTS® as shown below. For header
beam sizes refer Table 11. The connection
Double Posi-STRUT®
of the header to the double Posi-STRUT®
is as shown on page 15. Refer page 15
for fixing details
Note that header beams have
Header Beam
been designed to carry
Posi-STRUT® floor
loads only.
Double Posi-JOIST®
Knee wall
Shortened
Posi-STRUT®
Shortened
Posi-JOIST®
Note:
Posi-JOIST to be supported by fixing end vertical web
End supporting
as specified on page 10. structure
Header Beam
Posi-PLUS® Header Beam
Fixing Detail Double Posi-STRUT®
each side of stairwell opening
Joist Hanger
Shortened
Posi-STRUT®
with extended top chord
Packer block
Double Posi-PLUS®
Refer page 15
for fixing details
Header Beam
Double Posi-PLUS®
Shortened
Posi-PLUS®
14
Illustrated below are some common types of stairwells Table 12. Maximum Spans for double Posi-STRUTS®
(refer to Figures 1 to 3). For each diagram there are
Case 1 and Case 2 Supporting Header Beam (mm)
certain conditions that need to be observed.
Posi-STRUT® Timber Size Timber Grade
For other types of stairwells, and for dimensions
greater than those shown in Figures 1 to 3, contact your Size (mm x mm) F5 F8 F17
Posi-STRUT® supplier. PSW3520 35 x 70 - 3500 4100
Shortened Posi-STRUT® Shortened Posi-STRUT® 35 x 90 3400 3800 4200
Case 1 3000mm max. (4800mm max.) PSW3525 35 x 70 3500 4100 4500
35 x 90 3800 4500 4500
PSW3530 35 x 70 3800 4600 4600
35 x 90 4100 4600 4600
Double Posi-STRUT® as Table 12
PSW4525 45 x 70 3900 4600 4900
Header Beam Span
Opening
(void) PSW4530 45 x 70 3200 3600 3600
45 x 90 3600 3600 3600
Header Beam PSW4540 45 x 70 3800 4200 4200
45 x 90 4200 4200 4200
Figure 3
Note:
1. These double Posi-STRUTS® have been designed
to carry header beams which support shorter
Posi-STRUTS® only. They will not carry the stairwell
itself. 15
Typical
2. Double Posi-STRUTS® have also been designed Nailing
for 600mm maximum truss centres. Therefore, web Pattern
layouts of 600mm truss centres should be used. 15 65 70
15
CANTILEVERS
Non Load Bearing Wall
Cantilevered balconies can be formed using solid timber For cantilever beams built into Posi-STRUT® trusses
either fitted into trusses between chords or off to the side ensure full bearing along top and bottom chord using
of the truss as shown below. The cantilever beam can suitable dry timber packers fixed to both truss and beam
be sized from timber span charts and should extend back with 3.15mm dia. nails at 225mm centres.
into the building to a distance greater than the balcony For beams supplied separate to trusses, fix to vertical
length. Balcony cantilevers should be no greater than webs with a minimum of 3/3.15mm dia. nails and to the
one fifth of the floor truss span. first strongback with 1 Trip-L-Grip. Provide lateral ties to
top edge of beam at 600mm centres fixed to beam with
1/3.15mm dia. nail.
Built in cantilever beam.
X 3.15 dia. nails @ 225mm centres
Concealed beam
SECTION Y-Y
Cantilevered beam
Strongback
Balcony length no greater than S/5 Span to first support (S)
16
Packer block required for Posi-PLUS Tie Trip-L-Grip
Cantilevered beam
3/3.15 dia. nails
Strongback
Balcony length no greater than S/5 Span to first support (S)
50mm minimum
160mm maximum
Support Wall X 120 x 35 MGP12 Boundary Joist
Posi-TRUSS®
Posi-STRUT standard outrigger system is recommended
for Posi-TRUSS with small cantilevers with the following SECTION Y-Y
limitations.
Endwall supporting max 9m GN Back Brace Outriggers @ 600 crs. Block Outriggers to be End wall -
Fixing
span trusses for: min. 120 x 35 MGP12 supported off end wall load bearing
SECTION X-X
End wall
load bearing Outriggers @ 600 crs.
min. 120 x 35 MGP12
Cladding GQ100100 plates min.
Min. PSW25 Posi-STRUTS @ 600 crs.
17
BRACING Alternative End and Internal Support Bracing
End and Internal Support Bracing Plywood Bracing Frame at 2400 mm maximum
centres. Standard truss centres
Speedbrace bracing at 2400 mm maximum centres along less truss width
7mm structural plywood or 6.4mm thick
supporting walls. CSR masonite braceboard fixed to top and
bottom plates with 3.15 dia. x 50mm long Truss
3/30 x 2.8mm nails @ 75mm maximum centres height
reinforced head nails
3/30 x 2.8mm 3/3.15 dia. x 75mm long nails
reinforced head nails at both ends of plywood frame
to vertical web of floor truss
Speedbrace
2/30 x 2.8mm
2/30 x 2.8mm reinforced
reinforced head nails head nails
Speedbrace
70 x 35 (F5)
diagonal brace
Alternative brace to be in
opposite direction
2/30 x 2.8mm
reinforced head nails
30 x 2.8mm
reinforced head nails
@ 100mm centres
18
Strongbacks to
be fixed to vertical webs
at 2400mm maximum centres
MECHANICAL SERVICES
Posi-STRUT® trusses allow mechanical service ducts
and plumbing to be easily accommodated. Maximum A D
clearance available for the different Posi-STRUT® depths H
is given in Table 14.
W
Table 14. Maximum Mechanical Service Clearances
Dimension H
Posi-STRUT® Dimension Dimension
50 75 100 125 150 175 200
Size A D
Dimension W
PSW3520 127 120 280 200 120 - - - -
PSW3525 178 170 320 280 230 180 140 - -
PSW3530 232 220 350 310 280 240 210 170 130
PSW4525 158 150 310 260 200 150 60 - -
PSW4530 212 200 340 300 260 210 170 130 70
PSW4540 322 280 490 460 410 370 330 300 250
19