KUWAIT OIL COMPANY (K.S.C.

) Page No: 1 of 10
A Subsidiary of Kuwait Petroleum Corporation
Date: 2/3/2015
KOC Contract No: Project Title Company Doc No: Rev.

14050474 NEW GATHERING CENTRE, --- -


KOC Project No: GC-31, IN NORTH KUWAIT Contr.Doc No: Rev.

EF1903 050474-3108-DE10-DAT-0043 C
Contr.Job No: Document Title: KOC Doc No:(Provided at end of project) Rev.

50474
Mechanical Data Sheet for Wet Crude Storage Tank --- -
Facility No.: Equipment Description: Equipment Tag No
531-D-002
GC-31 Wet Crude Storage Tank

KUWAIT OIL COMPANY (K.S.C)

A. Approved/Reviewed
B. Approved/reviewed as Noted
Incorporate and Resubmit
C. Rejected-Resubmit
D. Information Reviewed

Approval by company related to the works shall in


no way relieve the Contractor from its obligation to
comply with the requirements of the Contract.

By Date

DOCUMENT TITLE
Mechanical Data Sheet for Wet Crude Storage Tank
EQUIPMENT TAG NO.

531-D-002

Contr.logo Contr. Name/Address

Dodsal Engineering & Construction Pte Ltd.


P.O.Box 8034, DNI Building, Sheikh Zayed Road, Dubai, UAE

C Issued for Client Approval SS MB NBR 2/3/2015

Re-issued as per API 650, Appendix-L format and for


B SS MB NBR 19/11/2014
Client Comments

A Issued for Client Comments. ASK MB NBR 28/09/2014

Rev. Description Prepared Checked Approved Date


Page No: 2 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation Date: 2/3/2015

Facility No. : Document Title Equipment Ta 531-D-002 Rev.

GC-31 Mechanical Data Sheet for Wet Crude Storage Tank Contr.Doc No: 050474-3108-DE10-DAT-0043 C

* For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. for all lines, see Appendix L for line-by-line instruction

GENERAL Special Documentation Package Requiements: NA _

Measurement Units to be Used in API Std 650: SI X US Customary

1 Manufacture TBD _ Contract No. _ TBD


Address TBD_
Mfg. Serial No. TBD Year Built TBD Edition & Addendum to API 650 12th. Edition March 2013, ERRATA July 2013

2 Purchaser: Dodsal Engineering & Construction Pte Ltd Contract No.: 50474

Address P.O.Box 8034, DNI Building, Sheikh Zayed Road, UAE

Tank Designation: Wet Crude Storage Tank Quantity: 1 No.

3 Owner/Operator Kuwait Oil Company (K.S.C.) Location: North Kuwait

4 Size Limitations 45,425mm ID Tank Diameter: 45,425mm ID Shell Height: 13,000 mm (Note-09)

Capacity: Maximum: 18,553 mᶟ Nominal Criteria 116,692 API BARRELS (Note-5)

5 Products Stored:

Liquid: LP Wet Crude Max. S.G.: 1.173 at 21 ˚C

Blanketing Gas Yes Vapor Pressure: bara at max. Operating Temp. 55 ˚C

% Aromatic: NA Suppl. Spec.: NA H₂ S Service? Yes X No Suppl. Spec. NACE MR0175 / ISO 15156

Other Special Service Conditions? Yes X No Suppl. Spec.: HIC (NACE TM0284)

DESIGN AND TESTING Purchaser to review Design Prior to Ordering Material? Yes X No

6 Applicable API Standard 650 Appendices: A B X E X F X G H I X J L X M O X P X S T X U V X W C

7 Max. Design. Temp. 93 ˚C Design Metal Temp. -3 ˚C Design Liquid Level 12,200 mm

Design Pressure: 254 mm WG(10 inWG)+liquid static head Ext. Pressure -38 mmWG (-1.5inWG) Max.Fill rate 2660 m³/hr(401600 BPD) Max.Emptying Rate 2660 m3/hr(401600 BPD)
C

Flotation Considerations? Yes No X Flot. Suppl. Spec: NA Applied Supplemental Load Spec. NA_

8 Seismic Design? Yes X No Appendix E X Alternate Seismic Criteria: Seismic Use Group One (I)

MBE Site Class "D" Vertical Seismic Design? Yes No Vertical Ground Motion Accelerator AV:

Basis of Lateral Acceleration (Select one): X Mapped Seismic Parameters? Ss0.598g S1 0.239g S0 ; Site-Specific Procedures: MCE

Design Required? Yes X No ; Other (Non-ASCE) Methods Per UBC, Vol.2:

X Freeboard Required for SUG I Design Roof Tie Rods @ Outer Ring?* Yes X No
9 Wind Velocity for non-U.S. sites, 50-yr. wind speed (3-sec. Gust)* 45m/s [However, Vendor's Wind design calculations shall be based on API:650,12th.Edition, Para: 5.2.1 (k)]

Top Wind Girder Style TBD Dimensions TBD Use Top Wind Girder as Walkway? Yes No X
Intermediate Wind Girders? Yes No Intermediate Wind Girder Style TBD Dimensions TBD

Check Buckling in Corroded Cond.? Yes X No

10 Shell Design: 1-Ft Mthd? Yes X No Variable-Des-Pt Mthd? Yes No X Alternate Elastic Anal. Mthd? Yes No X Alternate

Plate Stacking Criteria Centreline-Stacked? Yes X No Flush-Stacked? Yes No X Inside Outside

Plate Widths (Shell course heights) and Thicknesses * Numbers below Indicate Course Number.(Later)

1. 2. 3. 4. 5. _
6. 7. 8. 9. 10. _
11. 12. 13. 14. 15.
Joint Efficiency As per Spec./Code % Shell-to-Bottom Weld Type As per Spec./Code Shell-to-Bottom Weld Insp. Mthd WFMT

C
(TBD- To Be Determined or Later)
Page No: 3 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation Date: 2/3/2015

Facility No. : Document Title Equipment Tag 531-D-002 Rev.

GC-31 Mechanical Data Sheet for Wet Crude Storage Tank Contr.Doc No: 050474-3108-DE10-DAT-0043 C

* If box is blank, Manufacturer shall determine and submit as per Appendix L.

11 Fixed Roofs: Open Top? Yes No X (Note-23) C


Fixed Roof Type Cone Roof Support Columns: Pipe Or Structural Shape TBD
Cone Slope 1:6 Dome or Umbrella Radius NA Weld Joints Double Lap
(Lap, Butt, Other)
Seal Weld Underside of: Lap Joints? Yes X No Seal Weld Underside of Wind Girder Joints? Yes X No

Gas-tight? Yes X No Joint Efficiency* %

Thickness Later In Snow Load NA App. Suppl. Load Spec. NA Column Lateral Load NA

Normal Venting Devices NA Emergency Venting Devices As Per Spec./ Code

For Non-Frangible Roofs: Seal Weld Roof Plates to Top Angle on the Inside? Yes X No Weld Rafters to Roof Plates? Yes No X C

Roof-to-Shell Detail Deatail 'I' of Fig.F2 Radial Projection of Horizontal Component of Top Angle Inward Outward

12 Bottom: Thickness TBD Style Apex Up Slope 1 : 120 Weld Joint Type LAP _

Provide Drip ring? Yes X No Alternate Spec.

Provide Annular ring? Yes X No Annular Ring: Minimum Radial Width TBD Thickness TBD

13 Foundation: Furnished by Others Type Concrete Ring Wall ( Refer: EF1903-531-DD1-STD-0012.001 & KOC-C-026 ) C

Soil Allow: Bearing Pressure Later Per Spec. Later Anchors: Size TBD Qty. TBD

Foundation Design Loads: Base Shear Force: Wind TBD Seismic TBD Overturning Moment: Wind TBD Seismic TBD

Ring Forces: Weight of Shell + Roof New TBD Corroded TBD Roof Live Load TBD Internal Pressure TBD

Partial Vacuum TBD Wind TBD Seismic TBD

Bottom Forces: Floor Wt. New TBD Corroded TBD Product Wt. TBD Water Wt. TBD Internal Pressure TBD _

Partial Vacuum TBD Other Foundation Loads TBD Min. Projection of Fdn. Above Grade: TBD

14 Responsibility for Heating Water, if Required: NA Purchaser Manufacturer

Hydro-Test Fill Height* Per API:650, Para:7.3.5 Settlement Measurements Required? Yes X No Extended Duration of Hydro-Test: Per API:650

Predicted Settlement Profile is Attached

Responsibility for Setting Water Quality: Purchaser Manufacturer X Supplemental Test Water Quality Spec. KOC-G-011

Test Water Source & Disposal Tie-In Locations: KOC-G-011 Hydro-Test Appendix J Tank? Yes No

Post-Pressure-Test Activities Required of the Manufacturer: Broom Clean Potable Water Rinse Dry Interior
Other

15 Inspection by AL / DODSAL / Company in Shop; AL / DODSAL / Company in Field

Supplemental NDE Responsibility Weld Hardness Testing -By Tank Manufacturer Supplemental NDE Spec. KOC-MV-007
(Purch., Mfg., Other)
Positive Material Identification? Yes X No PMI Requirements: As per Specification
Max. Plate Thickness for Shearing: TBD
Must Welds not exceeding 6 mm (1/4 in.) Be Multi-Pass? Yes No Must Welds greater than 6 mm (1/4 in.) Be Multi-Pass? Yes X No
Leak Test Mthd: Roof As per Spec./Code Shell Water Test. Shell Noz./Manhole Reinf. Plt Air Test. C
Bottom Vacuum Box Floating Roof Components* NA
Modify or Waive API Dimensional Tolerances (see 7.5)? No X Yes Specify:
- Allowable Plumbness: Measure and Record at a Minimum of Locations or Every m (ft) around the Tank, at
the Following Shell Heights: (select one box): 1/3 H, 2/3 H and H Top of Each Shell Course Other:
- Allowable Roundness:** Measure Radius and Record at a Minimum of Locations or Every m (ft)

around the Tank, at the Following Shell Heights (select one box):
Top of Tank, H 1/3 H, 2/3 H and H Top of Each Shell Course Other:
**See Data Sheet Instructions for the Maximum Allowable Additional Radial Tolerance.
Page N 4 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation
Date: 2/3/2015

Facility No. : Document Title Equipment Ta 531-D-002 Rev.


Contr.Doc
GC-31 Mechanical Data Sheet for Wet Crude Storage Tank No: 050474-3108-DE10-DAT-0043 C

16 Coatings:
Internal Coatings by: Tank Manufacturer ( See Note: 2 & 7 on Page:10) Per Spec. KOC-P-002 Part 2 C
(Not Req'd., Others, Tank Mfg.)
External Coating by: Tank Manufacturer Per Spec. KOC-P-001(App.2 & 3, System A1-1) C
(Not Req'd., Others, Tank Mfg.)
Under-Bottom Coating by: Tank Manufacturer (Note-11) Per Spec. KOC-P-002 Part 2 C

(Not Req'd., Others, Tank Mfg.)

17 Cathodic Protection System? Yes X No As per Spec. KOC-L-018 ,KOC-L-026 & EF1903-531-DFO-SCH- C

18 Leak Detection System? Yes X No As per Spec./ Code

19 Release Prevention Barrier? Yes X No As per Spec./ Code


X
20 Tank Measurement System: Required? Yes No Remote Capability Required? Yes X No
By: CONTRACTOR Per Spec. As per Spec. / Code

21 Weight of Tank: Full of Water TBD Empty TBD Shipping TBD Brace/Lift Spec. NA _

22 References: API Std 650, Appendix L


_
23 Tank Venting Data: C

Max. Inbreathing rate = 9522 (8.53) Nm3/hr (MM SCFD) C

Max. Outbreathing rate = 36255 (32.5) Nm3/hr (MM SCFD) C

Emergency Relief = 7236 (6.5) Nm3/hr (MM SCFD) C

Max. Relieving temperature = 100 °C C

24 Set Pressure of PVRV is 250mm WG pressure and 25mm WG Vacuum. C


Page No: 5 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation
Date: 2/3/2015

Facility No. : Document Title Equipment Tag 531-D-002 Rev.

GC-31 Mechanical Data Sheet for Wet Crude Storage Tank Contr.Doc No: 050474-3108-DE10-DAT-0043 C
* For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. For all lines, see Appendix L for line-by-line instruction.

Table 1 MATERIALS OF CONSTRUCTION

Component Material /Thickness C.A. Component Material C.A.

Shell, Course to A-516 Gr.60N / Later 1.6mm Reinforcing Pads A-516 Gr.60N (Shell) / A-283 Gr.C (Roof) 1.6mm
A-516 Gr.60N (Shell) / A-283 Gr.C (Roof)/ A 106
Shell, Course to A-516 Gr.60N / Later 1.6mm Manhole/Nozzle Necks 1.6mm
Gr.B (Normalized)
A-516 Gr.60N (Shell) / A-283 Gr.C (Roof)/ A 105
Shell, Course to A-516 Gr.60N / Later 1.6mm Manhole/Cover / Nozzle Flanges 1.6mm
(Normalized)
Shell, Course to A-516 Gr.60N / Later 1.6mm Cleanout Door Covers A-516 Gr.60N 1.6mm
Lowest Shell Course upto
600mm from Bottom
A-516 Gr.60N + FGR Lining / Later 1.6mm Anchor Attachments A-516 Gr.60N 1.6mm

Roof A-283 Gr.C / Later 1.6mm All internal piping / Fittings A 106 Gr.B / A 234 Gr.WPB N/A
Bottom A-516 Gr.60N / Later 3 mm Wetted Structurals Same as shell 1.6mm+
Annular Ring A-516 Gr.60N / Later 3 mm Non-wetted Structurals Carbon steel and Lining / By Manufacturer 1.6mm+
Gasket Compressed Non-Asbestos Fibre (ARAMID / GLASS FIBRE)

Note: All Carbon steel material for internal wetted service shall be in accordance with NACE MR0175 / IS 15156. + Check here if C.A. is to apply to each exposed surface X
Table 2 BOLTS and ANCHORS

Component Head Type* Bolt or Anchor Material* Nut Material* Thread Series* C.A.

Flange Bolting TBD SA 193 Gr.B7 SA 194 Gr.2H As per Spec. 1.6mm+ +
Structural Bolting TBD SA 193 Gr.B7 SA 194 Gr.2H As per Spec. 1.6mm+ +
Anchor Bolts TBD SA 193 Gr.B7 SA 194 Gr.2H As per Spec. 1.6mm+ +
Internal Bolting TBD SA 193 Gr.B8MA CL.1A SA 194 Gr. 8MA As per Spec. 1.6mm+ +
++ Total C.A., on the nominal diameter. - Anchor Bolts shall be Galvanized C
Table 3 NOZZLE and MANHOLE SCHEDULE* (for Fixed Roof, Shell, and Bottom)
Full Gasket
Gasket Gasket Mat'l
Size, NPS, or Neck Sch or Reinf. Plate Pen. On Flange Bearing Surf. Proj. to FF or CL or
Mark Service Flange Std./ Rating Thick. and
Dia. (in.) Wall Thick. Dimensions Open. Type Dimen. and from Datum Lines
and Dimen. Descript.
(Y/N) Finish
SHELL / BOTTOM
M1 A/B/C Shell Manway 24 API 650
M3 A/B/C Cleanout Doors 36X48 API 650
N1 Wet Crude Intlet 36 WNRF ASME B16.47(A) / 150#
Wet Crude Outlet
N3 (with ID cruciform 24 SORF ASME B16.5 / 150# C
collector)
Effluent Water
N5 Outlet (with vortex 30 WNRF ASME B16.47(A) / 150# C
breaker)
N6 A-C Drain 6 SORF ASME B16.5 / 150#
As per API 650 As per API 650
N7 A-D Foam Pourer 4* SORF ASME B16.5 / 150#

N9 A-E Sample Connection 2 SORF ASME B16.5 / 150#

N10 A/B/C Utility Connection 3 SORF ASME B16.5 / 150#

N14 Spare 8 SORF ASME B16.5 / 150#


Wet Crude Pump
N16 out (with vortex 12 SORF ASME B16.5 / 150# C
breaker)
Future liquid feed
N20 inlet 14 SORF ASME B16.5 / 150# C
SHELL INSTRUMENT CONNECTIONS
J1 A/B LDIT / LDALL 2 SORF ASME B16.5 / 300#
J2 A/B LIT / LALL 2 SORF ASME B16.5 / 300#
J3 A-F LIT / LAHH 2 SORF ASME B16.5 / 300#
J4 A-H LIT / LIC 2 SORF ASME B16.5 / 300# C
J5 A/B LDIT / LDIC 2 SORF ASME B16.5 / 300#
J6 A-D LDG 2 As per API 650 As per API 650 SORF ASME B16.5 / 300#
J7A-C TW/ TG 2 SORF ASME B16.5 / 300#
J10 A/B LDIT / LDAH 2 SORF ASME B16.5 / 300#
J11 A-N LG 2 SORF ASME B16.5 / 300#
J12 TW / TG / TI 2 SORF ASME B16.5 / 300#
J13 A/B LALL 2 SORF ASME B16.5 / 300# C
FIXED ROOF
M2 A/B Roof Manway 24 API 650
N2 Vapour Inlet Feed 30 WNRF ASME B16.47(A) / 150#
N4 Vapour Outlet 24 SORF ASME B16.5 / 150#

N8 A/B Dip Pipe 6 SORF ASME B16.5 / 150#


As per API 650 As per API 650
N11 Vent 6 SORF ASME B16.5 / 150#
Pressure Relief /
N12 A-D 12 * SORF ASME B16.5 / 150#
Vacuum Breaker
N15 Blanket Gas 10 SORF ASME B16.5 / 150#

N19 Spare 3 SORF ASME B16.5 / 150#

ROOF INSTRUMENTS
J8 A/B PI T/ PG 2 SORF ASME B16.5 / 300#
As per API 650 As per API 650
J9 A/B PI T/ PG 2 SORF ASME B16.5 / 300#

* Quantity and sizing to be under 'HOLD'


Page N 6 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation Date: 2/3/2015

Facility No. : Document Title Equipment Ta 531-D-002 Rev.

GC-31 Mechanical Data Sheet for Wet Crude Storage Tank 050474-3108-DE10-DAT-0043 C
Contr.Doc
No:

* If box is blank, Manufacturer shall determine and submit as per Appendix L.

OTHER TANK APPURTENANCES

24 Platform, Stairway, and Railing: Galvanizing Req'd? Yes X No Stairway Style Helical Walk Surf. Type TBD
Access to the tanks to be provided by others. (Straight or Helical)
Stair and Walkway Clear Width 1000mm (min.) National Safety Standards Later
Architectural/Structural Specification As per Spec. (KOC-C-002)

Gauger's Platform Req'd? Yes X No Qty. Req'd TBD Per Spec. -

25 Jacket Required?* Yes No X Other Heaters/Coolers Required?* Yes No X

Supplemental Jacket, Heater, or Cooler Specificatio ns* _ N/A


26 Mixer/Agitator: Quantity NA Size* NA Per Spec.* _ NA
27 Insulation: Required? Yes No X Thickness* NA Material* NA _
Per Specs* NA Responsibility for Insulation and Installation: NA
(Purchaser, Manufacturer, Others)
28 Structural Attachments: Lift Lugs?* Yes No X Description NA _

Shell Anchorage? Yes X No Type LUGS Scaffold Cable Support? Yes No TBA

29 Various Other Items: Welded Flush-Type: Shell Connection X Cleanou t Fitting X Waive Application of Appendix P? Yes No X

Miscellany #1 Miscellany #2 _
Miscellany #3 Miscellany #4 _
Miscellany #5 Miscellany #6 _

Tabl e 4 OTHER TAN K APPURTENANCES*


Service or
Mark Quantity Size Orientation Height from Datum Material Remarks
Description

Ladder TBD

PVRV TBD

Foam Pourer TBD


Page No: 7 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation Date: 2/3/2015

Facility No. : Document Title Equipment Tag No 531-D-002 Rev.

GC-31 Mechanical Data Sheet for Wet Crude Storage Tank Contr.Doc No: 050474-3108-DE10-DAT-0043 C

* For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. For all lines, see Appendix L for line-by-line instructions.

FLOATING ROOF DATA

30 Floating Roof Selection


Design Basis: Appendix C Or Appendix H

Type of Roof: (External or Internal): Single Deck Pontoon* Double Deck*

(Internal Only): Tubular Pontoon* Metallic Sandwich Panel*

Other Supplemental Spec.:


31 Seals
Primary Seal: Shoe Envelope Wiper/Compression Plate Other Supplemental Spec.:
Shoe Mechanism: Mfg. Std. Other
Electrically Isolate Mechanism from Shoes? Yes No Wax Scrapers Required? Yes No

Minimum Shoe Thickness* Carbon Steel Shoes to be Galvanized? Yes No

Secondary Seal: Shoe Envelope Wiper None Other Supplemental Spec.:

32 Data for All Floating Roofs:

Overflow Openings in Shell Acceptable? Yes No Shell Extension? Yes No

Roof-Drain Check Valves Required? Yes No Roof-Drain Isolation Valves Required Yes No

Freeze Protection for Roof Drains Required? No Yes Supplemental Requirements:

Roof-Drain Piping to External Nozzles: Mfg. Std. Armored Flexible Pipe Swivels in Rigid Pipe Other

Foam Dam? Yes No Supplemental Spec.:

Minimum Deck Thickness*

Bulkhead Top Edges to be Liquid-Tight? Yes No Seal-Weld Underside of Roof? Yes No

Electrical Bonding: Shunts: Yes No Cables: Yes No Supplemental Spec.:


Qty. of Non-Guide-Pole Gauge Wells Required Qty. of Sample Hatches Required
Guide Pole for Gauging? Yes No Slots in Guide Pole? Yes No Datum Plates? Yes No Striking Plates? Yes No

Guide Pole Emissions-Limiting Devices: Sliding Cover Pole Wiper Pole Sleeve Float Float Wiper Pole Cap

Qty. of Roof Manholes* Minimum High-Roof Clearance Above Bottom:

Removable Leg Storage Racks? Yes No Leg Sleeves or Fixed Low Legs

33 Additional Data for External Floating Roofs:


Weather Shield? Yes No Supplemental Spec.:

Rolling Ladder Required? Yes No Field Adjustable Legs? Yes No

Design Rainfall Intensity in./hr. (mm/hr) Based on a Minute Duration Associated with the Storm

Design Accumulated 24-Hour Rainfall in. Based on the Storm

Distortion and Stability Determinations Required? Yes No Supplemental Specification

Landed Live Load* _


Page No: 8 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation
Date: 2/3/2015

Facility No. : Document Title Equipment Tag 531-D-002 Rev.

GC-31 Mechanical Data Sheet for Wet Crude Storage Tank Contr.Doc No: 050474-3108-DE10-DAT-0043 C

* For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. For all lines, see Appendix L for line-by-line instructions.

34 Additional Data for Internal Floating Roofs:

Two-Position Legs? Yes No Cable-Supported Roof? Yes No Fixed-Roof Insp. Hatches Required? Yes No

Internal Roof Drain Required? Yes No Omit Distribution Pads Supporting Uniform Live Loads? es No

Corrosion Gauge Required? Yes No Fixed Ladder Required? Yes No Type of Roof Vent:*

Modified Minimum Point Load? Yes No Supplemental Specification

Mfr. To Leak Test* % of Compartments in Assembly Yard in Erected Position Unknown; see separate contract terms

Roof Erector's Flotation Test: w/ Tank Hydro at Completion of Roof at a Later Date Not Required

Flotation Test Media: Water Product (see H.6.6.1) Potable


Water Quality: Other See Supplemental Spec.
Flotation Test: Duration Fill Height: _
Flotation Test Items Provided by Purchaser (see H.6.7): None List Attached

Responsible Party for Inspecting Roof During Initial Fill: Purchaser Other

Table 5 FLOATING ROOF MATERIALS

Component Material*/Thickness* C.A./Coating* Component Material*/Thickness* C.A./Coating*

Deck Plate Datum Plate

Inner Rim Plate Tubular Pontoon


Outer Rim Plate Pontoon Bulkhead
Foam Dam Submerged Pipe
Sandwich Panel Face Plate Guide Pole

Sandwich Panel Core Secondary Seal

Gauge Well Secondary Seal Fabric


Drain Sumps Wiper Tip
Opening Sleeves Wax Scraper

Floating Suction Lines Weather Seal


Primary Fabric Seal Envelope Fabric

Foam Log Core Shoe Mechanisms

Landing Legs Primary Seal Shoe

Landing Leg Bottom Pads Removable Covers

Manhole Necks Rolling Ladder

Vents Inlet Diffusers


Facility No. :
Sketch:

* For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. For all lines, see Appendix L for line-by-line instructions.
M2 N8 J8 N12 J9

GC-31
N15 N4 N20 N2
A/B A/B A/B A-D CYLINDRICAL A/B
GAS DOME
DRIP PAN C /W NON-SLIP BAR TREADS VERTICAL LADDER & PLATFORM
FULL PERIPHERAL 2000 Ø x 1800 H
2" NOZZLE FOR ROOF ACCESS (FOR SAFETY & INSTRUMENT
HANDRAIL AWAY FROM TANK RIM ACCESS)
N11
6

Document Title
SPIRAL 1
STAIRWAY

Mechanical Data Sheet for Wet Crude Storage Tank


TOP OF SHELL

WIND STIFFENER
N7 HLL +11110 mm (36'-5")

KUWAIT OIL COMPANY (K.S.C.)


A-D

A Subsidiary of Kuwait Petroleum Corporation


CONICAL ROOF WITH J7
SUPPORT STRUCTURE A-C
J3
A-F EL+7880
N3
EL+ 5500
J2 N16
A/B COLLECTION J12
HEADER
N9 J5
FULL DIAMETER
A-E A/B
COLLECTOR
EL+5100
J6 N21

1 30 00 mm ( 42' - 8" )
A-D INTERFACE
HHILL +4800 mm (15'-9")
J 11 HILL +4300 mm (14' -1")
A-N NILL +3300 mm (10' -10")
LILL +2300 mm (7'-7") DISTRIBUTOR J10
LLILL +1800 mm (5'-11") ACROSS FULL A/B
J 13
CROSS SECTIONAL
A/B
AREA OF TANK N10
J1 A-C
A/B
EL+3000
N1
J 4A-
H

No:
Contr.Doc
Equipment Ta

Date:

Page N
EL+725 N14
INTERNAL PIPEWORK
N5 SUPPORTS
EL+800
N19

2/3/2015
N6 VORTEX BREAKER

9 of 10
A-C TYPICAL TOP OF BASE EL 0.00

050474-3108-DE10-DAT-0043
1 1
120 120
CONE UP BASE ICCP ANODES EQUI -SPACED 3- EARTHING LUGS

531-D-002
SUMP TO FIG 5.21 REQUIRED OVER BASEPLATE EQUI-SPACED
API650 M3 M1
A/B/C A/B/C
45425 mm (149'-0") INSIDE DIAMETER

Rev.
C
Page No: 10 of 10
KUWAIT OIL COMPANY (K.S.C.)
A Subsidiary of Kuwait Petroleum Corporation
Date: 2/3/2015

Facility No. : Document Title Equipment Tag No 531-D-002 Rev.

GC-31 Mechanical Data Sheet for Wet Crude Storage Tank Contr.Doc No: 050474-3108-DE10-DAT-0043 C

* For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. For all lines, see Appendix L for line-by-line instructions.

NOTES:

1.) Design, construction, material, Inspection and testing of the tank shall be in accordance with API 650 12th Edition March 2013,ERRATA july 2013

and project specification KOC-MV-007 Rev. 1. 'Field Erected Storage Tanks"

2.) Internal Lining - Entire tank floor bottom + 0.6 metres of the lower internal shell shall be lined with fibreglass (FGRL), internal shell 0.6 up to 5 m

shall be lined with Glass Flake (GF) and the remainder of the internal shell shall be lined with Phenolic Epoxy (PE/HBE). The internal roof plate &

truss shall be coated with Phenolic Epoxy (PE) in accordance with the requirements of KOC-P-002 Part 2, Table I. All nozzle & internal piping

shall be coated as per KOC-P-002 Part 2 (table 1-page 7 of 43). Internal piping shall be coated for external & Internal surface. C

3.) Wet Crude Storage Tank shall be designed to achieve efficient oil / water separation. The design of the internal wet crude distribution pipe and water/

oil outlet colletion headers shall maximise the efficiency of the separation process.

4.) LP Fuel Gas contains 1,000 ppm of H2S (by vol.) and 20,000 ppm of CO2 (by vol.). Process fluids also contains H2S. Materials to be in accordance

with NACE MRO175 / ISO 15156, suitable for 6.9 mol% H2S in the gas phase, 0.1 mol% H2S in the liquid phase, pH 4.1 C

5.) Maximum Tank Capacity 116,692 BBLS is measured from Base of Tank to HHLL. The net working capacity between HHLL and LLILL is for the

sum of 3 hours water flow,6 hours oil flow(disengagement zone), 3 hours oil flow plus 1 hour of oil Ullage plus 10% margin. Total oil flow rate plus

recycle is 155,600 BOPD and total water flow rate is 246000 BWPD.

6.) Total inbreathing rate is calculated considering vacuum relief due to: Liquid pump out + Thermal inbreathing. Total out breathing rate is calculated

considering pressure relief due to: Liquid pump in + Thermal out breathing + Blanketing Gas PCV failure case. [Refer. API 2000]

7.) High Build Phenolic Epoxy (HBE) shall be used instead of Coal Tar Epoxy for internal paint system to KOC-P-002 PT 2.

8.) Roof to shell joint shall be as per Detail “i” of API 650, Fig. F-2

9.) Underside of roof truss shall be above HHLL. Tank shell height shall be increased to suit the depth of roof truss and to accommodate the

“Freeboard Allowance” calculated in accordance with para E.7.2 of API 650 in order to permit “sloshing” requirements as required for seismic

design in accordance with Appendix ‘E’ of API 650

10.) N20 is an Inlet liquid feed nozzle for future use and is anticipated to be located at an elevation of 5100 mm above tank bottom. Future inlet feed C

distributor at N20 is not required to be supplied with the tank but provision is to be made for its support

11.) The tank bottom underside (soil side) shall be blast cleaned & coated with minimum of 350 microns thickness High Build Epoxy

12.) Small bore nozzles lesser than or equal to 2” NB which require internal lining shall be supplied in solid Inconel 625.

13.) Wind load shall be calculated with 45m/sec corresponding to 3 sec gust at 10m height above ground and the applicable design code shall be

ASCE 7-05 or BS CP 3 chapter V.

14.) Vendor shall supply all internals such as Dip pipe, vortex breaker and pipe supports.

15.) Nozzle standout must project beyond the platform to provided access between top of platform grating and back of nozzle flange. Space must

provide adequate clearance for tightening flange bolting.

16.) Nozzle load shall be considered for the nozzles as per the cl. 8.13 of KOC specification KOC-MV-007 Rev. 1.

17.) Deleted C

18.) Internal coating of fixed roof crude tanks on exclusively dry service is required pyrophoric scaling

19.) All plates in excess of 19mm thickness for shell, annular ring, nozzle and manway neck, anchors and reinforcement shall be suject to impact

testing (Refer. KOC-MV-007 Cl.7.7)

20.) Parameters used here is taken from Winter Design Case HMBD. For maximum temperature, summer design case is considered.

21.) Normal Residence time is from (NLL to Bottom nozzle) is 3.6 hrs for Wet Service, 11.2 hrs for Dry Service and 4 hrs for Effluent Water service.
Surge time is from NLL to HLL is 3.1 hrs for Wet Service, 11 hrs for Dry Service and 1.5 hrs for EW service.

22.) Performance Guarantee : Water in Oil - max 10% vol/vol; Oil in Water - max 20ppm vol. The design of the internal wet crude distribution pipe

and water / Oil outlet collection headers shall maximise the efficiency of the separation process.

23.) Minimum roof live load 25 lb/ft2; Roof Air Test pressure 318 mm WG C