OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B> 632 of IS 5 & 90microns.
OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B> 697 of IS 5 & 125microns.
OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B> 220 of IS 5 & 90microns.
OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B>692 - BS 381C & 90microns
http://192.168.1.100:8080/OLG_LIVE/Jsp/Login/Login.jsp?X
B:TRANSFORMER DETAILS:
Rated Voltage : 11/0.433 kV Rated Current : 53.48 A Step Voltage : 137.5 V
2.SEQUENCE TEST: During the routine mechanical test sequence of operation of selector switch
contact was recorded oscillographically and switching time recorded was 50.03 millisecond which is
within the acceptable range
3.PRESSURE TEST:
i) OLTCs: 1Kg/sq.cm 30 Mints.(Tested on fabricated tank by applying Air pressure)
ii) Terminal Board : Tested Seprarately for 0.7kg/sq.cm 3Hours (Hot Oil at 80 Degree C)
4.AUXILIARY CIRCUIT INSULATION TEST: A test voltage of 2kV,50HZ was applied for one
minute between live terminals of all auxiliary circuits and the earth terminal on the housing.The test
was performed satisfactorily with out any sign of failure