Impedance Relay Characteristics Test Report 06-Jun-18


Paranas SS \ Paranas-Calbayog L1 main1

Location Path

Test and Test Definition Information

Test Plan Name PMS Paranas-Cal L1 April5


Test Name zchar
Test Type Z-Char

Test Definition Name Test Definition 1


Tested Date 4/5/2018

Tested By User Evaluation Fail

Test Definition Description

Relay Under Test General Parameters

Relay Name Paranas-Calbayog L1 main1


Serial Number T1003073
Manufacturer ABB Model Rel 670

Nominal Ratings: fn 60.000 Hz Max Test Current 2000.000% In


Vn 115.00 V (Ph-Ph) Max Test Voltage 1000.00% Vn
In 5.000 A Phase Names and Rotation A-B-C
VTR 138000 : 115 CTR 1200 : 5
Station Name

Protected Object Parameters

Protected Object Name

Protected Object Parameters

Relay Functions

Function Name Distance Function Type Impedance


Display values in Secondary Inherent Op Time 20.0 ms
General Tolerances

Absolute Minimum 0.010 Ohm Absolute Minimum Time 20.0 ms

Zone Elements
Zone Name Char Type Fault Characteristic t nom Residual Compensation Z tol t tol
Type Angle [ms]
-% +% -% +%

ZM01 General 3-Ph 81.47 0 10.00 10.00 10.00 10.00


ZM01 General Ph-Ph 81.47 0 10.00 10.00 10.00 10.00
ZM01 General Ph-N 81.47 0 KN 0.00 0.00 10.00 10.00 10.00 10.00
ZM02 General 3-Ph 81.49 500 2.00 2.00 10.00 10.00
ZM02 General Ph-Ph 81.49 500 2.00 2.00 10.00 10.00
ZM02 General Ph-N 81.49 500 KN 0.00 0.00 2.00 2.00 10.00 10.00
ZM03 General 3-Ph 81.48 1000 2.00 2.00 10.00 10.00
ZM03 General Ph-Ph 81.48 1000 2.00 2.00 10.00 10.00
ZM03 General Ph-N 81.48 1000 KN 0.00 0.00 2.00 2.00 10.00 10.00
Doble Page 2 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Relay Triggers

Signal Name F6 Sense Condition Relay OutPut


Input
No Name Terminal

Inp 1 LN1

F6000 Instrument HW and SW Information


F6TesT Software Version 3.12.2 Build 0002
F6000 Model Number F6150
F6000 CPU ID 67193153

F6000 Firmware Version 4.29.3


F6000 Options F6810 : High power convertible voltage/current sources
F6885 : GPS Receiver Interface
F6895 : GPS Receiver and Antenna
F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6800 : Metering & Transducer Interface
F6825 : CPU2
F6875 : Variable battery simulator
F6844 : Logic I/O 4 board

Test Configuration
Pre-fault Voltage 115.00 V
Pre-fault Current 0.000 A Angle 0 Deg

Test Method Constant Current


Desired Test Current 5 A
Max Acceptable Voltage 90 % of rating

dc transient, fault inception angle


Minimum Offset
Time constant L/R 0.00 ms CT direction Towards Line
Values are in Secondary

Test Timing Trigger Selection

Pre-fault Duration 0.3000 s Fault Type Trigger

Max. Fault Duration 1.1000 s AN LN1 0->1


Max Fault Duration For Faster x Tmax BN LN1 0->1
Zones
CN LN1 0->1
CB Trip Time 0.0000 s
AB LN1 0->1
Time between shots 0.1500 s
Time between shots 0.1500 s
BC LN1 0->1

CA LN1 0->1
ABC LN1 0->1

Doble Page 3 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Test Timing Trigger Selection

Pre-fault Duration 0.3000 s Fault Type Trigger

Max. Fault Duration 1.1000 s AN LN1 0->1


Max Fault Duration For Faster x Tmax BN LN1 0->1
Zones
CN LN1 0->1
CB Trip Time 0.0000 s
AB LN1 0->1
Time between shots 0.1500 s
BC LN1 0->1

CA LN1 0->1
ABC LN1 0->1
Doble Page 4 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Fault Type AN

Zone Name Angle Zexp Zmax Zmin Zact Error Eval Test Voltage
[°] [W] [W] [W] [W] [%]

ZM01 0.00 10.832 11.915 9.749 10.598 -2.156 Pass 52.99 5.0

ZM01 90.00 4.933 5.427 4.440 4.915 -0.375 Pass 24.58 5.0
ZM01 60.00 5.697 6.266 5.127 5.702 0.094 Pass 28.51 5.0
ZM02 0.00 11.470 12.617 10.323 10.621 -7.406 Pass 53.11 5.0
ZM02 90.00 8.096 8.906 7.286 8.066 -0.375 Pass 40.33 5.0
ZM02 60.00 9.348 10.283 8.414 9.357 0.094 Pass 46.78 5.0
ZM03 0.00 12.108 13.319 10.897 10.610 -12.375 Fail 53.05 5.0
ZM03 90.00 12.456 13.702 11.210 12.409 -0.375 Pass 59.76 4.8
ZM03 60.00 14.383 15.821 12.945 14.396 0.094 Pass 59.76 4.1

Fault Type AN

Doble Page 5 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Fault Type BN

Zone Name Angle Zexp Zmax Zmin Zact Error Eval Test Voltage
[°] [W] [W] [W] [W] [%]

ZM01 0.00 10.832 11.915 9.749 10.598 -2.156 Pass 52.99 5.0

ZM01 90.00 4.933 5.427 4.440 4.915 -0.375 Pass 24.58 5.0
ZM01 60.00 5.697 6.266 5.127 5.702 0.094 Pass 28.51 5.0
ZM02 0.00 11.470 12.617 10.323 10.567 -7.875 Pass 52.84 5.0
ZM02 90.00 8.096 8.906 7.286 8.066 -0.375 Pass 40.33 5.0
ZM02 60.00 9.348 10.283 8.414 9.357 0.094 Pass 46.78 5.0
ZM03 0.00 12.108 13.319 10.897 10.610 -12.375 Fail 53.05 5.0
ZM03 90.00 12.456 13.702 11.210 12.409 -0.375 Pass 59.76 4.8
ZM03 60.00 14.383 15.821 12.945 14.396 0.094 Pass 59.76 4.1

Fault Type BN

Doble Page 6 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Fault Type CN

Zone Name Angle Zexp Zmax Zmin Zact Error Eval Test Voltage
[°] [W] [W] [W] [W] [%]

ZM01 0.00 10.832 11.915 9.749 10.629 -1.875 Pass 53.14 5.0

ZM01 90.00 4.933 5.427 4.440 4.915 -0.375 Pass 24.58 5.0
ZM01 60.00 5.697 6.266 5.127 5.702 0.094 Pass 28.51 5.0
ZM02 0.00 11.470 12.617 10.323 10.621 -7.406 Pass 53.11 5.0
ZM02 90.00 8.096 8.906 7.286 8.066 -0.375 Pass 40.33 5.0
ZM02 60.00 9.348 10.283 8.414 9.357 0.094 Pass 46.78 5.0
ZM03 0.00 12.108 13.319 10.897 10.564 -12.750 Fail 52.82 5.0
ZM03 90.00 12.456 13.702 11.210 12.409 -0.375 Pass 59.76 4.8
ZM03 60.00 14.383 15.821 12.945 14.396 0.094 Pass 59.76 4.1

Fault Type CN

Doble Page 7 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Fault Type AB

Zone Name Angle Zexp Zmax Zmin Zact Error Eval Test Voltage
[°] [W] [W] [W] [W] [%]

ZM01 0.00 3.611 3.972 3.250 3.584 -0.750 Pass 35.84 5.0
ZM01 60.00 6.004 6.605 5.404 6.016 0.187 Pass 60.16 5.0
ZM01 90.00 5.200 5.720 4.680 5.161 -0.750 Pass 51.61 5.0
ZM02 0.00 3.823 4.205 3.441 3.814 -0.234 Pass 38.14 5.0
ZM02 60.00 9.348 10.283 8.414 9.366 0.187 Pass 93.66 5.0
ZM02 90.00 8.096 8.906 7.286 8.035 -0.750 Pass 80.35 5.0
ZM03 0.00 4.036 4.440 3.632 4.027 -0.234 Pass 40.27 5.0
ZM03 60.00 10.900 11.990 9.810 10.933 0.300 Pass 103.40 4.7
ZM03 90.00 12.456 13.702 11.210 12.363 -0.750 Pass 103.40 4.1

Fault Type AB

Doble Page 8 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Fault Type BC

Zone Name Angle Zexp Zmax Zmin Zact Error Eval Test Voltage
[°] [W] [W] [W] [W] [%]
ZM01 0.00 3.611 3.972 3.250 3.603 -0.234 Pass 36.03 5.0

ZM01 60.00 6.004 6.605 5.404 5.990 -0.234 Pass 59.90 5.0
ZM01 90.00 5.200 5.720 4.680 5.161 -0.750 Pass 51.61 5.0
ZM02 0.00 3.823 4.205 3.441 3.814 -0.234 Pass 38.14 5.0
ZM02 60.00 9.348 10.283 8.414 9.366 0.187 Pass 93.66 5.0
ZM02 90.00 8.096 8.906 7.286 8.035 -0.750 Pass 80.35 5.0
ZM03 0.00 4.036 4.440 3.632 4.006 -0.750 Pass 40.06 5.0
ZM03 60.00 10.900 11.990 9.810 10.655 -2.250 Pass 103.40 4.8
ZM03 90.00 12.456 13.702 11.210 12.363 -0.750 Pass 103.40 4.1

Fault Type BC

Doble Page 9 of 11

Impedance Relay Characteristics Test Report 06-Jun-18

Paranas SS \ Paranas-Calbayog L1 main1

Fault Type CA
Zone Name Angle Zexp Zmax Zmin Zact Error Eval Test Voltage
[°] [W] [W] [W] [W] [%]

ZM01 0.00 3.611 3.972 3.250 3.603 -0.234 Pass 36.03 5.0

ZM01 60.00 6.004 6.605 5.404 6.016 0.187 Pass 60.16 5.0
ZM01 90.00 5.200 5.720 4.680 5.161 -0.750 Pass 51.61 5.0
ZM02 0.00 3.823 4.205 3.441 3.794 -0.750 Pass 37.94 5.0
ZM02 60.00 9.348 10.283 8.414 9.366 0.187 Pass 93.66 5.0
ZM02 90.00 8.096 8.906 7.286 8.035 -0.750 Pass 80.35 5.0
ZM03 0.00 4.036 4.440 3.632 4.027 -0.234 Pass 40.27 5.0
ZM03 60.00 10.900 11.990 9.810 10.819 -0.750 Pass 103.40 4.7
ZM03 90.00 12.456 13.702 11.210 12.363 -0.750 Pass 103.40 4.1

Fault Type CA

Doble Page 10 of 11

Impedance Relay Characteristics Test Report 06-Jun-18


Paranas SS \ Paranas-Calbayog L1 main1

Fault Type ABC

Zone Name Angle Zexp Zmax Zmin Zact Error Eval Test Voltage
[°] [W] [W] [W] [W] [%]

ZM01 0.00 3.611 3.972 3.250 3.618 0.188 Pass 18.09 5.0

ZM01 60.00 6.004 6.605 5.404 6.016 0.187 Pass 30.08 5.0
ZM01 90.00 5.200 5.720 4.680 5.161 -0.750 Pass 25.81 5.0
ZM02 0.00 3.823 4.205 3.441 3.830 0.187 Pass 19.15 5.0
ZM02 60.00 9.348 10.283 8.414 8.297 -11.250 Fail 41.49 5.0
ZM02 90.00 8.096 8.906 7.286 8.035 -0.750 Pass 40.18 5.0
ZM03 0.00 4.036 4.440 3.632 4.044 0.188 Pass 20.22 5.0
ZM03 60.00 10.900 11.990 9.810 11.309 3.750 Pass 56.55 5.0
ZM03 90.00 12.456 13.702 11.210 12.363 -0.750 Pass 59.76 4.8

Fault Type ABC

Doble Page 11 of 11
Test Current

5.000

5.000
5.000
5.000
5.000
5.000
5.000
4.820
4.150

Test Current

5.000

5.000
5.000
5.000
5.000
5.000
5.000
4.820
4.150

Test Current

5.000

5.000
5.000
5.000
5.000
5.000
5.000
4.820
4.150

Test Current

5.000
5.000
5.000
5.000
5.000
5.000
5.000
4.730
4.180

Test Current
5.000

5.000
5.000
5.000
5.000
5.000
5.000
4.850
4.180
Test Current

5.000

5.000
5.000
5.000
5.000
5.000
5.000
4.780
4.180
Test Current

5.000

5.000
5.000
5.000
5.000
5.000
5.000
5.000
4.830