2
Engineering Bulletin EDP-3
Dependable (2004-3)
Protection
For An
Electrical
Distribution
System
Part 3
Component
Protection for
Electrical
Systems
Bussmann
Electrical Distribution System
3
Electrical Distribution System
Current-Limitation
A Definition of Current-Limitation
Today, most electrical distribution systems are capable Prospective available short-circuit
100,000 current that would flow when a
of delivering very high short-circuit currents, some in Fuse is not used.
excess of 200,000 amperes. If the components are not
capable of handling these short-circuit currents, they could
easily be damaged or destroyed. The current-limiting ability
of today’s modern fuses allows components with low short-
circuit withstand ratings to be specified in spite of high
Current
available fault currents.
Section 240-11 of the NEC offers the following
definition of a current limiting device:
“A current-limiting overcurrent protective device is a
device which, when interrupting currents in its current- Peak Let-Thru
10,000
limiting range, will reduce the current flowing in the faulted Current of Fuse
circuit to a magnitude substantially less than that 0
obtainable in the same circuit if the device were replaced Time
tc
with a solid conductor having comparable impedance.”
The concept of current-limitation is pointed out in Total Clearing Time of Fuse
Figure 1, where the prospective available fault current is
shown in conjunction with the limited current resulting when Figure 1. Current Limiting Effect of Fuses
a current-limiting fuse clears. The area under the current
curve indicates the amount of short-circuit energy being Thus, the current-limiting fuse in this example would
dissipated in the circuit. Since both magnetic forces and limit the let-thru energy to a fraction of the value which is
thermal energy are directly proportional to the square of the available from the system. In the first major loop of fault
current, it is important to limit the short-circuit current to as current, standard non-current limiting, electro-mechanical
small a value as possible. Magnetic forces vary as the protective devices would let-through approximately 100
square of the “PEAK” current and thermal energy varies as times* as much destructive energy as the fuse would let-
the square of the “RMS” current. through.
2
* (100,000
10,000 )
4
Electrical Distribution System
Current-Limitation
Analysis of Current-Limiting Fuse Let-Thru Charts how the curves are generated, and what circuit parameters
The degree of current-limitation of a given size and affect the let-thru curve data. Typically, there are three
type of fuse depends, in general, upon the available short- circuit parameters that can affect fuse let-thru performance
circuit current which can be delivered by the electrical for a given available short circuit current. These are:
system. Current-limitation of fuses is best described in the 1. Short circuit power factor
form of a let-thru chart which, when applied from a 2. Short circuit closing angle
practical point of view, is useful to determine the let-thru 3. Applied voltage
currents when a fuse opens.
Fuse let-thru charts are similar to the one shown in Current-limiting fuse let-thru curves are generated
Figure 2 and are plotted from actual test data. The test under worst case conditions, based on these three
circuit that establishes line A-B corresponds to a short- variable parameters. The benefit to the user is a
circuit power factor of 15%, which is associated with an X/R conservative resultant let-thru current (both Ip and IRMS).
ratio of 6.6. The fuse curves represent the cutoff value of Under actual field conditions, changing any one or a
the prospective available short-circuit current under the combination of these will result in lower let-thru currents.
given circuit conditions. Each type or class of fuse has its This provides for an additional degree of reliability when
own family of let-thru curves. applying fuses for equipment protection.
The let-thru data has been generated by actual short circuit See charts and tables on pages 25 thru 31 for
tests of current-limiting fuses. It is important to understand Bussmann fuse let-thru current data.
B
400,000 Available Peak Short-
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
3000
A
2000
1000
10,000
20,000
30,000
40,000
60,000
100,000
200,000
80,000
1000
2000
3000
4000
6000
8000
5
Electrical Distribution System
AMPERE
RATING
3000
the 800 ampere LOW-PEAK fuse is illustrated in Figure 4. A
2000
30,000
40,000
60,000
100,000
200,000
20,000
80,000
1000
2000
3000
4000
6000
8000
Step 3. Read the PEAK LET-THRU CURRENT as 49,000 Figure 4. Current-Limitation Curves – Bussmann LOW-PEAK®
amperes. (If a fuse had not been used, the peak current Time-Delay Fuse KRP-C800SP
would have been 198,000 amperes.)
6
Electrical Distribution System
7
Protecting System Components
100
80
60
50
40
D
30
N
O
D
C
N
SE
D
C
N
67
O
20
S
SE CO ND
01
C
3
67 SEC ON D
0.
SHORT CIRCUIT CURRENT - THOUSANDS OF AMPERES
00 SE CO
3
N
03
–
67
D
E
0.
66 S
6
LE
.0
D
C
S
0
YC
N
13
7
LE
D
C
0.
YC
N
2
LE
1
O
ES –
0 .
50
C
10
C
YC
S
–
00
SE
YC LE
2
0.
C
00
–
YC
4
L
S
1.
66
C
LE
8
8
1.
C
YC
ES
16
–
L
C
S
C
LE
30
Y
C
YC
60
6
C
0
5
10
4
3
CONDUCTOR: COPPER
.6 WHERE:
.5 I = SHORT-CIRCUIT CURRENT - AMPERES
.4 A = CONDUCTOR AREA - CIRCULAR MILS
t = TIME OF SHORT-CIRCUIT - SECONDS
.3 T1 = MAXIMUM OPERATING TEMPERATURE -
75°C
T2 = MAXIMUM SHORT-CIRCUIT TEMPERATURE -
.2
200°C
.1
10 8 6 4 2 1 1/0 2/0 3/0 4/0 AWG
CONDUCTOR SIZE 250 MCM 500 1000
Figure 6. Short-Circuit Current Withstand Chart for Copper Cables with Paper, Rubber, or Varnished Cloth Insulation
*Copyright 1969 (reaffirmed March, 1992) by the Insulated Cable Engineers Association (ICEA). Permission has been given by ICEA to reprint this chart.
8
Protecting System Components
100
80
60
50
40
30
C ND
D
SE O
N
20 3 EC
O
03 7 S
D
SHORT CIRCUIT CURRENT - THOUSANDS OF AMPERES
EC N
D
6
O
N
– .01
33 EC
3
D
N
0
O
0.
LE –
D
S
C
.1 7 6
N
SE
YC LE
ES – 06
O
S
O D
3
YC
C
.
7
0
N
10
SE
D
66
SE O
YC LE –
0
C
N
2
67 EC
S
00
1
0.
C
16 CY LE
C
S
50
2
–
8 YC
1. 000
0.
8
C
C
–
L
0
66
4
1.
LE
LE –
C
YC
YC ES
–
S
C
6
C
30
10 CY
5
C
60
0
4
3
CONDUCTOR: COPPER
2 INSULATION: THERMOPLASTIC
.1
10 8 6 4 2 1 1/0 2/0 3/0 4/0 AWG
CONDUCTOR SIZE 250 MCM 500 1000
Figure 7. Short-Circuit Current Withstand Chart for Copper Cables with Thermoplastic Insulation
*Copyright 1969 (reaffirmed March, 1992) by the Insulated Cable Engineers Association (ICEA). Permission has been given by ICEA to reprint this chart.
9
Protecting System Components
100
80
60
50
40
D
N
O
30
D
C
N
SE
D
C
N
67
6 7 SE
SE CO ND
01
C
20 3
67 SEC ON D
0.
E O
3
N
SHORT CIRCUIT CURRENT - THOUSANDS OF AMPERES
03
C
–
D
50 67 SE
0.
6
LE
.0
33
C ND
S
C
S
0
YC
YC LES – 0.13
LE
D
SE O
C
N
S
6
YC
0
2
O
LE
1
0
–
0 .
C
YC
1. 000
YC LE
2
0.
10
S
C
YC LE
–
YC
.0
4
66
1
C
–
8
C
YC ES
8
16
S
L
C
LE
30
C
60
C
0
6
10
4
CONDUCTOR: COPPER
3
INSULATION: CROSSLINKED POLYETHYLENE &
ETHYLENE PROPYLENE RUBBER
2 CURVES BASED ON FORMULA:
.2
.1
10 8 6 4 2 1 1/0 2/0 3/0 4/0 AWG
CONDUCTOR SIZE 250 MCM 500 1000
Figure 8. Short-Circuit Current Withstand Chart for Copper Cables with Crosslinked Polyethylene & Ethylene Propylene Rubber Insulation
*Copyright 1969 (reaffirmed March, 1992) by the Insulated Cable Engineers Association (ICEA). Permission has been given by ICEA to reprint this chart.
10
Protecting System Components
60
50
40
30
C ND
20
D
SE O
N
3 EC
O
SHORT CIRCUIT CURRENT - THOUSANDS OF AMPERES
03 7 S
D
EC N
D
6
O
N
– .01
33 EC
3
D
N
0
O
0.
LE –
D
S
C
.1 7 6
N
SE
YC LE
10
ES – 06
O
S
O D
3
YC
C
.
7
0
N
SE
D
66
SE O
YC LE –
0
C
N
2
67 EC
S
00
1
0.
C
16 CY LE
8 C
S
50
2
–
8 YC
1. 000
0.
C
C
–
L
0
66
4
1.
LE
LE –
C
6
YC
YC ES
–
S
C
5
C
30
10 CY
4
C
60
0
CONDUCTOR: ALUMINUM
2
INSULATION: PAPER, RUBBER, VARNISHED
CLOTH
.1
10 8 6 4 2 1 1/0 2/0 3/0 4/0 AWG
CONDUCTOR SIZE 250 MCM 500 1000
Figure 9. Short-Circuit Current Withstand Chart for Aluminum Cables with Paper, Rubber, or Varnished Cloth Insulation
*Copyright 1969 (reaffirmed March, 1992) by the Insulated Cable Engineers Association (ICEA). Permission has been given by ICEA to reprint this chart.
11
Protecting System Components
60
50
40
30
20
SHORT CIRCUIT CURRENT - THOUSANDS OF AMPERES
D
N
O
D
C
N
SE
O
C
67
SE CO D
SE
67 SE ON
D
01
N
33
10
0.
D
03
SE
N
–
O
0.
D
C
67
LE
N
26 33
06
O
S
YC
8 O D
LE
13
EC
0.
N
C
D
0.
YC
SE O
–
N
1
67 EC
S
00
0.
C
LE
C
S
50
2
–
LE
YC
00
S
0.
6
YC
LE
C
00
–
C
YC
66
4
1.
5
LE
8
1.
LE –
C
YC
YC LES
–
16
4
C
YC
30
3
C
60
0
10
CONDUCTOR: ALUMINUM
2
INSULATION: THERMOPLASTIC
.1
10 8 6 4 2 1 1/0 2/0 3/0 4/0 AWG
CONDUCTOR SIZE 250 MCM 500 1000
Figure 10. Short-Circuit Current Withstand Chart for Aluminum Cable with Thermoplastic Insulation
*Copyright 1969 (reaffirmed March, 1992) by the Insulated Cable Engineers Association (ICEA). Permission has been given by ICEA to reprint this chart.
12
Protecting System Components
100
80
60
50
40
30
D
N
20 SE CO
D
N
SHORT CIRCUIT CURRENT - THOUSANDS OF AMPERES
SE
O
C
67
SE CO ND
D
01
O
N
33
0.
D
03
0. 33 SE
N
–
O
E
0.
SE O D
S
C
0. 67
LE
67 SEC ON
26 3
10
C ND
06
S
YC
LE
D
0.
67
1
SE
N
C
YC
O
1
1. 000
C
LE
8
2
1. 000
LE
5
YC
0.
YC
LE
0
C
C CLE S –
66
C
YC
4
LE –
LE
8
C
6
YC
S
16
5
Y
YC
30
C
60
4
0
10
CONDUCTOR: ALUMINUM
2
INSULATION: CROSSLINKED POLYETHYLENE &
ETHYLENE PROPYLENE RUBBER
.1
10 8 6 4 2 1 1/0 2/0 3/0 4/0 AWG
CONDUCTOR SIZE 250 MCM 500 1000
Figure 11. Short-Circuit Current Withstand Chart for Aluminum Cables with Crosslinked Polyethylene & Ethylene Propylene Rubber
Insulation
*Copyright 1969 (reaffirmed March, 1992) by the Insulated Cable Engineers Association (ICEA). Permission has been given by ICEA to reprint this chart.
13
Protecting System Components
14
Protecting System Components
15
Protecting System Components
.3
.2
.1
.08
Short Time
.06 Delay - 6 Cycles Busway
Mechanical
.04 Capability
.03
.02
.01
80,000
100,000
60,000
1,000
2,000
3,000
4,000
6,000
8,000
10,000
20,000
30,000
40,000
100
200
300
400
600
800
Figure 13.
16
Protecting System Components
600
400
300
200
LPS-RK400SP
KRP-C800SP
100
80
60
40
30
20
10
8
6
TIME IN SECONDS
KRP-C800SP
4
2
LPS-RK400SP
1
.8
.6
.4
.3
.2
.1
.08
.06
Busway
.04 Mechanical
Capability
.03
.02
.01
60,000
1,000
2,000
3,000
4,000
6,000
8,000
10,000
20,000
30,000
40,000
80,000
100,000
100
200
300
400
600
800
17
Protecting System Components
18
Protecting System Components
Amps
IRMS = 22,000 Amp
As has been discussed previously, the two parameters
IRMS and Ip, must be compared to the equipment withstand
rating. The rule is simple: if the RMS and peak let-thru value
of the fuse are less than the equipment withstand rating,
Time
the equipment will be protected. This philosophy holds true
for various static components, such as wire and cable,
busway, and motor star ters. This basic protection
requirement is mandated in NEC Section 110-10. It will also Figure 16
be true for non-current-limiting circuit breakers when their
opening time is greater than one-half cycle. S.C.P.F. = 20%
S.C. Avail. = 22,000A 20A
In the past, as long as the fuse let-thru values were RCB XCB
RLINE XLINE RLOAD XLOAD
less than the breaker’s interrupting rating, the system was RS
considered sound. THIS METHOD HAS A SOLID HISTORY
OF SUCCESSFUL APPLICATIONS. However, due to XS
changes in circuit breaker design, the method may not
always work with today’s circuit breakers. Selecting a SOURCE: 4' Rated Wire (#12 Cu) 10" Rated Wire (#12 Cu)
current-limiting fuse to protect a downstream molded case Note: For calculations, R CB and X CB are assumed negligible.
circuit breaker has now become an increasingly more
complex problem. Figure 17
Quicker Operating Circuit Breakers Standard interrupting rating tests will allow for a
Simply put, if the total clearing energy of a quicker maximum 4-foot rated wire on the line side, and a 10-inch
acting molded case circuit breaker is less than the melting rated wire on the load side of the circuit breaker.
energy of a larger upstream fuse, the molded case circuit Performing a short-circuit analysis of this test circuit results
breaker will interrupt the full value of the system fault in the following short-circuit parameters, as seen by the
without the benefit of the fuse’s current-limiting effect. This circuit breaker.
situation can have catastrophic effects on the circuit Actual short-circuit RMS current = 9,900 amperes RMS
breaker as it tries to interrupt faults beyond its interrupting symmetrical
capacity. Currently, there is no available engineering Actual short-circuit power factor = 88%
method to predict protection of these faster breakers. Actual short-circuit peak current = 14,001 amperes
Molded Case Circuit Breakers - Agency Test Procedures A graphic analysis of this actual short-circuit follows
Some agency standards allow a unique test set-up for (Figure 18).
testing circuit breaker interrupting ratings. Figure 16
illustrates a typical calibrated test circuit waveform for a Ip = 14,001A
20A, 240-volt, two-pole molded case circuit breaker, with a
P.F. = 88%
marked interrupting rating of 22,000 amperes RMS
IRMS = 9,900 Amp
symmetrical. Figure 17 also illustrates the calibration IRMS = 9,900A
Amps
20
Protecting System Components
E. Transformers
1. Overload Protection Section 450-3b covers transformer protection when the
The National Electrical Code has developed separate primary voltage is 600 volts or less. Primary fusing at 125%
sections and sizing recommendations for fuses with of primary current will not require secondary protection.
primary voltages above and below 600 volts, nominal. The
following three paragraphs cover the basic requirements. Note: Secondary conductor and panelboard protection are
See NEC Sections 450-3 and 430-72 for the most common most often required by Articles 240 and 384 respectively.
exceptions.
Section 450-3a covers transformer protection when the Primary and secondary protection are required when
primar y voltage is greater than 600 volts. For low the primary fuse is greater than 125%. The primary fuse
impedance transformers, fuse protection on the primary may be sized no larger than 250% of primary current. The
can be sized as high as 300% of primary current. secondary fuse should then be sized no larger than 125%
Secondary protection must be offered at 250% or 125% for of the secondary current.
secondary voltages greater than 600 volts, or 600 volts or
less, respectively. See Figures 20 and 21. 2. Magnetizing Inrush Currents
Primary fuses must be capable of handling the inrush
Table 6. 450-3(a)(1) Transformers Over 600 Volts currents associated with the transformer during start-up. A
Maximum Rating or Setting for Overcurrent Device rule of thumb is that the fuse handle 12x full load current for
Primary Secondary
0.1 seconds, and 25x full load current for 0.01 seconds.
Over 600 Volts Over 600 Volts 600 Volts
or Below Dual-element time-delay fuses are best suited to meet the
Transformer Circuit Circuit Circuit Breaker sizing criteria of Article 450 and pass these initial surge
Rated Breaker Fuse Breaker Fuse Setting or characteristics.
Impedance Setting Rating Setting Rating Fuse Rating
Not more
Refer to Bussmann Bulletin EDP II for a discussion of
than 6% 600% 300% 300% 250% 125% these inrush points.
More than 6%
and not more 3. Short-Circuit Protection - Thermal and Magnetic
than 10% 400% 300% 250% 225% 125%
Withstand curves for distribution transformers define
how much current a transformer can withstand, and for how
Z = 6% (or less)
PRI. SEC.
long. As with any electrical component, if these curves are
over 600V Unsupervised exceeded the transformer may be damaged or destroyed.
600V or less Location These curves relate to both thermal and mechanical
damage, and are defined by different fault conditions.
Fuse at 300% of Fuse at 125% of Typically, three curves exist for a 3-phase transformer,
F.L.A. of primary F.L.A. of secondary defined by phase-phase, phase-phase-phase, and phase-
ground fault conditions.
Figure 20 It is the designer’s goal to find a fuse time-current
curve that falls to the left of the damage curves and to the
PRIMARY PROTECTION ONLY
right of the transformer inrush points.
PRI. & SEC. Refer to Bussmann Bulletin EDP II for a discussion of
600V or less how to analyze these curves and protection levels.
Figure 21
21
Protecting System Components
F. Ballasts
The National Electrical Code requires integral thermal Thermal Protector Short
Ballast
protection for ballasts in Section 410-73(e).
Testing agencies list ballasts for general use in lighting 200A
0.9-1.0 P.F.
fixtures which pass specific thermal and short-circuit tests.
The ballast must incorporate a thermal protector to sense
20 Amp Fuse Ballast Winding
certain over-temperature conditions and must also be able
to withstand 200 amperes of short-circuit current when
tested with a 20 ampere fuse. See Figure 22 for a typical Figure 22. Underwriters’ Laboratories Short-Circuit Test for
test for ballasts. Ballast Protectors.
Most systems today will deliver more than 200
20' #10 THW Wire Row of Lighting
amperes of short-circuit current to a row of fixtures. (See 2,000 Amperes Available Fixtures
Figure 23.) The fixtures should, therefore, be specified to 277 Volt
incorporate individual ballast fusing within the fixture and Lighting
Panel
external to the ballast. Fuse
Opens
Fusing each fixture, as shown in Figure 23, will also
provide isolation of the faulted ballast and reduce costly
and dangerous blackouts. When a ballast does fail, only Fixture
the fuse protecting that individual fixture opens - the Ballasts
Faulted Ballast
remaining fixtures continue in normal operation. Without this
individual ballast protection, a faulted ballast could cause
the branch circuit protective device to open, thereby Figure 23. Fusing Fixture Ballasts to Provide Short-Circuit
shutting off all the lights. With individual fusing, the Protection and Isolation of Faulted Ballast. Good
maintenance electrician can trouble shoot the problem Ballasts Remain on the Line.
much more quickly because only one fixture is “out”. And
this trouble shooting can be performed as part of a
scheduled maintenance procedure. It doesn’t have to
become an “emergency” because employees are left in the
dark.
22
Protecting System Components
G. Transfer Switches
Transfer switches are designed to transfer power Table 7. U.L. 1008 Minimum Withstand Test Requirement
sources under load in order to feed a system, typically an Automatic Transfer U.L. Minimum U.L. Test Current
Switch Rating Current Amps Power Factor
emergency system, on critical loads. These devices are 100 Amps or less 5,000 40% to 50%
tested to meet basic short-circuit testing requirements. 101-400 Amps 10,000 40% to 50%
Transfer switches are often tested per U.L. Standard 1008. 401 Amps and greater 20 times rating 40% to 50% for
Transfer switches should always be evaluated on the but not less current of 10,000
than 10,000 Amps Amps.
basis of the maximum available short-circuit currents. The OR
automatic transfer switch must withstand: a) the magnetic 25% to 30% for
currents of 20,000
stresses imposed by the instantaneous peak current Amps or less.
available at the point of application, and b) the thermal OR
stresses imposed by the available RMS short-circuit 20% or less for
current greater
current. The short-circuit current withstand rating of the than 20,000 Amps.
transfer switch must be equal to or greater than the
available short-circuit current at the point of application. Transfer switch manufacturers generally publish the
When properly coordinated with current-limiting withstand rating data for their products. When the available
devices, automatic transfer switches can be used on short-circuit current exceeds the withstand rating of the
circuits having available short-circuit currents greater than transfer switch, current-limitation is required. Properly sized
their unprotected withstand short-circuit current rating. modern current-limiting fuses ahead of the transfer switch
Modern current-limiting fuses, when properly sized, limit the limit the available short-circuit current to within the
short-circuit current to within the withstand rating of a withstand rating of a transfer switch, thereby protecting the
transfer switch. transfer switch. The transfer switch manufacturer will mark
Transfer switches must withstand minimum short-circuit the equipment with the fuse class and rating required to
currents at specified power factors, as listed in U.L. achieve these higher short-circuit ratings.
Standard 1008, until the overcurrent protective devices
open. See Table 7.
23
Protecting System Components
H. HVAC Equipment
Heating and cooling equipment must meet short-circuit Table 8. Short-Circuit Test Currents*
test requirements in U.L. Standard 1995 and CSA-C22.2 Product Ratings, A
Single-Phase Circuit Capacity,
No. 236-M90. Short-circuit tests are conducted at various 110-120V 200-208V 220-240V 254-277V A
levels, up to a maximum of only 5000 amperes, depending 9.8 or less 5.4 or less 4.9 or less – 200
on the rated current and voltage of the equipment. 9.9-16.0 5.5-8.8 5.0-8.0 6.65 or less 1000
Where available fault currents exceed the values given 16.1-34.0 8.9-18.6 8.1-17.0 – 2000
34.1-80.0 18.7-44.0 17.1-40.0 – 3500
in Table 55.1 of U.L. 1995 (Table 8 at right) it is necessary
Over 80.0 Over 44.0 Over 40.0 Over 6.65 5000
to specify a current limiting device to reduce the available 3-Phase Circuit Capacity,
current down to within the withstand capabilities of the 200-208V 220-240V 440-480V 550-600V A
equipment. 2.12 or less 2.0 or less – – 200
2.13-3.7 2.1-3.5 1.8 or less 1.4 or less 1000
Class J and Class RK1 dual-element current-limiting
3.8-9.5 3.6-9.0 – – 2000
fuses will offer the best component short-circuit protection 9.6-23.3 9.1-22.0 – – 3500
and current-limiting characteristics for this type of Over 23.3 Over 22.0 Over 1.8 Over 1.4 5000
equipment.
*Table 55.1 of U.L. Standard 1995.
24
Buss® Fuse Current- Limiting Let-Thru Charts
B
400,000
300,000 6,000
5,000
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
200,000 4,000
3,000
2,500
2,000
100,000 1,600
80,000 1,200
60,000 800
50,000 601
40,000
AMPERE
RATING
30,000
20,000
10,000
8,000
6,000
5,000
4,000
3,000
A
2,000
1,000
1,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
25
Buss® Fuse Current- Limiting Let-Thru Charts
60,000
40,000
600
10 40,000
30,000 400
7 30,000
200
20,000 6 20,000
3 100
10,000
60
1 10,000 50
8,000 8,000 40
6,000 6,000 30
AMPERE
RATING
4,000 4,000 20
3,000 3,000
15
A
2,000 2,000
AMPERE
RATING
1,000 1,000
800 800
600 600
400 400
300 300
A
200 200
100 100
1,000
2,000
3,000
4,000
6,000
8,000
10,000
20,000
30,000
40,000
60,000
80,000
100,000
200,000
100
200
300
400
600
800
1,000
2,000
3,000
4,000
6,000
8,000
10,000
20,000
30,000
40,000
60,000
80,000
100,000
200,000
100
200
300
400
600
800
PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS
26
Buss® Fuse Current- Limiting Let-Thru Charts
B B
400,000 400,000
300,000 300,000
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
AMPERE
AMPERE
RATING
RATING
100,000 100,000
80,000 80,000
60,000 60,000 600
600
50,000 50,000
40,000 400 40,000 400
30,000 30,000
200 200
20,000 20,000
100 100
60 60
10,000 10,000
8,000 8,000
30 30
6,000 6,000
5,000 5,000
4,000 4,000
3,000 3,000
A A
2,000 2,000
1,000 1,000
1,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
1,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS PROSPECTIVE SHORT CIRCUIT-CURRENT–SYMMETRICAL RMS AMPS
LPN-RK_SP – RMS & Peak Let-Thru Currents (kA) LPS-RK_SP – RMS & Peak Let-Thru Currents (kA)
Prosp. Fuse Size Prosp. Fuse Size
Short 30 60 100 200 400 600 Short 30 60 100 200 400 600
C.C. IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip C.C. IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip
1,000 1 1 1 2 1 2 1 2 1 2 1 2 1,000 1 1 1 2 1 2 1 2 1 2 1 2
2,000 1 2 1 3 2 4 2 5 2 5 2 5 2,000 1 2 1 3 2 4 2 4 2 4 2 4
3,000 1 2 1 3 2 4 3 6 3 7 3 7 3,000 1 2 1 3 2 4 3 6 3 7 3 7
5,000 1 2 2 4 2 5 3 7 5 12 5 12 5,000 1 2 2 4 2 5 3 7 5 12 5 12
10,000 1 3 2 4 2 6 4 9 7 15 9 21 10,000 1 3 2 5 3 6 4 9 7 16 9 21
15,000 1 3 2 5 3 6 4 10 7 17 10 23 15,000 1 3 2 5 3 7 5 11 8 18 10 24
20,000 1 3 2 6 3 7 5 11 8 19 11 25 20,000 1 3 3 6 3 7 5 12 8 19 11 26
25,000 1 3 3 6 3 7 5 12 9 20 12 27 25,000 2 4 3 6 3 8 5 12 9 21 12 28
30,000 2 3 3 6 3 8 5 12 9 21 13 29 30,000 2 4 3 6 4 8 6 13 10 22 13 30
35,000 2 4 3 7 4 8 6 13 10 22 13 30 35,000 2 4 3 7 4 9 6 14 10 23 13 31
40,000 2 4 3 7 4 9 6 13 10 23 13 31 40,000 2 4 3 7 4 9 6 14 10 24 14 32
50,000 2 4 3 7 4 9 6 14 10 24 14 33 50,000 2 5 3 8 4 10 7 15 11 26 15 35
60,000 2 4 3 8 4 10 7 15 11 26 15 35 60,000 2 5 3 8 4 10 7 16 12 28 16 37
70,000 2 4 3 8 4 10 7 16 12 27 16 36 70,000 2 5 4 8 5 11 7 17 13 29 17 39
80,000 2 5 4 8 5 11 7 16 12 28 17 38 80,000 2 5 4 9 5 11 8 18 13 30 17 40
90,000 2 5 4 9 5 11 7 17 13 29 17 39 90,000 2 5 4 9 5 12 8 18 13 31 18 42
100,000 2 5 4 9 5 11 8 18 13 30 17 40 100,000 2 6 4 9 5 12 8 19 14 32 19 44
150,000 2 6 4 10 5 13 8 19 16 36 20 46 150,000 3 6 5 11 6 14 9 21 16 36 22 50
200,000 3 6 5 11 6 14 9 21 18 42 22 50 200,000 3 7 5 12 7 15 10 23 17 40 23 54
Note: For Ip and IRMS values at 300,000 amperes, consult Factory. Note: For Ip and IRMS values at 300,000 amperes, consult Factory.
27
Data Section
FUSETRON® Class RK5 Dual-Element Time-Delay Fuses FUSETRON® Class RK5 Dual-Element Time-Delay Fuses
FRN-R FRS-R
B B
400,000 400,000
300,000 300,000
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
AMPERE
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
200,000
RATING
200,000
AMPERE
RATING
100,000 100,000
600 600
80,000 80,000
400
60,000 400 60,000
50,000 50,000 200
200 40,000
40,000
30,000 100 30,000
100
20,000 60 20,000 60
30
10,000 10,000
30
8,000 8,000
6,000 6,000
5,000 5,000
4,000 4,000
3,000 3,000
A A
2,000 2,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
1,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS
FRN-R – RMS & Peak Let-Thru Currents (kA) FRS-R – RMS & Peak Let-Thru Currents (kA)
Prosp. Fuse Size Prosp. Fuse Size
Short 30 60 100 200 400 600 Short 30 60 100 200 400 600
C.C. IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip C.C. IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip
5,000 1 2 2 5 3 8 5 11 5 12 5 12 5,000 1 3 2 4 3 8 5 12 5 12 5 12
10,000 1 3 3 6 5 11 7 15 9 21 10 23 10,000 2 4 3 6 5 11 7 16 10 23 10 23
15,000 1 3 3 7 6 13 8 18 11 25 14 33 15,000 2 5 3 7 5 13 8 19 13 30 15 35
20,000 2 4 4 8 7 15 8 20 12 28 16 37 20,000 2 6 3 8 6 14 10 22 14 33 17 40
25,000 2 4 4 9 7 16 9 21 13 30 17 40 25,000 3 6 4 9 7 16 10 24 16 37 19 44
30,000 2 4 4 10 7 17 10 23 14 32 19 43 30,000 3 7 4 9 7 17 11 25 17 39 20 47
35,000 2 4 5 11 8 18 11 25 15 34 20 45 35,000 3 7 4 10 7 17 12 27 18 41 22 50
40,000 2 5 5 11 8 19 11 25 15 35 20 47 40,000 3 7 5 11 8 18 12 28 19 43 23 52
50,000 2 5 5 12 9 20 12 27 16 37 22 50 50,000 3 8 5 12 8 19 13 30 20 46 24 56
60,000 2 6 6 13 9 21 12 28 17 40 23 54 60,000 4 9 5 12 9 20 14 32 21 49 26 60
70,000 3 6 6 14 10 22 13 30 18 41 24 56 70,000 4 9 6 13 9 21 15 34 22 50 27 62
80,000 3 6 6 15 10 23 13 31 19 43 25 58 80,000 4 9 6 14 9 22 15 35 23 52 28 64
90,000 3 6 7 15 10 23 14 32 19 44 26 60 90,000 4 10 6 14 10 22 16 36 23 54 29 66
100,000 3 7 7 16 10 24 14 33 20 46 27 62 100,000 4 10 7 15 10 23 16 37 24 56 30 68
150,000 3 8 8 18 11 26 16 37 23 52 30 70 150,000 5 12 7 17 11 25 18 42 26 60 33 75
200,000 4 8 8 20 12 27 17 40 24 56 32 74 200,000 6 13 8 19 11 26 19 44 27 63 35 80
28
Data Section
TRON® Class T Fast-Acting Fuses JJN TRON® Class T Fast-Acting Fuses JJS
B B
400,000 400,000
300,000 300,000
AMPERE
RATING
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
200,000 200,000
2,000 2,000
1,000 1,000
800 800
600 600
400 400
300 300
A A
200 200
1,000
2,000
3,000
4,000
6,000
8,000
10,000
20,000
30,000
40,000
60,000
80,000
100,000
200,000
100
200
300
400
600
800
1,000
2,000
3,000
4,000
6,000
8,000
10,000
20,000
30,000
40,000
60,000
80,000
100,000
200,000
100
200
300
400
600
800
PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS
LIMITRON® Class RK1 Fast-Acting Fuses KTN-R LIMITRON® Class RK1 Fast-Acting Fuses KTS-R
B B
400,000 400,000
300,000 300,000
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
AMPERE
RATING
AMPERE
RATING
100,000 100,000
80,000 80,000
600 600
60,000 60,000
50,000 50,000
400 400
40,000 40,000
30,000 30,000
200 200
20,000 20,000
100 100
10,000 10,000
60 60
8,000 8,000
6,000 30 6,000 30
5,000 5,000
4,000 4,000
3,000 3,000
A A
2,000 2,000
1,000 1,000
1,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
1,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS
KTN-R – RMS & Peak Let-Thru Currents (kA) KTS-R – RMS & Peak Let-Thru Currents (kA)
Prosp. Fuse Size Prosp. Fuse Size
Short 30 60 100 200 400 600 Short 30 60 100 200 400 600
C.C. IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip C.C. IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip IRMS Ip
5,000 1 2 1 3 2 4 3 6 5 10 5 12 5,000 1 2 1 3 2 4 3 6 5 12 5 12
10,000 1 2 1 3 2 5 3 8 6 14 8 19 10,000 1 2 2 4 2 5 4 8 7 15 9 20
15,000 1 3 2 4 2 6 4 9 7 17 10 22 15,000 1 3 2 4 3 6 4 10 8 18 11 24
20,000 1 3 2 4 3 6 4 10 8 19 11 25 20,000 1 3 2 5 3 7 5 11 9 20 12 28
25,000 1 3 2 5 3 7 4 10 9 20 12 27 25,000 1 3 2 5 3 7 5 12 10 22 13 31
30,000 1 3 2 5 3 7 5 11 10 22 13 29 30,000 1 3 2 5 3 8 5 13 10 24 14 33
35,000 1 3 2 5 3 8 5 12 10 23 13 31 35,000 2 4 2 5 4 8 6 13 11 25 15 35
40,000 1 3 2 5 3 8 5 12 10 24 14 32 40,000 2 4 2 6 4 9 6 14 11 26 16 37
50,000 2 4 2 5 4 9 6 13 11 26 15 36 50,000 2 4 3 6 4 9 6 14 12 28 17 40
60,000 2 4 2 6 4 9 6 14 12 28 17 38 60,000 2 4 3 6 4 10 7 15 13 30 19 43
70,000 2 4 3 6 4 9 6 15 13 29 17 40 70,000 2 4 3 7 5 10 7 16 14 32 20 45
80,000 2 4 3 6 4 10 7 15 13 30 18 42 80,000 2 4 3 7 5 11 7 17 14 33 21 48
90,000 2 4 3 6 5 10 7 16 13 31 19 44 90,000 2 5 3 7 5 12 8 18 15 35 22 50
100,000 2 4 3 7 5 11 7 17 14 32 20 46 100,000 2 5 3 7 5 12 8 19 16 36 23 52
150,000 2 5 3 7 5 13 8 19 16 37 23 53 150,000 2 5 4 8 6 14 9 21 18 41 26 60
200,000 2 5 3 8 6 14 9 21 18 41 26 59 200,000 3 6 4 9 7 15 10 23 20 46 29 66
30
Data Section
B
400,000
300,000
INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS
200,000
AMPERE
RATING
100,000
80,000
60,000
600
50,000
40,000
400
30,000
200
20,000
100
60
10,000
8,000
6,000 30
5,000
4,000
3,000
A
2,000
1,000
1,000
2,000
3,000
4,000
5,000
6,000
8,000
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
31
Buss Fuse Selection Chart (600 Volts or Less).
Circuit Load Ampere Fuse Symbol Voltage Class Interrupting Remarks
Rating Type Rating Rating
(AC) (KA)
Conventional Dimensions–Class RK1, RK5 (1/10-600A), L (601-6000A)
1
All type loads– /10 LOW-PEAK LPN-RK_SP 250V* RK1†† 300 All-purpose fuses.
resistive or to YELLOW™ LPS-RK_SP 600V* Unequaled for combined
inductive (optimum 600A (dual-element, short-circuit and
overcurrent time-delay) overload protection.
protection). 601 to LOW-PEAK KRP-C_SP 600V L 300 (Specification grade product)
6000A YELLOW™
(time-delay)
1
Motors, welders, /10 FUSETRON® FRN-R 250V* RK5†† 200 Moderate degree of
transformers, to (dual-element, FRS-R 600V* current limitation. Time-delay
capacitor banks 600A time-delay) passes surge currents.
(circuits with heavy 601 to LIMITRON® KLU 600V L 200 General purpose fuse.
Main, inrush currents). 4000A (time-delay) Time-delay passes
Feeder surge-currents.
and Non-motor loads KTN-R 250V RK1†† 200 Same short-circuit protection
Branch (circuits with no 1 KTS-R 600V as LOW-PEAK fuses, but
heavy inrush to must be sized larger for
LIMITRON®
currents). 600A circuits with surge currents,
(fast-acting)
LIMITRON fuses i.e., up to 300%.
suited for circuit 601 to KTU 600V L 200 A fast-acting, high-
breaker protection. 6000A performance fuse.
Reduced Dimensions For Installation in Restricted Space–Class J(1-600A), T(1-1200A), CC(1/10-30A), G(1/2-60A)
All type loads LOW-PEAK LPJ_SP 600V* J 300 All-purpose fuses.
(optimum YELLOW™ Unequaled for combined
overcurrent (dual-element, short-circuit and overload
protection). 1 time-delay) protection. (Specification
to grade product).
Non-motor loads 600A LIMITRON® JKS 600V J 200 Very similar to KTS-R
(circuits with no (quick-acting) LIMITRON, but smaller.
heavy inrush 1 to T-TRON™ JJN 300V T 200 The space saver (1/3 the
currents). 1200A JJS 600V size of KTN-R/KTS-R).
1
Control transformer /10 to 30A LIMITRON® KTK-R 600V CC 200 Very compact (13/32" x
circuits and lighting (fast-acting) 11/2"); rejection feature.
ballasts, etc. 1
/4 to 10A CC-TRON™ FNQ-R Excellent for control
Branch (time-delay) transformer protection .
All type loads - LOW-PEAK LP-CC
1
especially small /2 to 30A YELLOW™
HP motors (time-delay)
1
General purpose, /2 SC SC 300V G 100 Current-limiting;
i.e., lighting to 13/32"
dia. x varying
panelboards. 60A lengths per ampere rating.
1
Miscellaneous. /8 ONE-TIME NON 250V H or K5† 10 Forerunners of
to NOS 600V the modern
600A SUPER-LAG® REN 250V H 10 cartridge fuse.
General RENEWABLE RES 600V
Purpose Plug fuses can 1
/4 FUSTAT® S 125V S 10 Base threads of Type S
(non- be used for to (dual-element, differ with ampere ratings.
current- branch circuits 30A time-delay) T and W have Edison-base.
limiting and small T & S fuses recommended
FUSETRON® T 125V ** 10
fuses) component for motor circuits. W not
(dual-element,
protection. time-delay) recommended for circuits
with motor loads.
Buss Type W W 125V ** 10
* LPN-RK_SP, 125VDC; LPS-RK_SP, 300VDC. FRN-R, 125VDC; FRS-R, 300VDC; LPJ_SP, 300VDC.
** Listed as Edison-Base Plug Fuse.
† Some ampere ratings are available as Class K5 with a 50,000A interrupting rating.
†† RK1 and RK5 fuses fit standard switches, fuseblocks and holders; however, the rejection feature of Class R switches and fuseblocks designed specifically for rejection type fuses
(RK1 and RK5) prevent the insertion of the non-rejection fuses (K1, K5 and H).
Bussmann Cooper Industries, Inc. Bussmann Division, P.O. Box 14460, St. Louis, MO 63178-4460
Sales Offices: U.S.A. 314-527-3877 • United Kingdom 44-1509-880737
Denmark 45-44850910 • Germany 49-6105-76968 • Singapore 65-227-5346
Australia 61-2-743-8333 • Mexico 525-352-0088 • India 91-80-225-1133