Anda di halaman 1dari 44

INSTRUCTION MANUAL

INERTGAS GENERATOR

GENERAL INFORMATION

Series Gln 4500-0.15 FU


Doc nr 11215053R00 Based on 65010A053R08

EXAMINED

This plan has been examined and given the status as shown in
the Design Appraisal Document (DAD) number below:
RTS/ETS/14.1294
Date: 18 Dec 2014 Initials: awv

Rotterdam Technical Support Office


Lloyd's Register EMEA

LR001.4.2009
© 2012 Alfa Laval Aalborg Nijmegen B.V.

All rights reserved.


No part of this publication may be copied or published by means of printing, photocopying, microfilm or oth-
erwise without prior written consent of Alfa Laval Aalborg Nijmegen B.V.. This restriction also applies to the
corresponding drawings and diagrams.

The information given in this document has been collected for the general convenience of our clients. It has
been based on general data pertaining to construction material properties and working methods known to us
at the time of issue of the document and is therefore subject at any time to change or amendment. The right
to change or amend is hereby expressly reserved. The instructions in this publication only serve as a guide-
line for installation, use and maintenance of the machine mentioned on the cover page of this document.

This publication is to be used for the standard model of the machine of the type given on the cover page.
Thus Alfa Laval Aalborg Nijmegen B.V. cannot be held responsible for any damage resulting from the appli-
cation of this publication to the version actually delivered to you.

This publication has been written with great care. However, Alfa Laval Aalborg Nijmegen B.V. cannot be held
responsible, either for any errors occurring in this publication or for their consequences.
INSTRUCTION MANUAL

INERTGAS GENERATOR Series Gln

Type: Smit Gas™ Gln 4500 - 0.15 FU

Product number: 65016BR08..................................................................................

Order number: 142.10.1.1215..............................................................................

Manufacturing number: 14515...........................................................................................

Year of construction: 2014.............................................................................................

Yard: Sungdong Shipbuilding & Marine Eng Co. Ltd.............................

Ref. Customer: ....................................................................................................

Yard number: Hull S3075 ...................................................................................


11215053R00

TABLE OF CONTENTS 5.3.8 Effluent waterseal .. Fout! Bladwijzer niet


gedefinieerd.
5.3.9 Generator pressure control system .. Fout!
1 GENERAL INFORMATION ............. FOUT! Bladwijzer niet gedefinieerd.
BLADWIJZER NIET GEDEFINIEERD. 5.3.10 Generator delivery pressure ............ Fout!
1.1 SCOPE ....................... FOUT! BLADWIJZER NIET Bladwijzer niet gedefinieerd.
GEDEFINIEERD.
5.3.11 Purge / excess vent valve and delivery
1.2 LIABILITY ................. FOUT! BLADWIJZER NIET valve . Fout! Bladwijzer niet gedefinieerd.
GEDEFINIEERD.
5.3.12 Excess gas vent system – deck main
1.3 GUARANTEE ............. FOUT! BLADWIJZER NIET pressure .................. Fout! Bladwijzer niet
GEDEFINIEERD. gedefinieerd.
1.4 ABBREVIATIONS USED IN THIS MANUAL .. FOUT! 5.3.13 Deck main pressure control ............. Fout!
BLADWIJZER NIET GEDEFINIEERD. Bladwijzer niet gedefinieerd.
5.3.14 Measurement and safeguarding of the
2 SAFETY ........... FOUT! BLADWIJZER NIET oxygen content ....... Fout! Bladwijzer niet
GEDEFINIEERD. gedefinieerd.
2.1 GENERAL SAFETY INSTRUCTIONS ............ FOUT! 5.3.15 Fuel to air ratio / oxygen content..... Fout!
BLADWIJZER NIET GEDEFINIEERD. Bladwijzer niet gedefinieerd.
2.2 SAFETY INSTRUCTIONS FOR OPERATING & 6 TECHNICAL SPECIFICATION ...... FOUT!
MAINTENANCE .......... FOUT! BLADWIJZER NIET BLADWIJZER NIET GEDEFINIEERD.
GEDEFINIEERD.
6.1 DESIGN BASIS ........... FOUT! BLADWIJZER NIET
3 INSTALLATION....... FOUT! BLADWIJZER GEDEFINIEERD.
NIET GEDEFINIEERD. 6.2 INERT GAS SPECIFICATION . FOUT! BLADWIJZER
NIET GEDEFINIEERD.
3.1 INSTALLATION INSTRUCTIONS ................. FOUT!
BLADWIJZER NIET GEDEFINIEERD. 6.3 UTILITIES ................. FOUT! BLADWIJZER NIET
GEDEFINIEERD.
3.2 COMMISSIONING....... FOUT! BLADWIJZER NIET
GEDEFINIEERD. 7 OPERATING INSTRUCTIONS ....... FOUT!
4 STORAGE INSTRUCTIONS ............ FOUT! BLADWIJZER NIET GEDEFINIEERD.
BLADWIJZER NIET GEDEFINIEERD. 7.1 GENERAL ................. FOUT! BLADWIJZER NIET
GEDEFINIEERD.
4.1 GENERAL STORAGE INSTRUCTIONS ......... FOUT!
BLADWIJZER NIET GEDEFINIEERD. 7.2 CONTROL PANELS .... FOUT! BLADWIJZER NIET
GEDEFINIEERD.
4.2 STORAGE INSTRUCTIONS FOR THE
CONSTRUCTION PERIOD .... FOUT! BLADWIJZER
7.3 SWITCHING ON ......... FOUT! BLADWIJZER NIET
GEDEFINIEERD.
NIET GEDEFINIEERD.
7.3.1 Inert gas production ...... Fout! Bladwijzer
5 TECHNICAL DESCRIPTION .......... FOUT! niet gedefinieerd.
BLADWIJZER NIET GEDEFINIEERD. 7.3.2 Air production ........ Fout! Bladwijzer niet
5.1 GENERAL.................. FOUT! BLADWIJZER NIET gedefinieerd.
7.4 SWITCHING OFF ........ FOUT! BLADWIJZER NIET
GEDEFINIEERD.
GEDEFINIEERD.
5.2 PROCESS PRINCIPLE .. FOUT! BLADWIJZER NIET
7.4.1 Normal switch off ... Fout! Bladwijzer niet
GEDEFINIEERD.
5.3 DETAILED PROCESS DESCRIPTION ............ FOUT! gedefinieerd.
7.4.2 In case of a longer standstill ............ Fout!
BLADWIJZER NIET GEDEFINIEERD.
5.3.1 General................... Fout! Bladwijzer niet Bladwijzer niet gedefinieerd.
7.5 CHECKS DURING OPERATION ................... FOUT!
gedefinieerd.
5.3.2 Combustion air supply .. Fout! Bladwijzer BLADWIJZER NIET GEDEFINIEERD.
7.6 ADJUSTMENTS.......... FOUT! BLADWIJZER NIET
niet gedefinieerd.
GEDEFINIEERD.
5.3.3 Capacity control ..... Fout! Bladwijzer niet
7.6.1 Adjustments of the generator delivery
gedefinieerd.
5.3.4 Fuel oil supply ........ Fout! Bladwijzer niet pressure .................. Fout! Bladwijzer niet
gedefinieerd. gedefinieerd.
5.3.5 Pilot burner ............ Fout! Bladwijzer niet 7.6.2 Adjustments on the oxygen analyser Fout!
gedefinieerd. Bladwijzer niet gedefinieerd.
7.6.3 Adjustments of the deck main pressure
5.3.6 Main burner ........... Fout! Bladwijzer niet
......... Fout! Bladwijzer niet gedefinieerd.
gedefinieerd.
5.3.7 Combustion chamber and scrubbing 7.6.4 Adjustments to the pilot burner ........ Fout!
section .................... Fout! Bladwijzer niet Bladwijzer niet gedefinieerd.
gedefinieerd.

Rev. 0 Date.12 SEP 2014 4


11215053R00

7.6.5 Adjustments of the fuel-oil pump delivery 9.5 FREEZING PREVENTION ..... FOUT! BLADWIJZER
pressure .................. Fout! Bladwijzer niet NIET GEDEFINIEERD.
gedefinieerd. 9.6 COATING .................. FOUT! BLADWIJZER NIET
GEDEFINIEERD.
8 TROUBLE SHOOTING ..................... FOUT!
9.7 MAINTENANCE TABLES ..... FOUT! BLADWIJZER
BLADWIJZER NIET GEDEFINIEERD.
NIET GEDEFINIEERD.
8.1 FAILURES ................. FOUT! BLADWIJZER NIET 9.7.1 Before every start ... Fout! Bladwijzer niet
GEDEFINIEERD. gedefinieerd.
8.2 CONSEQUENCES OF FAILURES EXPLANATION 9.7.2 Every 250-hrs ......... Fout! Bladwijzer niet
....... FOUT! BLADWIJZER NIET GEDEFINIEERD. gedefinieerd.
8.3 TROUBLE SHOOTING CHARTS.................. FOUT! 9.7.3 Annually ................. Fout! Bladwijzer niet
BLADWIJZER NIET GEDEFINIEERD. gedefinieerd.
8.3.1 General trouble shooting chart ....... Fout! 9.7.4 After every stop ...... Fout! Bladwijzer niet
Bladwijzer niet gedefinieerd. gedefinieerd.
8.3.2 Consequences of failures trouble shooting 9.8 REPLACING THE PLC BATTERY ............... FOUT!
chart Fout! Bladwijzer niet gedefinieerd. BLADWIJZER NIET GEDEFINIEERD.
9.9 LUBRICATING SCHEDULE .. FOUT! BLADWIJZER
9 MAINTENANCE....... FOUT! BLADWIJZER
NIET GEDEFINIEERD.
NIET GEDEFINIEERD.
10 TEST PROTOCOL ....FOUT! BLADWIJZER
9.1 GENERAL MAINTENANCE INSTRUCTIONS . FOUT! NIET GEDEFINIEERD.
BLADWIJZER NIET GEDEFINIEERD.
9.2 COMBUSTION CHAMBER ... FOUT! BLADWIJZER 11 PROCESS DOCUMENTATION ....... FOUT!
NIET GEDEFINIEERD. BLADWIJZER NIET GEDEFINIEERD.
9.2.1 Draining combustion chamber ........ Fout!
12 DIMENSIONAL DRAWINGS........... FOUT!
Bladwijzer niet gedefinieerd.
BLADWIJZER NIET GEDEFINIEERD.
9.2.2 Rinsing the combustion chamber .... Fout!
Bladwijzer niet gedefinieerd. 13 ELECTRICAL DOCUMENTATION FOUT!
9.3 MAIN BURNER .......... FOUT! BLADWIJZER NIET BLADWIJZER NIET GEDEFINIEERD.
GEDEFINIEERD.
14 DOCUMENTATION .FOUT! BLADWIJZER
9.4 PILOT BURNER .......... FOUT! BLADWIJZER NIET
NIET GEDEFINIEERD.
GEDEFINIEERD.

Rev. 0 Date.12 SEP 2014 5


11215053R00

1 GENERAL INFORMATION 1.3 Guarantee


The guarantee conditions that are stated in the
1.1 Scope 'General conditions of Sale and Delivery of Alfa
This manual contains information for the Laval Aalborg Nijmegen B.V.' are applicable to
proper functioning and maintenance of the this product. The guarantee will become null
inert gas generator. It also contains important and void if:
instructions to prevent accidents and serious − service and maintenance are not carried
damage prior to and during operation of the out strictly in accordance with the
inert gas generator. instructions given,
Also the guidelines of IMO for Inert Gas − repair work is not carried out by authorised
Systems are to be followed. personnel or has been performed without
prior written consent;
Read this manual carefully before using the − the equipment has been modified without
inert gas generator, familiarise yourself with prior written consent;
the functioning and operation of the inert gas − non-original parts are used;
generator and strictly observe the instructions − the equipment is used incorrectly or not in
given. accordance with its intended use.
Wearing parts are not covered by the guarantee.
If you have any questions or need more de-
tails on specific aspects relating to the inert
gas generator, please contact: 1.4 Abbreviations used in this
manual
Alfa Laval Aalborg Nijmegen B.V.
St. Hubertusstraat 10 BP Bridge panel
6531 LB Nijmegen
The Netherlands
CCRP Cargo control room panel
CoF Consequences of Failures
P.O. Box 6664
6503 GD Nijmegen DWS Deck water seal
The Netherlands ERP Engine Room Panel
FOP Fuel oil pump
Tel.: +31 24 35 23 200 IG Inert Gas
Fax: +31 24 35 64 995 LCRP Local Control Room Panel
E-mail:
inertgasaftersales.nijmegen@alfalaval.com P/V- Pressure / Vacuum breaker
breaker
PVB Pressure / Vacuum breaker
1.2 Liability
The data published in this manual are based
on the latest information available. They are
subject to future modification.

We reserve the right to change the construction


and/or design of the product, without being
obliged to adapt earlier supplies accordingly.

Rev. 0 Date.12 SEP 2014 6


11215053R00

2 SAFETY • Before entering an enclosed or poorly ven-


tilated area containing an inert gas gen-
2.1 General Safety instructions erator or transmission equipment and pip-
This plant is designed to produce inert gas, with ing, follow all established local safety pre-
low oxygen content. Inert gas is an asphyxiating cautions and procedures.
gas and contains nitrogen (N2), carbon dioxide
(CO2) and little or no oxygen (O2). Furthermore • Product gas should not be vented or oth-
carbon monoxide (CO) and other toxic gasses erwise discharged except through the
that may be present. normal piping system. Appropriate signs
should be placed in the area of the nitro-
Exposure to or inhalation of the product gas gen system warning of the hazard.
should be avoided; the more so as no oxygen is
present. Leakage or venting of product gas into • Piping of the inert gas flow to areas of high
closed or confined areas, or at places where air circulation is recommended. Consult
personnel may be present, must be avoided. your own safety personnel for local, state
and federal procedures or regulations.
Any violation of these warnings may result in
accidents causing personal injuries. A general • All electrical installation should be in ac-
indication about the effects and symptoms in cordance with the recognised electrical
case of low oxygen content is given below: codes.

Oxygen content Effects and symptoms


15-19% Decreased ability to work strenuously. May impair the co-ordination.
12-14% Respiration increase with exertion, increase of pulse rate, impaired co-
ordination, reception and judgement affected.
10-12% Respiration further increases in rate and depth, poor judgement, blueness of
lips.
8-10% Mental failure, fainting, unconsciousness, ashen face, blueness of lips,
nausea and vomit.
9- 8% 8 minutes exposure: fatal; 6 minutes exposure: 50% fatal; 4-5 minutes
exposure recovery with treatment.
4- 6% Coma in 40 seconds, convulsions, respiration ceased or death.
Note: oxygen contents are indicated by volume percentage at atmospheric pressure.

Rev. 0 Date.12 SEP 2014 7


11215053R00

2.2 Safety instructions for Operat-


ing & maintenance
11. The emergency stop button should only
Operating the equipment in excess of the by used in case of urgent action!
conditions set forth in the Sales Contract In case the emergency stop button has
and the Technical Specification will been used the water supply to generator
subject it to stresses and strains that it will shut down immediately.
was not designed to withstand. As a result of that the temperature of the
generator jacket will by high for a short
Carefully read the cautions and instructions period. Please consult our service de-
before starting the equipment or doing any partment after an emergency stop: a vis-
maintenance. ual check by one of our service engineers
might be necessary.
1. Before doing any maintenance to the
electrical installation, be certain that the 12. For detail about operations see chapter 7.
electrical supply has been switched off by
the main switch.

2. Before doing any maintenance to the


equipment, be sure that all pressures of
the entire system have been vented.

3. When operating the equipment, do not If ventilation is insufficient this can cause
exceed the rated capacities, speeds, under-pressure (partial vacuum) in the
pressures or temperatures or act room. The result may be that doors cannot
otherwise than laid down in these be opened anymore.
instructions and the sub-contractors
manuals.

4. Do not remove any covers from rotating Do not enter any cargo space and/or
units, such as blowers, fuel pumps, tank before the oxygen content in
blowers etc. while the unit is in operation. these spaces is measured and found
sufficient to guarantee that these
5. At no time the unit should be energised places are not filled with inert gasses
and started in hazardous environments. or other gasses then air!

6. Sufficient ventilation air is obligatory in the


ig generator room.

7. Before any operation do test the alarms


and calibrate the O2 analyser.

8. The O2 content should not exceed 5%


when the inert gas is supplied to the tanks

9. Spilling oil (fuel or lubrication) may cause


slipperiness or fire damages.

10. The mode selection Inert Gas/ Air should


be made by the responsible person.

Rev. 0 Date.12 SEP 2014 8


11215053R00

Fig 1 shows the safety triangle that need be


used all the time for safe operation during in-
erting- gas freeing.

Never the area indicated as “flammable or


explosive region” may be entered.

Rev. 0 Date.12 SEP 2014 9


11215053R00

3 INSTALLATION In case seawater is supplied from another


source (not a dedicated seawater supply
3.1 Installation instructions pump), an automatic valve must always
be fitted in the supply line to the gas gen-
Carefully read the cautions and instruc- erator.
tions before installing the equipment:
7. For free discharge of the seawater (con-
1. Remove all packing material carefully. sequently pressure-less), the piping must
not have a great resistance (see dimen-
2. The inert gas installations are delivered sions on the dimensional drawings). In
on foundation frames; on behalf of order to be able to discharge the cooling
transport, the installation is divided or water pressure-less during swinging (roll-
parts are disassembled that are delivered ing) of the ship, the water discharge lines
separately, depending on the dimensions. must have a slope of at least 20°. This
applies to the connection line between the
3. The diameters of the piping, to which the washing tower and the water seal and to
supply, vent, discharge and distribution the discharge line of the water seal to
lines on board must be connected, are in- overboard.
dicated on the diagrams and drawings
(Process documentation and dimensional 8. When fitting the water seal and its supply
drawings). In case a big pressure drop will and discharge lines, attention should be
occur in the pipe system, these lines paid to the fact that during operation no
should be of an extra ample design. air bubbles can arise in this line. Bubbles
When choosing the pipe diameters, the can block the water passage; at possible
capacities and pressures mentioned in air collecting places a venting pipe must
the technical specification should be con- be made, e.g. in bends, high fitted piping
sidered. parts, under the lid of the water seal etc.

4. If more than one generator is placed on a 9. Inert gas generator must be installed
ship, each generator must be provided above highest waterline. For more details
with its own fittings, such as shut-off see the flow diagrams in the "Process
valves, filters, reducing valves etc in the documentation". If the generator is placed
various supply and discharge lines. This near or below water level, special ar-
in order to be able to guarantee an inde- rangements for the generator and the wa-
pendent operation of each generator. ter seal are required.

5. No rain or water from the outside may find 10. Seawater pipes must be protected against
its way into the venting and aerating corrosion;
pipes.
11. The temperature of the combustion air
6. The seawater supply pressure should may not be subjected to a sudden strong
remain as constant as possible (+/- 20%). variation. It is recommended to suck in
If big pressure fluctuations in the sea- the combustion air from "inside" the ship.
water are to be expected, it is recom-
mended to fit a dedicated seawater sup- 12. There should be a constant fuel quality
ply pump. and viscosity, this being important for the
fuel air ratio.
6B The sea water supply to the gas genera-
tor must be stopped when a failure in the 13. The compressed air supply may not con-
seawater discharge of the generator oc- tain rests of lubricating oil and must be
curs either by closing an automatic valve free of condense.
(to be fitted in the sea water supply line),
or by stopping the sea water supply 14. All blow-off piping indicated on the draw-
pump. For that purpose an electrical con- ings must be led to the "outside".
tact is made available.

Rev. 0 Date.12 SEP 2014 10


11215053R00

15. When the generator is erected in a room


specially meant for it, there has to be a
forced purge of air to discharge the heat
developed; a fan must be fitted in the dis-
charge canal.

16. The I.G. generator is equipped with a Zir-


conia type of O2-analyser. This item con-
tains no moving or rotating parts and ship
movements or vibrations will have no ef-
fect. The O2 measurement and the O2-
sensor will last for many years. The only
attention this analyser requires is regular
calibration. Calibration requires a calibra-
tion nitrogen gas (with some O2) bottle in-
cluding pressure reducing set. This nitro-
gen cylinder with oxygen must be on
board of the ship, close to the O2-
analyser.

17. The wiring of the auxiliary (control) current


part is performed according to the X-
wiring principle, which means that the
wires are running at the rear side of the
mounting plates. The internal wiring is of
the required flexible type for shipboard
use. All connections are made with wire
connectors.

18. The entrance of the main supply cables


can be made on a suitable place on the
starter panel. The electrical connections
(cables) between the terminal boxes, oth-
er electrical parts and the panels must be
laid alongside the ship's steel structure.
These cables should be laid during erec-
tion on board.

19. See document “mounting instructions”


65010A051R00 (chapter 14) for instruc-
tion that have been given to the yard. This
document all installation instruction need-
ed during construction of the ship.

3.2 Commissioning

The unit need be commissioned by the Aal-


borg Industries service department. Only after
this the inert gas plant is released for use by
the customer.

Rev. 0 Date.12 SEP 2014 11


11215053R00

4 STORAGE INSTRUCTIONS 4.2 Storage instructions for the


construction period
4.1 General storage instructions With the construction period Smit Gas
The equipment must be stored at a clean and Systems means:
dry place, protected against weather and ”The period between removing the packaging
moisture. Ambient temperature should not be material, the installation of the equipment into
below 0 °C and above +50 °C. the ship (or into a segment of the ship) and
the commissioning of the complete ship”.
During transportation, severe shocks or vibra-
tions should be prevented. During this construction period of the ship the
equipment must be stored according to the
All equipment is packed by Alfa Laval Aalborg General storage instructions mentioned
Nijmegen B.V. and suitable for storage under above.
above-mentioned conditions. If equipment,
such as blowers, is stored for a period longer Great care must be taken to protect the
than equipment against damages while working in
12 months, it may be required to check the the surrounding area of the equipment.
lubrication. If necessary, it must be replaced.
Special care must be taken to protect the
equipment from sparks when welding near to
the equipment.

Rev. 0 Date.12 SEP 2014 12


11215053R00

5 TECHNICAL DESCRIPTION The combustion is a chemical reaction be-


tween the hydrocarbon and the oxygen, main-
5.1 General ly giving carbon dioxide and water. Some little
An inert gas system contains the following rest quantities of oxygen, carbon monoxide
standard equipment: and hydrogen also remain. The nitrogen
leaves the generator unchanged.
1) 2 (two) air blowers. The burner is not ignited at air production.
Each equipped with local control panel
and motor starters A good combustion process is the first re-
quirement of a reliable inert gas generator.
2) 1 (one) generator, consisting of: The burner is of our special design, in accord-
- Combustion chamber and washing ance with the Alfa Laval Aalborg Nijmegen
tower B.V. Ultramizing Combustion System.
- Burner
- Local control panel The combustion air is supplied to the burner
- Oxygen analyser under pressure. In the burner, the fuel oil is
- Other valves and instrumentation atomised in such a way that a perfect mixing of
fuel and air is achieved.
3) 2 Fuel Oil Pumps (FOP) both connect- Consequently, a bright blue flame is seen, that
ed including motor starter panel will not create any soot. Soot cannot be toler-
ated in the plant, neither in the ship’s cargo
4) Valves at main line. tanks nor in piping system. Prevention of soot
- Pressure control valve. is only possible in an extremely stable and
- Delivery valve. well-balanced combustion process as used by
- Purge valve. Alfa Laval Aalborg Nijmegen B.V..
- Bleed valve.
- Check valve. The hot inert gas produced mainly consists out
of nitrogen and carbon dioxide. The hot com-
5) Cargo Control Room Panel (CCRP): bustion gases are cooled directly and indirectly
- Recorder / Deck pressure and oxygen for the best results.
contents
- Several alarms, indicators and opera- The first indirectly cooling occurs in the com-
tors bustion chamber by a cooling-water jacket. The
main cooling of the combustion gases occurs
6) Deck Water Seal (DWS) in the cooling / washing section of the com-
bustion chamber.
7) Pressure/Vacuum breaker (P/V-breaker)
(PVB) During the main cooling the inert gas is direct-
ly cooled with seawater. At the same time, the
8) Bridge Panel (BP) sulphur oxides are washed out. The sulphur is
present in the fuel and is oxidised during
5.2 Process principle combustion. The inert gas is cooled down to a
The I.G. generator is capable of producing few degrees over seawater inlet temperature
inert gas or air. See chapter 14 for operation and saturated with water of that temperature.
guidelines.
At the end of the cooling section, the water
Inert gas is produced by stoichiometric com- droplets are separated, as the gas passes
bustion of fuel oil with air. through a demister.

The fuel oil is a hydrocarbon and the air a mix- The required final pressure of the generator is
ture of mainly 79% nitrogen and 21% oxygen. achieved by a blower installed in front of the
combustion chamber and a pressure control
valve in the inert gas line. This causes an
overpressure inside the combustion chamber
and the gas cooling section. A water seal un-

Rev. 0 Date.12 SEP 2014 13


11215053R00

der the cooling section discharges the water, ratio can be changed by the pressure control
while at the same time maintaining the re- valve (2032).
quired pressure and avoiding the escape of Only the first time after installation the oil
inert gas. regulating valve (2032) has to be adjusted
stepwise. This fuel-regulating valve used has
an adjustable gradient. See the sub-suppliers
5.3 Detailed process description documentation of Maxon (the valve normally
is set by the commissioning engineer of Smit
5.3.1 General and this need be done only once and is com-
The process descriptions and tag numbers plicated; it is advice not to change if not need-
refer to the flow diagrams, which you will find ed)
in the chapter “Process documentation” This means that with the aid of several ad-
justment screws, the right quantity of fuel oil
5.3.2 Combustion air supply can be supplied to the main burner, to match
The combustion air is supplied to the main the combustion airflow at any position of the
burner (2001) by a centrifugal blower or blow- burner gun.
er (2202 or 2222).
The quantity of combustion air to the burner is By applying these kinds of valves a reliable
adjusted via the burner lance. and repeatable adjustment of the O2 content
can be obtained. The capacity will be auto-
The air pressure is monitored by a pressure matically adjusted via a hand wheel or cylin-
transmitter (2011) for ‘pressure too low’ (PIZA- der (option) at the main burner.
8011).
If the fuel-oil/air ratio is not correct over the
I.G. generator is equipped with two combustion whole of the capacity range, then the fuel-
air blowers according the classification re- oil/air ratio can be changed by the pressure
quirements. Both blowers have block valves regulating valve (1071).
(2205 and 2225) at the outlet This change is advised if the O2 content is too
The block valves are equipped with limit high/low over the whole range.
switches for safe operation and protection of If the fuel oil pressure is high, the O2 content
the blowers. The operator will not be able to will be low. If the pressure is low the O2 content
start the generator without having these valves will be high.
in the correct position.
To start the generator, the burner gun has to
5.3.3 Capacity control be in its start position, safeguarded by a limit
The capacity of the inert gas generator can be switch (2001a) and indicated on the mimic
adjusted by the hand wheel on the main burn- panel.
er. With this the burner gun (lance) can be
moved forward and backward in its casing. During inert gas or air production the capacity
The passages of the slots in the atomising must be adjusted in such a way that the deck
ring round the burner head will consequently main pressure can be maintained at the set
get smaller or bigger. value without blowing-off a too great quantity
of gas via the purge/excess gas valve (6021).
Because the supply pressure of the blower is
almost constant, less or more combustion air Note:
will flow through the slots. − After re-adjustment of the capacity during
inert gas production, especially with larger
By means of a linkage, the fuel-regulating changes, the system (pressure and
valve (2032) is coupled to the burner gun. temperatures) may require some time to
stabilise, before the oxygen content is
This results in a simultaneously controlled between the set limits again. Small steps
supply of fuel and of combustion air. are to be advised.
If the fuel-oil/air ratio is not correct over a part − The minimum and maximum capacity
of the capacity range, then the fuel-oil/air positions, the stroke of the burner gun, are
fixed by mechanical stops on the burner

Rev. 0 Date.12 SEP 2014 14


11215053R00

mounting slides. These may never be The tangential impulse flow is created by sup-
changed. plying the air through slots in a ring fitted
around the spray nozzle.
5.3.4 Fuel oil supply
Fuel oil is sucked in and supplied at a con- The optimum gas quality is achieved by:
stant pressure by a fuel oil pump (1012). The - the correct atomization by combustion
fuel oil pump has a built in pressure safety air
relief valve. - The burner cone that concentrates the
heat, resulting in a complete chemical
Prior to starting the ignition, and while the reaction of fuel and air
pump is already running (pre-purge time); all
the fuel oil is pumped back via the overflow An optimal atomisation of the fuel is achieved if
valve (1071). By means of this valve, the oper- the differential pressure over the slots of the
ating pressure of the pump is adjusted as well. atomising ring is minimum 0.1 bar. This means
the difference between the combustion pres-
The fuel oil flows to the nozzle of the main sure (2012) and the pressure inside the com-
burner via two valves (1059, 2040) and a fuel- bustion chamber (= pressure indicator mounted
oil-regulating valve (2032). on controller 8005 in the control panel).

During ignition, a small quantity of fuel oil is At a lower atomising pressure, the quality of
supplied at the set pressure to the pilot burner combustion will grow worse and soot could be
(2101) via two solenoid valves (2103, 2105). formed.
A transmitter (1053) safeguards the fuel oil
pressure (8055). The burner cone is a part of wear and tear.
Therefore this cone must be checked periodi-
5.3.5 Pilot burner cally for damage, (see the chapter “Mainte-
During a certain interval of the ignition se- nance”), and replaced as soon as necessary
quence, the pilot burner is supplied with fuel (see drw P-X00047). The life of the burner
oil at the set pump pressure and instrument cone is strongly influenced by the quality of
air for atomisation and combustion. the fuel oil (DMA, DMB or DMC) and the cor-
rect adjustment of the system (setting of O2
The pilot burner is ignited with the aid of a spark content, above mentioned atomizing pressure,
generated by means of a spark plug. An ignition water pressure, etc). Alfa Laval Aalborg
transformer (2131) is supplying the high voltage Nijmegen B.V. experienced based on this, life
for the spark plug. times of less than 1000 hours and more than
3500 hours. So the correct operation is most
The burning of the flame is monitored by an UV- important.
flame detector (2121), in conjunction with the
flame safeguard relay in the electric system. 5.3.7 Combustion chamber and
scrubbing section
5.3.6 Main burner Main and pilot burners are mounted on the
The main burner (2001) is ignited by the pilot combustion chamber (2301). A cooling-water
burner. The burning of the flame is monitored jacket surrounds the combustion chamber to
by an U.V.-flame detector (2021), together discharge the generated heat as much as
with the flame safeguarding relay in the elec- possible. The cooling water jacket has a spi-
tric system. ral, so the cooling water flows round the com-
bustion chamber wall and an optimum cooling
The fuel oil is atomised in two steps. First a effect is achieved.
spray nozzle disperses the fuel oil. Then it is
subjected to the inside a tangential impulse The hot inert gas flows through the cool-
flow of combustion air, which added to the ing/washing tower, where it is directly cooled
mainly axially orientated impulse flow of the with seawater to a few degrees above sea-
liquid itself, results in an ultra-fine dispersion of water inlet temperature.
the liquid.

Rev. 0 Date.12 SEP 2014 15


11215053R00

At the same time, the sulphur oxides are of the generator a constant and stable pres-
washed out of the inert gas. These sulphur sure can be maintained. The consequence is
oxides are formed during combustion of the a constant combustion air supply, thus a con-
fuel oil, as the fuel oil always contains sulphur. stant oxygen percentage.

The seawater is supplied to the sprayers and The height of the water seal smoothly follows
the combustion chamber jacket via orifices the pressure in the generator. In conjunction
(2314 and 2316), which distribute the cooling with the (optional) pressure control system of
water in the correct quantities. Orifice 2316 the generator a constant and stable pressure
has been adjusted during commissioning to can be maintained. Therefore a constant
meet a water inlet pressure of approx 1.8 combustion air supply and thus a constant
barg. oxygen percentage is obtained.

The seawater leaving the sprayers flows out


via the water seal. Low- and high-alarm pres- For a proper functioning of the water seal, the
sure (8020, 8070) safeguards the seawater discharge line must have a slope of minimal
supply. 20° to overboard. In case of less slope aera-
tion connections back to inert gas main must
Sufficient cooling of the combustion chamber be made.
wall is safeguarded by high temperature alarm
(8060). Sufficient cooling of the inert gas is A level switch (2322) safeguards a proper
safeguarded by high temperature alarm discharge of water to the effluent water seal.
(8035). For draining a pneumatic valve (2410) is
mounted in front of the control valve. The
A demister (2307) on top of the scrubbing drain valve is normally closed and can be
tower prevents a mist from being carried away opened via a solenoid valve. Draining will take
with the inert gas. The mist is condensed and place in case of a burner failure at start-up.
re-supplied as water droplets, which are car- The water, with some fuel oil, is discharged to
ried off via the water seal. the bilge.
As long as this draining valve is opened, the
After stopping the unit, the combustion cham- generator cannot be (re)started as the limit
ber will be drained automatically (opening of switch ((2410) GSb) of the valve is connected
valve 2351) followed by automatically rinsing to the starting circuit of the generator.
with fresh water (opening of valve 2340)
5.3.9 Generator pressure control
5.3.8 Effluent water seal system
The pressure inside the generator should be
A water seal mounted under the cooling sec- kept constant at 0.15 bar (g). This insures a
tion discharges the cooling water and the proper combustion with a constant quantity of
condensate from the generator, at the same combustion air at a given capacity.
time maintaining the required overpressure in
the generator and avoiding the escape of gas The pressure is held constant by the pressure
or air. control valve (6001). The valve is controlled in the
manner described below.
Level controller (8015) controls the height of
the water seal. This controller becomes its The generator pressure is measured by a
input signal from differential pressure transmit- pressure transmitter (6006). The output signal
ter (2415), which is fitted in front of control is fed to a pressure controller (8005) where it
valve (2419). As soon as the cooling water is compared with the set value (150 mbar).
pump has been started the level control will be
activated. Because the level control is operat- Depending on the difference between the
ed by a differential pressure transmitter, this measured and the set values, a proportionally
control is independent from the pressure in- integrated signal is generated, which is
side of the combustion chamber. Therefore, in passed through to a positioner (6003) of the
conjunction with the pressure control system control valve.

Rev. 0 Date.12 SEP 2014 16


11215053R00

When the delivery valve is opened, the purge


At the start up the control valve will be opened valve will automatically start controlling the
completely. Direct after the start, the pressure deck main pressure.
control system will be activated automatically.
The generator pressure will increase to the set In case of the mode ‘INERT GAS
working pressure. PRODUCTION’, the purge air and (after
ignition) the initially produced inert gas, are
As the main burner starts on low capacity, the blown off to the outside air for about 5 minutes
expansion of the gasses during ignition of this until the inert gas quality has stabilised.
burner has no effect on the ignition of the
burner or effluent water seal of the generator. Provided no alarms are indicated the inert gas
can be led to the cargo tanks. On the LCRP,
5.3.10 Generator delivery pressure the operator must operate the ‘GENERATOR
The delivery pressure is one of the most im- STAND-BY’ switch. The inert gas delivery
portant characteristics of the generator, which valve can now be opened via the CCRP.
always has to be observed.
5.3.12 Excess gas vent system – deck
The air quantity delivered by the blower de- main pressure
pends both on the difference between the Through the purge valve / excess gas vent
blower pressure and the generator back pres- valve (6021) the overcapacity of inert gas is
sure and on the passage of the slots in the blown-off and the pressure in the inert gas
atomising ring of the main burner. deck main line is adjusted in accordance with
the pre-set pressure.
If the back pressure deviates from the set val-
ue the quantity of combustion air at the ad- The pressure transmitter (6306, 0 – 0.25 barg)
justed capacity position will be too high or too measures the deck main pressure. The 4 – 20
low to match the fuel supply adjusted and thus mA signal is led to a controller (8008). The set
the oxygen content will be influenced. value for the deck main pressure has to be
determined during the first start-up on board.
The quality of combustion depends on the
pressure difference (about 0.1 bar) over the
atomising ring of the main burner.

If this pressure becomes too low, the quality of


combustion will decrease with the risk that
soot is being formed.

5.3.11 Purge / excess vent valve and


delivery valve
The delivery valve (6041) is a pneumatic stop
valve in the delivery line of the generator. The
delivery valve is closed by a spring in fail safe
position. It is controlled via a solenoid valve
(6044) in the instrument airline to the valve
actuator (6042).

The purge/excess gas valve (6021) is a


pneumatic valve in the purge line. The purge
valve is normally opened by a spring in fail safe
position. The function of the purge valve is to
purge air to the outside during the start-up and
to control the deck main pressure.

Rev. 0 Date.12 SEP 2014 17


11215053R00

Note:
The purge valve only controls the deck main
line pressure if the inert gas generator is 4. Other protections which are not part of the
running and delivering inert gas to the tanks. Alfa Laval Aalborg Nijmegen B.V. scope
of supply are:
5.3.13 Deck main pressure control
The deck main pressure is controlled and pro- 7) PV-valves
tected by several protections. - Ship’s tank pressure monitoring system

1. The purge / excess gas vent valve pro- 5. Alfa Laval Aalborg Nijmegen B.V. delivers
tects the tanks against overpressure dur- standard a liquid filled P/V-breaker. In case
ing inerting of the tanks. If the capacity of of vacuum or too high pressure, the liquid
the generator is larger than the capacity in the P/V-valve will break through. This is
of the cargo pumps, a part of the inert gas an absolute emergency action which will
will be blown to the atmosphere. only happen if all other systems or actions
have failed. The liquid level of P/V-breaker
must be checked regularly and must be re-
2. Alfa Laval Aalborg Nijmegen B.V. delivers filled if necessary. Unlike the deck water
a deck main pressure monitoring set seal the P/V-breaker will not be filled
standard with the installation. This set automatically but has a permanent
comprises of two pressure transmitters glycol/water mixture as filling. One has to
(6306, 6304), and a pressure indicator fill up the liquid into the P/V-breaker up to
(6302). the height that the liquid flows out the filling
opening again.
The signal from pressure transmitter
(6306) is used by controller (8008) for the The standard sequence for the safety of the
control of the purge valve during inerting tanks is:
and indicating and recording the deck 1. Pre-alarm at CCRP or ship’s systems.
main pressure at the CCRP. Personnel will act to prevent the alarms
and or the shutdowns.
The signal from the pressure transmitter
also provides a signal for the deck main 2. The low-low alarm from the generator will
pressure alarms (high or low). shutdown the cargo-pumps.

The high and low alarms are also


available when the generator is not in 3. P/V-valves will open at a too low or too
operation. The high alarm will put the high tank pressure when actions 1 and 2
generator in purge mode. The low deck did not have any effect.
main pressure alarm is a pre-alarm. In
case of a low alarm the generator must be
started or the capacity of the generator 4. P/V-breaker will break through at a too
must be increased or the cargo pumps low or too high tank pressure. This is an
capacity should be decreased etc. absolute emergency situation; the P/V-
valves do not have enough capacity (i.e.
In case of low alarm, there is still a safe blocked P/V-valve as result of corrosion).
situation, but immediate action should be The P/V-breaker cannot be blocked since
taken. it has no mechanical moving parts. The
P/V-breaker will always assure that the
3. Low-low deck main pressure alarm formed tank pressure will be within the safe
by pressure transmitter (6304) in range!
combination with a switching module
(control panel). Potential free contacts are
provided by Alfa Laval Aalborg Nijmegen The set value for the inert gas main line pres-
B.V. to stop cargo pumps. The generator sure has to be determinate during the start up
keeps running when this alarm is activated. of the installation on board of the ship (for au-

Rev. 0 Date.12 SEP 2014 18


11215053R00

tomatic control keep tension on the CCRP all (7001). This analyser gives a 4 – 20 mA
the time) signal, which corresponds linearly with the
analyser range.
Note:
The ship may have additional safety devices, The output (4 – 20 mA) is supplied to a
but this is outside the scope of supply and recorder (8009) in the cargo control room
responsibility of Alfa Laval Aalborg Nijmegen panel.
B.V..
5.3.15 Fuel to air ratio / oxygen con-
5.3.14 Measurement and safeguarding tent
of the oxygen content The fuel to air ratio, (and with this the oxygen
The oxygen analyser (7001) constantly content of the inert gas produced), has been
measures the oxygen content in the inert gas set over the whole capacity range by means
and will effect an alarm if a set maximum or of the adjustable screws in the fuel oil regulat-
minimum quantity of oxygen is exceeded. ing valve (2032).

The maximum value is fixed by the application This setting is permanent and should not be
of the inert gas (normally about. 4 vol. % O2). changed!
The minimum value protects against under-
stoichiometric combustion (a too high content In case of large changes in air temperature,
of combustibles CO + H2 with the risk of soot), air humidity or quality of the fuel oil, the O2-
normally set at 2 vol. % O2. content becomes too high or too low.

The generator will not stop at an O2 HIGH or In this event, the fuel-oil pressure before the
an O2 LOW alarm condition. A visible and fuel-oil regulating valve (2032) must be in-
audible alarm will occur. If such a failure creased or decreased by means of a pressure
remains for more than 60 seconds, purge control valve (1071) in the fuel-oil return line.
valve (6021) will open; delivery valve (6041)
will close. In case of a re-adjustment take care of the
following:
The inert gas produced will be blown off now
and not discharged to the cargo tanks. This • BE SURE, THAT THE FUEL OIL PUMP
enables the operator to change the adjustment DELIVERY PRESSURE, INDICATED ON
of the equipment and to see the result. THE MANOMETER (1003), DOES NOT
EXCEED A PRESSURE OF 20 bar (g)!
In case of an O2 alarm the O2 content can be This to prevent a back flow of oil in the
changed by supplying either more or less fuel pump via a built-in overflow valve.
oil to the main burner. This has to be controlled • Adjust with small steps, this due to the
manually by the pressure-regulating valve response time of the measuring system.
(1071) in the fuel oil supply line. This can be • In case an excess of fuel is supplied in
necessary e.g. at temperature variations of the proportion to the combustion air (O2-
combustion air. content measured below minimum setting)
or the atomising pressure is too low, the
When the oxygen content in the inert gas risk exists that soot is being formed. Soot
produced is in the correct range the product can foul and damage the equipment. An
can be led to the deck again. indication for this phenomenon is the
flame becoming yellow.
The analyser has to be calibrated regularly, • The fuel pressure on the main burner will
with the aid of a ‘span’ gas (instrument air) not always have the same value for certain
and with the aid of a calibration gas oxygen contents this depends on the fuel
(N2 + 1.5% O2). temperature, the viscosity and the quality
(see technical specifications).
Registration of the oxygen content • The blower takes in a constant volume of
The oxygen content of the inert gas is combustion air at a certain burner position.
constantly measured by an O2 –analyser

Rev. 0 Date.12 SEP 2014 19


11215053R00

The quantity of kilograms of oxygen in that


air depends on the ambient temperature
and humidity.
• Prior to re-adjusting check the generator
delivery pressure; it has to be exactly 0.15
bar.
• After re-adjustment of the capacity during
inert gas production, (especially with larger
changes), the oxygen measuring system
may require some time to stabilise, before
the oxygen content is between the set lim-
its again.

Rev. 0 Date.12 SEP 2014 20


11215053R00

6 TECHNICAL SPECIFICATION Dew point


Saturated (at gas temperature)
6.1 Design basis

The layout of the installation has been 6.3 Utilities


calculated and based upon the following
criteria. Fuel:
Marine Diesel oil according to
− The unit is designed and will be built in ISO 8217 2010, grade DMA, DMB or DMZ
accordance with the regulations of IMO and
the rules of the applicable classification Inlet pressure: 0 – 0.4 bar(g)
society. Consumption (at
− Shipboard use, indoor erection. design capacity): approx. 331 kg/h
− The inert gas capacity and composition is
calculated with combustion air of + 25 °C Electricity:
and 100% relative humidity at atmospheric Main supply system
pressure. The average cooling water has a 440 V / 3 Ph / 60 Hz
temperature of + 25 °C. 220 V / 1 Ph / 60 Hz
− Pressures mentioned are effective working 24V DC
pressures (± 5% tolerance).
− Temperature tolerances ± 1 °C. Combustion air blower motor
− Quantities tolerance ± 3%; Rating: 63.3 kW
Consumption: 56 kWh/h
− Electrical supply voltage tolerance
+10% / -15%.
FOP motor
− The combustion chamber cooling water
Rating: 0.9 kW
jacket is designed for a maximum of 1 bar
Consumption: 0.7 kWh/h
overpressure.
Auxiliaries
6.2 Inert gas specification Rating: 3 kW
Consumption: 3 kWh/h
Capacity:
Adjustable 4500 m3/h Cooling water:
Turndown ratio 1:4 Seawater consumption
Discharge pressure max. 0.15 bar (g) Generator: 327 m3/h
Deck water seal: 3 m3/h
Gas composition (based on dry gas): Quality: filtered seawater
Oxygen O2 2 – 4 vol. % (mesh size 4 mm)
Carbon monoxide CO max 500 ppm Inlet pressure: 2 – 4 bar
Carbon dioxide CO2 max 14.0 vol. % Outlet pressure: atmospheric
Sulphur oxides SOx max. 20 ppm Inlet temperature: max. 32 °C
Nitrogen N2 balance Temperature rises: about. 10 °C average
Soot 0 (on scale
Bacharach) Rinsing water
Note: Fresh water
-Bacharach 0 = complete absence; consumption 4 m3/h
-at lower O2-content, CO-content will increase.
Instrument air:
Temperature: Quality: free from dust, oil and
About 6 °C above cooling water inlet condensed water
temperature. Supply pressure: 6-9 bar
Consumption for
pneumatic valves: 2 Nm3/h
Consumption for pilot

Rev. 0 Date.12 SEP 2014 21


11215053R00

burner per start: 170 litres Ambient air:


Temperature: between 0 and 50 °C
Consumption for
combustion: about 5057 Nm3/h
Pressure atmospheric
Humidity max. 95%

Sufficient ventilation in the ig generator


room is obligatory!

If ventilation is insufficient this can cause


under pressure in the room. The result may
be that doors cannot be opened anymore.

Noise level:
Noise produced
by blower*: max. abt 100 dB (A)
Measured at 1m distance (in free field)

Rev. 0 Date.12 SEP 2014 22


11215053R00

7 OPERATING INSTRUCTIONS • The Engine room panel (ERP).


This is an optional panel. The panel con-
Before operating the unit, read the tains information useful for engine room
SAFETY INSTRUCTIONS. personnel, such as generator status and
supply of utilities. Depending on the user’s
7.1 General requirements Alfa Laval Aalborg Nijmegen
The complete generator is controlled by the B.V. can supply this panel. However this is
PLC. The PLC program is not a part of this not required by classification.
manual since the program details are not
required for installation or operation of this
system. However in case of problems or • Other panels:
questions, please contact ALFA LAVAL Equipment such as the blowers and fuel
AALBORG NIJMEGEN B.V., for further oil pump are equipped with starter panels
assistance. comprising of motor starters and some
basic indicators.
Soot can foul and damage the system.

For more details about the control panels,


To prevent soot from being formed, always please refer to the electrical diagrams
make sure that: collected in the “Electrical documentation”

• The correct fuel quality is used (see the


chapter Technical specifications). 7.3 Switching on
• The differential air pressure over the main
burner is correct, about 0.1 bar (g); this is 7.3.1 Inert gas production
the atomising pressure. 1. Turn the main supply switches ‘ON’. Keep
• No excess of fuel is supplied; i.e. oxygen ‘ON’ normally for the analyser (for pro-
content indicated on the O2-analyser must longing the lifetime of the sensor) and for
always be more than 1%. the deck equipment/alarms.
• The oxygen analyser is regularly calibrat-
ed; Switching ‘ON’ has to be done at least 1
hour before the generator is started. This
in conjunction with the warm-up time for
7.2 Control panels the oxygen analyser.
An inert gas system comprises several control
panels which are described below. 2. Before starting.
- Open the instrument air shut off valve
• The Local Control Room Panel (LCRP). (1501).
This is the main panel of the generator - Calibrate the oxygen analyser accord-
from which the generator can be operated. ing to the instructions given in the O2-
analyser manual (see the Sub-
• The Cargo Control Room Panel (CCRP). suppliers documentation).
From this panel the inert gas delivery
valve can be operated and the deck line 3. Checks.
main pressure is controlled. This panel is - Check if the instrumentation valves for
the interface between the inert gas gener- the pressure indicators and transmit-
ator and the cargo tanks. ters are opened
- Check if the drain plug on the main
burner is closed.
• The Bridge panel (BP).
This is a small panel with only a few ele-
mentary functions, which are required by
the classification.

Rev. 0 Date.12 SEP 2014 23


11215053R00

4. Starting up the seawater supply: 13. The burner start up sequence is start-
- Open the valves in cooling water sup- ed now:
ply and the discharge lines of the com-
bustion chamber and the water seal. 0 sec. Blower starts running (pre-purge
- Open the valves in the water supply time of 60 seconds).
and the discharge lines of the deck wa- 0 sec. Fuel oil pump starts running.
ter seal (should always be stand-by).
- Start the cooling water supply pump. 60 sec Test UV detectors
- Check pressure: approx 1.8 barg 63 sec Ignition pilot burner.
- Start the deck water seal water supply Solenoid valves (2103, 2105,
pump. 2114) for fuel oil and instrument
air to the pilot burner open; The
5. Open the main fuel oil shut off valve ignition transformer (2131) and the
(1001). spark plug are energised.
70 sec. Ignition transformer de-energised.
6. Check that the fuel oil control valve UV-flame detector (2121) must
(1071), in the oil return line to the tank, is have detected the flame of the
opened. pilot burner, otherwise the genera-
tor shuts down and an alarm is
7. Open isolating valves (1015 and 1005) of given.
the fuel oil pump. Rotate the handle of the 74 sec. Ignition of the main burner.
fuel oil filter (1002) twice. The two valves for fuel to main
burner open (1059 and 2040). The
8. Open the fuel oil shut-off valve (1051) on pilot burner ignites the main burn-
the generator. er.
83 sec. The solenoid valves (2103, 2105,
9. Put the main burner in the starting posi- and 2114) for the fuel oil and the
tion (optional: automatic). If the burner is instrument air to the pilot burner
in the start position this is indicated on the are closed again. The Pilot burner
LCRP, the indicator light turns on. If the extinguishes.
light is blinking this indicates that it is not UV-flame detector (2021) must
in the starting position. have detected the flame of the
main burner, otherwise the gener-
10. Select the production mode ‘INERT GAS ator shuts down and an alarm is
PRODUCTION’. given.
The pressure control system is
11. Check that the deck seal and the P/V now being activated.
breaker are correctly filled. The air pressure inside the gener-
ator must be checked and if nec-
12. If the indication ‘SYSTEM READY TO essary adjusted to the set value of
START’ on the mimic panel lights up, start 0.15 bar (g).
the inert gas generator by pushing the 300 sec. From this moment on, inert gas
START button on the LCRP. If the indica- can be delivered to the tanks, pro-
tion light does not light up consult “Trou- vided that the O2-content is be-
ble shooting”. tween its limits.

14. Check:
- Pressures.
- Temperatures.
- Oxygen content of inert gas produced.
See the test protocol. Re-adjust, if neces-
sary.

Rev. 0 Date.12 SEP 2014 24


11215053R00

15. Adjust the burner capacity with the hand 4. Put production mode selector, into posi-
wheel on the main burner if this is neces- tion ‘AIR PRODUCTION’.
sary (optional: automatic control by deck
pressure) 5. Adjust the main burner into its start ca-
pacity position (limit switch 2001) with its
16. Wait for at least 5 minutes. hand wheel.

17. If the generator operates normally and the 6. If the indication “SYSTEM READY TO
composition of the gas is correct (STAND- START” lights-up then start the generator
BY FOR DELIVERY blinking), then push with the START button. The blower starts
the ‘STAND BY FOR DELIVERY’ on the and the pressure control system is opera-
LCRP (the stand-by lamp starts steady). tive.

18. On the LCRP and the CCRP the indica- If the indication “SYSTEM READY TO
tion ‘STAND BY FOR DELIVERY’ will START” does not lights-up then consult
light up. This means the generator is the additional operation notes.
ready to deliver the inert gas to the tanks.
The necessary charging operations can 7. Check pressures and temperatures.
now be controlled from the Cargo Control
Room Panel. 8. If the generator operates normally then
turn the ‘STAND BY FOR DELIVERY’
19. Push the “START DELIVERY” button(on button on the LCRP
the CCRP)
10. On the LCRP and the CCRP the indica-
20. Provided the O2-content of the inert gas tion ‘STAND BY’ will light up. This means
produced is between the limits set on the the generator is ready to deliver the air to
alarm set points of the oxygen analyser the tanks.
the following will happen.
- The delivery valve (6041) of the gen- 11. Push “start delivery” button (on CCRP).
erator opens. This will have following effect:
- The purge/excess gas vent valve - The delivery valve (6041) of the gen-
(6021) is slowly controlled to the work- erator opens.
ing position. - The purge/excess valve (6021) is slow-
- Check if bleed valve 6051 is closed. ly controlled to its closed position or to
a controlled working position if the
If the required deck main pressure cannot deck main pressure increases.
be obtained then the capacity of the burn-
er has to be increased by the hand wheel
on the burner. 7.4 Switching off

7.3.2 Air production 7.4.1 Normal switch off


1. Turn the main supply switches ‘ON’, (and 7) Push “delivery stop” (on the CCRP), so
keep ‘ON’ normally). the delivery of air/inert gas to the tanks
is stopped.
2. Open the instrument-air shut-off valve
(1501). This will open purge valve 6021 and close
delivery valve 6041
3. Start up the seawater supply. The indication ‘INERTGAS OR AIR TO
- Open the valves in the cooling water DECK’ extinguishes.
supply and discharge lines of combus- 2. Push the “generator stop” button on the
tion chamber and water seal. local control panel for stopping inert gas
- Open the valves in the water supply or air production (the blower keeps run-
and discharge lines of the deck seal. ning for some time). The combustion
- Start the seawater supply pump. room is purged with air now to remove the
- Start the deck seal supply pump. oil vapour and the gasses with sulphur.

Rev. 0 Date.12 SEP 2014 25


11215053R00

7.5 Checks during operation


7) The blowers will be automatically
switched off after about 3 minutes. Checks after every start and further every
4 hours’ operating time:
5. Switch off the cooling water pump only • Check the O2-content (inert gas production
after approx 15 minutes. only).
This enables the combustion • Check the pressures and temperatures
chamber to cool down (see test protocol). Record these values to
properly and reduce corrosion observe any irregularity as quickly as pos-
sible.
7) Close the fuel oil shut off valves (1001 • Check whether an equal flow of inert gas
and 1051). is indicated on the flow indicator on the
oxygen analyser panel (inert gas produc-
tion only).
7.4.2 In case of a longer standstill • Check the fuel oil pump delivery pressure.
• Check the fuel oil pump discharge pres-
1. Close the cooling water supply valves. sure after start; the oil must return to the
tank via pressure control valve (1071) in
2. Valve (2340) in the fresh water line to the fuel oil return line; IF NOT, STOP THE
jacket of the combustion chamber will SYSTEM and RE-ADJUST valve (1071);
open automatically and the unit will be see Sub-suppliers documentation.
rinsed with fresh water for a half hour. • Check the filter in the oxygen sample line
(7022).
• Check the temperature and smooth run-
ning of the combustion air blower.

Checks every week:


• Check the calibration of the O2-analyser.
An exactly calibrated O2-analyser is very
important (correct gas quality, prevention
of soot formation)!
• Lamp test.
• Alarm test.

Checks every month:


• Open drain plug at the bottom of the burn-
er housing to drain possible collected oil

Rev. 0 Date.12 SEP 2014 26


11215053R00

7.6 Adjustments (1071) built on the fuel-oil return line. The


pump pressure, indicted on the manometer
7.6.1 Adjustments of the generator (1003) at the pump discharge line, must al-
delivery pressure ways be the same.
The generator delivery pressure can be ad-
justed via the set point adjustment on the The pump pressure must be checked at
pressure controller (8005) which is mounted in every start and further regularly.
the LCRP.
The controller is adjusted in the Alfa Laval The fuel-oil pump delivery pressure is safe-
Aalborg Nijmegen B.V. workshop, but it is guarded by means of a built-in overflow valve.
possible that some adjustments have to be This valve is adjusted on 25 barg.
changed during the test run on board.
For more detailed information and adjustment
see the controller instructions in “Sub-
suppliers documentation”.

7.6.2 Adjustments on the oxygen an-


alyser
Following values are set on the oxygen ana-
lyser for wet inert gas:
Oxygen alarm low: 2.0 %
Oxygen alarm high: 4.0 %
Analyser range: 0 – 5 % with an output of
4 – 20 mA.

For calibration a gas with a content of 1.5 %


oxygen must be used at the measuring range
of 0 – 5% oxygen. Never use nitrogen only

Note:
The correct analyser range is essential for the
delivery valve (6041) to open.

7.6.3 Adjustments of the deck main


pressure
The deck main pressure can be adjusted on
the controller (PIC8008) in the CCRP.

The settings for the controller are indicated in


the test protocol (see Test protocol).

7.6.4 Adjustments to the pilot burner


A pressure regulator (PIC 2112) can adjust
the instrument air to the pilot burner (approx.
0.8 bar with valve open)

Adjustment has to be carried out in such a


way that a stable non-flickering flame of suffi-
cient length is obtained.

7.6.5 Adjustments of the fuel-oil


pump delivery pressure
The fuel-oil pump delivery pressure can be
adjusted with the pressure regulating valve

Rev. 0 Date.12 SEP 2014 27


11215053R00

8 TROUBLE SHOOTING 8.2 Consequences of failures ex-


planation
8.1 Failures See column ‘C.o.F.’ in ‘Consequences of fail-
ures table’
• In case of a failure, an audible alarm is
given and a failure indicating signal lamp 1. a. Purge valve opens.
lights up (blinking). b. Delivery valve closes.
c. Audible and visible alarm.
• After pushing the ACKNOWLEDGEMENT
button on the panels, the audible alarm is 2. a. Blower and cooling water pump are
switched off, but the signal lamp remains switched off after an after purge time
lightened (steady). of 180 seconds.
b. Fuel oil pump is switched off.
c. Fuel oil valves close. Burner extin-
• After eliminating the cause of the failure, guishes.
the installation has to be reset by pushing d. Purge valve opens.
the RESET button on the local control e. Delivery valve closes.
panel. f. Visible and audible alarm.
After this the generator can be restarted.
3. a. Blower switched off immediately.
b. Same as 1b up to 1f incl.
• The setting of all safety devices is given in
the test-protocol. 4. a. Blower switched off immediately.
b. Cooling water supply pump switched
off.
• The “Trouble Shooting Chart” is a chart in c. Same as 1b up to 1f incl.
which all failures that are indicated on the
control panels, also some general genera- 5. a. Cargo pumps stop.
tor failures are mentioned. b. Audible and visible alarm.

6. a. Audible and visible alarm.


• For specific failures in operation of the
various accessories belonging to the in-
stallation, the manufacturer’s instructions
in the Sub-suppliers documentation have
to be consulted.

• In the trouble shooting chart, one column


is named ‘C.o.F.’, which means ‘Conse-
quences of failures’. The figures indicated
are explained in Consequences of failures.

Rev. 0 Date.12 SEP 2014 28


11215053R00

8.3 Trouble Shooting Charts

8.3.1 General trouble shooting chart

Failure Possible causes Remedies


Generator doesn’t start, while Purge gas valve (6021) not If one of these valves is not in
no failure is indicated and indi- completely open. its correct position, the valve
cating light ‘SYSTEM READY Delivery valve (6041) not com- may be jammed, or its actuator
TO START’ doesn’t light up on pletely closed. or solenoid valve may be defec-
control panel: Drain bilge valve (2410) not tive. Un-jam, clean, replace.
closed.
Emergency stop button Release the emergency stop
pressed. button.
Main burner not in its starting Reposition the main burner.
position.
Seawater pump not started yet Start the seawater pump.
First failure circuit generator Push ‘RESET’ button.
energised.
No power supply (any). See Apply power.
Mimic diagram
Loose electrical connection. Reconnect.
System does not change over Delivery is interlocked. Wait for 5 minutes after starting
to ‘charging’ (inert gas/air to the generator.
deck): The O2-content of the produced Change the O2-content.
inert gas is not between the
limits set on the high and low
alarm units of the oxygen ana-
lyser
Switch not operated correctly. Push the button (INERT GAS
OR AIR TO DECK) again

Rev. 0 Date.12 SEP 2014 29


11215053R00

8.3.2 Consequences of failures trouble shooting chart

Failure CoF Safety Possible causes Remedies


Fuel oil pump motor 2 1013 Motor overloaded. Check and repair.
failure: Heavy run of the fuel oil
pump.
Adjustment of the over- Re-adjust (see specification
load relay is incorrect. plate on the motor).
Fuel oil pressure low: 2 PZA-L 8055 Pump isolating valves Open it.
closed.
Pump not running. Check fuses, isolating
switch, etc.
Air in fuel oil lines. Vent.
Setting overflow valve Check and re-adjust.
(1071) incorrect.
Filters (1002, 1052) Clean them.
clogged.
Instrument air pres- 4 PZA-L 8050 Shut off valve (1501) Open it
sure low: closed.
Filter (1502) clogged. Clean them.
Leaks in system. Check for leaks and repair.
Supply system defect. Repair.
Combustion air pres- 2 PZA-L 8011 Blower not running. Check fuses, isolating
sure low: switch, etc.
Flexible joint in blower Repair/replace.
outlet defective.
No flame: The main 2 (4, XZA 2021 Main burner flame de- Check main burner flame
burner does not ignite see tector (2021). Window detector. Clean or replace.
or extinguishes during note) may be dirty or the de-
operation tector may be defective.
Flame safeguard relay in Repair/replace.
Note: generator control panel
Situation is true for defective.
bilge drain valve se- Oil pressure low. Check fuel oil pressure be-
lection in “cancel” fore regulating valves.
mode. Oil nozzle main burner Clean or replace it.
dirty.
If the drain valve se- Solenoid valves (1059 Check functioning
lection mode is “auto- and 2040) in fuel line to
matic”, then the c.o.f. main burner not func-
3 is true with extra tioning correctly.
opening of bilge drain
valve 2410 (this hap-
pens only during 30
seconds of flame fail-
ure)
No flame The pilot 2 XZA 2121 Check instrument air Adjust with pressure regula-
burner does not ignite: pressure to pilot burner. tor PIC 2112 (see Pilot
burner).
Oil atomiser of pilot Replace.
burner dirty.

Rev. 0 Date.12 SEP 2014 30


11215053R00

Failure CoF Safety Possible causes Remedies


No flame The pilot 2 XZA 2121 Delivery pressure of Check pressure. Adjusta-
burner does not ig- the fuel oil pump incor- ble with built in return
nite (continued): rect. valve of fuel oil pump
and/or pressure regulating
valve (1071) in fuel oil
return line (see Sub-
suppliers documentation).
Pilot burner flame de- Clean or replace it.
tector (2121) not func-
tioning correctly. The
window may be dirty or
the detector may be
defective.
The flush airline of Un-block it.
detector (2121) is
blocked
Flame safeguard relay Replace
in generator control
panel defective
Solenoid valves for Check and or replace.
instrument air and fuel
oil to pilot burner not
functioning correctly
Spark plug not func- Check, replace or adjust.
tioning correctly. Distance between elec-
Insufficient contact of trodes should be approx. 2
sparkplugs cap. Elec- mm.
trodes worn out or
wet?
Not enough air Adjust air pressure (2112)
to 0.8 bar with valve open
Blower motor failure: 3 2203 Motor overloaded
2223 Adjustment of the Re-adjust (see specifica-
overload relay incor- tion plate on motor).
rect.
Blower is switched off Switch on.
(no source supply).
Cooling water outlet 2 TZA-H 8060 No free discharge of Check free discharge of
temperature high: cooling water from cooling water.
combustion chamber. Check that the discharge
valves are open.
Orifice in cooling water Clean it.
line to combustion
chamber may be
clogged.
Cooling water inlet 2 PZA-L 8020 Cooling water supply Check fuses, duty switch-
pressure low: pump not running. es etc.
Pump isolation valve Open it.
closed
Filter clogged. Clean it

Rev. 0 Date.12 SEP 2014 31


11215053R00

Failure CoF Safety Possible causes Remedies


Cooling water supply 4 PZA-H 8070 Stoppage in combus- Clean it
pressure combustion tion chamber cooling
chamber high: water discharge line.
Excessive supply of Reduce.
cooling water.
Cooling water level 4 LZA-H 2322 Check free discharges Clean it.
high: of cooling water from Open the discharge valve.
water seal.
Controller 8015 not set Change setting.
correctly.
Inert gas tempera- 2 TIZA-H 8035 Supply cooling water Check pressure.
ture behind the low.
scrubber high: Sprayer pipes in Clean them.
scrubber clogged.
Orifice(s) clogged. Clean them.
Inert gas delivery 3 PZA-H 8065 Some of the valves in Open or clean them.
pressure high: the inert gas delivery
or main line are closed
or blocked.
Controller 8005 not set Set at 0.15 bar.
correctly.
The purge excess gas Check it.
vent valve (6121) is
not working correctly.
O2 analyser defect: 1 7001 Consult the Sub-suppliers
documentation manual in
Sub-suppliers documenta-
tion
O2 content low: 1 QIA-L 7001 Change in oxygen con- Re-adjust pressure by
tent may be the result means of pressure control
of changes in condi- valve (1071) in fuel oil
tions of ambient air return line.
(pressure, tempera-
ture, humidity) or a
result of a change in
fuel quality.
If generator delivery Re-adjust the generator
pressure is too high, delivery pressure
the air capacity supply
by the blower will be
too low to match the
fuel supply at the given
capacity position; as a
result the oxygen con-
tent will be too low.

Rev. 0 Date.12 SEP 2014 32


11215053R00

Failure CoF Safety Possible causes Remedies


O2 content high: 1 QIA-H 7001 Change in oxygen con- Re-adjust pressure by
tent may be the result means of pressure control
of changes in condi- valve (1071) in fuel oil
tions of ambient air return line.
(temperature, humidi-
ty) or a result of a
change in fuel quality.
If generator delivery Re-adjust the generator
pressure is too low, the delivery pressure
air capacity supply by
the blower will be too
high to match the fuel
supply at the given
capacity position; as a
result the oxygen con-
tent will be too high.
Oil nozzle dirty. Clean.
Deck main pressure 1 PICA-H 8008 Generator capacity to Decrease capacity.
high: high.
The excess gas vent Check correct functioning
system (6021) is not and setting.
functioning correctly.
Deck main pressure 6 PICA-L 8008 Generator capacity to Increase capacity.
low: low.
Bleed valve (6051) Close it.
open.
The excess gas vent Check correct functioning
system (6021) is not and setting.
functioning correctly.
Deck main pressure 5 PA-LL 8014 Capacity of generator Increase capacity.
low-low: insufficient to follow
cargo unloading. Gen-
erator capacity to low.
The excess gas vent Check correct functioning
system (6021) is not and setting.
functioning correctly.
Bleed valve (6051) not Close it.
closed.
Deck water seal wa- 6 LA-L 6104 Water supply too low. Check and increase.
ter level low: Drain valve open. Close it.
Deck water seal wa- 2 PZA-L 8075 Deck water seal water Check fuses, duty switch-
ter pressure low: supply pump not run- es etc.
ning.
Pump isolating Open it (them).
valve(s) closed.
Filter clogged. Clean it

Rev. 0 Date.12 SEP 2014 33


11215053R00

9 MAINTENANCE clean the combustion chamber will not be


drained correctly.
Before operating the unit, read the • Fig. 9.1 Flange 2350
SAFETY INSTRUCTIONS.

9.1 General maintenance


instructions
Next pages include the maintenance schedule
for the installation. The detailed instructions
for maintenance and repair of equipment can
be found in the instruction manuals of the sub-
suppliers. Consult the Sub-suppliers docu-
mentation.
KEEP THE VALVE + FILTER CLEAN
Because maintenance greatly depends on the AT ALL TIMES
operating conditions, the maintenance inter-
vals might have to be shortened or extended • Even stainless steel (especially welds) can
due to these conditions. corrode if it is exposed to non-flowing
This is to the operator’s experience. seawater for longer periods.

• Keep the electric power to the local control


In case of a longer stand still the instal- panel turned on to prolong the lifetime of
lation must be switched on each month the O2-sensor.
for approximately half an hour. To avoid
corrosion, valves being jammed, etc.
9.2.2 Rinsing the combustion cham-
9.2 Combustion chamber ber

9.2.1 Draining combustion chamber NEVER USE SALT WATER.

The combustion chamber should be drained


from seawater after every use. This done au- The combustion chamber of the generator
tomatically, but correct working of this system must be rinsed with fresh water after each stop
should be checked carefully. after stop the combustion is draining (automati-
cally) the sea water, and then starts the rinsing
IMPORTANT: with fresh water.
• In the lower side of the internal wall of the The fresh water is entered into the combustion
jacket of the combustion chamber there is chamber through valve 2340.
a valve with a small hole attached to a
flange (2351). Through this valve, the 9.3 Main burner
jacket of the combustion chamber is The burner cone is a wear and tear part.
drained during standstill. This draining is Therefore this cone must be checked periodi-
quick when valve is full open and slow in cally on damage to determine if replacement
case of failure of this valve (true small hole is necessary see drawing P-X00047
in disc). Check this valve and hole in disc
for. The jacket part for the sprayer does The life of the burner cone is strongly influ-
also need to be drained. This done via fil- enced by:
ter 2350. Also see “Rinsing the combus- − The quality of the fuel that is used
tion chamber” below. − The correct adjustment of the burner (no
• Always check that the filter attached to soot production).
flange 2350, (fig 9.1) and the hole in the
disc of valve 2351 is clean. If this is not To replace the cone the upper cover of the
combustion chamber must be removed:

Rev. 0 Date.12 SEP 2014 34


11215053R00

− Depressurise the combustion chamber and


all supplies. • Cooling water supply and discharge pipes,
− Disconnect all pipes to the main burner.
− Remove the cover by loosening the bolts.
− Take out the cone. 9.6 Coating
− Place the new cone.
− Reassemble in reverse order. Both the Deck Water Seal and the PV breaker
have a special coating on the inside. Both
Note: need regular inspection.
Mind the correct position for the hole for the
pilot burner. As the Deck Water Seal is filled with sea wa-
ter and there is a stainless steel heater in-
stalled there is a risk for galvanic corrosion.
9.4 Pilot burner For this reason an anode (6102) has been
installed. This anode should be inspected and
replaced if needed.

Fig. 9.2 Purge nozzle instrument air.

Always keep the 1.5 mm hole in the purge


nozzle (fig. 9.2-1) clean and open. This hole is
used for purging the UV detector (2121) and
the ignition transformer (2131).
Use a needle to un-block the hole.

9.5 Freezing prevention


In case the ambient temperature for the Inert
gas installation becomes below 0 °C and the
installation is out of service, attention must be
paid to the draining of the below mentioned
items.

From all these items the water (condense,


fresh water from rinsing) must be removed
and or drained.

• The combustion chamber and the scrub-


ber jacket. Normally these jackets will
drain automatically and if the maintenance
is carried out as indicated in the Mainte-
nance tables below, the jackets will be
empty.

Rev. 0 Date.12 SEP 2014 35


11215053R00

9.7 Maintenance tables 9.7.3 Annually

9.7.1 Before every start Component: Maintenance Remarks:


description
Component: Maintenance Remarks: Combustion Remove the
description chamber 2301 inspection lid
O2-analyser Check calibra- OEM manual on the cooling
QIA-7001 tion tower and
Fuel oil filter Rotate handle clean with
1002 twice solvent
Filter in O2 Check pollu- Replace if Demister Inspect from
measuring tion grade black colour 2307 bottom side
line (7022) instead of Water spray- Inspect and
white or if wet. ers, pipes clean if nec-
Filters in air Clean 2303 – 2306 essary.
pressure con- Deck water Check internal Replace an-
trol system seal coating ode 6102 if
(6004) and O2 needed
analyser lines Deck pres- Test alarm for Class re-
(7049/7050) sure low/low proper func- quirement:
Filter in in- Clean (8014) tioning clean sample
strument air line
lines (1502) Temperature Check the
& pressure calibration
9.7.2 Every 250-hrs gauges
Safety devic- Check correct See the set-
Component: Maintenance Remarks: es adjustment tings in the
description and functional test protocol.
Main burner Check cone Replace if operation
2001 on damage. necessary
9.7.4 After every stop
Fuel oil filter Drain sump
1002, 1052 Component: Maintenance Remarks:
Instrument air Disassemble description
filter 1502 and clean Combustion Rinse with DO NOT USE
Filters of Clean filter chamber 2301 fresh water. SALT WA-
pressure element TER!
regulators Filter 2350 Clean.
6004,6024,
7050
Filters 7022 Clean filter
element
9.8 Replacing the PLC battery

The PLC is almost maintenance free. There


are only a few points for maintenance.

Replacement battery of Mitsubishi PLC.


There are two plc types used with different
backup systems.

FX1N for cargo control room: no battery, only


EEPROM memory backup.

Rev. 0 Date.12 SEP 2014 36


11215053R00

FX3U for local panel: battery and EEPROM


memory backup.

The battery is maintenance free. It must be


replaced every 3 years. So make sure there
is a spare battery on board of the ship for
each CPU FX3U unit.

Actions:

- Replacement battery of FX1N

Nothing to do, because there is no battery to


replace.

7) Replacement battery of FX3U PLC.

Replacement to be done in 20 seconds, to


keep the ram memory intact. Some status
values can be lost, but will not effect the nor-
mal working of the PLC. The ram memory will
be reloaded from EEPROM, when the power
is back on.
The PLC starts then from the beginning with a
cold start and starts at the correct point in the
program.

1. Turn off the power supply to the PLC.


2. Remove left top cover of the PLC.
3. Remove battery from holder.
4. Disconnect the connector of battery.
5. Replace the battery.
6. Connect the connector of battery.
7. Refit the cover.
8. Turn on the power supply to the PLC.
9. Power and Run led should light up.
10. Check? Try lamp test. If all led light’s
up, then the program runs and the unit can
be started.
Batt.V led should be off. CPU led should
be off.

Rev. 0 Date.12 SEP 2014 37


11215053R00

9.9 Lubricating schedule

For lubricating instructions of the E-motors,


consult the instructions in the Sub-suppliers
documentation

Rev. 0 Date.12 SEP 2014 38


11215053R00

10 TEST PROTOCOL

List of documentation:

No. Doc. No. Title

1. Test report 11215 Test report for inert gas plant

Rev. 0 Date.12 SEP 2014 39


11215053R00

11 PROCESS DOCUMENTATION

List of documentation:

No. Dwg. No. Title

1) 11215PLR08 Parts list


2) 11215001R03 Schematic diagram I.G. generator
3) 11215004R02 I.G. delivery line
4) 11215025R02 Alarm & Safety Table
5) 65000A024R01 Codes/Symbols
6) 65010A052R04 Guidelines for installing supply and
discharge piping

Rev. 0 Date.12 SEP 2014 40


11215053R00

12 DIMENSIONAL DRAWINGS

List of documentation:

No. Dwg. No. Title

1) 11215299R01 Dimensions IG generator


2) 11215309R01 Dimensions Blower
3) 11215319R00 Dimensions FOP
4) 11215449R02 P/V breaker
5) 11215474R01 Deck seal
6) P-G00042 Maintenance Main Burner
7) P-000588 Maintenance Pilot Burner
8) P-X00082 Pilot burner Purge nozzle instrument air
9) P-X00047 Status burner cone
10) P-000599 Burner cone
11) P-000594 Demister holder

Rev. 0 Date.12 SEP 2014 41


11215053R00

13 ELECTRICAL DOCUMENTATION

List of documentation:

No. Dwg. No. Title

11215COMR02 Electrical drawings

Rev. 0 Date.12 SEP 2014 42


11215053R00

14 DOCUMENTATION

List of documentation:

Supplier Description

01. Alfa Laval Aalborg Nijme- - Mounting instructions doc. Nr. 65010A051R04
gen B.V.

02. Alfa Laval Aalborg Nijme- - Operation Guidelines doc. Nr. 65010A054R02
gen B.V.

03. Alfa Laval Aalborg Nijme- - Oxygen analyser AAL 7000_R03


gen B.V.

04. Besta - Besta level switches mounting and service instructions (APR 76)

05. Danfoss - Connection and operating instructions Plug-in Display


MBD 1000 (07-2007)
- MBD 1000 datasheet (08-2003)

06. Endress & Hauser - Operating Instructions FMD76 Differential pressure transmitter
(software version 02.11.zz)

07. Fluidics - Oil nozzle 24-5GOM-6K-E (11-11-09)

08. Giuliani Anello - Strainers, turners (rev. 00)

09. Honeywell - Minipeeper Ultraviolet flame detectors C7027A, C7035A, C7044A


(60-2026-01)
- Flame detector relay R 4343 D,E. (MU2C-0028SZ20 R1404)

10. HP TECHNIK - Oil Pump (KSN) (11-2004)

11. Maxon - Control valves (6-11)

12. PMA - Industrial controller Aalborg KS 50 (10-2007

13. Brainchild - CR06 brochure (rev. 00)


- Manual CR06 OCT. 2006 (2nd edition)

14. Rotodyne - Operating instructions for fan centrifugal type (rev. 01)

15. Marathon - Maintenance and installation procedures and re-greasing periods


(rev. 00)

16. SIEMENS - Sipart PS2 (09-2008)

17. WWE - Manual WWE Actuators

Rev. 0 Date.12 SEP 2014 43


11215053R00

Alfa Laval Aalborg Nijmegen B.V.


St. Hubertusstraat 10
6531 LB Nijmegen
P.O. Box 6664
6503 GD Nijmegen
The Netherlands
tel.: +31 (0)24 35 23 100
fax: +31 (0)24 35 64 995
E-mail: info.nijmegen@alfalval.com
Http://www.alfalaval.com

Rev. 0 Date.12 SEP 2014 44

Anda mungkin juga menyukai