Physical data
Plates
Positive Negative
Type of plates Pocket Type of plates Pocket
Electrolyte
Connection
ALCAD confidential and proprietary. The data herein given are for information purposes only and are not binding on ALCAD. They may be
modified without prior notice. Please contact an ALCAD representative in order to obtain confirmation of the above data.
Visit our website at www.alcad.com
(377207) Version: 2.3, Last updated on 05/2018 P 1/3
Wednesday, June 27, 2018
Charging
Float voltage 1.42 V/Cell High rate voltage (min) 1.47 V/Cell
Single-level voltage 1.43 V/Cell
Resistance/Short circuit
Performance data
Current discharge
After prolonged float charge of fully charged cells. Available amperes at +20°C +/- 5°C (+68°F +/- 9°F)
1 2.03 2.52 4.00 6.41 8.56 10.0 12.2 15.3 16.7 17.8 19.4 21.9 25.3 27.2 32.1 36.0
1.05 2.00 2.49 3.91 5.67 7.48 8.93 10.7 13.1 14.3 14.9 15.9 17.2 20.2 21.7 25.7 28.5
1.1 1.97 2.36 3.47 5.10 6.72 7.97 9.47 11.0 11.6 11.9 12.4 13.2 15.5 16.9 20.0 22.5
1.14 1.88 2.20 2.89 3.97 4.93 5.71 6.59 7.73 8.28 8.45 8.90 10.1 12.0 13.1 15.8 17.4
Power discharge
Available power (W), after prolonged float charged of fully charged cells at +20°C +/- 5°C (+68°F +/- 9°F)
1 2.35 2.88 4.47 6.85 8.96 10.4 12.4 15.4 16.8 17.8 19.5 21.9 25.3 27.2 32.1 36.0
1.05 2.33 2.87 4.45 6.24 8.10 9.6 11.4 13.9 15.1 15.7 16.7 18.0 21.2 22.8 27.0 30.0
1.1 2.30 2.75 4.01 5.77 7.54 8.89 10.5 12.2 12.8 13.1 13.6 14.5 17.0 18.6 22.0 24.8
1.14 2.21 2.58 3.37 4.59 5.68 6.56 7.54 8.83 9.45 9.6 10.2 11.5 13.7 14.9 18.0 19.9
ALCAD confidential and proprietary. The data herein given are for information purposes only and are not binding on ALCAD. They may be
modified without prior notice. Please contact an ALCAD representative in order to obtain confirmation of the above data.
Visit our website at www.alcad.com
(377207) Version: 2.3, Last updated on 05/2018 P 2/3
Wednesday, June 27, 2018
Current discharge
After prolonged float charge of fully charged cells. Kt factor at +20°C +/- 5°C (+68°F +/- 9°F)
1 9.9 7.93 5.00 3.12 2.34 1.99 1.64 1.31 1.20 1.13 1.03 0.91 0.79 0.73 0.62 0.56
1.05 10.0 8.02 5.11 3.53 2.67 2.24 1.87 1.53 1.40 1.34 1.26 1.17 0.99 0.92 0.78 0.70
1.1 10.1 8.47 5.76 3.92 2.97 2.51 2.11 1.82 1.72 1.68 1.62 1.52 1.29 1.19 1.00 0.89
1.14 10.6 9.08 6.93 5.04 4.05 3.50 3.04 2.59 2.42 2.37 2.25 1.99 1.66 1.53 1.27 1.15
Power discharge
Kt factor power, after prolonged float charged of fully charged cells at +20°C +/- 5°C (+68°F +/- 9°F)
1 8.51 6.94 4.47 2.92 2.23 1.92 1.61 1.30 1.19 1.12 1.03 0.91 0.79 0.73 0.62 0.56
1.05 8.59 6.96 4.50 3.20 2.47 2.08 1.76 1.44 1.33 1.28 1.20 1.11 0.94 0.88 0.74 0.67
1.1 8.68 7.28 4.99 3.46 2.65 2.25 1.90 1.65 1.56 1.53 1.47 1.38 1.17 1.08 0.91 0.81
1.14 9.05 7.75 5.93 4.36 3.52 3.05 2.65 2.27 2.12 2.08 1.97 1.74 1.46 1.34 1.11 1.01
ALCAD confidential and proprietary. The data herein given are for information purposes only and are not binding on ALCAD. They may be
modified without prior notice. Please contact an ALCAD representative in order to obtain confirmation of the above data.
Visit our website at www.alcad.com
(377207) Version: 2.3, Last updated on 05/2018 P 3/3