Applicable Standards
Introduction
Kotsons Pvt. Ltd. in collaboration with E. I. DuPont, U.S.A. has developed Ventilated Dry Type transformers in
India with a DuPont ReliatraN® branded solution.
ReliatraN® Brand Transformers are manufactured with UL® Certified Insulation Materials and Systems, by a
network of ISO 9000 Certified Manufacturers worldwide, meeting the highest of International Standards for
Quality, Design, Construction and Performance.
Kotsons Pvt. Ltd. is the first and only Operating Licensed Manufacturer of DuPont's ReliatraN® Brand
Transformers in India.
Description
Kotsons manufactures Ventilated Dry Type transformer ranging from 40 KVA to 5000 KVA with voltage class of
33 KV. These transformers are fitted in Enclosure confirming to IP 21 to IP 33 for Indoor location and IP 45 for
out door location. Kotsons Ventilated Dry Type Transformer are totally maintenance free and safe from fire as
material used are metals, ceramics, fiberglass and resin. It is environment friendly as there is no oil, hence
handling becomes easier and there are no chances of spillages and leakages and there is minimal non toxic
smoke in case of fire.
Kotsons offers Ventilated Dry Type Transformers with Class H / C insulation which
can bear heat upto 180 / 220 Deg C and can be used in humid and chemically
polluted atmosphere.
Kotsons can supply Indoor/Outdoor, 3 phase, 50/60 Hz, Resin Impregnated, AN/FA
cooled, step up/step down, double wound with Cu conductor transformer from 40
KVA to 5000 KVA upto 33 KV Class with H / C Class Insulation and designed to
withstand Short Circuit, & Impulse Test in accordance to IEC / IS.
Core structure is of nonaging, Cold Rolled Grain Oriented, high permeability silicon
steel. All core laminations are free of burr and staked without gaps The core
assembly is painted with a protective paint to protect against corrosion.
Winding :
VPI:
Testing :
After the Core- Coil assembly. All transformers are tested for routine test. Kotsons has in house facilities for
conducting all routine tests as per IEC & IS. Kotsons is equipped with adequate digital readout measuring
devices wherever required and the digital sampling techniques with computer calculations. Precision digital
meters such as digital power analyser, WT -130 of Yokogawa make are used for measuring of load losses,
Impedance Voltage, No load losses, and no load currents. KPL is having in house Partial Discharge (PD) testing
facility.
Warranty :
• Class H & C ventilated dry type transformers can be built smaller, reducing the footprint to the
environment, conserving space.
End-of-Life Aspects
• NOMEX® insulation can be easily disposed of by incineration or burial, since it is inert to the
environment.
• NOMEX® insulated VDT transformers have low volumes of insulation, eliminating the burden of
disposal of large amounts of resin.
Quality :
KOTSONS PVT. LTD., is certified for ISO 9001:2000 by DET NORSKE VERITAS, B.V., NETHERLANDS. Kotsons
has set up a complete quality management system to offer the best customer satisfaction. Each and every
Ventilated Dry Type Transformer is identified with ReliatraN ® identification labels.
Kotsons makes Indoor/Outdoor, 3 phase, 50/60 Hz, Resin Impregnated, AN/FA cooled, step up/step down,
double wound with Cu conductor transformer from 40 KVA to 5000 KVA upto 33 KV Class with H / C Class
Insulation and designed to withstand Short Circuit, & Impulse Test in accordance to IEC / IS.
No Outline
Rating Load Total Total
Load Impedance Dimension (mm)
Sl.No. Loss Loss( Weight
Loss (%)
KVA KV (Watts) Watts) L W H (Kg)
(Watts)
11/0.
1 630 1725 6920 8645 5 1850 1200 1750 2520
433
11/0.
2 800 1920 7880 9800 5 1900 1200 1850 2855
433
11/0.
3 1000 2235 10145 12380 5 1950 1250 1950 3125
433
11/0.
4 1250 2630 12600 15230 5 1950 1250 2100 3520
433
11/0.
5 1600 3010 14765 17775 6.25 2050 1350 2250 4230
433
11/0.
6 2000 3540 18375 21915 6.25 2150 1450 2450 4940
433
11/0.
7 2500 4305 21260 25565 6.25 2250 1550 2550 5855
433
Note :
• The dimensions and weights shown above apply to a typical range of KST (Kotsons standard
transformers) design to the specification IS : 2026. As all transformers are usually design and built to
customers specification their exact dimensions and weights can vary.
• Due to improvements continuously taking place in design, the details given here may vary marginally
irrespective of Length, Width, Height and Total Weight . However the variations will be within
permissible tolerance limits as per IS 2026 latest.
ITEM
DESCRIPTION STANDARD OPTIONAL
No.
1. H.V. TERMINAL BUSBAR Yes No
2. L.V. TERMINAL BUSBAR Yes No
L.V. SEPERATE NEUTRAL EARTHING
3. No Yes
BUSHING
4. SEPERATOR NEUTRAL EARTH BUSBAR No Yes
5. OFF CIRCUIT TAPPING LINK BOARD Yes No
6. TAP LINK POSITION PLATE Yes No
ACCESS DOORS/WINDOWS FOR TAP
7. Yes No
CHANGING LINKS
8. VENTILATION LOUVERS Yes No
9. RAIN WATER GUARD Yes No
10. RATING AND DIAGRAM PLATE Yes No
LIFTING LUGS FOR TOP COVER & COMPLETE
11. Yes No
TRANSFORMER LIFTING
LIFTING HOLES FOR CORE-COIL ASSY.
12. Yes No
LIFTING
ENCLOSURE (DEGREE OF PROTACTION IP-
13. Yes No
21/23)
14. MARSHLING BO-- Yes No
15. PHASE C.T. Yes No
16. WINDING TEMPERATURE INDICATOR Yes No
17. SPACE HEATER No Yes
DETACHABLE H.V. CABLE GLAND PLATE
18. Yes No
WITH 1 KNOCKOUT
19. H.V. CABLE GLAND No Yes
20. H.V. CABLE LUG WITH INSIDE KNURLING No Yes
21. H.T. CABLE CLAMP Yes No
22. SURGE ARRESTER No Yes
23. SURGE ARRESTER GROUNDING BUSHING No Yes
24. SURGE ARRESTER GROUNDING BUSBAR No Yes
DETACHABLE L.V. CABLE GLAND PLATE
25. Yes No
WITH REQD. KNOCKOUTS
26. L.V. CABLE GLAND No Yes
27. L.V. CABLE LUG WITH INSIDE KNURLING No Yes
28. L.T. CABLE CLAMP Yes No
29. SKID UNDER BASE WITH HAULAGE HOLES Yes No
30. BI – DIRECTIONAL FLAT ROLLERS Yes No
31. BODY EARTHING TERMINALS Yes No
32. PHASE IDENTIFICATION PLATES Yes No
33. DANGER PLATES Yes No
34. H.V. CABLE BO-- No Yes
35. L.V. CABLE BO-- No Yes
36. L.V. BUSDUCT BO-- No Yes
37. Fans No Yes
38. OLTC, AVR, RTCC No Yes
NOTE:- OPTIONAL FEATURES ARE AVAILABLE ON BUYER'S REQUEST & AT EXTRA COST.