PERHITUNGAN KAPASITAS POMPA AIR BERSIH

MAINTENANCE BUILDING PROJECT

Woman
DESCRIPTION Man Toilet Pantry TOTAL L/min TOTAL Remarks
NO. Toilet

1 Closet (Jongkok) Toto : CE 6 1 1 0 2 10 20

2 Closet (Duduk) Toto : CW 421 0 2 0 2 10 20

3 Urinal Toto : U 57 M 0 4 0 4 20 80

4 Lavatory Toto : LW 220 J/ TGL 220 M 1 2 0 3 8 24

5 Faucet Toto : T 23 B 13 (N) 2 3 1 6 4 24

6 Shower - 0 1 0 1 20 20

18 TOTAL 188

Q = 188 L/min x 18% = 155 L/Min x 1.1 = 170 L/Min H1 = 100 m x 0.03 = 3.00 m
Qh = 170 x 60 ÷ 3 = 3,200 L/Hr H2 = 50% H1 = 1.50 m
Qd = 3,400 L/h x 10 h = 34,000 L/day ( 34 M³ ) H3 = Actual Height = 4.00 m
H4 = Suction Height = 1.50 m
H5 = Discharge Pressure ( 0.7 Kg/cm² ) = 7.00 m
17 x 1.1 = 18.7 = 20 mH
Pompa yang dipilih, Booster Pump.
Dengan kapasitas 2 x 100 L / min x 20 mH
Jumlah pompa 1 set ( 1 set = 2 pompa )