Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 1
• Transmission lines constitute more than 60% of asset of power
transmission.

• They traverse an incredible range of kilometer in harsh


environments, climates and terrains.

• In India many of the Transmission lines currently in service


Transmissio were built in the 1960s and 70s and are subject to many
problems including ageing.
n lines
• With growing demands, there is huge expectations from
transmission companies to keep the transmission line uptime
near to 100%.

• Hence accurate fault location, health check / monitoring the


same is very much essential.
Prashant Das Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 2
Type of
common
faults in All Types of Open & Short Category faults
overhead
Transmission
lines

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 3
• Pre-Commissioning Check of EHV Lines –Continuity,
Overhead Phase Sequence, line length verification.
Transmission • Ascertaining line healthiness before re-Charging.
line fault
• For Preventive & Predictive Maintenance of
locator & existing EHV Lines.
Analyzer
• Restore the EHV lines ASAP to maintain UP TIME.

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 4
Fault OVER HEADTRANSMISSIONLINE FAULT
LOCATOR (OHFL)
Locator and
types of • Online
fault locator • Offline

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 5
• ONLINE-Systems works on the principal of power
system Parameters & Data is taken during stressed
OHFL breakdown condition and this data is in percentage
accuracy depending on the residual impedance of
Basic the line.
Principals of
• OFFLINE-Systems works on the principal of Multiple
working pulse Eco Co-relation technique & doesn't require
any input parameters for accurate fault finding.

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 6
• Each Line require one dedicated
equipment.
Online • It is not helpful for spur lines.
• Open Circuit faults can’t locate through
method online systems.
some of it’s • Fault locating accuracy may vary in
limitations percentage. (+/_ 10% or more)
• Pre-Commissioning tests are not possible.

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 7
• Advanced high frequency multiple pulse
co-relation technique

• How it works:
Offline - High frequency Coded pulse sent in to
the powerline
method - picks up different types of disturbance
and location
- Information Decoded
- Generates User Friendly Report and gives
complete vision of the line end to end

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 8
• It’ is accurate up to +/- 100Mtr.
• One equipment is enough for whole sub station.
Offline • It can be used for Spur line fault locating.
• Pre –Commissioning tests are possible.
methods • Offline system can identify the secondary faults
and it’s before re charging the line.
• It can find out Open Circuit faults.
advantages • Does not require any complimentary system at other
end of the sub station.
• It can Locate faults up to 2500KM.

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 9
Offline • Fault Locator(Breakdown): For finding the faults at
accurate distance.
OHFL
Diagnostic • Line Signature Analysis: for understanding the
healthiness of the line.
outputs

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 10
Overhead • Apart from finding dead faults , useful for
predictive and preventive maintenance-
transmission i) It can detect developing faults .
line fault ii) It can detect nature of the fault(Open/Short)
iii) It can indicate severity of the fault (Level of the
locator Faults).
• Less time to find faults and its location.
benefits • Healthiness check up for the entire line .

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 11
• Short circuit Fault
• De-capping
Case • All jumpers not through in Quad line
Studies • Leaky Insulators
• Clearance related problems
• High frequency effects on transmission lines

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 12
CASE STUDIES SHORT CIRCUIT FAULT at 112 KM

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related problems
High frequency effects on
transmission lines

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 13
CASE
STUDIES Decapping Fault at 69 Km in B Phase

Short circuit Fault Decapping


De-capping Fault
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 14
CASE
STUDIES ALL JUMPERS NOT THROUGH AT 55 KM

Short circuit Fault


De-capping
All jumpers not through
in Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 15
CASE
STUDIES Corona due to loose jumper

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 16
CASE
SIGNATURE AFTER THROUGH JUMPER
STUDIES

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 17
CASE
Flashover insulator at 5.8 and 5.3 KM
STUDIES

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 18
CASE
STUDIES

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 19
CASE
STUDIES Trees very close to Transmission Line in B-phase

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 20
CASE
STUDIES After Removal of trees

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 21
CASE
STUDIES
• Line Signature Analyser could identify the stress of the line
caused by high frequency noise flowing on the surface of
insulators and flashover.

• Line Signature Analyser printout with and without filters


reveal the presence of several kV’s of high frequency noise
Short circuit Fault and really a cause for flash over of insulators
De-capping
All jumpers not through in • The noise was later found due to parallel HVDC lines and
Quad line thyristor switching action
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 22
CASE
Annexure –A without filter
STUDIES Padghe – BBLR – gain 1 without filter-Lots of noise

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 23
CASE
Annexure – B with HVDC filter
STUDIES Padghe – BBLR– Gain1 No noise observed

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
Prashant Das
lines Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 24
Case Studies of 25 lines taken in a Transmission ZONE during 2011-2012 . Statistics are based on the OnM internal
CASE record maintained for 365 days
STUDIES Without OHFL
With
No. Of
Ideally Time
Time taken
Average with taken to Tota
OHFL time time Lines in Total to find
Line No. of OHFL OHFL find OHFL l EXTRA
taken to taken to the Zone Trippi fault in
Lengths in Tripping time used fault not time HOUR
rectify the rectify (Total ngs in HRS
KMs in a would at with used take S
fault in a fault in a Sample 25 a Year without
Year/Line have OHFL in n
line (Hrs) line lines) OHFL (Hrs)
taken ( Hrs)
(Hrs)

OFFLINE 0 to 150
15 3 19 3 57
171 30 90 27 405 495 324
KMs hrs places hrs places hrs hrs hrs
OVERHEAD
LINE FAULT
150 to 32 5 20 3 95 115 83
LOCATOR 250 Kms
19 4 4 2 8
hrs Places hrs Places hrs hrs hrs

250 to 16 1 4 1 23 27 11
23 4 2 2 4
350 Kms hrs places hrs place hrs hrs hrs

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 25
Case Case Studies of 73 new lines in a Utility Transmission company in India
Studies
No. of lines
No of Tripping
No.of Lines signature successfully charged
KV of the line No.of Lines Without Line
test was done after Signature
Signature test
Analyzer

OFFLINE OHFL 132KV 5 3 3 3

Line 220KV 20 11 9 9
Signature
400KV 40 16 14 14

765KV 8 3 3 3

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 26
Important
parameters- • Equipment should be Portable & Battery operated.
• Induction Voltage Suppression capability.
while • Auto Impedance matching facility for the kit to be
choosing an used in any EHV Lines.
overheadtransmis • Instrument should be EMI/EMC Compliance.
sion line fault
locator

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 27
PAPER

Presented by

POWERGRID IN CBIP
– INTERNATIONAL
CONFERENCE

Using Offline Fault


Locator

TO DIAGNOSE THE
TRANSMISSION LINE

Prashant Das Tauruspowertronics Pvt. Ltd


prashant.das@tauruspowertronics.com www.tauruspowertronics.com 28
29
Thank
you for For more information Write to :

your PRASHANT DAS

attendan prashant.das@tauruspowertronics.com
+91 9766355355

ce
Prashant Das Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com www.tauruspowertronics.com 30