CLIENT :
JOB NO. : DATE :
Tank Footing Design Based on ACI 318-14
INPUT DATA
TANK HEIGHT H = 24.17 ft
TANK DIAMETER d = 38.67 ft
TANK THICKNESS t= 2 in
WT OF TANK & MAX CONTENTS W = 1920.05 kips
SOIL WEIGHT ws = 0.11 kcf
FOOTING EMBEDMENT DEPTH Df = 1 ft
FOOTING THICKNESS T= 18 in
ALLOW SOIL PRESSURE Qa = 2 ksf
FOOTING DIAMETER D = 40.67 ft
TOTAL ANCHORAGE POINTS n= 26 ( @ 56" o.c. along perimeter.)
ANCHOR BOLT DIAMETER f= 3/4 in
CONCRETE STRENGTH fc ' = 3 ksi
REBAR YIELD STRESS fy = 60 ksi
FOOTING REBAR 2 # 6
@ 18 in o.c. each way, at top & bot.
DESIGN SUMMARY
FOOTING 40.67 ft DIA x 18 in THK. w/ #6 @ 18" o.c. EACH WAY, AT TOP & BOT.
ANALYSIS
2 1/ 2
DETERMINE LATERAL LOADS
L wD
T 7.65 10 6
D t <
0.023 sec, (SEAOC IBC 06 Manual I, page 188)
(rigid nonbuilding stru
Where L = 24.17 ft
w =W/L= 79439 plf
D = 38.67 ft
V = (SDS IE W / 1.4) 0.30 = 0.12 W = 221.354 kips, ASD (for IBC, Seismic)
Where SDS = 0.538 (ASCE 7-10, 11.4.4)
IE = 1.00 (IBC Tab 1604.5 & ASCE 7 Tab 11.5-1)
Factor = 0.30 (ASCE 7-10, 15.4.2)
COMBINED LOADS AT TOP FOOTING (IBC 1605.3.2 & ACI 318 5.3)
CASE 1: DL + LL P = 1920 kips 1.2 DL + 1.6 LL
M = 0 ft-kips
e = 0.0 ft, fr cl ftg
CASE 2: DL + LL + E / 1.4 P = 1920 kips 1.2 DL + 1.0 LL + 1.0 E
M = 3647 ft-kips
e = 1.9 ft, fr cl ftg
CASE 3: 0.9 DL + E / 1.4 P = 393 kips 0.9 DL + 1.0 E
M = 829 ft-kips
e = 2.1 ft, fr cl ftg
CHECK OVERTURNING FACTOR AT WIND LOAD WITHOUT CONTENTS (IBC 1605.2.1, 1808.3.1, & ASCE 7 12.13.4)
MR / MO = 55.6 > 1.16667 [Satisfactory]
Where MO = Vwind (2 / 3) (H + T) = 267 k-ft , MR = (PDL + Pftg) 0.5 D =
[Satisfactory]
CHECK FLEXURE
Location Mu,max d (in) min reqD max smax provD
Top Slab 4.0 ft-k / ft 15.63 0.0004 0.0003 0.0155 no limit 0.0016
Bottom Slab -13.8 ft-k / ft 14.63 0.0016 0.0012 0.0155 18 0.0017
Technical References:
1. "Seismic Design Manual (UBC 97) - Volume 1, Code Application Examples", Structural Engineers
Association of California, 1999.
2. "2006 IBC Structural/Seismic Design Manual - Volume 1, Code Application Examples", Structural Engine
Association of California, 2007.
PAGE :
DESIGN BY :
REVIEW BY :
0.06 sec
(rigid nonbuilding structure, ASCE 7-10, 15.4.2)
RING SLOSHING EFFECTS, USE 295.688 kips.
Pu = 2897 kips
Mu = 0 ft-kips
eu = 0.0 ft, fr cl ftg
.2 DL + 1.0 LL + 1.0 E Pu = 2007 kips
Mu = 5106 ft-kips
eu = 2.5 ft, fr cl ftg
Pu = 393 kips
Mu = 1161 ft-kips
eu = 3.0 ft, fr cl ftg
k
ft (from center of footing)
k, (footing increasing)
k, (net loads)
ft
ksf
ksf
ksf
k
ft
k, (factored footingloads)
k
ft
ksf
ksf
6/8 d 7/8 d R Edge D
30.00 34.84 39.67 40.67
35.78 28.51 12.60 0.00
2.47 2.47 2.47 0.00
30,087 42,314 56,022 58,920
2,530 2,836 2,897 2,897
0.27 0.27 0.27 0.27
3,688 5,145 6,784 7,133
301 339 349 351
-2.50 -2.50 -2.50 -2.50
-34151 -47644 -62820 -66052
-2,791 -3,139 -3,232 -3,248
-376 -185 -14 0
40 35 14 0
(cont'd)
[Satisfactory]
, Structural Engineers