Tank Footing Design Based on ACI 318-14

INPUT DATA
TANK HEIGHT H = 24.17 ft
TANK DIAMETER d = 38.67 ft
TANK THICKNESS t= 2 in
WT OF TANK & MAX CONTENTS W = 1920.05 kips
SOIL WEIGHT ws = 0.11 kcf
FOOTING EMBEDMENT DEPTH Df = 1 ft
FOOTING THICKNESS T= 18 in
ALLOW SOIL PRESSURE Qa = 2 ksf
FOOTING DIAMETER D = 40.67 ft
TOTAL ANCHORAGE POINTS n= 26 ( @ 56" o.c. along perimeter.)
ANCHOR BOLT DIAMETER f= 3/4 in
CONCRETE STRENGTH fc ' = 3 ksi
REBAR YIELD STRESS fy = 60 ksi
FOOTING REBAR 2 # 6
@ 18 in o.c. each way, at top & bot.
DESIGN SUMMARY
FOOTING 40.67 ft DIA x 18 in THK. w/ #6 @ 18" o.c. EACH WAY, AT TOP & BOT.

THE FOOTING DESIGN IS ADEQUATE.

ANALYSIS
2 1/ 2
DETERMINE LATERAL LOADS
L   wD 
T  7.65  10 6    
D  t  <
0.023 sec, (SEAOC IBC 06 Manual I, page 188)
(rigid nonbuilding stru
Where L = 24.17 ft
w =W/L= 79439 plf
D = 38.67 ft

V = (SDS IE W / 1.4) 0.30 = 0.12 W = 221.354 kips, ASD (for IBC, Seismic)
Where SDS = 0.538 (ASCE 7-10, 11.4.4)
IE = 1.00 (IBC Tab 1604.5 & ASCE 7 Tab 11.5-1)
Factor = 0.30 (ASCE 7-10, 15.4.2)

V = (Ca IE W / 1.4) 0.7 = 0.14 W = 268.807 kips, ASD (for Seismic)


Where Ca = 0.28 (2001 CBC / UBC 97 1634.3)
IE = 1.00 (2001 CBC / UBC 97 Table 16-K)
Factor = 0.7 (2001 CBC / UBC 97 1634.3)

V = (2 / 3) P A = 0.01 W = 15.58 kips, ASD (for Wind)


Where A = 934.6539 ft , (projected area)
2

P = 25 psf, (wind pressure)


Circular Factor = 2/3
CONSIDERING SLOSHING EFFECTS,

COMBINED LOADS AT TOP FOOTING (IBC 1605.3.2 & ACI 318 5.3)
CASE 1: DL + LL P = 1920 kips 1.2 DL + 1.6 LL
M = 0 ft-kips
e = 0.0 ft, fr cl ftg
CASE 2: DL + LL + E / 1.4 P = 1920 kips 1.2 DL + 1.0 LL + 1.0 E
M = 3647 ft-kips
e = 1.9 ft, fr cl ftg
CASE 3: 0.9 DL + E / 1.4 P = 393 kips 0.9 DL + 1.0 E
M = 829 ft-kips
e = 2.1 ft, fr cl ftg

CHECK OVERTURNING FACTOR AT WIND LOAD WITHOUT CONTENTS (IBC 1605.2.1, 1808.3.1, & ASCE 7 12.13.4)
MR / MO = 55.6 > 1.16667 [Satisfactory]
Where MO = Vwind (2 / 3) (H + T) = 267 k-ft , MR = (PDL + Pftg) 0.5 D =

Pftg = (0.15 kcf) T D2 p / 4 = 292.29 k, footing weight. F = 1.5, for wind


CHECK SOIL BEARING CAPACITY (ACI 318 13.3.1.1)

Service Loads CASE 1 CASE 2 CASE 3


P 1920.1 1920.1 392.9
e 0.0 2.1 2.9
Pftg - Psoil 149.4 149.4 134.5
SP 2069.4 2069.4 527.4
e 0.0 1.9 2.1
qmin 1.6 1.0 0.2
x @ 0.00 ft from edge @ 0.00 ft from edge
qmax 1.59 2.22 0.58
qallowable 2.00 2.67 2.67

[Satisfactory]

CHECK ENTIRE FLEXURE & SHEAR OF FOOTING


(ACI 31813,  & 22) T
21, 4  0.85 1 f c' u
MIN MIN 0.0018  ,    MAX
 d 3  f y u t
 Mu 
0.85 f c' 1  1  
 0.383b d
2
f
'

  c 
fy

FACTORED SOIL PRESSURE


Factored Loads CASE 1 CASE 2 CASE 3
Pu 2897.4 2007.4 392.9
eu 0.0 2.7 4.0
g (0.15 T) A 350.8 350.8 263.1
S Pu 3248.2 2358.1 656.0
eu 0.0 2.3 2.4
qu, min 2.50 0.94 0.25
x @ 0.00 ft from edge @ 0.00 ft from edge
qu, max 2.50 2.69 0.75
FOOTING MOMENT & SHEAR FOR CASE 1
Section 0 L Edge 1/8 d 2/8 d 3/8 d Center 5/8 d
Xu (ft, dist. from left of footing) 0 1.00 5.83 10.67 15.50 20.34 25.17
Tangent (ft) 0.00 12.60 28.51 35.78 39.50 40.67 39.50
qu,tank (ksf) 0.00 2.47 2.47 2.47 2.47 2.47 2.47
Mu,tank (ft-k) 0 0 298 2,076 5,793 11,676 19,798
Vu,tank (k) 0 0 62 368 769 1,680 2,129
qu,ftg (ksf) 0.27 0.27 0.27 0.27 0.27 0.27 0.27
Mu,ftg (ft-k) 0 2 58 297 763 1,481 2,459
Vu,ftg (k) 0 2 12 49 96 202 254
qu,soil (ksf) -2.50 -2.50 -2.50 -2.50 -2.50 -2.50 -2.50
Mu,soil (ft-k) 0 -15.907 -541.36 -2749.3 -7068.6 -13719 -22770
Vu,soil (k) 0 -16 -109 -457 -894 -1,872 -2,355
S Mu (ft-k) 0 -14 -185 -376 -513 -561 -513
S Vu (kips) 0 -14 -35 -40 -28 10 28
FOOTING MOMENT & SHEAR FOR CASE 2
Section 0 L Edge 1/8 d 2/8 d 3/8 d Center 5/8 d
Xu (ft, dist. from left of footing) 0 1.00 5.83 10.67 15.50 20.34 25.17
Tangent (ft) 0.00 12.60 28.51 35.78 39.50 40.67 39.50
qu,tank (ksf) 0.00 0.69 1.05 1.30 1.56 1.81 2.07
Mu,tank (ft-k) 0 0 78.5045 751.089 2390.25 5321.08 9803.89
Vu,tank (k) 0 0 16 139 340 929 1,284
qu,ftg (ksf) 0.27 0.27 0.27 0.27 0.27 0.27 0.27
Mu,ftg (ft-k) 0 2 58 297 763 1,481 2,459
Vu,ftg (k) 0 2 12 49 96 202 254
qu,soil (ksf) -0.94 -0.98 -1.19 -1.40 -1.61 -1.82 -2.02
Mu,soil (ft-k) 0 -6.0025 -212.05 -1222.9 -3420.5 -7123.3 -12577
Vu,soil (k) 0 -6 -43 -209 -455 -1,128 -1,520
S Mu (ft-k) 0 -4 -75 -175 -267 -321 -314
S Vu (kips) 0 -4 -15 -20 -18 3 18

FOOTING MOMENT & SHEAR FOR CASE 3


Section 0 L Edge 1/8 d 2/8 d 3/8 d Center 5/8 d
Xu (ft, dist. from left of footing) 0 1.00 5.83 10.67 15.50 20.34 25.17
Tangent (ft) 0.00 12.60 28.51 35.78 39.50 40.67 39.50
qu,tank (ksf) 0.00 0.04 0.15 0.22 0.29 0.36 0.44
Mu,tank (ft-k) 0 0 4.85326 90.5347 334.556 814.317 1598.18
Vu,tank (k) 0 0 1 18 51 162 236
qu,ftg (ksf) 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Mu,ftg (ft-k) 0 1 44 223 572 1,111 1,844
Vu,ftg (k) 0 1 9 37 72 152 191
qu,soil (ksf) -0.25 -0.27 -0.33 -0.39 -0.45 -0.50 -0.56
Mu,soil (ft-k) 0 -1.63 -57.69 -334.65 -939.25 -1961.3 -3470.3
Vu,soil (k) 0 -2 -12 -57 -125 -312 -422
S Mu (ft-k) 0 0 -9 -21 -32 -36 -28
S Vu (kips) 0 0 -2 -3 -2 2 5

FOOTING MOMENT & SHEAR SUMMARY


Section 0 L Edge 1/8 d 2/8 d 3/8 d Center 5/8 d
Xu (ft, dist. from left of footing) 0 1.00 5.83 10.67 15.50 20.34 25.17
Tangent (ft) 0.00 12.60 28.51 35.78 39.50 40.67 39.50
Case Mu, (ft-k / ft) 0.0 -1.1 -6.5 -10.5 -13.0 -13.8 -13.0
niform Loads

1 Vu, (k / ft) 0.0 -1.1 -1.2 -1.1 -0.7 0.2 0.7


Case Mu, (ft-k / ft) 0.0 -0.3 -2.6 -4.9 -6.8 -7.9 -8.0
Uniform Load
2 Vu, (k / ft) 0.0 -0.3 -0.5 -0.6 -0.5 0.1 0.5
Case Mu, (ft-k / ft) 0.0 0.0 -0.3 -0.6 -0.8 -0.9 -0.7
3 Vu, (k / ft) 0.0 0.0 -0.1 -0.1 -0.1 0.0 0.1

CHECK FLEXURE
Location Mu,max d (in) min reqD max smax provD
Top Slab 4.0 ft-k / ft 15.63 0.0004 0.0003 0.0155 no limit 0.0016
Bottom Slab -13.8 ft-k / ft 14.63 0.0016 0.0012 0.0155 18 0.0017

CHECK FLEXURE SHEAR


Vu,max fVc = 2 f b d (fc')0.5 check Vu < f Vc
1.2 k / ft 14 k [Satisfactory]

Technical References:
1. "Seismic Design Manual (UBC 97) - Volume 1, Code Application Examples", Structural Engineers
Association of California, 1999.
2. "2006 IBC Structural/Seismic Design Manual - Volume 1, Code Application Examples", Structural Engine
Association of California, 2007.
PAGE :
DESIGN BY :
REVIEW BY :

0.06 sec
(rigid nonbuilding structure, ASCE 7-10, 15.4.2)
RING SLOSHING EFFECTS, USE 295.688 kips.

Pu = 2897 kips
Mu = 0 ft-kips
eu = 0.0 ft, fr cl ftg
.2 DL + 1.0 LL + 1.0 E Pu = 2007 kips
Mu = 5106 ft-kips
eu = 2.5 ft, fr cl ftg
Pu = 393 kips
Mu = 1161 ft-kips
eu = 3.0 ft, fr cl ftg

1808.3.1, & ASCE 7 12.13.4)

(PDL + Pftg) 0.5 D = 14822 k-ft


(cont'd)

k
ft (from center of footing)
k, (footing increasing)
k, (net loads)
ft
ksf

ksf
ksf

k
ft
k, (factored footingloads)
k
ft
ksf

ksf
6/8 d 7/8 d R Edge D
30.00 34.84 39.67 40.67
35.78 28.51 12.60 0.00
2.47 2.47 2.47 0.00
30,087 42,314 56,022 58,920
2,530 2,836 2,897 2,897
0.27 0.27 0.27 0.27
3,688 5,145 6,784 7,133
301 339 349 351
-2.50 -2.50 -2.50 -2.50
-34151 -47644 -62820 -66052
-2,791 -3,139 -3,232 -3,248
-376 -185 -14 0
40 35 14 0
(cont'd)

6/8 d 7/8 d R Edge D


30.00 34.84 39.67 40.67
35.78 28.51 12.60 0.00
2.32 2.58 2.73 0.00
16000 23918 33295 35300
1,641 1,943 2,007 2,007
0.27 0.27 0.27 0.27
3,688 5,145 6,784 7,133
301 339 349 351
-2.23 -2.44 -2.65 -2.69
-19926 -29168 -40061 -42432
-1,912 -2,253 -2,352 -2,358
-238 -105 -19 0
30 29 4 0

6/8 d 7/8 d R Edge D


30.00 34.84 39.67 40.67
35.78 28.51 12.60 0.00
0.51 0.58 0.63 0.00
2735.2 4240.61 6067.48 6415.16
312 379 393 393
0.20 0.20 0.20 0.20
2,766 3,859 5,088 5,349
226 254 262 263
-0.62 -0.68 -0.74 -0.75
-5508.1 -8075.3 -11104 -11765
-531 -627 -654 -656
-7 24 51 0
7 6 0 0

6/8 d 7/8 d R Edge D


30.00 34.84 39.67 40.67
35.78 28.51 12.60 0.00
-10.5 -6.5 -1.1 0.0
1.1 1.2 1.1 0.0
-6.6 -3.7 -1.5 0.0
0.8 1.0 0.3 0.0
-0.2 0.8 4.0 0.0
0.2 0.2 0.0 0.0

[Satisfactory]