Job No Sheet No Dwg Ref Rev No

CC-474
Job Title A&A Works at 16 Kent Rd
Part of Structure
Client Prepared Date
Chk By 11/06/17

1.0 Synopsis

A proposed A&A works to be carried out at 16 Kent Road, Kowloon Tong. And several works are listed
as followings:-

Roof Floor
i. Tempered Glass Balustrade
A 1100mm height tempered glass balustrade to be erected on edge beams. The fixing of balustrade
to be used of steel angle and fixed by anchor bolts to existing parent structrure.

ii. Slabs Reinstatement


Existing void at Grid B-C/1-2, Grid B-C/2-2a, and Grid B-C/3-4 are proposed to be covered by
reinforcement concrete slabs, which supported by steel strengthening channel underneath and
fixed to existing parent structure.

1F
i. Slabs Reinstatement
Existing void at Grid B-C/1-2, Grid B-C/2-2a, and Grid B-C/3-4 are proposed to be covered by
reinforcement concrete slabs, which supported by steel strengthening channel underneath and
fixed to existing parent structure.

Overall Building
i. Grid 4-5/A-D
Existing reinforcement concrete slabs, beams-columns to be demolished. And replaced by new
structural steel frame with overall size 1975mm x 15087mm x 6706mm H.

Form of structure
The proposed steel frame to be in form of structural steel with welded connection, and final seat
on new reinforcement concrete transfer beam TB1 which supported by existing
columns (C4, D4, A5, B5, C5, and D6) and walls (W2, and W6).

2.0 Structural Appraisal

a. Site Inspection

Visual inspection was carried out by RSE regarding the condition of the existing structure elements
affected by the Proposed Works.

During the inspection, no undue cracks and / or spalling were noted. The existing structure is
considered to be in fair condition.

b. Conclusion

The works mentioned above which to be commence in this captioned works. Therefore,
the works will NOT cause any adverse effect to the existing parent structure.
Job No Sheet No Dwg Ref Rev No
CC-474
Job Title A&A Works at 16 Kent Rd
Part of Structure
Client Prepared Date
Chk By 11/06/17

3.0 Material Specification


a. Structural Steel
i. All structural steel other than hollow section to be S275 class 1 to BS EN 10025 PART 2, 2004.
ii. All structural hollow section to be S355 class 1 to BS EN 10210 PART 1, 1994
iii. The steel strength to be as following
Steel Grade = S275 S355
Steel Strength, py = 275.00 355.00 MPa

b. Welds
i. All welds to BS EN 1011 PART 1:1998 & PART 2:2001.
ii. The design strength of fillet welds stress = 220 MPa

c. Anchor
i. All anchor bolts to be "HILTI" anchor with Factor of Safety 3.0 adopted.
ii. Installation of Hilti anchor bolts shall comply strictly with the manufacturer's specification.

d. Concrete
i. Design concrete grade for structural member to be Grade 30D/20 with characteristic strength 30MPa.
ii. Minimum concrete cover to main reinforcement to be
Slabs = 25 mm
Beam = 30 mm
Footing = 75 mm
iii. All reinforcements to be high yield deformed type 2 bar and comply with CS2:1995.
the characteristic strength to be 500MPa.

e. Bolts
i. All Bolts to be Grade ISO 8.8, unless otherwise stated and comply with bs 3692:2001.
ii. Design Strength of Grade ISO 8.8 bolt.
Tensile Strength, pt = 560.0 N/mm²
Shear Strength, ps = 375.0 N/mm²
Bearing Strength, pbb = 1000.0 N/mm²

f. Tempered Glass
i. All glass to be 19mm laminated tempered glass and complied with BS 6262.
ii. Density of Glass = 25.0 kN/m³
Modulus of Elasticity = 730000.0 kg/cm² x 9.807x10-2 = 71591.10 MPa.
Permissible Bending Stress = 50.0 MPa
Deflection Limit = 50mm at 1100mm AFL.

g. Soil Bearing Pressure


i. Allowable Soil Bearing Pressure = 125.00 kPa
ii. 25% overstress on allowable bearing capacity may be allowed for
combinations including wind.

h. Existing Structural Data


i. Maximum premissible stresses in ordinary and quality A concretes in reinforced concrete
Compression
Grade Bending Direct Shear
Grade IIIA (1-2-4A) 6.90 5.24 0.69
iii. Maximum premissible stresses in steel reinforcement.
Steel reinforcement grade = high tensile steel
Tensile stress other than in shear reinforcement, pst = 230 MPa
Tensile stress in shear reinforcement, psv = 175 MPa
Compressive stress, psc = 175 MPa
Job No Sheet No Dwg Ref Rev No
CC-474
Job Title A&A Works at 16 Kent Rd
Part of Structure
Client Prepared Date
Chk By 11/06/17

4.0 List of Reference

a. Building (Construction) Regulations, 1990.


b. The code of practice for Dead and Imposed Loads, 2011.
c. The code of practice on wind effects in Hong Kong, 2004.
d. The code of practice for the Structural Use of Steel, 2011.
e. The code of practice for the Structural Use of Concrete, 2013.
f. The code of practice for Foundations, 2017.
g. Hilti Fastening Technology Manual, 2016.