attenuation. However due to geometrical structure of GIS and
Abstract— One of the primary requirements in the planning and the enclosure material, skin losses are usually neglected [3].
design of the power system is reliability. The major cause of power Very fast electromagnetic transients caused by switching
system interruption is due to insulation failure resulting from over operations in gas insulated substations (GIS) cannot be
voltages in the power system. The objective of this paper is to calculated if conventional techniques of modeling and
simulate an EHV-GIS substation and to study what is effect of the
simulations are used. Choice and adjustments of the most
generated VFT (very fast transient) in EHV-GIS system. The
system has been modeled and simulated using PSCAD 4.2.1. suitable models as well as determinations of their limitations
in digital simulations of very fast transients in GIS are very
important. Results obtained from very extensive field tests as
I. INTRODUCTION well as from digital simulations for different types of GIS
have been used for development of more accurate models for
Gas insulated substations (GIS) have found an increasingly GIS components and GIS as whole. A comparison between
wide range of application during the last three decades field test and calculation results enables development of a
because of their remarkable advantages over their model which takes into account the most decisive physical
conventional counterparts. These advantages include phenomena inherent to the very fast transients in the GIS.
compactness, freedom from environmental influences, high Modeling can be divided into different parts which as a whole
reliability and minimum maintenance, excellent protection make the complete system [2] - [6]. Equivalent circuits of
against atmospheric over voltages and flexibility in choice of various GIS components have been given in Table I. Busbar
arrangement and for future expansion. The development of can be modeled as the lossless distributed parameter
GIS technology has made it competitive and, in many cases, transmission line with an impedance of 95 ȍ. Spacer can be
preferable in techno- economic comparison with the open-air represented by a capacitance of value exceeding 20 pF. For
type substation. In spite of these merits, GIS has its unique elbows a capacitor of value 6 pF can be used. The modeling of
problems, among which is the susceptibility of the insulation closed switch and disconnector can be done using distributed
system under very fast transients (VFT) caused by parameter lines with surge impedance of 42 ȍ has been used.
disconnector operation [1]. Open disconnector is represented by a capacitor of value 4 pF.
Bushing has been modeled using a short transmission line in
For accurate and reliable study of the transients it is essential series with a capacitor. The surge impedance of the line is 126
to replicate the system corresponding to frequency range in ȍ and capacitor has been taken of any value greater than 10
which transients occur. Very fast transients belong to highest pF. A fixed resistance in series with a variable resistance
frequency range. This means that the model used should be represents the modeling of spark resistance. Capacitive
suitable for the frequencies 100 kHz to 50 MHz [2]. Main voltage transformer is represented by a capacitor. Aerial line
subject of very fast transients are effects in Gas insulated is modeled using the surge impedance of line.
substations (GIS). Modeling and effects of GIS are therefore
main subjects of this paper. This paper summarizes the results III. SIMULATION STUDY OF EHV-GIS SUBSTATION
obtained with the help of computer simulation.
For the purpose of modeling and simulation a 420KV GIS has
II. MODELLING OF EHV-GIS SUBSTATION been taken. It consists of one incoming line feeder bay and
one outgoing feeder with transformer. Block diagram of this
The quality of the simulation depends on the quality of the system is shown in Fig.1. The system used consists of a
model of each individual GIS component. In order to achieve double bus bar with sectionalizers. According to their internal
reasonable results even for longer time periods of some micro- design all parts of GIS has been represented thoroughly by
seconds or for very complex GIS structures highly accurate line sections with the corresponding surge impedance and
models for each of the internal equipment and also for traveling time and by lumped capacitance for spacers and
components connected to the GIS are necessary. Due to additional capacitance caused by shielding devices [5]. The
traveling wave nature of VFT, modeling of GIS components behavior of the spark in the disconnect switch during closing
make use of electrical equivalent circuits composed of lumped operation is represented by a fixed resistance of Rf =0.5 ohm
elements and distributed parameters lines. At very high in series with an exponentially decreasing resistance R=R0e-t/T,
frequencies, the skin losses can produce a noticeable R0 = 1012 and T=1 ns resulting in a time duration of voltage
breakdown of about 10 ns. After the successful modeling of
Amit Kumar (e-mail: amitthakur13@gmail.com) and Mahesk K. the GIS substations voltages are measured at different points
Mishra (e-mail: mahesh@ee.iitm.ac.in) are with the department of Electrical as Em1 to Em5. Em1 shows the voltage stress at connection
Engineering, Indian Institute of Technology Madras, Chennai, India.
13
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008
inside the transformer between bushing and transformer Em2, Em3, Em4, and Em5. These points have been shown in
winding. Em2 shows the high frequency oscillations at the appendix B.
GIS side of transformer bushing. Em3 shows the voltage
oscillations at the end of busbar ss2. Em4 shows the voltage at Incoming Line
oscillations at busbar ss1 and Em5 shows the voltage
oscillations in the transformer feeder at the end of closed
disconnector. This system has been modeled using the Gas to ai r
electromagnetic transient program PSCAD 4.2.1 and will be Bushing
used for the further study. The actual simulated system has
been given in Appendix A.
DS
TABLE I DS- Disconnector
EQUIVALENT CIRCUIT OF GIS COMPONENTS
Component Equivalent Notes CB-Circuit Breaker
circuit CB
Bus bar Loss free distributed
parameter transmission line
of Z=95 ohm
Spacer C > 20 pF DS DS DS
Elbows C= 6pF
Surge arrester
DS
IV. RESULTS
Simulation results of the VFT studies have been taken in three
different cases. The time step for simulation is 0.01ms In case Transformer Gas to oil
1, normal lengths of the system given in appendix A have Load
Bushing
been used, In case 2, the length of busbar has been changed to
the double of the given length and In case 3, lengths of the
disconnector and bushing have been changed.
Fig. 1. Block diagram of the system used for the simulation
Case 1: There are five points at which VFT over voltages have
been measured. These VFT Over voltages are given by Em1,
14
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008
Fig. 4 (a). VFT over voltage Em3 Fig. 6 (b). Enlarged version of the VFT over voltage Em5
15
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008
16
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008
15-16 -- -- 4 11-E -- -- 12
16-17 0.30 42 --
17-18 0.65 95 --
18-19 0.40 42 --
19-20 1.10 42 -- A. 3- Details of simulation data for transformer feeder
20-21 0.30 95 -- Branc
21-22 0.70 95 -- Length Z (ȍ) C (pF)
h
22-23 1.10 66 -- 1-2 1.20 95 --
23-24 1.15 66 -- 2-3 0.75 42 --
24-25 0.70 95 -- 3-4 0.15 42 --
8-25 2.30 95 -- 4-5 0.30 42 --
17-26 0.80 95 -- 5-6 0.45 95 --
26-27 0.90 72 -- 6-7 0.45 95 --
7-8 0.15 42 --
27-28 0.80 95 --
7-9 0.75 42 --
28-29 0.90 95 --
9-10 -- -- 4
29-30 1.50 95 -- 10-11 0.30 42 --
30-31 0.80 95 -- 11-12 1.10 95 --
31-32 0.60 95 -- 12-13 1.15 95 --
32-33 0.60 25 -- 13-14 1.20 95 --
31-34 11 25 -- 13-15 0.75 42 --
34-35* 2.30 126 -- 15-16* -- -- 4
2-E -- -- 10 16-17 0.30 42 --
17-18 0.65 95 --
5-E -- -- 14
18-19 0.40 42 --
6-E -- -- 10
19-20 1.10 42 --
8-E -- -- 10 20-21 0.30 95 --
11-E -- -- 24 21-22 0.70 95 --
13-E -- -- 10 22-23 1.10 66 --
17-E -- -- 10 23-24 1.15 66 --
22-E -- -- 10 24-25 0.70 95 --
23-E -- -- 32 8-25 2.30 95 --
24-E -- -- 32 17-26 0.80 95 --
26-27 0.90 72 --
25-E -- -- 32
27-28 0.60 95 --
26-E -- -- 10
28-29 0.60 25 --
27-E -- -- 10 27-30 4 95 --
28-E -- -- 16 30-31 0.15 95 --
29-E -- -- 10 31-32 0.1.5 95 --
30-E -- -- 10 32-33** 4.9 95 --
31-E -- -- 10 2-E -- -- 10
33-E -- -- 10 5-E -- -- 14
34-E -- -- 14 6-E -- -- 10
8-E -- -- 10
11-E -- -- 24
(*) special bushing arrangement 17-E -- -- 10
A. 2- Details of simulation data for busbar 21-E -- -- 10
Branch Length Z (ȍ) C(pF) 22-E -- -- 10
1-2 1.8 157 -- 23-E -- -- 32
2-3 2.7 157 -- 24-E -- -- 32
3-4 5.6 157 -- 25-E -- -- 32
4-5 0.90 157 -- 26-E -- -- 10
5-6 0.85 104 -- 27-E -- -- 10
6-7 0.15 104 -- 28-E -- -- 10
7-8 0.20 104 -- 29-E -- -- 10
7-9 1.80 157 -- 30-E -- -- 16
9-10 7.4 157 -- 31-E -- -- 16
10-11 1.8 157 --
1-E -- -- 12 (*) by-pass disconnector switch
2-E -- -- 3 (**) special bushing arrangement
3-E -- -- 3
4-E -- -- 3
8-E -- -- 3
Note—These values given in appendix A are used in
9-E -- -- 3 simulation purpose for different sections of the circuit.
10-E -- -- 3
17
Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008
APPENDIX B
Fig.7. Simulated Circuit
REFRENCES
[1] C.Y. lui and J. Hiley, “Computational study of very fast transients in GIS
with special reference to effects of trapped charge and rise time on over-
voltage amplitude,” IEE Proc.-Genre. Transom. Distrib., vol. 141, no. 5, pp.
485-490, September 1994.
[2] IEEE TF on Very Fast Transients (D. Povh, Chairman), "Modeling and
analysis guidelines for very fast transients," IEEE Trans. on Power Delivery,
vol. 11, no. 4, pp. 2028-2035, October 1996.
18