Welcome to Braunschweiger Flammenfilter GmbH. In your hand, you are holding the most recent edition of our catalogue.
Braunschweiger Flammenfilter GmbH is a medium sized company with over 400 co-workers in multiple locations
worldwide. With 12 subsidiaries we are present on all continents. Under the brand name PROTEGO®, we manufacture
a wide range of safety devices and tank accessories where as a market leader we have specialized in this field.
We are ready to advise our customers worldwide with products you can trust whether for process engineering
applications, chemicals production, pharmaceutical, petroleum or the biogas industry.
For over 60 years, Braunschweiger Flammenfilter GmbH is known for its efficient know-how in developing safety devices
particularly for the production, storage and transport of flammable liquids and gases.
Our customers find that we achieve top-level performance of:
● Problem solving
● Quality
● Consulting/Advising
● Environmental preservation
Together with our subsidiaries and sales partners such as PROTEGO® Authorized Repair Centers (PARC) we
accomplish this mission globally.
As a medium sized family owned business we have maintained power and flexibility and are financially independent of our
partners. We are proud of our highly qualified and motivated staff with whom we continuously evolve and develop into the
future.
Illuminate yourself with an oversight of our competence and perspective of teamwork at Braunschweiger Flammenfilter
GmbH.
5
PROTEGO® Product Overview
All rights and alterations reserved acc. ISO 16016; additional devices available on request
6
Information at a glance
New additions to our catalogue New products are marked with the symbol shown
on the right.
NEW
QR codes in the catalogue Scan the QR code for speedy access to additional
information online.
7
Contents
Catalogue
Flame Arresters
Valves
Pressure and Vacuum Relief Valves with Flame Arresters, end-of-line.......................... Volume 7
8
PROTEGO® Technology
Volume 1
Volume 1
• Flame Arresters
• Valves
• Tank Accessories
10 KA / 1 / 0218 / GB
Contents
PROTEGO® – about us 12
Technical Fundamentals 14
Flame Arresters.................................................................................................................................................................. 14
Pressure and Vacuum Relief Valves...................................................................................................................................19
Pressure and Vacuum Relief Valves with Flame Arresters................................................................................................. 24
Venting Requirements of Aboveground Storage Tanks - Sizing and Calculation Formulas............................................... 26
Appendix 44
Regulations, Laws, Standards and PROTEGO Publications............................................................................................ 44
®
Glossary..............................................................................................................................................................................46
Materials, Units and Conversion Factors........................................................................................................................... 56
Data Sheet for PROTEGO® Devices.................................................................................................................................. 57
KA / 1 / 0316 / GB 11
PROTEGO® - about us
Corporate Video
12 KA / 1 / 1217 / GB
Competences Maintenance & Service Contact
KA / 1 / 0218 / GB 13
Technical Fundamentals
Flame Arresters
Flame Arresters
Development
Flame arresters protect systems subject to explosion
hazards from the effects of explosions. Ever since methane gas
explosions were successfully suppressed in the mining industry
in the mid-19th century by the development of the mine shaft
lamp with a Davy screen, solutions have been found for making
systems safer in modern hydrocarbon chemistry, where much
more hazardous gases are used.
In addition, filling stations became necessary with the introduc-
tion of the automobile. With filling station tanks, the problem
of explosive vapours arose, consisting of hydrocarbons and
air that form around the tanks and loading equipment, which
can ignite. Given the need for safe handling in dangerous
atmospheres, the large oil companies advanced the deve-
lopment of protective devices for both industrial and military
applications.
Initial successes were achieved with gravel pots that were used
on fuel tanks. The entrance of an explosion in the atmosphere
into the storage tank or into the connected line was stopped by
the gravel, and the flame was extinguished. The tank remained
protected. The problem with loose gravel, however, is the not Figure 1a: Flamefilter® wound out of corrugated metal strips
reproducible flame arresting capability and the high pressure
losses. In 1929, a new development was patented that replaced
the loose gravel with wound corrugated strips of metal (Fig. 1a).
Together with the patented shock-absorber, a protective device
was developed that stopped detonative combustion processes
in the pipe at minimum pressure loss. The PROTEGO® deto-
nation flame arrester – developed by Robert Leinemann – was
born (Fig. 1b). It was given its name many years later in 1954
when Robert Leinemann founded his company Braunschweiger
Flammenfilter.
As chemical processes developed, the requirements on protec-
tive devices became increasingly complex. To this the require-
ments of environmental protection were added. Vapours from
processes needed to be disposed in an environmentally friendly
manner and supplied to combustion systems according to clean-
air regulations. The continuously or only occasionally explosive
mixture was sent to an ignition source during operation. These
particular hazards had to be countered with special measures.
PROTEGO® flame arresters offer reliable protection in plant
systems; these flame arresters always correspond to the state-
of-the-art as a result of continuous research and development.
14 KA / 1 / 0218 / GB
Combustion Processes
Explosive mixtures can burn in various ways. The following,
among other things, can influence the combustion process: the
chemical composition of the mixture, possible pressure waves,
pre-compression, the geometric shape of the combustion cham-
ber, and the flame propagation speed.
The relevant combustion processes for flame arresters are
defined by international standards:
Explosion is the generic term for abrupt oxidation or decompo-
sition reaction producing an increase in temperature, pressure
or both simultaneously [also see EN 1127-1].
Deflagration is an explosion that propagates at subsonic ve- Figure 2: Atmospheric deflagration
lo-city [EN 1127-1]. Depending on the geometric shape of the
combustion area, a distinction is drawn between atmospheric
deflagration, pre-volume deflagration and in-line deflagration.
Atmospheric deflagration (Fig. 2) is an explosion that occurs
in open air without a noticeable increase in pressure.
Pre-volume deflagration (Fig. 3) is an explosion in a confined
volume (such as within a vessel) initiated by an internal ignition
source.
In-line deflagration (Fig. 5) is an accelerated explosion within
Figure 3: Pre-volume deflagration
a pipe that moves along the axis of the pipe at the flame propa-
gation speed.
Stabilized burning is the even, steady burning of a flame,
stabilized at or close to the flame arrester element. A distinction
is drawn between short time burning (stabilized burning for a
specific period) and endurance burning (stabilized burning for
an unlimited period) (Fig. 4).
Detonation is an explosion propagating at supersonic
velocity and is characterised by a shock wave [EN 1127-1].
A distinction is drawn between stable detonations and unstab-
le detonations (Fig. 5).
A detonation is stable when it progresses through a confined Figure 4: Stabilized burning
system without a significant variation of velocity and pressure
characteristic (for atmospheric conditions, test mixtures and
test procedures typical velocities are between 1,600 and 2,200 accelerating
deflagration
unstable
detonation L
stable
detonation
meter/second). A detonation is unstable during the transition Transition zone
(DDT)
of the combustion process from a deflagration into a stable
detonation. The transition occurs in a spatially limited area in
which the velocity of the combustion wave is not constant and
where the explosion pressure is significantly higher than in a
stable detonation. NOTE: The position of this transition zone
depends, among others, on the operating pressure and operating
V→
p→
temperature, on the pipe diameter, the pipe configuration, the Velocity of the flame front
Pressure built-up caused by volume-
test gas and the explosion group and must be predetermined by expansion of the burnt mixture
KA / 1 / 0514 / GB 15
Technical Fundamentals
Flame Arresters
Master Types
Flame arresters are subdivided into different types depending
upon the combustion process (Endurance burning, Deflagration,
energy dissipation
Detonation and the various sub-groups) and in accordance to into the
the installation (in-line, end-of-line, in equipment). boundary layer
and forms the flame arrester element. The principle of flame energy dissipation
into the
quenching in small gaps is applied in PROTEGO® end-of-line boundary layer
flame arresters and PROTEGO® in-line flame arresters (volume
2, 3, 4 and 7).
burnt mixture flame front unburnt mixture
When a mixture ignites in a gap between two walls, the flame
spreads towards the non-combusted mixture. The expansion in
volume of the combusted mixture pre-compresses the non-com- total energy dissipation
busted mixture and accelerates the flame.
By heat dissipation in the boundary layer “s”, transferring it to breakdown of
the large surface of the gap-length compared to the gap-width energy flow
Plan view
Figure 7:
FLAMEFILTER® (a) with gap widths and gap lengths and
PROTEGO® flame arrester unit (b) with FLAMEFILTER®,
spacer and FLAMEFILTER® cage
16 KA / 1 / 0514 / GB
Definitions
1. Flame arresters (Fig. 8a) are devices that are installed c) Dynamic flame arresters
at the opening of an enclosure or to the connecting pipe
High velocity flame arresters are designed to produce flow
of a system of enclosures and whose intended function
velocities under operating conditions which exceed the flame
is to allow flow but prevent the transmission of flame.
velocity of the explosive mixture thus preventing flame trans-
mission. This principle is applied in PROTEGO® Pressure Relief
Diaphragm Valves (Vol. 7) and in PROTEGO® High Velocity
8a Valves (Vol. 7) with appropriate high set pressure.
Flame arresters are type-examined Protective Systems in
accordance with ATEX directive and are marked with CE.
They are tested according to EN ISO 16852. They are
certified in accordance with the specific requirements of the
standard. Any certification according to other international
standards is shown by marking with the appropriate indication.
8b
water which acts like a liquid barrier. The PROTEGO® hydraulic IIB2 > 0,75 C Ethene
flame arrester is designed and certified to stop deflagrations, IIB3 > 0,65 C Ethene
detonations and endurance burning combustions. It is tailor-ma-
IIB > 0,5 B Hydrogen
de with regard to the specific customers requirements (Vol. 4).
IIC < 0,5 B Hydrogen
When installing the PROTEGO® hydraulic flame arrester as in-
line flame arrester, as vent header collection drum and back * former designation Expl. Gr. I
flow preventer in vapour collecting lines close to the incinerator,
The following table shows the categorization
important safety measures have to be taken into consideration
of substances into the respective explosion
to assure the required explosion safety.
group corresponding to their MESG
(IEC 79-1, EN ISO 16852).
KA / 1 / 0316 / GB 17
Technical Fundamentals
Flame Arresters
Please refer to more specific literature (especially technical ves (see Volume 7: Pressure and Vacuum Relief Valves with
information concerning safety ratings) for the MESG of PROTEGO® flame arresters).
individual substances, additional ratings and characteristic PROTEGO® Pre-volume flame arresters are flame arresters
substance quantities. This information is provided by which avoid flame transmission from the inside of an explosion-
PROTEGO® upon special request. proof vessel to the outside or to a conntected pipe.
As the pressure and temperature increase, the load on the flame PROTEGO® In-line flame arresters protect against deflagrati-
arresters generally increases. Flame arresters that have been on , stable or unstable detonations in pipes. Stable detonation
tested under standard conditions are approved and can be flame arresters avoid an explosion transmission of deflagrations
used up to 60°C (140°F) and 1.1 bar (15.9 psi). If the operating and stable detonations. In-line flame arresters which are tested
temperature and/or the operating pressure is higher, the flame against unstable detonations protect from deflagrations, stable
arrester must undergo a special examination for the higher ope- and unstable detonations.
rating parameters. The flame arresters should be located according to their spe-
cified use. In the case of in-line deflagration flame arresters,
PROTEGO offers flame arresters for the above mentioned ex-
®
make sure that the allowable L/D (L = distance between the igni-
plosion groups for higher pressures (>1.1bar abs, 15.9 psi) and tion source and the installation location of the flame arrester,
higher temperatures (>60°C, 140°F) as required by the D = pipe diameter) is not exceeded and that the in-line defla-
operating pressure or temperature. gration flame arresters are not installed too far from the ignition
Location of installation source, so that they are not subject to a detonation because the
path is too long. The allowable L/D is stated in the manufactu-
Depending on the location of installation, the flame arresters rers manual of the flame arrester.
must fulfill various protective tasks:
Selection
At the opening of a system part to the atmosphere
▬► End-of-line flame arrester The effectiveness of flame arresters must be tested and
At the opening of an equipment onto a connecting pipe approved. Flame arresters are categorized according to the
▬► Pre-volume flame arrester combustion process and the installation site.
In the pipe
The selection criteria are described in the appropriate volumes.
▬► In-line flame arrester
The different variations and wide range of types arises from the
PROTEGO® End-of-line flame arresters protect against at- tailored solutions for different applications. PROTEGO® flame
mospheric deflagrations and stabilised burning — either short arresters are generally service-friendly due to the modular de-
time burning or endurance burning. They can only be connected sign of the flame arrester unit. Special details of the design (pa-
on one side and can not be installed in the pipe. PROTEGO® tented Shock Wave Guide Tube Effect SWGTE or Shock-absor-
end-of-line flame arresters can however be combined with val- ber) enable a superior flow due to the minimum pressure loss.
Location of End-of-line On- In-line
Installation equipment
18 KA / 1 / 0514 / GB
Technical Fundamentals
Pressure and Vacuum Relief Valves
Valves
KA / 1 / 0218 / GB 19
Technical Fundamentals
Pressure and Vacuum Relief Valves
The sealing between valve pallet and valve seat is provided by After the initial response, the rise in pressure is proportional to
an FEP air cushion seal, a metal to metal sealing, or PTFE flat the discharged flow up to a full lift. When the back pressure in
sealing depending on the set pressure or on the application. The the connected pipeline is high or the valve is installed in com-
best sealing is obtained with a metal valve disc lapped to be bination with a pressure control valve, this method provides
seated on the metal valve seat (metal to metal). When the set greater stability for the overall system. However, the overall flow
pressures are low, an FEP air cushion seal provides a tight seal. performance is not as good as that of valves with full-lift valve
The tightness of the PROTEGO® valves is far above the normal pallets. These valve pallets (Fig. 6) are primarily used in in-line
standard (API2000 resp. EN ISO 28300) and hence meets the valves when required by operating conditions.
stringent demands of emission control regulations.
Depending on the design of the valve and the valve pallets, the
PROTEGO® pressure and vacuum relief valves with full-lift design pressure and design vacuum (negative gauge pressure)
pallet discharge the flow within 10% overpressure from the set is achieved with different overpressure (Fig. 7).
pressure to a fully opened valve (full-lift). Unless otherwise agreed, the standard PROTEGO® valve
design is for 10% technology.
Tank pressure
Design point
e
↓ sur
rpres
ove
closed Discharge with full-lift
of the valve pallet rim with the adapted, machined and lapped
valve seat. In addition, the flow-enhancing design reinforces the
overall effect on the outflow side. These valve pallets are used Figure 7: Opening characteristics of valves with different
in end-of-line and in-line valves. overpressure levels
20 KA / 1 / 0514 / GB
pressure can be maintained with safety valves that are not
subject to the regulations of Pressure Equipment Directive
(PED). They need to meet other criteria however: Provide a
good seal, be frostproof, trouble-free and easy to maintain.
PROTEGO® pressure and vacuum conservation valves meet
these requirements while being highly efficient, operate stable
and offer safe function even at very low pressures due to the
10% technology. In addition emissions of the products are
reduced.
National and international technical regulations for maintaining
Figure 8: Diaphragm Valve PROTEGO® UB/SF-0
clean air serve as the basis for calculating savings (such as
The self-controlled PROTEGO® pilot operated valve VDI 3479: “Emission Control - Marketing Installation Tank
(Fig. 9) discharges the flow without requiring additional overpres- Farms”, VOC Directive 1999/13/EC and 94/63/EC or API MPMS
sure. Up to the set pressure until the pilot reacts, the valve remains Chapter 19.1: “API Manual of Petroleum Measurement
sealed; it immediately opens in a full-lift after the set pressure Standards - Chapter 19, Evaporative Loss Measurement,
is reached without overpressure and releases the cross-section Section 1 - Evaporative Loss from Fixed-Roof Tanks, 3rd Edition”).
of the valve (set pressure = opening pressure). As the pressure The design of the tank, the paint, the insulation, and pressu-
increases, the seal increases up to the set pressure. Once the re maintenance via the valves influence - among others - the
flow is discharged and the pressure falls below the opening reduction of emissions.
pressure, the valve recloses. PROTEGO® pilot valves are
The effect that pressure maintenance has on the reduction
generally used as safety relief valves for low-temperature
of product (vapour) loss improves as the set pressure of the
storage tanks or wherever the valve must be very tightly sealed
valve approaches the maximum allowable tank pressure. The
up to the set pressure.
flow needs to be reliably discharged without the tank rupturing.
A comparison of product loss at different overpressures clearly
reveals the advantages of the 10% technology over the 40%
overpressure and especially in contrast to a 100% overpressure:
The specially developed design yields measurable savings by
decreasing the accumulation up to the required performance
(Fig. 10).
Emission reduction at a petrol storage tank with 20 mbar
max. allowable tank pressure and different valve technologies
80
70
60
% Emmission reduction
50
40
30
Figure 9: pilot operated pressure relief valve PROTEGO® PM/DS 71 65 51 35
20
KA / 1 / 0316 / GB 21
Technical Fundamentals
Pressure and Vacuum Relief Valves
22 KA / 1 / 0514 / GB
Operating states of pressure and vacuum relief valves: The When the design flow is not being reached during discharge the
valve is optimally sized when the operating point lies on the valve does not open completely. The valve pallet only lifts briefly,
performance curve, i.e., when the attained maximum flow is discharges the volume, and then recloses when the pressure
discharged with the valve completely open without requiring an falls below the set pressure. The reseating pressure depends
additional overpressure (with completely open valve) (full-load on the design of the valve pallet and the geometry of the valve.
operating range A, Fig. 12). There are partial-load operating ranges in which the full-lift is
not reached (over-sized valves) and overload ranges in which
an additional overpressure is required after a full lift to discharge
the flow (under-sized valves). Within the overload range, the
valve is stable; in the partial load range, the valve pallet can
flutter due to instability. A proper sizing that takes possible
operating conditions into consideration is therefore essential.
Selection
Flow (m /h)
3
The valves are selected using the above selection criteria
depending on the location of installation and whether the
opening pressure resp. tank design pressure
set pressure = overpressure %
valve is to function as a pressure relief valve, vacuum relief
1+
100% valve, or combined pressure and vacuum relief valve.
Figure 12: Design and operating points in the flow chart
Function Pressure Relief Vacuum Relief Pressure and Pressure Pressure or Pressure and Blanketing
Valves Valves Vacuum Relief Relief and Vacuum Relief Vacuum Relief Valves
Valves Vacuum Valves Valves
Valves, pilot
operated
Example of → Storage tank, page 35 → Vent header, page 35
Use
PROTEGO® has the right valve for all applications For venting of tanks storing products at low temperatures and
storing critical products
For venting of storage tanks and vessels
▬► PROTEGO® Pressure and Vacuum Relief Valves, ▬► PROTEGO® Pressure / Vacuum Relief
end-of-line (Vol. 5) Diaphragm Valves, end-of-line (Vol. 5)
As overflow valves or backflow preventers
▬► PROTEGO® Pressure or Vacuum Relief Valves,
in-line (Vol. 6)
KA / 1 / 0311 / GB 23
Technical Fundamentals
Pressure and Vacuum Relief Valves with Flame Arresters
Figure 2:
Pressure and vacuum relief valve protecting against deflagration and
endurance burning PROTEGO® VD/SV-HR
24 KA / 1 / 0316 / GB
Location of installation
Valves with flame arrester units are always end-of-line valves
since the heat must be released to the environment with no
heat build-up to prevent transmission of flame. Otherwise the
unallowable heat build-up would effect a heat accumulation at
the flame arrester which finally results in a flash-back. They are
primarily used for storage tanks and containers in which flammable
liquids are stored or processed and for relief openings in
process containers in which the occurence of explosive mixtures
cannot be excluded.
Design and operating states of valves
Figure 3a: Endurance-burning test with The sizing and operating states of the pressure and vacuum
diaphragm valve PROTEGO® UB/SF relief valves are described on pages 22 and 23.
Selection
The high velocity valve (Fig. 4) has special flame-transmission
protection with a dynamic discharge between the valve cone Since PROTEGO® pressure/vacuum relief valves with flame
and valve seat starting at a set pressure of +60 mbar (24 inch arrester units are always end-of-line valves, they are selected
W.C.). The high velocity valve is endurance burning proof. taking into consideration their function as a pressure valve,
vacuum valve, or combined pressure and vacuum relief valve.
After the explosion group of the products and the possible
combustion process have been determined, the valve can be
selected regarding its flame-transmission protection. When
selecting PROTEGO® valves with a flame arrester unit, one must
establish whether flame-transmission protection is to be provided
against atmospheric deflagrations or endurance burning.
Endurance burning flame arresters include protection against
atmospheric deflagrations. Flame-transmission-proof vacuum
relief valves are deflagration-proof. The danger of a stabilized
burning does not exist for vacuum relief valves.
Function Pressure Relief Vacuum Relief Pressure and Pressure- / Vacuum High Velocity Valve
Valve with Flame Valve with Flame Vacuum Relief Relief Diaphragm Valve
Arrester Arrester Valve with Flame with Flame Arrester
Arrester
Example of Use → Storage tank, Emergency venting / pressure relief, page 35 → Storage tank,
Tank ships, page 38
PROTEGO® has the right valve for all applications. For frost-proof application, for critical products, and for flame-
For flame-transmission-proof pressure and vacuum relief of transmission-proof pressure and vacuum relief of tanks and
storage tanks and containers containers
▬► PROTEGO® Pressure and Vacuum Relief Valves with ▬► PROTEGO® Pressure -/ Vacuum Relief Diaphragm
Flame Arresters, end-of-line Valves
For flame-transmission-proof pressure and
vacuum relief of tank ships
▬► PROTEGO® High Velocity Valves
KA / 1 / 0514 / GB 25
Technical Fundamentals
Venting Requirements of Aboveground Storage Tanks - Sizing and Calculation Formulas
Pressure Terms and Definitions adjusted only 10% below the opening pressure. In accordance
Tanks storing flammable and non-flammable liquids are to EN 14015 and API 650 (Fig. 1A and 1B) the design
designed and manufactured in accordance to different standards: pressure or MAWP = Maximum Allowable Working Pressure
EN 14015, API 620 or API 650 are the most important standards of the tank must not be exceeded not even in fire-case or
worldwide. Depending on the standard different maximum tank system mal-function. Following API 620 (Fig. 1C) the valve
pressures are allowable to relief the required massflow. must relief the required regular massflow out of thermal
influences and pumping at 10% above the design pressure (in
Fig. 1 shows the most common terms for tanks and valves. general the MAWP) at the latest. For fire-case or emergency an
This comparison clarifies the sizing of end-of-line relief valves overpressure of 20% is allowable: after exceeding the MAWP
featuring the 10% overpressure technology with a set pressure by maximum 20% the required emergency massflow must be
Figure 1: API 620
Comparison of pressure terms for storage tanks and vent valves designed and manufactured in
accordance to different standards (e.g. API 620 or API 650 or EN 14015) equipped with pressure Tank Valve
relief devices (illustration simplified and based on 10% overpressure technology of the valve).
The different definition of the term accumulation is explained on Page 22. p
p p
accumulation
design pressure 100 opening Internal Design 100 opening MAWP 100 set pressure
= test pressure pressure Pressure pressure (Design)
for tanks with
p<10mbar
blow down
overpressure overpressure
OPP
operating 90 set pressure (< Internal 90 set pressure OPP 90 reseating
pressure Design (< MAWP) pressure
(< design Pressure)
pressure) blow down blow down
reseating reseating
pressure pressure
% of design pressure = p = % of opening pressure % of MAWP = p = % of opening pressure % of MAWP = p = % of set pressure
design pressure opening pressure internal design opening pressure MAAP Max. allowable set
= calculated pressure < design pressure; pressure < internal design = Maximum Allowable pressure
= Maximum Allowab- = max. relieving pres- pressure Acumulated Pressure = MAWP for 10%
le Working Pressure set pressure = 0,9 x sure under operating = max. relieving pres- overpressure
(MAWP) to be not opening pressure for condition, fire con- set pressure = 0,9 x sure under operating technology.
exceeded at all ope- 10% overpressure dition or emergency opening pressure for condition (max. re- MAWP = Maximum
rating conditions. For technology. (max. relieving pres- 10% overpressure lieving pressure for Allowable Working
fire and emergency sure for valve and technology. valve). Relief Pres- Pressure
conditions weak roof emergency valve). sure for fire-case or
to shell attachment or emergency condition
emergency relief val- OPP = Operating relief at 20% excess
ves to be provided. Figure 1A Pressure Figure 1B overpressure. Figure 1C
26 KA / 1 / 0514 / GB
Engineering Service QuEST - Quick Engineering and Sizing Tool
relieved. Fig. 2 shows the procedure to determine the set pressure is a result of the opening pressure minus the overpressure of the
for valves with different overpressure characteristics by considering valve which is a characteristic of the specific valve. If the tank
the specific tank design pressure. These examples are for end-of- is manufactured in accordance to API 620 the opening pressure
line relief valves only without a back-pressure originated by e.g. may exceed the tank design pressure by 10% for regular brea-
connected pipe-away-line. If the tank is designed in accordance to thing and 20% for fire-case (Fig. 2B). The set pressure again is
EN 14015 or API 650 the opening pressure must not exceed the the result of the opening pressure minus the valve-characteristic
design pressure (=MAWP) of the tank (Fig. 2A). The set pressure overpressure.
design
100 opening pressure MAWP 100 set pressure set
pressure (Design) for 10% pressure
overpressure overpressure
for fire
PROTEGO (conventional vent
10% Technology valves)
overpressure
(conventional vent
90 set pressure max. 90 valves)
for 10% allowable
overpressure in
overpressure accordance to reseating
DIN/TRbF
pressure
80 80
set pressure
overpressure for 40%
reseating (conventional vent
overpressure
pressure valves)
70 set pressure 70
for 40%
overpressure
reseating
pressure
60 60
set pressure
reseating for 100%
pressure overpressure
40 reseating 40
Figure 2A: Design in acc. to EN 14015 or API 650 pressure Figure 2B: Design in acc. to API 620
KA / 1 / 0218 / GB 27
Technical Fundamentals
Venting Requirements of Aboveground Storage Tanks - Sizing and Calculation Formulas
Calculation of the Out- and Inbreathing venting Particular influences to be considered are e.g.:
capacity in acc. to ISO 28300/API 2000: Failure of the nitrogen blanketing valve – Installation of an
The maximum required venting capacity is the total amount of additional emergency relief valve to vent the non calculated
pump capacity and capacity out of thermal influences: flow which was not foreseen under operation
. . .
V out = V thermal out + V pump in Filling the empty hot tank with cold liquid product –
Considering the additional flow due to the sudden cooling
. . . down when calculating the necessary vacuum capacity
V in = V thermal in + V pump out
Exceeding the maximum given pump out capacity –
The calculation of the maximum required capacity out of the Considering a safety factor when calculating the required
thermal influences is based on ISO 28300 with regard to above- inbreathing capacity
ground storage tanks with or without insulation.
28 KA / 1 / 0917 / GB
Calcuation of emergency venting capacity according to API 2000 5th edition and ISO 28300
Excerpt of API 2000 5th ed. Excerpt of API 2000 5th ed.
Figure 2A Figure 2B
KA / 1 / 0218 / GB 29
Technical Fundamentals
Venting Requirements of Aboveground Storage Tanks - Sizing and Calculation Formulas
Emergency Venting required for Fire Exposure Emergency Venting required for Fire Exposure
Versus Wetted Surface Area Versus Wetted Surface Area
(English Units) (Metric Units)
. .
Wetted Area A Venting Requirement V Wetted Area A Venting Requirement V
square feet SCFH m2 Nm3/h
20 21.100 2 608
40 42.100 4 1.217
60 63.200 6 1.825
80 84.200 8 2.434
Excerpt of API 2000 5th ed. Excerpt of API 2000 5th ed.
Figure 3A Figure 3B
Excerpt of API 2000 5th ed. Excerpt of API 2000 5th ed.
Figure 4A Figure 4B
30 KA / 1 / 0909 / GB
Conversion of operational flow into equivalent
diagram flow for use of flow charts
To use the flow charts (pressure vs. flow diagram) by conside-
ring the operational and product data, it is necessary to convert
.
the given operational flow V B,Gas into the equivalent diagram-
. .
flow V Dia. This V Dia then creates the same pressure loss as the
actual operational flow.
.
1) Conversion of the operational flow V B,Gas into the standard
.
flow V N,Gas:
. . T * pB . pB * 273,15K
VN, Gas = V B, Gas * N = VB, Gas *
TB * pN TB * 1,013 bar abs.
.
2) Conversion of the standard flow V N,Gas into the equivalent
.
diagram flow V Dia:
. . p N, Gas *pN *TB
VDia = VN, Gas *
p Dia *pG *TN
Terms
.
V = Flow m3/h (CFH)
p = Pressure bar abs (psi abs)
T = Temperature K
v = Volume fraction
Indices
N = Standard condition (at 1,013 bar abs and 273,15 K)
B = Operational condition (pressure and temperature
in acc. to operation)
Gas = Actual product
Dia = Related to the Diagram, when using the flow chart for
sizing (pDia=1,189 kg/m3 related density of air at 20 °C
and 1 bar abs.)
G = related to the outlet of the device ( pG back pressure)
for operating conditions
KA / 1 / 0514 / GB 31
Technical Fundamentals
Venting Requirements of Aboveground Storage Tanks - Sizing and Calculation Formulas
Zone 1
Non water soluble
A place in which an explosive atmosphere consisting of a
previous actual
mixture of air with flammable substances in the form of
(A I FP< 21 °C) FP < 0 °C (32°F) Extremely flammable gas, vapour or mist is likely to occur in normal operation
FP < 21 °C (70°F) Highly flammable occasionally.
(A II FP 21–55 °C) FP 21-55°C (70-131°F) Flammable
Zone 2
(A III FP 55–100 °C) -
A place in which an explosive atmosphere consisting of
a mixture of air with flammable substances in the form of
Water soluble
gas, vapour or mist is not likely to occur in normal
previous actual
operation but, if it does occur, will persist for a short
(B < FP 21 °C) FP < 0 °C (32°F) Extremely flammable period only.
FP < 21 °C (70°F) Highly flammable
FP 21–55 °C (70-131°F) Flammable To work out a risk assessment, the possible ignition sources
must be evaluated under normal operating conditions as well
FP = Flashpoint as under special operating conditions like cleaning and mainte-
nance work (see EN 1127-1):
Products with a flashpoint FP>55°C (>131°F) get flammable
when being heated close to the flashpoint (∆T = 5 degree safety effective ignition source:
margin as a rule of thumb for hydrocarbons as well as 15 de- Steady and continuously under normal operation
gree for mixtures). Solely as a result of malfunctions
Vapours: classification of the gas/vapour-air-mixtures in Solely as a result of rare malfunctions
accordance to the MESG of the products or the mixture into Effective ignition sources are chemical reactions, flames and
the Explosion Groups IIA1, IIA, IIB1, IIB2, IIB3, IIB and IIC (page hot gases, hot surfaces, mechanical generated sparks, static
17) (NEC Group D, C and B). electricity, lightning, electromagnetic waves, ultrasonics,
adiabatic compression, shock waves etc.
Effectiveness of the ignition source is to be compared to the
flammability of the flammable substance.
32 KA / 1 / 0316 / GB
Step 5
Selection, number and location of the suitable Equipment,
Protective System and Component must follow the require-
ments of national and international regulations (ATEX Directive).
For equipment (blowers, agitators, containers etc.)
KA / 1 / 0316 / GB 33
Safe Systems in Practice
Overview
Applications
34 KA / 1 / 0218 / GB
Safe Systems in Practice
Storage Tanks in Tank Farms for Refineries and Chemical Processing Plants (exemplary)
Storage Tanks
UB/SF DV/ZT
P/EB
P/EB EB EB DR/ES
AL/DK D/SR
DR/ES
SV/E SV/E
SE/K
LDA-F SA/S
LDA-W LDA-WF
VD/SV
VD/SV-HRL DV/ZW DV/ZT UB/SF
DR/ES DR/ES
DR/ES
LDA-W LDA-WF
PV/EBR
VD/SV
ER/V
7
LDA-F
DR/ES
DA-G
EF/V LDA
1 Floating-roof storage tank with floating-roof drainage vacuum safety relief valve DV/ZT or DV/ZW (→ Volume 6),
system SE/K (→ Volume 8), roof valve D/SR (→ Volume 8), liquid detonation arrester in the filling line LDA-W and
stem-actuated valve AL/DK (→ Volume 8) with deflagration emptying line LDA-WF (→ Volume 4)
flame arresters EB (→ Volume 2) 5 Fixed-roof storage tank for non-flammable liquids with
2 Fixed-roof storage tank for flammable liquids with pressure pressure and vacuum conservation valve VD/SV
and vacuum diaphragm valve UB/SF (→ Volume 7), liquid (→ Volume 5) and emergency pressure relief valve ER/V
detonation flame arrester LDA-F (→ Volume 4), in the (→ Volume 5) instead of weak seam
protective gas blanket line DR/ES (→ Volume 4) with DV/ZT
6 Underground storage tank with safety devices in the filling
(→ Volume 6)
line LDA-F (→ Volume 4), detonation flame arrester in the
3 Fixed-roof storage tank for flammable liquids with pres- drain line DR/ES (→ Volume 4), and in the vent line DR/ES
sure safety relief valve P/EB (→ Volume 7) and vacuum (→ Volume 4) and VD/SV (→ Volume 5)
safety relief valve SV/E (→ Volume 7), liquid detonation
7 Aboveground tank for flammable liquids with pressure and
flame arrester LDA-W (→ Volume 4) and/or LDA-W-F
vacuum safety relief valve PV/EBR (→ Volume 7), liquid
(→ Volume 4) in the filling and emptying line, float-controlled
detonation flame arrester LDA (→ Volume 4) in the filling
swing pipe system SA/S (→ Volume 8), detonation-proof
line and an additional detonation flame arrester DA-G
gas displacement connection DR/ES (→ Volume 4)
(→ Volume 4) ensures that the tank is not emptied, detonation
4 Fixed-roof storage tank for flammable liquids with pressure proof foot valve for suction line EF/V (→ Volume 4),
and vacuum relief valve VD/SV-HRL (→ Volume 7), pressu- detonation flame arrester DR/ES (→ Volume 4) in vapour
re and vacuum relief diaphragm valve UB/SF (→ Volume 7), return pipeline.
connection to gas vent header system with detonation fla-
me arrester DR/ES (→ Volume 4) and in-line pressure and
KA / 1 / 0218 / GB 35
Safe Systems in Practice
Chemical and Pharmaceutical Processing Facilities (exemplary)
UB/SF DR/ES-V 5
SV/T-0-SH
SD/BS-SH DR/SE-SH
UB/SF
DZ/T
DR/ES
DR/ES DR/ES
DR/ES
DR/ES 3
FA-I-T
4
FA-I-P
FA-I-V-T FA-I-T
1 Tank farms for flammable liquids with pressure and vacuum 4 Protecting pressure-resistant radial blowers as type-
relief diaphragm valve UB/SF (→ Volume 7), connection examined zone-0 blowers with integrated PROTEGO®
to gas vent header system with detonation flame arrester flame arresters FA-I-V-T and FA-I-P (→ Volume 3)
DR/ES-V or DR/ES (→ Volume 4) and pressure or vacuum 5 Protection of storage tanks for media that can only be
relief valve DZ/T (→ Volume 6)
pumped with assistance of heating systems. These appli-
2 Ventilation of industrial mixers and process vessels in a cations, e.g. bitumen storage, need fully heated devices
common vapour vent header via detonation flame arresters such as the pressure relief valve SD / BS - H (→ Volume 5),
DR/ES (→ Volume 4) vacuum relief valve SV / T - 0 - H (→ Volume 5) and
heated detonation flame arrester DR / SE – SH to a heating
3 Temperature-monitored deflagration flame arresters
temperature of the heating jacket to 320 ° C at 6 bar.
FA-I-T (→ Volume 3) in the feed line for vapour combustion
at the maximum allowable distance from the ignition source
and in parallel for the sake of availability for servicing or
emergency switching in case of an endurance burning on
the arrester. Vapour pipeline from plant to vapour combusti-
on unit with deflagration flame arrester FA-I-T (→ Volume 3)
to protect the vent header collection line and the operating
locations in the plant.
36 KA / 1 / 0218 / GB
Safe Systems in Practice
Vapour Combustion Systems and Flares (exemplary)
VD/SV-HRL
EB
DA-SB-T
DR/SBW
FA-I-T
FA-I-T
FA-I-T
1 Flare pipes or ground flares with detonation flame 4 Temperature-monitored deflagration flame arresters
arresters DA-SB-T (→ Volume 4) FA-I-T (→ Volume 3) in the feed line for vapour combustion
at the maximum allowable distance from the ignition source
2 Emergency pressure relief stack with endurance-
and in parallel for the sake of availability for servicing or
burning-proof pressure and vacuum relief valve
emergency switching in case of an endurance burning on
VD/SV-HRL (→ Volume 7)
the arrester
3 Gasholder with detonation flame arrester DR/SBW
Vapour pipeline from plant to vapour combustion unit with
(→ Volume 4) in the gas supply and end-of-line
deflagration flame arrester FA-I-T (→ Volume 3) to protect
deflagration flame arrester EB (→ Volume 2), which
the vent header collection line and the operating locations
protects against endurance burning, above the diaphragm
in the plant.
KA / 1 / 0218 / GB 37
Safe Systems in Practice
Ship Building and Loading Systems (exemplary)
DA-SB
DE/S
SV/E-S
BR/TS
DA-SB DA-SB
DA-SB
1 Tank ships for flammable products/chemical tankers with Not shown: Offshore platforms/drilling platforms with
detonation flame arresters BR/TS (→ Volume 4) on the detonation flame arresters DA-SB (→ Volume 4) and
individual tank, endurance-burning-proof high-velocity vent deflagration flame arresters FA-CN (→ Volume 3), FPSOs
valves DE/S (→ Volume 7), and explosion-proof vacuum (Floating Production Storage and Offloading) with IMO-
flame arrester SV/E-S (→ Volume 7) approved detonation flame arresters DA-SB (→ Volume 4)
and pressure and vacuum relief valves VD/TS (→ Volume 7),
2 Detonation-proof connection of the gas return line at the
hydraulic control boxes with deflagration flame arresters
loading terminal for flammable liquids with a detonation
BE-AD (→ Volume 2)
flame arrester DA-SB (→ Volume 4)
3 Detonation flame arresters DA-SB (→ Volume 4) in the gas
displacement/gas return line from the loading stations for
tank waggons and tank trucks
38 KA / 1 / 0218 / GB
Safe Systems in Practice
Biogas Systems, Wastewater Treatment and Landfill Gas Systems (exemplary)
UB/SF DR/ES
P/EBR
SV/E EB
FA-CN(-T) FA-CN(-T)
FA-CN(-T) FA-CN(-T)
FA-CN(-T)
FA-CN(-T)
1 Protecting the sewage tower and storage tank with a 4 Ground flares, block-type thermal power stations, and diesel
frost-proof pressure and vacuum relief valve UB/SF engine aggregates are potential sources of ignition for
(→ Volume 7) and with detonation flame arresters DR/ES biogas (methane) air mixture. Suitable flame arresters must
(→ Volume 4) in the gas collection line be installed in the pipe toward the system that consider
temperature and pressure. Either temperature-monitored
2 Protecting the desulphurization system with deflagration
deflagration flame arresters FA-CN-T or FA-E-T (→ Volume
flame arresters suitable for temperature and pressure
3) or - at a great distance from the potential ignition source
FA-CN, FA-CN-T alternatively FA-E (→ Volume 3)
- detonation flame arresters DA-SB or DR/ES
3 Protecting the intermediate gasholder in the pressure and (→ Volume 4) are used.
vacuum relief line with endurance burning proof deflagration
flame arrester, end-of-line EB (→ Volume 2), equipping the
emergency vent stack with deflagration and endurance bur-
ning proof pressure relief valve P/EBR (→ Volume 7) and
deflagration proof vacuum relief valve SV/E (→ Volume 7)
KA / 1 / 0218 / GB 39
Safe Systems in Practice
Flame Arresters as integrated Equipment Components (exemplary)
FA-I-P
FA-I-V-T
Blower EV/VD
EV/VS-T
Flamefilter® or PROTEGO® flame arresters as OEM Not shown: Flamefilter® are used in gas analyzers to
components are product varieties, that are integrated by protect the explosive environment from explosions arising
equipment manufacturers in their brand-name products. in the device from the ignition of the gases or vapours to
be measured or analyzed. PROTEGO® flame arresters are
installed in the pressure and vacuum relief openings of air-
1 Protecting pressure-resistant radial blowers as type-
plane fuel tanks to protect from external explosions.
examined zone-0 blowers with integrated PROTEGO®
flame arresters FA-I-V-T and FA-I-P (→ Volume 3)
2 Protecting dry-running vacuum pumps with PROTEGO®
flame arresters EV/VS-T and EV/VD (→ Volume 3) at the
inlet and at the outlet, which are tested and certified
together with the vacuum pump. Other forms of
protection with DR/ES and DR/ES-T (→ Volume 4) are
possible.
40 KA / 1 / 0218 / GB
Safe Systems in Practice
Cryogenic Tanks (exemplary)
Cryogenic Tanks
DA-SB-T
SI/DP
VN-A-PCPF-NV DA-SB
VN-A-PCPF-NV V/SV-XL
LIN-LOX-LAR Storage Tank
DA-SB-T
● ATEX approved Flame Arresters
ITV-S - End-of-line applications
Deflagration flame arresters
Endurance burning proof arresters
- In-line applications
Propylene Storage Tank Deflagration flame arresters
Detonation flame arresters
KA / 1 / 0218 / GB 41
Overview of Products and Services
Catalogue
Flame Arresters
Deflagration Flame Arresters, end-of-line and Vent Caps.................................................................Volume 2
Deflagration flame arresters, deflagration proof, short time burning proof, endurance burning proof
Vent caps without flame arresters
Explosion groups: IIA1, IIA, IIB1, IIB2, IIB3, IIB, IIC
Nominal sizes: 15 to 800 mm (½“ to 32“)
Materials: carbon steel, stainless steel, Hastelloy, ECTFE-coated
Special designs according to customer specifications
Services and spare parts
42 KA / 1 / 0218 / GB
Valves
Pressure and Vacuum Relief Valves, end-of-line .................................................................Volume 5
Pressure relief valves, vacuum relief valves, pressure and vacuum relief valves,
pressure relief and vacuum valves
Pressure settings: 2 to 200 mbar (0.08 to 8 inch W.C.)
Nominal sizes: 50 to 700 mm (2“ to 28“)
Materials: carbon steel, stainless steel, Hastelloy, aluminum, PP, PE, PVDF, PTFE,
ECTFE-coated
Special designs according to customer specifications
Services and spare parts
Pressure and Vacuum Relief Valves with Flame Arresters, end-of-line................................ Volume 7
Pressure relief valves, vacuum relief valves, pressure and vacuum relief valves,
pressure-/vacuum relief diaphragm valves, pressure relief valves, high velocity valves
Deflagration-proof and endurance-burning-proof or deflagration-proof only
Explosion groups: IIA1, IIA, IIB1, IIB2, IIB3, IIB, IIC
Pressure settings: 2 to 200 mbar (0.08 to 8 inch W.C.)
Nominal sizes: 50 to 300 mm (2“ to 12“)
Materials: carbon steel, stainless steel, Hastelloy, ECTFE-coated
Special designs according to customer specifications
Services and spare parts
KA / 1 / 0218 / GB 43
Appendix
Regulations, Laws, Standards and PROTEGO® Publications Standardisation Commitees
Regulations and Laws ASTM F1273-91 Standard Specification for Tank Vent Flame Arresters,
Reapproved 2007
2014/34/EU Directive of the European Parliament and the Council of February
21, 2014 on the approximate of the laws of the Member States concerning NFPA 30 Flammable and Combustible Liquids Code, 2015 ed.
equipment and Protective Systems intended for use in potentially explosive NFPA 36 Standard for Solvent Extraction Plants, 2017 ed.
atmospheres (recast, replace 94/9/EC after April, 20 2016)
NFPA 59A Standard for the Production, Storage, and Handling of Liquefied
94/9/EC Directive of the European Parliament and the Council of March 23, 1994 Natural Gas (LNG), 2016 ed.
on the approximate of the laws of the Member States concerning equipment
NFPA 67 Guide on Explosion Protection for Gaseous Mixtures in Pipe Systems,
and Protective Systems intended for use in potentially explosive atmospheres
2016 ed.
(replaced by 2014/34/EU)
NFPA 68, Venting of Deflagrations, 2013 ed.
1999/92/EC Directive of the Council on minimum requirements for
improving the safety and health of workers potentially at risk from explosive NFPA 69 Standard on Explosion Prevention Systems, 2014 ed.
atmospheres (individual directive according to article 16 of Directive 89/391/EEC)
NFPA 497 Recommended Practice for the Classification of Flammable Vapors
2006/42/EC Directive on machinery of 17 May 2006 and of Hazardous Locations for Electrical Installations in Chemical Process
Areas, 2017 ed.
2014/68/EU (PED) Pressure equipment directive of the European
Parliament and the European Council replace 97/23/EC from 17.7.2015 shall HSG176 The Storage of Flammable Liquids in Tanks, 2015
applied from July 19, 2016
IEC 60079-10-1 Explosive atmospheres. Classification ofareas. Explosive gas
97/23/EC Pressure equipment directive of the European Parliament and the atmospheres, 2016
European Council valid until July 18, 2016
EN 60079-20-1 Explosive atmospheres - Part 20-1: Material characteristics for
1999/13/EC Control of VOC emissions resulting from storage and gas and vapour classification - Test methods and data (IEC 60079-20-1), 2010
distribution of petrol
PD CEN/TR 16793:2016 Guide for the selection, application and use of flame
Standards arresters
EN ISO 28300: Petroleum, petrochemical and natural gas industries - Venting of EN ISO 80079-36: 2016 Explosive atmospheres - Part 36: Non-electrical
atmospheric and low-pressure storage tanks, 2008 equipment for explosive atmospheres - Basic method and requirements
(ISO 80079-36:2016)
EN ISO 16852: Flame Arresters - Performance requirements, test methods and
limits for use, 2016 EN ISO 80079-37:2016 Explosive atmospheres - Part 37: Non-electrical type of
protection constructional safety „c“, control of ignition sources „b“, liquid immersi-
EN 12874 Flame Arresters: Performance Requirements, Test Methods, andLimits
on „k“ (ISO 80079-37: 2016) (Endorsed by AENOR in September of 2016)
for Use, 2001
Technical Regulations
EN 1127-1 Explosive Atmospheres. Explosion Prevention and Protection.
Part 1: Basic Concepts and Methodology, 2011 Occupational Safety and Health Protection Rules - Explosion Protection Rules
(EX-RL), 2015 - German
EN 1012-2 Compressors and Vacuum Pumps. Part 2: Vacuum pumps, 2011
TRBS 2152 Hazardous explosive atmosphere, 2016
EN 12255-10 Wastewater Treatment Plants - Part 10: Safety and
Construction Principles, 2001 TRBS 3151 Vermeidung von Brand-, Explosions- und Druckgefährdungen an
Tankstellen und Füllanlagen zur Befüllung von Landfahrzeugen, 2015
EN 13463-1 Non-Electrical Equipment Intended For Use in Potentially Explosive
Atmospheres - Part 1: Basic Methods and Requirements, 2009 TRbF 20 Läger, 2002
EN 13463-5 Non-electrical equipment intended for use in potentially explosive VdTÜV-Merkblatt Tankanlagen 967, 2012
atmospheres - Part 5: Protection by constructional safety ‘c’, 2012
VDI 3479, Emission Reduction, Distribution Storage for Mineral Oil Far from
EN ISO/IEC 80079-34 Explosive atmospheres - Part 34: Application of quality Refineries, 2010
systems for equipment manufacture, 2012
GUV-R 127 Regeln für Sicherheit und Gesundheitsschutz, Deponien, 2001
EN 14015 Specification for the Design and Manufacture of Site-Built,
AO 8.06/77 Explosion Protection in the Manufacture and Processing of Fermen-
Abo- ve-Ground, Vertical, Cylindrical, and Welded Flat-Bottomed, Steel Tanks for
ted Spirits (Alcohol Memorandum), Institution for Statutory Accident Insurance
the Storage of Liquids at Ambient Temperature and Above,
and Prevention in the Food Industry and the Catering Trade - German
Appendix L: Requirements for Pressure and Vacuum Relief Systems, 2005
TRGS 509 Lagern von flüssigen und festen Gefahrstoffen in ortsfesten Behältern
33 CFR Part Facilities Transferring Oil Or Hazardous Material in Bulk
sowie Füll- und Entleerstellen für ortsbewegliche Behälter 2014 - German
(USCG-Rule)
Techncal Literature (Selection)
API STD 2000 7th ed. Venting Atmospheric and Low-Pressure Storage Tanks,
Handbook of Explosion Prevention and Protection (Editor: Steen, H.)
2014
Wiley-VCH Verlag,Weinheim (2008)
API Publ 2210 3rd ed. Flame Arresters for Vents of Tanks Storing
Lexikon Explosionsschutz, Sammlung definierter Begriffe, Berthold Dyrba,
Petroleum Products, 2000 (in revision)
Carl Heymanns Verlag (2006)
API Publ 2028 2nd ed. Flame Arresters in Piping, 1991
6. Nachtrag zu Sicherheitstechnischen Kennzahlen brennbarer Gase
API Bulletin 2521, Use of Pressure-Vacuum Vent Valves for Atmospheric und Dämpfe (K. Nabert, G. Schön), Deutscher Eichverlag GmbH,
Pressure Tanks to Reduce Evaporation Loss,1993 Braunschweig 1990
ANSI/UL 525 6th ed. Standard for Flame Arresters, 1994
44 KA / 1 / 0218 / GB
Brandes, E., Möller W. Safety Characteristic Data Volume 1: Flammable Liquids New standards for flame arresters and tank venting; Dr. T. Heidermann;
and Gases, Schünemann Verlag, 2008 13th International Symposium on Loss Prevention
Schampel K.: Flammendurchschlagsicherungen, Expert Verlag, 1988 FLAME TRANSMISSION TESTS WITH P/V VALVES; Dr. M. Davies/
Dr. T. Heidermann; Test Report, 2007
Brandes, E., März, G., Redeker, T., Normspaltweiten von Mehr-Brennstoff-
komponenten-Gemischen in Abhängigkeit der Brennstoffzusammen- FLAME ARRESTERS; Dr. M. Davies/Dr. T. Heidermann; Perry´s chemical
setzung, PTB-Bericht PTB-W-69, Juni 1997 engineers Handbook 8th EDITION Green Perry; 23-92
Steen, H., Schampel, K.: Stoffabhängigkeit der Wirkung flammendurch- CFD-Modeling for Optimizing the Function of Low-Pressure Valves;
schlagsicherer Einrichtungen. Fortschritt-Berichte VDI, Reihe 6, Nr. 122 1983 F. Helmsen, T. Kirchner; Process and Plant Safety; 2012 Wiley-VCH Verlag
GmbH & Co. KGaA
Schampel, K.: Verhinderung eines Dauerbrandes an Flammendurch-
schlagsicherungen in Lüftungsleitungen von Behältern und Apparaturen, Sicherheit bei Problemprodukten; Dr. M. Davies/Dr. P. Bosse/ T. Klocke;
2. Sicherheitstechnische Vortragsveranstaltung über Fragen des Explosions- POWTECH, TECHNOPHARM, EXPLORISK
schutzes, PTB-Bericht W-20 (1983) 20-29. New ISO standard for flame arresters to increase explosion isolation
Bartknecht, W.: Explosionsschutz, Grundlagen und Anwendungen, efficiency; Dr. M. Davies/Dr. T. Heidermann/Dr. P. Bosse;
Springer Verlag, Berlin, Heidelberg, 1993 HYDROCARBON ENGINEERING
Prof. Dr. Hans Witt, Explosionsschutz bei Ventilatoren, Witt & Sohn GmbH&Co., No safe substitute, FLAME ARRESTERS; HAZARDOUS CARGO
Pinneberg, 1998 BULLETIN, 2008
Meidinger, Ventilatoren zur Förderung von Gas/Luft- oder Dampf/ Schwerpunkt: Lagerung: Flammen filtern; T. Schaper/Dr. P. Bosse;
Luftgemischen der Zone 0, 1998 Gefährliche Ladung, 2005
Eberhard Grabs, Anforderungen an explosionsgeschützte Vakuumpumpen - A conservation vents is not a safe substitute for a flame arrester;
Ergebnisse einer Risikobewertung - Veröff. in PTB Mitteilungen 106 5/96 Dr. T. Heidermann/Dr. M. Davies/D. Preusse; HYDROCARBON
ENGINEERING, 2008
U. Füssel, Vakuum ohne Abwässer - Trockenläufer setzen sich durch, Chemie
Technik, 1998 Venting Technologies for reducing vapour losses; Dr. P. Bosse/
Dr. M. Da- vies; HYDROCARBON ENGINEERING, 2008
U. Friedrichsen, Konzept erfolgreich getestet - Trockenlaufende Vakuumpumpe
sichert wirtschaftlichen Prozess, Chemie Technik, 1998 Auslegung, sicherer Betrieb und Instandhaltung von Schutzsystemen in
explosionsgefährdeten überwachungsbedürftigen Anlagen; Dr. V. Halstrick;
Bjerketvedt, D., Bakke, J.R., van Wingerden, K.: Gas Explosion
Technische Sicherheit, 2012
Handbook,Journal of Hazardous Materials 52 (1997), 1 – 150
Protect Your Process With The Proper Flame Arresters. Dr. M. Davies,
Redeker, T.: Sicherheitstechnische Kennzahlen – Basis für den Explosions-
Dr. T. Heidermann, CEP, 2013
schutz, 9. Internationales Kolloquium für die Verhütung von Arbeitsunfällen und
Berufskrankheiten in der chemischen Industrie Luzern, 1984 Alt neben Neu - Konzept für qualifizierte und regelmäßigeWartung;
T. Anderssohn; Verfahrenstechnik, 2012
Stanley S. Grossel: Deflagration und Detonation Flame Arresters, 2002
Flammendurchschlagsicherungen - Planung, Betrieb, Wartung;
PROTEGO® Publications
T. Anderssohn; Industriearmaturen, 2013R. Raman, D. Moncalvo,
Absicherung der Abblaseleitung eines Sicherheitsventils durch eine T. Heidermann, S. Kostos; Overfilling Protection for Weak Tanks,
Defla- grationsendsicherung; Dr. T. Heidermann/H. Kuchta; Technische CCPS 2015
Überwachung, 2003
Influence of Overpressure in Pressure Vacuum Safety Valves on Emission
In-line Flame Arresters to Prevent Flashback of Thermal Combustion Units; Reduction and Explosion Risk Minimization of Atmospheric Storage Tanks;
Dr. T. Heidermann/Dr. M. Davies; Wiley InterScience, 2006 11th Global Congress of Process Safety;
Keeping explosion in isolation; Dr. T. Heidermann/Dr. M. Davies/ Dr.-Ing. Davide Moncalvo, Dr.-Ing. Michael Davies, 2015
Dr. P. Bosse; HYDROCARBON ENGINEERING, 2008 Overfilling Protection for Weak Tanks, 11th Global
A Research Study on Safe Application of Flame Arresters for Thermal Congress of Process Safety; Rahul Raman,
HYDROCARBON ENGINEERING, 2008 “Breathing losses from low-pressure storage tanks due to atmospheric weather
FLAME ARRESTERS FOR PLANTS HANDLING ACETYLENE AND ETHY- change”; Dr. D. Moncalvo, Dr. M. Davies, R. Weber, R. Stolz; Journal of Loss
LENE OXIDE; D. Long/Dr. T. Heidermann; IChemE, 2009 Prevention in the Process Industries 43, 2016
KA / 1 / 0917 / GB 45
Appendix
Glossary
46 KA / 1 / 0909 / GB
Glossary
design pressure / pressure, together with the design temperature, used to determine ISO 23251 - 3.23
design temperature the minimum permissible thickness or physical characteristic of
(general design) each component, as determined by the design rules of the
pressure-design code
design vacuum max. permissible vacuum (negative gauge pressure) in the space -
(negative gauge pressure) above the stored liquid
detonation explosion propagating at supersonic velocity and characterized EN 13237 - 3.18
by a stock wave (EN 1127-1: 1997)
detonation flame arrester flame arrester designed to prevent the transmission of a ISO 16852 3.15
detonation. It can be an end-of-line flame arrester or an
in-line flame arrester
detonation proof by-pass dry-type detonation proof by-pass to keep a minimum liquid for -
safety reasons
diaphragm valve valve, where the moving valve part consists of a diaphragm -
emergency venting venting required when an abnormal condition, such as ruptured ISO 28300 - 3.23
internal heating coils or an external fire, exists either inside or
outside a tank
emergency venting valves pressure relief valves for emergency venting -
end-of-line flame arrester flame arrester that is fitted with one pipe connection only ISO 16852 - 3.23
endurance burning stabilized burning for an unlimited time ISO 16852 - 3.6
endurance burning flame arrester flame arrester that prevents flame transmission during and after ISO 16852 - 3.16
endurance burning
equipment „equipment“ means machines, apparatus, fixed or mobile devices, EN 1127 - 3.5
control components and instrumentation thereof and detection
and prevention systems which, separately or jointly, are intended
for the generation, transfer, storage, measurement, control and
conversion of energy, for the processing of material, and which
are capable of causing an explosion through their own potential
sources of ignition
equipment category within an equipment group, a category is the classification EN 13237 - 3.26
according to the required level of protection. The categories
are defined as given in A.6.
explosion abrupt oxidation or decomposition reaction producing an ISO 16852 - 3.7
increase in temperature, pressure or in both simultaneously
explosion limits limits of explosion range (EN 1127-1:1997) EN 13237 - 3.29
explosive atmosphere mixture with air, under atmospheric conditions, of flammable EN 1127 - 3.17
substances in the form of gases, vapors, mists or dusts, in which,
after ignition has occurred, combustion spreads to the entire
unburned mixture
flame arrester a device fitted to the opening of an enclosure or to the connecting ISO 16852 - 3.1
pipework of a system of enclosures and whose intended function
is to allow flow but prevent the transmission of flame
flame arrester cage enclosure for the flame arrester element including spider rings -
flame arrester element crimped ribbon element -
KA / 1 / 0909 / GB 47
Appendix
Glossary
flame arrester element gap flame arrester elements have profiles, which are more or less -
triangular. The flame arrester element gap is the triangular height
of the flame arrester element
flame arrester housing that portion of a flame arrester whose principal function is to ISO 16852 - 3.2
provide a suitable enclosure for the flame arrester element and
allow mechanical connections to other systems
flame arrester set combination of flame arrester elements with spacers -
flame arrester unit flame arrester cage with flame arrester elements and spacers -
flame transmission proof characteristic of a device to avoid flashback -
FLAMEFILTER® international trademarks by Braunschweiger Flammenfilter GmbH -
for flame arrester element made of crimped ribbon
FLAMEFILTER® cage enclosure for FLAMEFILTER® including spider rings -
FLAMEFILTER gap ®
flame arrester element gap of a crimped ribbon element type -
FLAMEFILTER®
FLAMEFILTER® set combination of FLAMEFILTER® with spacers -
flammable gas or vapor gas or vapor which, when mixed with air in certain proportions, EN 13237 - 3.44
will form an explosive gas atmosphere (EN 60079-10:1996)
flammable liquid liquid capable of producing a flammable vapor under any EN 13237 - 3.45
foreseeable operating condition (EN 60079-10:1996)
flammable material material which is flammable of itself, or is capable of producing EN 13237 - 3.46
a flammable gas, vapor or mist (EN 60079-10:1996)
flammable substances substance in the form of gas, vapor, liquid, solid, or mixtures of EN 13237 - 3.48
these, able to undergo an exothermic reaction with air when
ignited (EN 1127-1:1997)
flashback phenomenon occurring in a flammable mixture of air and gas ISO 23251 - 3.34
when the local velocity of the combustible mixture becomes less
than the flame velocity, causing the flame to travel back to the
point of mixture
flashpoint lowest temperature, corrected to a barometric pressure of 101,3 EN 13237 - 3.49
kPa, at which application of a test flame causes the vapor of the
test portion to ignite under the specified conditions of test (ISO
13736:1997)
floating cover structure which floats on the surface of a liquid inside a fixed roof EN 14015 - 3.1.22
tank, primarily to reduce vapor loss
floating roof metallic structure which floats on the surface of a liquid inside an EN 14015 - 3.1.21
open top tank shell, and in complete contact with this surface
floating suction unit mechanical device, sometimes articulated, installed in some EN 14015 - 3.1.28
tanks, which floats on the liquid surface and only permits product
to be withdrawn from this point
foot valve flame arrester a flame arrester designed to use the liquid product combined with ISO 16852 - 3.19.2
a non return valve to form a barrier to flame transmission
free vents open vents EN 14015 - 3.1.40
48 KA / 1 / 0909 / GB
Glossary
KA / 1 / 0909 / GB 49
Appendix
Glossary
leak rate leakage of a device in volume per time (liter per second) -
left-hand wound orientation (angle) of gaps of crimped ribbon element -
lift actual travel of the valve disc away from the closed position ISO 4126 - 3.3
limiting oxygen concentration maximum oxygen concentration in a mixture of a flammable EN 13237 - 3.64
(LOC) substance and air and an inert gas, in which an explosion will
not occur, determined under specified test conditions
(EN 1127-1:1997)
lining protective cladding with defined minimum/maximum thickness -
to protect against aggressive mixtures (e.g. acid)
liquid product detonation flame flame arrester in which the liquid product is used to form a liquid ISO 16852 - 3.19
arrester seal as a flame arrester medium, in order to prevent flame trans-
mission of a detonation. There are two types of liquid product
detonation flame arrester for use in liquid product lines: liquid
seals and foot valves
liquid seal (water seal) device that directs the flow of relief gases through a liquid ISO 23251-3.43
(normally water) on the path to the flare burner, used to protect
the flare header from air infiltration or flashback, to divert flow,
or to create back pressure for the flare header
lower explosion limit (LEL) the lower limit of the explosion range EN 1127 - 3.8
maintenance combination of all technical and administrative actions, including EN 13237 - 3.78
supervision actions, intended to retain an item in, or restore it to,
a state in which it can perform a required function
malfunction the equipment, protective system and components do not perform EN 1127 - 3.25
the intended function
manifold piping system for the collection and/or distribution of a fluid to or ISO 23251 - 3.45
from multiple flow paths
maximum allowable explosion calculated maximum explosion pressure which the equipment will EN 14460 - 3.7
pressure withstand
maximum allowable pressure maximum pressure for which the equipment is designed as 97/23/EC (PED)
(pressure equipment) specified by the manufacturer
maximum allowable temperature maximum temperature for which the equipment is designed as 97/23/EC (PED)
(pressure equipment) specified by the manufacturer
maximum allowable working maximum gauge pressure permissible at the top of a ISO 23251 - 3.47
pressure (MAWP) completed vessel in its normal operating position at the
designated coincident temperature specified for that pressure
maximum experimental safe gap the maximum gap of the joint between the two parts of the -
(MESG) interior chamber of the test apparatus which, when the internal
gas mixture is ignited and under specified conditions, prevents
ignition of the external gas mixture through a 25 mm long joint,
for all concentrations of the tested gas or vapor in air. The MESG
is a property of the respective gas mixture (EN 1127-1: 1997)
Note: IEC 60079-1 A standardizes the test apparatus and the test
method
maximum operating temperature maximum temperature reached when equipment or protective -
system is operating at its intended operating conditions
50 KA / 1 / 0909 / GB
Glossary
measurable type a flame arrester where the quenching gaps of the flame arrester ISO 16852 - 3.17.1
(static flame arrester) element can be technically drawn, measured and controlled
most easily ignitable explosive explosive atmosphere with a concentration of flammable EN 13237 - 3.87
atmosphere substances which under specified conditions, requires the lowest
energy for its ignition
nominal size, nominal diameter (DN) a numerical size designation used for all components of a -
piping system, for which the external diameter or the size of
thread is not indicated. The figure is rounded and has only an
approximate relation to the machined dimensions
non-measurable type a flame arrester where the quenching gaps of the flame arrester ISO 16852 - 3.17.2
(static flame arrester) element cannot be technically drawn, measured or controlled
(e.g. random such knitted mesh, sintered metal and gravel beds)
normal pressure venting outbreathing under normal operating conditions EN 14015 - 3.1.35
(pumping product into the tank and thermal outbreathing)
normal vacuum venting inbreathing under normal operating conditions EN 14015 - 3.1.36
(pumping product out of the tank and thermal inbreating)
normal venting venting required because of operational requirements or ISO 28300 – 3.7
atmosheric changes
opening pressure the opening pressure is the vacuum resp. gauge pressure at DIN 3320 - 54
which the lift is sufficient to discharge the predetermined mass
flow; it is equal to the set pressure plus overpressure
operating pressure pressure in the process system experiences during normal ISO 23251 - 3.49
operation, including normal variations
operating temperature temperature reached when the apparatus is operating at its rating -
overpressure pressure increase over the set pressure, at which the safety valve ISO 4126 - 3.2.3
attains the lift specified by the manufacturer, usually expressed as
a percentage of the set pressure
pallet guidance element of valve providing guidance of valve pallet -
pallet type valve (disc valve) valve with discoidal seal and axial guide -
pilot-operated pressure relief pressure relief valve in which the major relieving device or main ISO 23251 - 3.52
valve valve is combined with and controlled by a self-actuated auxiliary
pressure-relief valve (pilot)
pilot-operated valve valve actuated by a control device (pilot) -
pipe away valve pressure or vacuum valve to which a vent pipe may be EN 14015 - 3.1.44
connected
pressure pressure unit used in this standard is the bar (1 bar = 10000 Pa), ISO 4126 - 3.2
quoted as gauge (relative to atmospheric pressure) or absolute
as appropriate
pressure-relief valve valve designed to open and relieve excess pressure and to ISO 23251 - 3.56
reclose and prevent the further flow of fluid after normal
conditions have been restored
pressure/vacuum valve weight-loaded, pilot-operated, or spring-loaded valve, used to ISO 23251 - 3.11
(PV valve) relieve excess pressure and/or vacuum that has developed in
a tank
KA / 1 / 0909 / GB 51
Appendix
Glossary
pre-volume flame arrester flame arrester that, after ignition by an internal ignition source, ISO 16852 - 3.23
prevents flame transmission from inside an explosion-pressure-
resistant containment (e.g. a vessel or closed pipe work) to the
outside, or into the connecting pipe work
product term product covers equipment, protective systems, devices, EN 13237 - 3.95
components and their combinations as well as software as
defined in 3.4.2 of EN ISO 9000:2000 (EN 13980.2002)
protective screen component, which provides free flow, but prevents entrance -
of foreign matter, for example animals
protective system „protective system“ means design units which are intended to halt EN 1127 - 3.36
incipient explosions immediately and/or to limit the effective range
of explosion flames and explosion pressures. Protective systems
may be integrated into equipment or separately placed on the
market for use as autonomous systems
quenching cooling of a fluid by mixing it with another fluid of a lower ISO 23251 - 3.59
temperature
relieving pressure pressure at the inlet of a relief device when the fluid is flowing at ISO 28300 - 3.15
the required relieving capacity
reseating pressure value of the inlet static pressure at which the disc re-establishes ISO 4126 - 3.2.4
(closing pressure) contact with the seat or at which the lift becomes zero
right-hand wound orientation (angle) of gaps of crimped ribbon element -
safety shut-off valve a safety shut-off valve is a valve which closes automatically to DIN 3320-2
prevent a predetermined gauge pressure being exceeded
safety valve valve which automatically, without the assistance of any energy ISO 4126 - 3.1
other than that of the fluid concerned, discharges a quantity of
the fluid so as to prevent further flow of fluid after normal pressure
conditions of service have been restored
sampling and air bleed valve flashbackproof and non flashbackproof taps or valves out- and -
inbreathing of parts of plant
set pressure gauge pressure at the device inlet at which the relief device is set ISO 28300 - 3.19
to start opening under service conditions
set vacuum internal negative gauge pressure at which a vacuum valve first -
opens
shock absorber component to reduce the kinetic energy of a detonation -
Shock-Wave-Guide-Tube component for decoupling of shock wave and flame front: -
(SWGT) PROTEGO® patent
short time burning stabilized burning for a specific time ISO 16852 - 3.5
spacer component, which lies on and between the crimped ribbon -
elements of a flame arrester unit
sparge pipe pipe leading into the dip liquid of an hydraulic flame arrester -
stabilized burning steady burning of a flame stabilized at, or close to the flame ISO 16852 - 3.4
arrester element
stable detonation a detonation is stable when it progresses through a confined ISO 16852 - 3.10
system without significant variation of velocity and pressure
characteristics
52 KA / 1 / 0909 / GB
Glossary
static electricity build-up of an electrical difference of potential or charge, through EN 14015 - 3.1.18
friction of dissimilar materials or substances e.g. product flow
through a pipe
static flame arrester a flame arrester designed to prevent flame transmission by ISO 16852 - 3.17
quenching gaps
stoichiometric air chemically correct ratio of fuel to air capable of perfect ISO 23251 - 3.73
combustion with no infused fuel or air
storage tank fixed tank or vessel that is not part of the processing unit in ISO 23251 - 3.74
storage vessel petrochemical facilities, refineries, gas plants, oil and gas
production facilities, and other facilities
swing pipe unit flexible pipeline with or without float within a storage tank for filling -
and emptying
swivel joint part of a swing pipe system -
temperature class classification of equipment, protective system or component EN 13237 - 3.111
for explosive atmospheres based on its maximum surface
temperature
temperature sensor temperature sensor for monitoring the temperature -
test pressure pressure to test the mechanical stability of devices and or to test -
devices for leak
thermal inbreathing movement of air or blanketing gas into a tank, when vapours in ISO 28300 - 3.20
the tank contract or condense as a result of weather changes (e.g.
decrease in atmospheric temperature)
thermal outbreathing movement of air or blanketing gas out of a tank, when vapours in ISO 28300 - 3.21
the tank expand and liquid in the tank vapourizes as a result of
weather changes (e.g. increase in atmospheric temperature)
unstable detonation detonation during the transition of a combustion process from a ISO 16852 - 3.11
deflagration into a stable detonation. The transition occurs in an
limited spatial zone where the velocity of the combustion wave
is not constant and where the explosion pressure is significantly
higher than in a stable detonation
upper explosion limit (UEL) the upper limit of the explosion range EN 1127 - 3.9
valve lift actual travel of the valve pallet away from the closed position, -
when a valve is relieving
valve pallet gasket sealing element between valve pallet and valve seat -
vent cap end-of-line device for free out- and inbreathing of plant -
components. This device can be flame transmission proof
vent header piping system that collects and delivers the relief gases to the ISO 23251 - 3.78
vent stack
vent pipes pipes connected to pipe away valves EN 14015 - 3.1.45
venting system system, which consists of pipeline and devices for free out- and -
inbreathing of parts of plants
venting system with flame free vents or pressure and/or vacuum valves combined with DIN EN 14015 - 3.1.42
arresting capability a flame arrester or with integrated flame arresting elements
KA / 1 / 0909 / GB 53
Appendix
Glossary
vessel container or structural envelope in which materials are processed, ISO 23251 - 3.80
treated or stored
zone 0 place in which an explosive atmosphere consisting of a mixture EN 13237 - 3.119-1
with air of flammable substances in the form of gas, vapor or mist
is present continuously or for long periods or frequently
zone 1 place in which an explosive atmosphere consisting of a mixture EN 13237 - 3.119-2
with air of flammable substances in the form of gas, vapor or mist
is likely to occur in normal operation occasionally
zone 2 place in which an explosive atmosphere consisting of a mixture EN 13237 - 3.119-3
with air of flammable substances in the form of gas, vapor or mist
is not likely to occur in normal operation but, if it does occur, will
persist for a short period only
zones for gases/vapours hazardous areas are classified into zones based upon the EN 13237 - 3.119
frequency of the occurrence and the duration of an explosive
gas atmosphere, the definitions are only applicable to equipment
group II
54 KA / 1 / 0909 / GB
Notes:
KA / 1 / 0318 / GB 55
Materials, Terms and Conversion Tables
Pressure DN 10 15 20 25 32 40 50 65 80 100
14.504 psi 1 lb/ft2 = 47,88 N/m2
1 bar =
= 29.530 inch Hg = 0,4788 mbar Size 1/4 1/2 3/4 1 11/4 11/2 2 21/2 3 4
= 0.987 atm = 4,882 mm WC
= 401.46 inch W.C. DN 125 150 200 250 300 350 400 450 500 600
1 mbar =
0.0145 psi 1 inch W.C. = 249,09 N/m2 Size 5 6 8 10 12 14 16 18 20 24
= 0.0295 inch Hg = 2,4909 mbar
= 0.4015 inch W.C. = 25,4 mm WC
= 2.089 lb/ft2 1 inch Hg = 33,864 mbar DN 700 800 900 1000 1200 1400 1600 1800 2000
Size 28 32 36 40 48 56 64 72 80
1 kPa = 10 mbar 1 psi = 68,94757 mbar
1 inch H2O =
2,49089 mbar 1 inch Hg = 33,8639 mbar
1 Pa = 1 N/m2 1 psi = 1 lb/in2
Length
Temperature 1 cm = 0.3937 inch 1 inch = 25,4 mm
To convert ºC in ºF use TF = 32 + 1,8 TC 1 m = 3.2808 ft 1 ft = 12 inch = 0,3048 m
0ºC = 32ºF = 1.0936 yards 1 yard = 3 ft = 0,9144 m
100ºC = 212ºF 1 km = 0.621 miles 1 mile = 1,609 km
5/9 (T - 32)
To convert ºF in ºC use TC = F
0ºF = -17,8ºC
100ºF = 37,8ºC Area
1cm2 = 0.1550 sq inch 1 sq inch = 6,4516 cm2
Material 1 m2 = 10.7639 sq ft 1 sq ft = 0,0929 m2
DIN Material DIN-Material ASTM-Material = 1.196 sq yards 1 sq yard = 0,836 m2
Number 1km2 = 100 hectares
0.6020 GG 20 A 278-30 C.I. = 0.3861 sq miles
0.7040 GGG 40 A 536-77 C.I. = 247 acres
1.0619 GS-C 25 A 216 Gr. WCB C.S.
1.4301 X5 CrNi 18 10 A 240 Gr. 304 S.S.
1.4408 G-X6 CrNiMo 18 10 A 351 Gr. CF 8 M S.S. Volume
1.0425 P 265 GH A 515 Gr. 60 C.S. 1 cm3 = 0.06102 cu inch 1 cu inch = 16,3870 cm3
1.4541 X6 CrNiTi 18 10 A 240 Gr. 321 S.S. 1 liter = 0.03531 cu ft 1 cu ft = 28,317 liter
1.4571 X10 CrNiMoTi 18 10 A 240 Gr. 316 Ti S.S. = 0.21997 gal (UK) 1 gal (UK) = 4,5461 liter
3.2581 AC 44200 A 413 Alu = 0.26417 gal (US) 1 gal (US) = 3,785 liter
Ta Tantal UNS R05200 1 m3 = 35.315 cu ft 1 cu ft = 0,028317 m3
2.4610 NiMo 16 Cr 16 Ti UNS N06455 C-4 = 6.290 petr. barrels 1 petr. barrel = 0,15899 m3
2.4686 G-NiMo 17 Cr UNS N30107 Casting
2.4602 NiCr 21 Mo 14 W UNS N06022 C-22
2.4819 NiMo 16 Cr 15 W UNS N10276 C-276 Mass
1 g = 0.03527 oz 1 oz = 28,35 g
The applicable materials are specified in the quotation or the order 1 kg = 2.2046 lb 1 lb = 16 oz
acknowledgement: = 0,4536 kg
In general the following means
CS (Carbon steel) = 1.0619 or 1.0425
SS (Stainless steel) = 1.4408 or 1.4571 Velocity and Volume Flow
Hastelloy = 2.4686 or 2.4602 1 m/s = 196.85 ft/min 1 ft/min = 0,508 cm/s
1 km/h = 0.6214 mph 1 mph = 1,60934 km/h
Important differences: US decimals in accordance to 1 m3/h = 4.403 gal/min (US) 1 gal/min (US) = 0,227 m3/h
SI-System = 3.666 gal/min (UK) 1 gal/min (UK) = 0,273 m3/h
e.g. 1 m = 100 cm = 100,00 cm (UK/US: 100.00 cm) = 0.5886 cu ft/min 1 cu ft/min = 28,317 liter/min
1 km = 1.000 m = 1.000,00 m (UK/US: 1,000.00 m) 1 kg/h = 0.0367 lb/min 1 lb/min = 27,216 kg/h
1 cu ft/h = 0,028317 m3/h
Sealings and Coatings
PTFE = polytetrafluoroethylene
PVDF = polyvinylidene fluoride Torsion
PFA = perfluoralkoxy polymer 1 Nm = 0.738 lb ft 1 lb ft = 1,36 Nm
FPM 70 = fluoropolimer elastomer
WS 3822 = aramide and anorganic fibers as well as mineral
reinforcement materials bonded with NBR rubber Density
ECTFE = ethylene chlorotrifluoro etylene 1 kg/dm3 = 62.43 lb/cu ft 1 lb/cu ft = 0,016 kg/dm3
FEP = perfluoroethylene propylene
56 KA / 1 / 0410 / GB
Data Sheet for PROTEGO® - Valves and Flame Arresters
Processing Plant
design temperature °C/°F design pressure bar/psi
operating temperature °C/°F operating pressure bar/psi back pressure mbar/inch W.C.
Installation
in-line horizontal distance to source of ignition m/ft
end-of-line vertical
Function
pressure endurance burning proof temperature monitored on side
vacuum short-time burning proof temperature monitored both side
pressure/vacuum combined deflagration proof pressure monitored
detonation proof bidirectional flame arrester
Valve and Flame Arrester Data
.
size nominal DN flow V m³/h cu ft/min density kg/m³ lb/cu ft
pressure nominal PN inlet flange DN PN form
set pressure mbar/inch W.C. outlet flange DN PN form
set vacuum mbar/inch W.C. pressure drop ∆p mbar/inch W.C.
Material
pressure carrying parts internals lining
Inspection/Documentation
material certificate works certificate performance certificate
Piping Flow Diagram (excerpt) / Additional Remarks / Miscellaneous → refer to seperate sheet
KA / 1 / 0909 / GB 57
www.protego.com
for safety and environment
58
PROTEGO® Deflagration Flame Arresters
end-of line
and Vent Caps
Volume 2
Volume 2
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
60 KA / 2 / 0318 / D
Preferred applications Sizing
PROTEGO® end-of-line deflagration flame arresters and vent The size of the device is selected or double checked with our
caps are mainly installed on storage tanks and vessels of the volume flow / pressure drop diagrams. Should clogging of the
chemical, petrochemical and pharmaceutical industry in order flame arrester element be likely a safety factor should be con-
to protect them. sidered for sizing.
.
Given: Flow rate V m3/h or CFH
max. all. pressure drop p in mbar or inch W.C.
Installation and maintenance
Desired: Size of the device DN
The modular design of the end-of-line deflagration flame
arresters assures the easiest possible maintenance. For onsite Procedure: Intersection point of straight line through the
maintenance purposes, the device has to be installed in a loca- flow rate and maximum allowable pressure drop
tion where it can be easily accessed. For larger sizes it may is above or on the size curve
be necessary to provide lifting equipment. With trained personal
maintenance is most efficient. .
Given: Flow rate V m3/h or CFH
PROTEGO® end-of-line deflagration flame arresters are
size of nozzle connection DN
installed in explosion hazardous areas. It is important to select
the correct device for the specific application. The manufacturer´s Desired: Pressure drop (flow resistance)
statement of conformity confirms the tasks for which the defla- p in mbar or inch W.C.
gration flame arrester is suitable. The user documents proper
Procedure: Intersection point of the straight line through the
use in accordance with the applicable safety regulations.
flow rate and size curve, horizontal straight line
provides the pressure drop
Selection
Based on main process data, the different types of devices can
be selected from our product range:
• Atmospheric deflagration proof, short time burning proof,
airflow in thousands of CFH
endurance burning proof or vent caps
• Explosion group of the processed mixture
atures
After that the following criteria have to be verified or selected:
• Size and type of connection
• Approvals according to ATEX, etc.
• Heating jacket or heating coil
After this pre-selection other details, such as material, coating .
flow rate V (m³/h)
etc. can be selected or defined in the data sheet.
Should it not be possible to determine a device fitting your re-
Guidance for calculating the volume flow or influence of density
quirements, please do not hesitate to contact us: in many cases
is covered in the “Technical Fundamentals” (see Vol. 1).
we can provide special designs or approvals.
The device can be specified or ordered if all above steps are
completed.
For special applications, please complete the process data
sheet from Volume 1 to provide the necessary information for
a quotation.
KA / 2 / 0318 / D 61
Selection Guide
Explosion group
X = Heating jacket /
X = Special design
temperatures
Size
for higher
Type DN ATEX NEC Page
heating coil
Approvals
Deflagration flame arrester, end-of-line
15 - 50 IIB3, C
BE/AD ATEX 64 - 66
½" - 2" IIC B
50 - 800 IIB3, C
LH/AD ATEX X 68 - 70
2" - 32" IIC B
50 - 800 IIB3, C
LH/AD-T ATEX X 72 - 74
2" - 32" IIC B
25 - 800 IIA, D
EB ATEX 76 - 79
1“ - 32“ IIB B
20 - 700
IIA, D
EB-DN/DN2 ¾“ - 28“ ATEX X X 76 - 79
IIB B
NEW
15 - 32
EB-Z IIA D ATEX
½" - 1¼"
20 - 80
IIA, D
¾" - 3"
BE/HK ATEX X
20 - 32
IIB3 C
¾" - 1¼"
20 - 80
BE/HK-E IIB1 – ATEX X 80 - 81
¾" - 3"
80 ATEX
BE/HK-E IIB3 C X
3" IMO
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
62 KA / 2 / 0318 / D
Explosion group
X = Heating jacket /
X = Special design
temperatures
Size
for higher
Type DN ATEX NEC Page
heating coil
Approvals
Deflagration flame arrester, endurance burning proof, end-of-line (Continuation)
80 - 100 IIA, D
BE/HR ATEX X
3" - 4" IIB3 C
80 - 100
BE/HR-E IIB1 – ATEX X 82 - 83
3“ - 4“
150 - 200
BE/HR 400 IIA D ATEX X
6" - 8"
150 - 400
LH/EB IIA1 (I) - ATEX
6" - 16"
20 - 80
EH/0
¾" - 3"
100 - 600
EH/0S
4" - 24"
50 - 200
E/KS
2" - 8"
KA / 2 / 0318 / D 63
Deflagration Flame Arrester, End-of-Line
PROTEGO® BE/AD
Øa
3
2
b
DN
The PROTEGO® BE/AD consists of a housing (1), a weather • low operating and lifecycle cost
hood (2) and the PROTEGO® flame arrester unit (3). The device • cost effective device
is equipped with a metal weather hood. The FLAMEFILTER®
gap size will depend on the devices intended use. Detailing the • cost effective spare parts
operating conditions such as the temperature, pressure, explo-
sion group and the composition of the fluid, enables PROTEGO®
to select the best end-of-line deflagration flame arrester for your Design Type and Specification
application. The PROTEGO® BE/AD series end-of-line deflagra-
Deflagration flame arrester, end-of-line, basic design BE/AD
tion flame arrester is available for substances from explosion
groups IIA to IIC (NEC groups D to B). Special designs available on request
The standard design can be used with operating temperature of
up to +60°C / 140°F.
Type-approved in accordance with the current ATEX Directive
and EN ISO 16852 as well as other international standards.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
64 KA / 2 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
DN 15 / G ½" 20 / G ¾" 25 / G 1" 32 / G 1¼" 40 / G 1½" 50 / G 2"
a 116 / 4.57 116 / 4.57 116 / 4.57 116 / 4.57 200 / 7.87 200 / 7.87
b 80 / 3.15 80 / 3.15 85 / 3.35 85 / 3.35 150 / 5.91 150 / 5.91
KA / 2 / 0318 / GB 65
Deflagration Flame Arrester, End-of-Line
Flow Capacity Charts
PROTEGO® BE/AD
BE/AD-IIB3
.
flow rate V (m³/h) Leistung-000231-en
BE/AD-IIC
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000232-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). Con-
version to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
66 KA / 2 / 0318 / GB
Notes:
67
Deflagration Flame Arrester, End-of-Line
PROTEGO® LH/AD
Øb
Øa
2
c
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
68 KA / 2 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
IIB3 IIC
DN a b
c* c*
50 / 2" 100 / 3.94 200 / 7.87 170 / 6.69 185 / 7.28
80 / 3" 150 / 5.91 240 / 9.45 180 / 7.09 195 / 7.68
100 / 4" 200 / 7.87 295 / 11.61 220 / 8.66 235 / 9.25
125 / 5” 250 / 9.84 350 / 13.78 240 / 9.45 -
150 / 6" 300 / 11.81 550 / 21.65 260 / 10.24 270 / 10.63
200 / 8" 300 / 11.81 550 / 21.65 260 / 10.24 270 / 10.63
250 / 10" 400 / 15.75 600 / 23.62 355 / 13.98 365 / 14.37
300 / 12" 400 / 15.75 600 / 23.62 340 / 13.39 350 / 13.78
350 / 14" 600 / 23.62 800 / 31.50 390 / 15.35 400 / 15.75
400 / 16" 600 / 23.62 800 / 31.50 380 / 14.96 390 / 15.35
500 / 20" 700 / 27.56 1000 / 39.37 400 / 15.75 410 / 16.14
600 / 24" 800 / 31.50 1200 / 47.24 475 / 18.70 485 / 19.09
700 / 28" 1000 / 39.37 1400 / 55.12 505 / 19.88 515 / 20.28
800 / 32" 1200 / 47.24 1600 / 62.99 550 / 21.65 560 / 22.05
* c are reference values. Exact measures depend on the flange connection.
KA / 2 / 0318 / GB 69
Deflagration Flame Arrester, End-of-Line
Flow Capacity Charts
PROTEGO® LH/AD
.
flow rate V (m³/h) Leistung-000228-en
LH/AD-IIC
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000347-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
70 KA / 2 / 0318 / GB
Notes:
71
Deflagration Flame Arrester, short time burning-proof, End-of-Line
PROTEGO® LH/AD-T
Øb
c
1
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
72 KA / 2 / 0318 / D
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
IIB3 IIC
DN a b
c* c*
50 / 2" 100 / 3.94 240 / 9.45 530 / 20.87 550 / 21.65
80 / 3" 150 / 5.91 295 / 11.61 560 / 22.05 580 / 22.83
100 / 4" 200 / 7.87 350 / 13.78 585 / 23.03 605 / 23.82
150 / 6" 300 / 11.81 600 / 23.62 630 / 24.80 655 / 25.79
200 / 8" 300 / 11.81 600 / 23.62 630 / 24.80 655 / 25.79
250 / 10" 400 / 15.75 800 / 31.50 750 / 29.53 770 / 30.31
300 / 12" 400 / 15.75 800 / 31.50 740 / 29.13 760 / 29.92
350 / 14" 600 / 23.62 1000 / 39.37 800 / 31.50 820 / 32.28
400 / 16" 600 / 23.62 1000 / 39.37 790 / 31.10 815 / 32.09
500 / 20" 700 / 27.56 1200 / 47.24 810 / 31.89 835 / 32.87
600 / 24" 800 / 31.50 1200 / 47.24 935 / 36.81 960 / 37.80
700 / 28" 1000 / 39.37 1500 / 59.06 975 / 38.39 995 / 39.17
800 / 32" 1200 / 47.24 1700 / 66.93 1015 / 39.96 1035 / 40.75
* c are reference values. Exact measures depend on the flange connection.
KA / 2 / 0318 / D 73
Deflagration Flame Arrester, short time burning-proof, End-of-Line
Flow Capacity Charts
PROTEGO® LH/AD-T
LH/AD-T-IIB3
.
flow rate V (m³/h) Leistung-000346-en
LH/AD-T-IIC
pressure drop ∆p - inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000348-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
74 KA / 2 / 0318 / D
Notes:
75
Deflagration Flame Arrester, endurance burning proof, End-of-Line
DN 25 - 150 / 1“
1 -6
6“ Øa View A
A
b
c
DN
2 4 1 3 5 6 7
Øa
DN
c
e f
d
b*
DN DN
DN2 DN2
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
76 KA / 2 / 0318 / GB
PROTEGO® EB Demonstration of endurance burning
(Flyer pdf) Video
Function and Description Special Features and Advantages
The PROTEGO EB end-of-line deflagration flame arrester has been
® • weather hood protects against environmental impact
successfully used to protect vessels and plants which are not pres- (i.e. weather, bird nests, etc.)
surized. The device provides protection against atmospheric defla- • weather hood will open and signal the impact of a flame
gration and stabilized flames which can burn for very long time on the
• protection against atmospheric deflagration and endurance
flame arrester element surface, so called endurance burning. Main
burning of pure hydrocarbons
application area is on suction and vent lines, with the goal to prevent
flame transmission caused by endurance burning or atmospheric def- • fusible link is resistant against chemicals
lagration from propagating into the vessel or plant. • modular design allows replacement of single
The PROTEGO® EB-IIA consists of the PROTEGO® flame arrester FLAMEFILTER®
unit (1) and the metal weather hood (2). During normal operation • easy maintenance without disassembling of the
the metal weather hood is in a closed position. If a stabilized FLAMEFILTER®
flame burns on the flame arrester element surface, the fusible • modular design results in low spare part costs
link (3), located in a center position, will melt and let the spring loaded
weather hood move into the open position. The PROTEGO® flame
arrester unit consists of one ore more FLAMEFILTER® (5), which are
installed in a FLAMEFILTER® cage (4), a intersecting ribs (6) and
Design Types and Specifications
a spider ring (7). The FLAMEFILTER® gap size, the height and the End-of-line deflagration flame arrester, EB
quantity depend on the devices intended use.
basic design
The PROTEGO® EB series end-of-line deflagration flame arrester is
available for substances from explosion group IIA and IIB (NEC group End-of-line deflagration flame arrester, EB - DN/DN2
D and B). with cone
The standard design can be used with operating temperature of up
to +60°C / 140°F. Devices with special approval can be obtained for End-of-line deflagration flame arrester, EB - H - DN/DN2
higher temperatures upon request. with cone and heating jacket
Type-approved in accordance with the current ATEX Directive and
Special designs available on request
EN ISO 16852 as well as other international standards.
KA / 2 / 0318 / GB 77
Deflagration Flame Arrester, endurance burning proof, End-of-Line
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
78 KA / 2 / 0318 / GB
Deflagration Flame Arrester, endurance burning proof, End-of-Line
Flow Capacity Charts
EB-IIA
.
flow rate V (m³/h) Leistung-000036-en
Remark: Flow capacity charts for EB-DN/DN2-IIA/IIB with cone upon request
EB-IIB
pressure drop ∆p - inch W.C.
EB-IIB
without cone
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000224-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 2 / 0318 / GB 79
Deflagration Flame Arrester, endurance burning proof, End-of-Line
PROTEGO® BE/HK-E
Øa 5
the spring loaded weather hood move into the open position.
The PROTEGO® flame arrester unit consists of two FLAME-
2
FILTER® discs (4), which are installed in a FLAMEFILTER®
cage. The PROTEGO® BE/HK-E end-of-line deflagration flame
3 arrester is available for alcohols and other substances with
MESG ≥ 0,85mm.
The standard design can be used for operating temperatures up
to +60°C / 140°F.
4 Type-approved in accordance with the current ATEX Directive
and EN ISO 16852 as well as other international standards.
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
80 KA / 2 / 0318 / GB
Demonstration of endurance burning
Video
.
flow rate V (m³/h) Leistung-000072-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 2 / 0318 / GB 81
Deflagration Flame Arrester, endurance burning proof, End-of-Line
PROTEGO® BE/HR-E
1 2 3 5 4
The PROTEGO® BE/HR-E end-of-line deflagration flame • modular design results in low spare part cost
arrester was specifically developed for vessels which are not
pressurized and store Ethanol or other alcohols with a MESG
≥ 0,85 mm. The combustion of alcohol requires a modified flame Design Types and Specifications
arrester element design to provide protection against endurance There are two different designs:
burning. In addition, the device provides protection against at-
mospheric deflagration. Main application area is on suction and End-of-line deflagration flame arrester, BE/HR - E - –
vent lines, with the goal to prevent flame transmission caused by basic design
endurance burning or atmospheric deflagration from propagating
End-of-line deflagration flame arrester with BE/HR - E - H
into the vessel or plant.
heating jacket
The PROTEGO® BE/HR-E consists of a housing (1), a weather
Special designs available on request
hood (2) and the PROTEGO® flame arrester unit (3). During
normal operation, the metal weather hood is in a closed posi-
tion. If a flame burns on the flame arrester element surface, the
fusible link (5), located in a center position, will melt and let the
spring loaded weather hood move into the open position. The
PROTEGO® flame arrester unit consists of two FLAMEFILTER®
discs (4), which are installed in a FLAMEFILTER® cage.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
82 KA / 2 / 0318 / GB
Demonstration of endurance burning
Video
.
flow rate V (m³/h) Leistung-000249-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 2 / 0318 / GB 83
www.protego.com
for safety and environment
PROTEGO® Deflagration Flame Arresters
Volume 3
Volume 3
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
86 KA / 3 / 0318 / GB
In-line deflagration test In-line deflagration test without
The Flame Arrester reliable stops working Flame Arrester
the explosion (Video) (Video)
Given the modular design of the PROTEGO® flame arrester unit, Desired: Nominal diameter of the
any type of deflagration flame arrester is extremely easy to ser- deflagration flame arrester DN
vice. For servicing reasons, the location of the flame arrester Procedure: Intersection of the lines with volume flow and
must be planned to be very accessible; a hoist must be provided maximum allowable pressure drop lies above
if the flame arrester is heavy. Servicing is easy for trained per- or on the desired nominal diameter curve of
sonnel. the device
PROTEGO® deflagration flame arresters are used in areas Given: Volume flow m3/h or CFH
subject to explosion hazards. Devices have to be selected that
match the intended use. The manufacturer‘s certificate of con- Given: Nominal diameter of pipe DN
formity provides the boundary conditions for which the device is Desired: Pressure drop ∆p mbar or inch W.C.
suitable. The user has to document proper use in accordance
with applicable safety guidelines or standards. Procedure: Intersection of the lines with the volume flow and
nominal diameter curve of the device, horizontal
straight line leads to the desired flow resistance
Selection
The following main points should be considered for choosing the
correct device for your application:
• In-line flame arrester or component on equipment airflow in thousands of CFH
(e.g. vacuum pump or blower)
KA / 3 / 0318 / GB 87
Selection Guide
(polimerisation, corrosi-
higher temperatures
Special designs for
Explosion-
and pressures
unidirectional
bidirectional
Approvals
Design
Size cc = concentric
Type DN ec = eccentric ATEX NEC Page
X =
=
=
=
In-line deflagration flame arrester
straight IIA, D,
25 - 300
FA-E through, IIB3, C, ATEX X 90 - 95
1" - 12"
ec IIC B
40 - 300 straight
FA-CN IIC B ATEX X 100 - 102
1½" - 12" through, cc
IIA, D,
straight
FA-G G½-G2 IIB3, C, ATEX X 104 - 107
through, cc
IIC B
50 - 150 straight
FA-I-PTFE IIA D ATEX X
2" - 6" through, cc
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
88 KA / 3 / 0318 / GB
Notes:
89
In-Line Deflagration Flame Arrester
eccentric design,
bidirectional
PROTEGO® FA-E
Øc
Special Features and Advantages
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
90 KA / 3 / 0318 / GB
Stabilized FLAMEFILTER® New PROTEGO® Flame Arrester Unit unique L/D ratio (Flyer pdf)
Discs (Flyer pdf) maintenance friendly design (Flyer pdf)
KA / 3 / 0318 / GB 91
In-Line Deflagration Flame Arrester
eccentric design,
bidirectional
PROTEGO® FA-E
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
92 KA / 3 / 0318 / GB
In-Line Deflagration Flame arrester
Flow Capacity Charts
PROTEGO® FA-E
FA-E-IIA-P1.2
.
flow rate V (m³/h) Leistung-000251-en
FA-E-IIA-P1.6
pressure drop ∆p – inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000279-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 3 / 0318 / GB 93
In-Line Deflagration Flame Arrester
Flow Capacity Charts
PROTEGO® FA-E
FA-E-IIB3-P1.1
.
flow rate V (m³/h) Leistung-000280-en
FA-E-IIB3-P1.6
pressure drop ∆p – inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000281-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
94 KA / 3 / 0318 / GB
* P1.2 *
FA-E-IIC-P1.1
.
flow rate V (m³/h) Leistung-000282-en
KA / 3 / 0318 / GB 95
In-Line Deflagration Flame Arrester
concentric design,
bidirectional
PROTEGO® FA-CN-IIA and IIB3
1 2 3 4
a
The standard design can be used up to an operating tempera-
ture of +60°C / 140°F and an absolute operating pressure up
to 1.1 bar / 15.9 psi. Devices with special approval can be
b
DN
DN
c
Special Features and Advantages
• design available for elevated operating temperatures and
pressures
Design with two
• compact design with easy access cover
Design with one temperature sensors
temperature sensor • easy maintenance without disassembling of the pipeline
each temperature sensor turned • modular flame arrester unit enables individual
by 90° on the drawing FLAMEFILTER® to be replaced and cleaned
Connection to the protected side • bidirectional flame transmission proof design
(only for type FA-CN-T-....)
• provides protection against deflagrations for group IIA
Function and Description and IIB3 vapours (NEC group D and C)
The PROTEGO® FA-CN in-line deflagration flame arrester is a • lowest pressure drop results in low operating and
compact design utilizing an easy access cover for easy main- lifecycle costs
tainability. The PROTEGO® flame arrester unit can be removed • modular design reduces spare parts cost
and cleaned within moments without having to disassemble
the pipe. When installing the deflagration flame arrester, make
sure that the distance between potential ignition sources and
the location of the installed device, does not exceed the L/D
ratio (pipe length/pipe diameter), for which the device was test- Design and Specifications
ed. According to EN ISO 16852 this device is approved for a
There are three different designs:
(L/D)max ratio of 50.
Basic in-line deflagration flame arrester FA-CN - –
The deflagration flame arrester is symmetrical and offers bidi-
rectional flame transmission protection. The device consists of a In-line deflagration flame arrester with in- FA-CN - T
housing (1) with an easy access cover (3) and the PROTEGO® tegrated temperature sensor* as additional
flame arrester unit (2) in the center. The PROTEGO® flame ar- protection against short time burning from
rester unit is modular and consists of several FLAMEFILTER® one side
discs (3) and spacers firmly held in a FLAMEFILTER® cage. The
In-line deflagration flame arrester with two FA-CN - TB
number of FLAMEFILTER® discs and their gap size depend on
integrated temperature sensors* for additional
the devices intended use.
protection against short-time burning from
Providing the operating conditions such as the temperature, both sides
pressure, explosion group and the composition of the fluid, en-
Additional special devices available upon
ables PROTEGO® to select the best deflagration flame arrester
request
for your application. This version of PROTEGO® FA-CN-IIA and
IIB3 flame arrester protects against deflagrations of fuel/air mix- *Resistance thermometer for device group II,
tures of explosion groups IIA and IIB 3 (NEC D and C (MESG ≥ category (1) 2 (GII cat. (1) 2)
0.65 mm)). PROTEGO® FA-CN devices for substances of explo-
sion groups IIA1 and IIC (NEC group B) are shown on separate
pages.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
96 KA / 3 / 0318 / GB
Stabilized FLAMEFILTER® L/D ratio (Flyer pdf)
Discs (Flyer pdf)
KA / 3 / 0318 / GB 97
In-Line Deflagration Flame Arrester
Flow Capacity Charts
FA-CN-IIA-P1.2
.
flow rate V (m³/h) Leistung-000340-en
P* see table 3
FA-CN-IIA-P*
pressure drop ∆p – inch W.C.
3-fold FLAMEFILTER®
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000341-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
98 KA / 3 / 0318 / GB
airflow in thousands of CFH
FA-CN-IIB3-P1.1
.
flow rate V (m³/h) Leistung-000342-en
FA-CN-IIB3-P1.6
pressure drop ∆p – inch W.C.
3-fold FLAMEFILTER®
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000343-en
KA / 3 / 0318 / GB 99
In-Line Deflagration Flame Arrester
for hydrogen/air-mixtures, concentric design,
bidirectional
PROTEGO® FA-CN-IIC
1 2 3 4
DN
DN
c
Special Features and Advantages
• state of the art protection for any hydrogen/air mixture
Design with two • can be applied to process flows with small liquid or
Design with one temperature sensors particle load
temperature sensor • compact design with easy access cover
each temperature sensor turned
by 90° on the drawing • easy maintenance without disassembling of the pipeline
• modular flame arrester unit enables individual
Connection to the protected side
FLAMEFILTER® to be replaced and cleaned
(only for type FA-CN-T-....)
• bidirectional flame transmission proof design
Function and Description
• protects against deflagrations for all explosion groups
The PROTEGO® FA-CN in-line deflagration flame arrester is a
compact design utilizing an easy access cover for easy maintain- • lowest pressure drop results in low operating and
ability. The special PROTEGO® FA-CN-IIC version was devel- lifecycle costs
oped for hydrogen applications (group IIC vapours – NEC group
• modular design reduces spare parts cost
B). The device is designed to have comparetively large gaps, in
relation to other flame arresters for the same explosion group.
This allows to apply it to processes having small fluid droplets or
particles. The PROTEGO® flame arrester unit can be removed Design and Specifications
and cleaned within moments without having to disassemble
the pipe. When installing the deflagration flame arrester, make There are three different designs:
sure that the distance between potential ignition sources and the
location of the installed device, does not exceed the L/D ratio Basic in-line deflagration flame arrester FA-CN - –
(pipe length/pipe diameter), for which the device was approved In-line deflagration flame arrester with in- FA-CN - T
(see table 4). tegrated temperature sensor* as additional
The deflagration flame arrester is symmetrical and offers bidi- protection against short time burning from one
rectional flame transmission protection. The device consists of a side
housing (1) with an easy access cover (3) and the PROTEGO® In-line deflagration flame arrester with two FA-CN - TB
flame arrester unit (2) in the center. The PROTEGO® flame ar- integrated temperature sensors* for additional
rester unit is modular and consists of several FLAMEFILTER® protection against short-time burning from
discs (3) and spacers firmly held in a FLAMEFILTER® cage. The both sides
number of FLAMEFILTER® discs and their gap size depend on
Additional special devices available upon
the devices intended use.
request
Providing the operating conditions such as the temperature,
*Resistance thermometer for device group II,
pressure, explosion group and the composition of the fluid, en-
category (1) 2 (GII cat. (1) 2)
ables PROTEGO® to select the best deflagration flame arrester
for your application. The versions of PROTEGO® FA-CN-IIC
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
100 KA / 3 / 0318 / GB
Stabilized FLAMEFILTER® L/D ratio (Flyer pdf)
Discs (Flyer pdf)
(L/D) max 30 30 10 10 10 20 20 10 10 5
KA / 3 / 0318 / GB 101
In-Line Deflagration Flame Arrester
Flow Capacity Chart
PROTEGO® FA-CN-IIC
X see table 4
FA-CN-IIC-P1.1-X
.
flow rate V (m³/h) Leistung-000344-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
102 KA / 3 / 0318 / GB
Notes:
103
In-Line Deflagration Flame Arrester
concentric design,
bidirectional
PROTEGO® FA-G
Design with one Design with two termined by the operating data and parameters of the mixture
temperature sensor temperature sensors flowing in the line (explosion group, pressure, temperature). The
PROTEGO® FA-G series in-line deflagration flame arresters is
available for explosion groups IIA, IIB3 and IIC (NEC groups D,
(temperature sensor)
Type-approved in accordance with the current ATEX Directive
and EN ISO 16852 as well as other international standards.
• modular design
• the individual FLAMEFILTER® can be quickly removed and
installed
• threaded connection for direct mounting into pipeline
• bidirectional flame transmission proof design
c • protects against deflagrations for all explosion groups
Connection to the protected side • use of temperature sensors for G 1½ and G 2 is possible
(only for type FA-G-T-...)
• cost efficient spare parts
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
104 KA / 3 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
KA / 3 / 0318 / GB 105
In-Line Deflagration Flame Arrester
Flow Capacity Charts
P* see table 3
FA-G-IIA-P*
.
flow rate V (m³/h) Leistung-000011-en
FA-G-IIB3-P1.2
pressure drop ∆p – inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000016-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
106 KA / 3 / 0318 / GB
airflow in thousands of CFH
FA-G-IIC-P1.1
.
flow rate V (m³/h) Leistung-000038-en
KA / 3 / 0318 / GB 107
In-Line Deflagration Flame Arrester
concentric design,
bidirectional
PROTEGO® FA-I
Øa
DN
NG
• optimized flow capacity
• different series allow increase of FLAMEFILTER® size
for given flange connection resulting in lower pressure
drop across the device
• option for integrated cleaning nozzles can be provided
b
• modular flame arrester unit enables each individual
1 2 3 FLAMEFILTER® to be replaced and cleaned
• bidirectional flame transmission proof design
Connection to the protected side • protects with deflagrations for explosion groups
(only for type FA-I-T-....) IIA and IIB3 (NEC groups D and C)
• design available for elevated operating temperatures
Function and Description and pressures
In the development of the PROTEGO® FA-I in-line deflagration • available sizes from DN 50 / 2” to DN 1000 / 40”
flame arrester, special effort was made to optimize the fluid dy-
• lowest pressure drop results in low operating and
namic flow characteristics.For a given flange connection size of
lifecycle costs
the flame arrester, the FLAMEFILTER® size can be chosen for
the most adequate flow capacity. When installing the deflagra- • modular design reduces spare parts cost NEW
tion flame arrester, make sure that the distance between poten-
• use of stabilized FLAMEFILTER® discs is possible
tial ignition sources and the location of the installed device, does
not exceed the L/D ratio (pipe length/pipe diameter), for which • use of PROTEGO® Flame Arrester Unit in unique
the device was tested (see table 4). maintenance friendly design reduces service cost
The deflagration flame arrester is symmetrical and offers bidi-
rectional flame transmission protection. The device essentially Design and Specifications
consists of two housing parts (1) and the PROTEGO® flame There are three different designs:
arrester unit (2) in the center. The PROTEGO® flame arrester
Basic deflagration flame arrester design FA-I- –
unit is modular and consists of several FLAMEFILTER® discs
(3) and spacers firmly held in a FLAMEFILTER® cage. The num- In-line deflagration flame arrester with inte- FA-I- T
ber of FLAMEFILTER® discs and their gap size depends on the grated temperature sensor* for additional protec-
arrester´s conditions of use. tion against short-time burning from one side
Providing the operating conditions such as the temperature, In-line deflagration flame arrester with two FA-I- TB
pressure, explosion group and the composition of the fluid, en- integrated temperature sensors* for additional
ables PROTEGO® to select the best deflagration flame arrester protection against short-time burning from both
for your application. The PROTEGO® FA-I series of deflagration sides
flame arresters is available for substances of explosion groups
Additional special devices available upon re-
IIA and IIB3 (NEC groups D and C (MESG ≥ 0.65 mm)).
quest
*Resistance thermometer for device group II,
category (1) 2 (GII cat. (1) 2)
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
108 KA / 3 / 0318 / GB
Stabilized FLAMEFILTER® New PROTEGO® Flame Arrester Unit unique
Discs (Flyer pdf) maintenance friendly design (Flyer pdf)
14.33 14.33 17.79 22.99 25.12 27.09 31.50 35.43 39.37 43.31 53.15 57.09
364 / 364 / 464 / 596 / 650 / 700 / 800 / 900 / 1000 / 1100 / 1350 / 1450 /
IIB3 b*
14.33 14.33 18.27 23.46 25.59 27.56 31.50 35.43 39.37 43.31 53.15 57.09
500 / 500 / 520 / 570 / 620 / 670 / 700 / 900 / 1000 / 1100 / 1350 / 1450 /
c
19.69 19.69 20.47 22.44 24.41 26.38 31.50 35.43 39.37 43.31 53.15 57.09
*Dimension b only for P1.2 (IIA) and P1.1 (IIB3).
26.1 26.1 21.7 21.7 21.7 21.7 21.7 20.3 18.8 18.8 17.4 15.9
1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.1 / 1.1 / 1.1 /
IIB3 Pmax
17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 15.9 15.9 15.9
Pmax = maximum allowable operating pressure in bar / psi absolut, higher operating pressure upon request
KA / 3 / 0318 / GB 109
In-Line Deflagration Flame Arrester
concentric design,
bidirectional
PROTEGO® FA-I
(L/D) max 50 50 50 50 50 50 50 50 50 50 50 50
1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.3 / 1.3 / 1.2 / 1.1 /
IIA Pmax
17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 18.8 18.8 17.4 15.9
Designa-
- - - - - - - - - - - -
tion
(L/D) max 50 50 40 40 35 35 35 30 30 30 25 25
Pmax 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 /
IIB3
(bar /psi) 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
Designa-
- - X6 X6 X7 X7 X7 X8 X8 X8 X9 X9
tion
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
110 KA / 3 / 0318 / GB
In-Line Deflagration Flame Arrester
Flow Capacity Charts
PROTEGO® FA-I
* **
N
/D
DN 500/20“, DN 600/24“; P1.3
* = NG 1400/56" / DN 800/32"; P1.2
— NG
** = NG 1600/64" / DN 800/32"; P1.1
FA-I-IIA-P
.
flow rate V (m³/h) Leistung-000242-en
* **
X see table 4
* = NG 1400/56" / DN 800/32",
N
** = NG 1600/64" / DN 800/32"
/D
* and ** 4 FLAMEFILTER® ,
— NG
FA-I-IIB3-P1.1-X
pressure drop ∆p – inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000245-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 3 / 0318 / GB 111
www.protego.com
for safety and environment
PROTEGO® Detonation Flame Arresters
Volume 4
Volume 4
P
Preferred applications
Protection of
Piping systems
PROTEGO ® flame arrester unit Tanks and vessels in chemical, petrochemical,
and pharmaceutical processing plants
All dry detonation flame arrester types have a modular design.
de
For larger nominal diameters,
eters, energy is withdrawn fromfro the Loading systems
detonation shock wave upon entering the patented shock s ab-
Gas collection systems
sorber, the SWGTE (Shock Wave Guide Effect), and other
ide Tube Effect)
innovative technical solutions, before the detonation
detonat reaches Exhaust gas combustion systems
the FLAMEFILTER®.
Flare systems
Dry PROTEGO® detonation flame arresters are also tested and
Landfills and biogas systems
safe with respect to deflagrations. Equipped with an additional
temperature sensor, they are also protected from short-time sta- Waste-water treatment plants
bilized burning on the FLAMEFILTER®.
In close collaboration with scientific institutions, PROTEGO® has
developed safety devices that can be used in any area subject
to an explosion hazard and protects against stable and unsta-
ble detonations, unidirectional or bidirectional. Corresponding
statements of conformity (CE, etc.) have been awarded based
on type tests according to ATEX, PED, and other international
standards.
A wide range of types, designs, nominal diameters and materi-
als are available. In addition, we are able to develop tailor made
solutions at our worldwide unique testing facility.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
114 KA / 4 / 0318 / GB
Installation and maintenance Sizing
PROTEGO® detonation flame arresters are also tested and The nominal diameter of the device is determined or checked in
protect against deflagrations so that they can be used at any the p/V flow chart. A safety margin must be provided when the
distance from a potential ignition source. However, they are pre- processed fluid is highly contaminated.
ferably installed as close as possible to the part of the system
Given: Volume flow m3/h or CFH
to be protected. No pipes with a nominal diameter greater than
the nominal diameter of the devices shall be connected to deto- Given: Max. all. pressure drop ∆p mbar or inch W.C.
nation arresters.
Desired: Nominal diameter of the
Given the modular design of the PROTEGO® flame arrester unit, detonation flame arrester DN
any type of detonation flame arrester is extremely easy to ser-
Procedure: Intersection of the lines with the volume flow and
vice. For servicing reasons, the location of the flame arrester
maximum allowable pressure drop lies above or
must be planned to be very accessible; a hoist must be provided
on the desired nominal diameter curve
if the flame arrester is heavy. Servicing is easy for trained per-
sonnel. or
PROTEGO® detonation flame arresters are used in areas Given: Volume flow m3/h or CFH
subject to explosion hazards. Select devices that match the Given: Nominal diameter of pipe DN
intended use. The manufacturer‘s certificate of conformity pro-
vides the boundary conditions for which the device is suitable. Desired: Pressure drop ∆p mbar or inch W.C.
The user has to document proper use in accordance with ap- Procedure: Intersection of the lines with the volume flow and
plicable safety guidelines or standards. nominal diameter curve, horizontal straight line leads to the
desired pressure drop
Instructions on how to calculate the volumetric flow or influence
Selection of density are found in Vol. 1 „Technical Fundamentals“.
The possible types are pre-selected from the product After all steps are complete, the device can be completely spe-
line based on the most important process data: cified and requested or ordered.
KA / 4 / 0318 / GB 115
Selection Guide
(polimerisation, corrosion,
= for critical medium
= unidirectional,
crystallisation)
Explosion Group
x = bidirectional
cc = concentric
parameter
x = liquid type
ec = eccentric
= dry type
Approvals
Design
straight
DR/SV G½-G¾ IIA D ATEX
through, cc
IIA, D,
50-600 straight
DA-SB IIB3, C, ATEX x 126 - 131
2" - 24" through, cc
IIC B
50-100 straight
DA-SB-PTFE IIA D ATEX x
2" - 4" through, cc
IIA, D,
DR/ES G ¼ -G ¾ 90-degree IIB3, C, ATEX 132 - 134
IIC B
25-200 IIA, D,
DR/ES 90-degree ATEX /x 136 - 140
1" - 8" IIB3 C
40-200 IIA, D,
DR/ES-V 90-degree ATEX 142 - 145
1 ½" - 8" IIB3 C
40-150
DR/ES-PTFE 90-degree IIA D ATEX
1 ½" - 6"
All rights and alterations reserved acc. ISO 16016. - Active data sheet at www.protego.com
116 KA / 4 / 0318 / GB
= Heating jacket, Heating coil
= for non-standartd operating
(polimerisation, corrosion,
= for critical medium
= unidirectional,
crystallisation)
Explosion Group
x = bidirectional
cc = concentric
x = liquid type
ec = eccentric
parameter
= dry type
Approvals
Design
Type Size Page
ATEX NEC
for stable detonation / for liquid detonation
25-250 IIA, D,
LDA vertical ATEX x 150 - 151
1" - 10" IIB3 C
25-250 IIA, D,
LDA-F vertical ATEX x 152 - 153
1" - 10" IIB3 C
25-250
EF/V vertical IIB3 C ATEX x 154 - 155
1" - 10"
TS/P IIA, D,
TS/E IIB3, C, ATEX x 156 - 157
TS/W IIC B
for unstable detonation
IIA, D,
25-150
DR/EU 90-degree IIB2, C, ATEX 166 - 168
1" - 6"
IIB3 C
KA / 4 / 0318 / GB 117
In-Line Detonation Flame Arrester
for stable detonations and deflagrations in a straight through design,
bidirectional
PROTEGO® DA-G
(temperature sensor)
displaced nection. The thread can be executed to international standards.
The detonation arrester can be used at any location in the pipe,
independently from the location of the ignition source.
Type-approved in accordance with the current ATEX Directive
and EN ISO 16852 as well as other international standards.
Øb
• bidirectional
• modular design
• the individual FLAMEFILTER® discs can be quickly removed
and installed
1
c • the individual FLAMEFILTER® discs are easy to service and
replace
Connection to the protected side • different application possibilities
(only for type DA-G-T-...)
• use of temperature sensors for G 1½ and G 2 is possible
• cost efficient spare parts
Function and Description Design Types and Specifications
The PROTEGO® DA-G series is a compact in-line detonation
flame arrester for installation in pipes with diameters up to 2“, There are three different designs available:
and is used, for example, in industrial applications such as gas Basic design of the DA-G in-line detonation DA-G- –
analyzing lines. flame arrester, size ½“ to 2“
Once a detonation enters the flame arrester, energy is absorbed In-line detonation flame arrester with inte- DA-G- T
from the shock wave, and the flame is extinguished in the nar- grated temperature sensor* as additional
row gaps of the FLAMEFILTER® (1). protection against short burning from one
The PROTEGO® flame arrester unit consists of several FLAME- side, size 1½“ to 2“
FILTER® discs firmly held in a housing. The gap size and num- In-line detonation flame arrester with two in- DA-G- TB
ber of FLAMEFILTER® discs are determined by the operating tegrated temperature sensors* as additional
data and parameters of the mixture flowing in the line (explosion protection against short time burning from
group, pressure, temperature). both sides, size 1½“ to 2“
To provide an optimum result between the housing size, number of *Resistance thermometer for device group II,
FLAMEFILTER® discs and their gap size, a device was developed category (1) 2 (GII cat. (1) 2)
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
118 KA / 4 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches, SW = width across flats
To select the nominal size (DN), please use the flow capacity charts on the following pages
DN G½ G¾ G1 G1¼ G1½ G2
a 80 / 3.15 80 / 3.15 100 / 3.94 100 / 3.94 155 / 6.10 155 / 6.10
b 55 / 2.17 55 / 2.17 76 / 2.99 76 / 2.99 124 / 4.88 124 / 4.88
c (IIA) 112 / 4.41 112 / 4.41 122 / 4.80 122 / 4.80 205 / 8.07 205 / 8.07
c (IIB3 and IIC) 135 / 5.31 135 / 5.31 145 / 5.71 145 / 5.71 205 / 8.07 205 / 8.07
d — — — — 400 / 15.75 400 / 15.75
SW 32 / 1.26 32 / 1.26 50 / 1.97 50 / 1.97 75 / 2.95 75 / 2.95
KA / 4 / 0318 / GB 119
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DA-G
DA-G-IIA-P1.1
.
flow rate V (m³/h) Leistung-000337-en
* P1.4 *
*
DA-G-IIB3-P1.1
pressure drop ∆p – inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000338-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
120 KA / 4 / 0318 / GB
In-Line Detonation Flame Arrester
Flow Capacity Chart
PROTEGO® DA-G
* P1.6
*
*
DA-G-IIC-P1.1
.
flow rate V (m³/h) Leistung-000339-en
KA / 4 / 0318 / GB 121
Eccentric In-Line Detonation Flame Arrester
for stable detonations and deflagrations in a straight through design,
bidirectional
PROTEGO® DA-E
Øc
Special Features and Advantages
b
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
122 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
11.97/12.4* 11.97/12.4* 12.60 12.80 14.57 14.76 14.96 18.94 19.17 20.08 21.26 22.05
304/ 304/ 357/ 361/ 408/ 412/ 428/ 493/ 499/ 522/ 552/ 572/
IIB3 a
11.97 11.97 14.06 14.21 16.06 16.22 16.85 19.41 19.65 20.55 21.73 22.52
29/ 29/ 29/ 29/ 38/ 38/ 39/ 65/ 65/ 55/ 58/ 60/
b
1.14 1.14 1.14 1.14 1.50 1.50 1.53 2.56 2.56 2.17 2.28 2.36
185/ 185/ 210/ 210/ 250/ 250/ 275/ 385/ 385/ 450/ 500/ 575/
c
7.28 7.28 8.27 8.27 9.84 9.84 10.83 15.16 15.16 17.72 19.69 22.64
400/ 400/ 410/ 410/ 440/ 440/ 460/ 520/ 520/ 540/ 570/ 600/
d
15.75 15.75 16.14 16.14 17.32 17.32 18.11 20.47 20.47 21.26 22.44 23.62
* for IIA-P2.0
Table 2: Selection of the explosion group
MESG Expl. Gr. (IEC/CEN) Gas Group (NEC)
> 0,90 mm IIA D Special approvals upon request
≥ 0,65 mm IIB3 C
29.0 29.0 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
1.1 / 1.1 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 / 1.2 /
IIB3 Pmax
15.9 15.9 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
Pmax = maximum allowable operating pressure in bar / psi (absolute), higher operating pressure upon request
KA / 4 / 0318 / GB 123
Eccentric In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DA-E
*
*
* P1.3
DA-E
DA
DA-E-IIA-P1.2
-E-I
-IIA
IA-P
-P1.
1.2
2
.
flow rate V (m³/h) Leistung-000236-en
1943-L
*
*
* P1.1
.
flow rate V (m³/h) Leistung-000237-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
124 KA / 4 / 0318 / GB
Notes:
125
In-Line Detonation Flame Arrester
for stable detonations and deflagrations in a straight through design
with shock tube, bidirectional
PROTEGO® DA-SB
NG
Øa
DN
DN
b • expanded
e application range for higher operating
temperatures
t and pressures
• bidirectional operation as well as any direction of flow and
1 2 3
Connection to the protected side installation position
(only for type DA-SB-T-...) • installation of temperature sensors are possible
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
126 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER® New PROTEGO® Flame Arrester Unit unique
Discs (Flyer pdf) maintenance friendly design (Flyer pdf)
1.4 / 1.4 / 1.4 / 1.8 / 1.8 / 1.8 / 1.8 / 1.4 / 1.4 / 1.1 / 1.1 /
IIB3 Pmax
20.3 20.3 20.3 26.1 26.1 26.1 26.1 20.3 20.3 15.9 15.9
2.2 / 2.2 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 / * 1.1 / * 1.1 / *
IIC Pmax
31.9 31.9 15.9 15.9 15.9 15.9 15.9 15.9 15.9
Pmax = maximum allowable operating pressure in bar / psi absolut, higher operating pressure upon request
in-between size up to Pmax upon request
* capacity charts upon request
KA / 4 / 0318 / GB 127
In-Line Detonation Flame Arrester
for stable detonations and deflagrations in a straight through design with shock tube,
bidirectional
PROTEGO® DA-SB
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
128 KA / 4 / 0318 / GB
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DA-SB
* * **
* P1.4
N
** P1.2
/D
— NG
airflow in thousands of CFH
DA-SB-IIA-P1.1
.
flow rate V (m³/h) Leistung-000324-en
N
temperature 200 °C
— NG
.
flow rate V (m³/h) Leistung-000022-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 4 / 0318 / GB 129
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DA-SB
N
/D
— NG
airflow in thousands of CFH
DA-SB-IIB3-P1.1
.
flow rate V (m³/h) Leistung-000332-en
temperature 200 °C
— NG
DA-SB-IIB3-P1.4-X3
pressure drop ∆p – inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000026-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). Con-
version to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
130 KA / 4 / 0318 / GB
N
/D
— NG
airflow in thousands of CFH
DA-SB-IIC-P1.1
.
flow rate V (m³/h) Leistung-000333-en
KA / 4 / 0318 / GB 131
In-Line Detonation Flame Arrester
for stable detonations and deflagrations in right angle design,
unidirectional
PROTEGO® DR/ES
a
The PROTEGO® flame arrester unit (2) consists of several
FLAMEFILTER® discs and spacers (for explosion group IIC -
NEC group B) whose gap size and number is determined by the
operating parameters of the processed fluid (explosion group,
pressure, temperature). This device is available for explosion
groups IIB3 and IIC (NEC group C MESG ≥ 0.65 mm and B).
DN
This in-line detonation flame arrester functions unidirectional
and is equipped with a threaded connection. The thread can
d
1
be adapted to international standards. The standard design is
approved at an operating temperature up to +60°C / 140°F and
2 an absolute operating pressure acc. to table 3. Devices with
c special approvals can be obtained for higher pressures and
3 higher temperatures upon request.
Type-approved in accordance with the current ATEX Directive
and EN ISO 16852 as well as other international standards.
only for DN
design IIB3 Special Features and Advantages
Øe
• compact design
b
• minimum number of FLAMEFILTER® discs due to shock
absorber technology and optimal geometry
Connection to the protected side
Design for IIB3: • the device can be serviced without discon-
necting the pipe
• the individual FLAMEFILTER® can be
Function and Description quickly removed and installed
• provides protection from deflagration and stable detonation
The PROTEGO® DR/ES series in-line detonation flame arrester
with connection size up to ¾“ is ideal for installation in small • through right angle design no pipe elbows are needed
pipes and to protect equipment such as gas analyzers. The de- • works for nearly any flammable gas and gas mixture
vice protects against deflagrations and stable detonations. It can
be installed anywhere in the pipe no matter what the distance is • low life-cycle cost
from the potential ignition source. The small and compact flame • cost efficient spare parts
arrester has a right angle design.
Once a detonation enters the flame arrester, energy is absorbed
from the detonation shock wave by diversion mainly through
the shock absorber (1) before the flame is extinguished in the
narrow gaps of the FLAMEFILTER® (3).
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
132 KA / 4 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
DN G¼ G½ G¾
a 48 / 1.89 70 / 2.76 80 / 3.15
b 35 / 1.38 40 / 1.57 47 / 1.85
c 70 / 2.76 75 / 2.95 87 / 3.43
d 108 / 4.25 115 / 4.53 135 / 5.31
e 34 / 1.34 50 / 1.97 60 / 2.36
KA / 4 / 0318 / GB 133
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DR/ES
.
flow rate V (m³/h) Leistung-000427-en
DR/ES-IIC-P1.1
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000428-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). Con-
version to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
134 KA / 4 / 0318 / GB
Notes:
135
In-Line Detonation Flame Arrester
for stable detonations and deflagrations in right angle design with shock absorber,
unidirectional
PROTEGO® DR/ES
The PROTEGO® DR/ES in-line detonation flame arrester has Basic in-line detonation flame arrester DR/ES- – - –
been used for decades in industrial plant construction because In-line detonation flame arrester with inte- DR/ES- T - –
its right angle design offers advantages towards maintenance grated temperature sensor* as additional
and costs in comparison to most straight designs. protection against short time burning
Once a detonation enters the device, energy is absorbed from In-line detonation flame arrester with heating DR/ES- H - –
the detonation shock wave by the integrated shock absorber jacket
(1) before the flame is extinguished in the narrow gaps of the
FLAMEFILTER® (3). In-line detonation flame arrester with inte- DR/ES- H - T
grated temperature sensor* against short
The PROTEGO® flame arrester unit (2) consists of several time burning and heating jacket
FLAMEFILTER® discs and spacers firmly held in the FLAME-
FILTER® cage (4). The gap size and number of FLAMEFILTER® *Resistance thermometer for device group II,
discs are determined by the operating data of the mixture flow- category (1) 2 (GII cat. (1) 2)
ing in the line (explosion group, pressure, temperature). This
device is approved for explosion groups from IIA to IIB3 (NEC
group D to C MESG ≥ 0.65 mm).
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
136 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
IIA Pmax 4.0/58.0 4.0/58.0 4.0/58.0 4.0/58.0 2.9/42.1 2.9/42.1 2.0/29.0 2.0/29.0 2.0/29.0 1.2/17.4
Expl. Gr.
IIB3 Pmax 3.0/43.5 3.0/43.5 2.0/29.0 2.0/29.0 2.0/29.0 2.0/29.0 1.5/21.7 1.4/20.3 1.4/20.3 1.1/15.9
Pmax = maximum allowable operating pressure in bar / psi (absolute), higher operating pressure upon request
KA / 4 / 0318 / GB 137
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DR/ES
.
flow rate V (m³/h) Leistung-000275-en
DR/ES-IIA-P1.6
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000271-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). Con-
version to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
138 KA / 4 / 0318 / GB
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DR/ES
.
flow rate V (m³/h) Leistung-000269-en
* DN 25 - DN 80; P1.6
DN 100; P1.5
DN 125, DN 150; P1.4
DN 200; P1.1
DR/ES-IIB3-P*
pressure drop ∆p - inch W.C.
pressure drop ∆p (mbar)
.
flow rate V (m³/h) Leistung-000272-en
KA / 4 / 0318 / GB 139
In-Line Detonation Flame Arrester
Flow Capacity Charts (liquid)
PROTEGO® DR/ES
(liquid)
.
flow rate V (m³/h) (liquid) Leistung-000273-en
* DN 25 - DN 80; P1.6
DN 100; P1.5
DN 125, DN 150; P1.4
DN 200; P1.1
(liquid)
.
flow rate V (m³/h) (liquid) Leistung-000265-en
. . pwater
Conversion: Vliquid = Vwater *
pliquid
.
The volume flow V in m³/h was determined with water according to DIN EN 60534 at a temperature Tn = 15°C and
an atmospheric pressure pn = 1,013 bar, kinematic viscosity v = 10-6 m²/s
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
140 KA / 4 / 0318 / GB
Notes:
141
In-Line Detonation Flame Arrester
with integrated pressure relief valve, for stable detonations and deflagrations
in right angle design with shock absorber, unidirectional
PROTEGO® DR/ES-V
DN
ture). This device is available for explosion groups from IIA to
5 IIB3 (NEC group D to C MESG ≥ 0.65 mm).
The standard design is approved at an operating temperature
c
2 up to +60°C / 140°F and absolute operating pressure up to
1.2 bar / 17.4 psi. Devices with special approvals can be obtained
b
Special Features and Advantages
DN
• integration of in-line detonation flame arrester and
a pressure relief valve in one device
Connection to the protected side • excellent tightness of the valve
Set pressure: from +2.0 mbar up to +35 mbar • applicable as a detonation-proof check valve in suction
from +0.8 inch W.C. up to +14 inch W.C. lines of storage tanks
Higher or lower settings upon request • optimum for use as an overflow valve in venting and
recovering vapour lines
Function and Description
• minimum number of FLAMEFILTER® discs due to the
PROTEGO® DR/ES-V series uniquely combines the function of effective shock absorber
a in-line detonation flame arrester with the function of a pressure
• quick removal and installation of the complete
relief valve in one device. The device protects against deflagra-
PROTEGO® flame arrester unit and the individual
tion and stable detonation. The weight-loaded pallet type valve
FLAMEFILTER® discs in the cage
(5) integrated in the shock absorber (1) of the in-line detonation
flame arrester is designed as pressure relief valve. The set pres- • provides protection from deflagration and stable detonations
sure of the valve is adjusted in the factory and can range from • extended application range for higher operating tempera-
2 to 35 mbar (0.8 to 14 inch W.C.). After the pressure increases tures and pressures
40% from its set pressure, the valve completely opens to yield • cost efficient spare parts
the maximum volumetric flow. If installed in vent headers com-
ected to storage tanks, the valve pallet works as check valve. Design Types and Specifications
This means that the product can not flow back from the suction
line into the tank. Although several functions are integrated in a There are two different designs available:
single housing, the device is extremely easy to service, which is Basic version of the detonation arrester with DR/ES- V - –
primarily due to the classic right angle design. check valve
Once a detonation enters the flame arrester, energy is ab- Detonation arrester with check valve and DR/ES- V - H
sorbed from the detonation shock wave by the integrated shock heating jacket
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
25 / 1 /
DN 40 / 1 ½" 50 / 2" 65 / 2 ½" 80 / 3" 100 / 4" 125 / 5" 150 / 6" 200 / 8"
32 / 1 ¼"
a 125 / 4.92 153 / 6.02 155 / 6.10 198 / 7.80 200 / 7.87 250 / 9.84 332 / 13.07 335 / 13.19 425 / 16.73
b 140 / 5.51 183 / 7.20 185 / 7.28 223 / 8.78 225 / 8.86 290 / 11.42 357 / 14.06 360 / 14.17 505 / 19.88
c 237 / 9.33 305 / 12.01 305 / 12.01 395 / 15.55 395 / 15.55 460 / 18.11 575 / 22.64 575 / 22.64 863 / 33.98
c1 345 / 13.58 410 / 16.14 410 / 16.14 530 / 20.87 530 / 20.87 615 / 24.21 790 / 31.10 790 / 31.10 1295 / 50.98
d 149 / 5.87 210 / 8.27 210 / 8.27 275 / 10.83 275 / 10.83 325 / 12.80 460 / 18.11 460 / 18.11 620 / 24.41
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
142 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
KA / 4 / 0318 / GB 143
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DR/ES-V
DR/ES-V-IIA-P1.2
40 % overpressure
.
flow rate V (m³/h) Leistung-000261-en
DR/ES-V-IIA-P1.6
40 % overpressure
.
flow rate V (m³/h) Leistung-000260-en
Remark
opening pressure resp. tank design pressure
set pressure =
1,4
Set pressure = the valve starts to open
Opening pressure = set pressure plus overpressure
Overpressure = pressure increase over the set pressure
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
144 KA / 4 / 0318 / GB
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DR/ES-V
DR/ES-V-IIB3-P1.2
40 % overpressure
.
flow rate V (m³/h) Leistung-000256-en
* DN 25 - DN 80; P1.6
DN 100; P1.5
DN 125, DN 150; P1.4
DN 200; P1.1
DR/ES-V-IIB3-P*
40 % overpressure
.
flow rate V (m³/h) Leistung-000258-en
KA / 4 / 0318 / GB 145
In-Line Liquid Detonation Flame Arrester
for filling lines - external installation
PROTEGO® LDA-W
a
When a highly accelerated pipe deflagration or detonation
Ød occurs, the combustion pressure and flame propagation speed
is first substantially reduced by the construction and convert-
ed into a low-energy deflagration that is then stopped by the
remaining immersion liquid.
The application range for the device is a product vapour/
air mixture temperature up to +60°C / 140°F and an absolute
pressure up to 1.1 bar / 15.9 psi. This covers all of the pos-
DN
DN
sible operating conditions of empty lines for flammable liquids.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
146 KA / 4 / 0318 / GB
Table 2: Selection of the explosion group
MESG Expl. Gr. (IEC/CEN) Gas Group (NEC)
> 0,90 mm IIA D Special approvals upon request
≥ 0,65 mm IIB3 C
.
flow rate V (m³/h) (liquid) Leistung-000369-en
. . pwater
Conversion: Vliquid = Vwater *
pliquid
.
The volume flow V in m³/h was determined with water according to DIN EN 60534 at a temperature
Tn = 15°C and an atmospheric pressure pn = 1,013 bar, kinematic viscosity v = 10-6 m²/s.
To avoid electrostatic charge of flammable liquids the maximum flow is limited (refer to BG-Regulation 132,
CENELEC-Report CLC/TR 50404).
for safety and environment
KA / 4 / 0318 / GB 147
In-Line Liquid Detonation Flame Arrester
for filling and drain lines - external installation
PROTEGO® LDA-WF(W)
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
148 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
LDA-WF(W)-IIB3
.
flow rate V (m³/h) (liquid) Leistung-000423-en
. . pwater
Conversion: Vliquid = Vwater *
pliquid
.
The volume flow V in m³/h was determined with water according to DIN EN 60534 at a temperature
Tn = 15°C and an atmospheric pressure pn = 1,013 bar, kinematic viscosity v = 10-6 m²/s.
To avoid electrostatic charge of flammable liquids the maximum flow is limited (refer to BG-Regulation 132,
CENELEC-Report CLC/TR 50404).
for safety and environment
KA / 4 / 0318 / GB 149
Liquid Detonation Flame Arrester
for filling lines - internal installation
PROTEGO® LDA
Ød The device is installed inside the tank at the end of the line and
DN prevents the combustion from being transferred into the tank if
the explosive atmosphere ignites. The liquid detonation arresters
function according to the siphon principle in which the liquid
product serves as a liquid barrier to flame propagation.
When a highly accelerated pipe deflagration or detonation
occurs, the combustion pressure and flame propagation speed
is first substantially reduced by the design and converted into a
c
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
150 KA / 4 / 0318 / GB
Table 2: Selection of the explosion group
MESG Expl. Gr. (IEC/CEN) Gas Group (NEC)
> 0,90 mm IIA D Special approvals upon request
≥ 0,65 mm IIB3 C
.
flow rate V (m³/h) (liquid) Leistung-000367-en
. . pwater
Conversion: Vliquid = Vwater *
pliquid
.
The volume flow V in m³/h was determined with water according to DIN EN 60534 at a temperature
Tn = 15°C and an atmospheric pressure pn = 1,013 bar, kinematic viscosity v = 10-6 m²/s.
To avoid electrostatic charge of flammable liquids the maximum flow is limited (refer to BG-Regulation 132,
CENELEC-Report CLC/TR 50404).
for safety and environment
KA / 4 / 0318 / GB 151
Liquid Detonation Flame Arrester
for filling and drain lines - internal installation
PROTEGO® LDA-F
1 product serves as a barrier to flame propagation.
When a highly accelerated pipe deflagration or deto-
2 nation occurs, the combustion pressure and flame
propagation speed is first substantially reduced by the de-
DN sign and converted into a low-energy deflagration that is
3
then stopped by the remaining immersion liquid and the
Outlet type II
PROTEGO® flame arrester.
a
4
The application limits for the device is product vapour/air
mixture temperatures up to +60°C / 140°F and an abso-
lute pressure up to 1.1 bar / 15.9 psi. This covers all of
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
152 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
LDA-F-IIB3
pressure drop ∆p (mbar)
.
flow rate V (m³/h) (liquid) Leistung-000368-en
. . pwater
Conversion: Vliquid = Vwater * pliquid
.
The volume flow V in m³/h was determined with water according to DIN EN 60534 at a temperature
Tn = 15°C and an atmospheric pressure pn = 1,013 bar, kinematic viscosity v = 10-6 m²/s.
To avoid electrostatic charge of flammable liquids the maximum flow is limited (refer to BG-Regulation 132,
CENELEC-Report CLC/TR 50404).
for safety and environment
KA / 4 / 0318 / GB 153
Detonation Flame Arrester
Detonation-proof foot valve for suction lines
PROTEGO® EF/V-IIB3
a
ture temperature up to +60°C / 140°F and an absolute pressure
up to 1.1 bar / 15.9 psi. This covers all of the possible operating
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
154 KA / 4 / 0318 / GB
Table 3: Specification of max. operating temperature
≤ 60°C / 140°F Tmaximum allowable operating temperature in °C
higher operating temperatures upon request
- Designation
EF/V-IIB3
.
flow rate V (m³/h) (liquid) 2078-L
. . pwater
Conversion: Vliquid = Vwater *
pliquid
.
The volume flow V in m³/h was determined with water according to DIN EN 60534 at a temperature Tn = 15°C
and an atmospheric pressure pn = 1,013 bar, kinematic viscosity v = 10-6 m²/s.
To avoid electrostatic charge of flammable liquids the maximum flow is limited (refer to BG-Regulation 132,
CENELEC-Report CLC/TR 50404).
KA / 4 / 0318 / GB 155
Hydraulic Flame Arresters
deflagration proof, detonation proof and short-time burning proof
9 6
3 7 4
5 10 11 1 8 2
Function and Description arrester to allow cleaning of the drill holes and the pipes. At the
off gas inlet the manifold has the required flange connection and
The PROTEGO hydraulic flame arresters of type TS/… are
®
the relevant number of nozzles for distributing the off gas into
mainly designed to protect process plants which are connected
required number of sparge pipes.
to waste thermal combustion units. Hydraulic flame arresters of
the TS/… series are particularly suitable to protect plants which In PROTEGO® hydraulic flame arresters of type TS/… the flam-
supply heavily contaminated, sticking, polymerizing or even mable mixtures are passed through a water seal with a defined
foaming substances into thermal combustion units. Generally immersion depth. The mixture flow is prorated up and passed
it is necessary to protect the plant against in-line deflagration, to the individual sparge pipes. The sparge pipes have small drill
stable detonation and endurance burning hazards taking into holes and therefore produce defined bubble columns. In case of
account the plant’s operating conditions. an ignition in the flowing gas mixture the flame is prevented from
transmission into the inlet line. The following parameters have a
The PROTEGO® TS/… series of hydraulic flame arresters gua-
significant effect on the flame arresting efficiency of the device in
rantees flame transmission protection during short time burning,
case of deflagrations, detonations or short time burning:
deflagration and stable detonation of gas/air mixtures or product
vapour/air mixtures of the relevant explosion groups in all rang- • Mixture volume flow,
es of flammable concentrations up to a service temperature of
• Immersion depth from the water seal’s surface to the upper
+60 °C / 140 °F and under an operating pressure up to 1.1 bar /
edges of the drill holes in the sparge pipes,
15 psi (absolute).
• Water temperature in the hydraulic flame arrester
Flame arresters of type TS/… are the only hydraulic flame
arresters which have been tested and certified for substances of • Sizes, form and density of the bubbles and therefore the
all explosion groups. precise drill hole diameter in the sparge pipes.
Type-approved in accordance with the current ATEX Directive If the mixture ignites under certain operating conditions within
and EN ISO 16852 as well as other international standards. the hydraulic flame arrester and burns directly on the liquid sur-
face prevention of flame transmission can only be guaranteed
Hydraulic flame arresters of series TS/… mainly consist of the
for a limited amount of time. Therefore a number of tempera-
immersion tank (1) with off gas nozzle and connection nozzles
ture sensors are installed in the gas space and when reach-
for the sparge pipes, the sparge pipes (2) with elbows and con-
ing a specified temperature they trigger appropriate emergency
nection flanges as well as the manifolds (3) with connection
functions upstream in the system connected (shut down,
flanges. To allow measurement of the immersion liquid tem-
inerting, etc.).
perature the tank (1) has a minimum of one nozzle (5), and for
measuring the temperature of the off gas there is a minimum A high accuracy volume flow meter must be installed as an
of one connection for each exhaust gas nozzle (6) for insertion essential technical safety element. It has to guarantee that
of temperature sensors. Additionally the tank has two nozzles the maximum allowable volume flow, on which the design
(7, 8) for level measurement, two nozzles (9, 10) for level con- of the hydraulic flame arrester has been based, is recorded
trol, and one nozzle (11) for draining. Inspection-glasses (4) are and limited so that emergency functions are triggered if the
included for inspection of the immersion liquid and gas space. off gas volumes exceed the safe level. In addition, a minimum
The sparge pipes can be pulled out of the hydraulic flame flame-transmission-proof immersion height is necessary, i.e. an
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
156 KA / 4 / 0318 / GB
adequate water level must be guaranteed by suitable measuring Types TS/P 1000 / 40” or TS/P 2000 / 80”
equipment.
For explosion group IIB3 (NEC group C)
The pressure loss of a hydraulic flame arrester at maximum vol- Types TS/E 1000 / 40” or TS/E 2000 / 80”
ume flow equals losses at inflow and outflow of approximately
For explosion group IIC (NEC group B)
12 to 18 mbar / 4.8 to 7.2 In W.C. plus the immersion depth,
Types TS/W 1000 / 40” or TS/W 2000 / 80”
e.g. 350 mm = 35 mbar / 13.8 In = 14.1 In W.C., so the total is
between 47 and 53 mbar / 18.9 and 21.3 In W.C. The number of sparge pipes depends on the design volume
flow.
Instrumentation
Example: TS/E-1000-5 is a hydraulic flame arrester for sub-
The efficiency and function of the PROTEGO TS/… hydraulic
stances of explosion group IIB3 (NEC group C) with a diameter
flame arrester requires measurement and control equipment for
of 1000 mm / 40” and 5 sparge pipes.
the filling level, volume flow and temperature of the system. It is
necessary to maintain the minimum operating immersion depth Dimensions
and measure the maximum mixture volume flow, maximum
Standard diameters of TS/… series hydraulic flame arresters are
gas temperature and minimum water temperature. If the safe
1000 mm / 40” and 2000 mm / 80”. Alternatively diameters from
operational envelope is exceeded, the measurement and control
600 mm / 24” to 3000 mm / 120” are available depending on the
equipment must quickly initiate automatic emergency functions.
off gas volume flow. Hydraulic flame arresters with diameters
Measurement and control safety equipment must be explosion
from 2000 mm / 80” and larger have a restriction plate to prevent
proof and approved for zone 0.
wave motions in the sparging zone. All outlet headers and inlet
Measurement and control equipment is not part of standard headers as well as internal are components relevant for techni-
scope of supply. cal safety, and it is therefore not allowed to change their design
and function nor that of the hydraulic flame arrester!
Maximum Volume Flow
Material Selection
The maximum allowable operating volume flow is calculated by
multiplying the number of sparge pipes by the maximum allow- The material selection is determined by the exhaust air process
able operating volume flow for each sparge pipe at its immersion data. Tank designs of steel, stainless steel, coated steel or
depth. steel lined with ECTFE or resin are available depending on the
application. The sparge pipes are made of stainless, hastelloy
In special cases it may not be necessary to measure the volume
or plastic.
flow provided that the volume flow limitation is guaranteed by
other components in the system such as a conveyor system or Flange Connection Type
a choke in combination with a decompression device.
The standard flange connections are made to EN 1092-1;
Level Measurement and Level Control Form B1. Optionally, the connecting flanges can be made ac-
cording to any international standard.
The operating immersion depth should be kept constant by a
controlled automatic water supply so that the level does not fall Selection and Design
below the minimum immersion depth.
The static immersion depth and the resistance due to dynamic
Temperature Measurement and Limitation flow in the sparge pipes and the off gas supply lines create the
total pressure loss. The manufacturer’s advice about technical
In order to prevent endurance burning in the arrester the off gas
safety is absolutely necessary in any case!
supply must be stopped automatically when the temperature
exceeds T = 80°C / 176 °F at the gas outlet. Temperature sensors For particularly corrosive mixtures the hydraulic flame arrester
monitor the mixture temperature. may be coated. The materials of tank, installations and sparge
pipes have to be selected according to the corrosive properties
If the water temperature falls below T < 10°C / 50 °F (danger
of the mixture.
of freezing) or rises above the limiting temperature in the gas
space, a quick action gate valve must shut automatically and Data Necessary for Specification
stop the off gas supply.
The following operational data is required for the technical safety
As an option temperature sensors can be supplied. of the hydraulic flame arrester design:
Design Types and Specifications Off gas volume flow taking into account the maximum possible
volume flow (m³/h or CFH)
The hydraulic flame arresters are designated by explosion
groups, diameters and numbers of sparge pipes. They are Off gas composition (vol.%)
designed in modules and type tested for the corresponding ex-
Operating temperature (°C or °F)
plosion groups.
For explosion group IIA (NEC group D)
KA / 4 / 0318 / GB 157
In-Line Detonation Flame Arrester
for unstable and stable detonations and deflagrations in a straight through design
with a shock tube, bidirectional
PROTEGO® DA-UB
NG
Øa
DN
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
158 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER® New PROTEGO® Flame Arrester Unit unique
Discs (Flyer pdf) maintenance friendly design (Flyer pdf)
26.1 26.1 23.2 23.2 15.9 15.9 15.9 15.9 15.9 23.2
1.5 / 1.5 / 1.5 / 1.5 / 1.1 / 1.1 / 1.1 / 1.1 / 1.1 /
IIB3 Pmax
21.7 21.7 21.7 21.7 15.9 15.9 15.9 15.9 15.9
Pmax = maximum allowable operating pressure in bar / psi (absolute), higher operating pressure upon request
in-between size up to Pmax upon request
KA / 4 / 0318 / GB 159
In-Line Detonation Flame Arrester
for unstable and stable detonations and deflagrations in a straight through design
with a shock tube, bidirectional
PROTEGO® DA-UB
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
160 KA / 4 / 0318 / GB
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DA-UB
* *
* *
DN/
— NG
* P1.2
DA-UB-IIA-P1.1
.
flow rate V (m³/h) Leistung-000349-en
* * *
N
/D
* P1.2
— NG
.
flow rate V (m³/h) Leistung-000350-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 4 / 0318 / GB 161
In-Line Detonation Flame Arrester
for unstable and stable detonations and deflagrations in a straight through design
with shock absorber, bidirectional
PROTEGO® DA-CG
DN
Øa
NG
DN
The standard design can be used up to an operating tempera- Additional special flame arresters upon request
ture of +60°C / 140°F and an absolute operating pressure acc. to
table 3. Devices with special approvals can be obtained for *Resistance thermometer for device group II,
higher pressures and higher temperatures upon request. category (1) 2 (GII cat. (1) 2)
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
162 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
1.6 / 1.6 / 1.6 / 1.6 / 1.6 / 1.6 / 1.6 / 1.6 / 1.6 / 1.6 / 1.6 /
IIB3 Pmax
23.2 23.2 23.2 23.2 23.2 23.2 23.2 23.2 23.26 23.2 23.2
Pmax = maximum allowable operating pressure in bar / psi (absolute), higher operating pressure upon request
KA / 4 / 0318 / GB 163
In-Line Detonation Flame Arrester
for unstable and stable detonations and deflagrations in a straight through design
with shock absorber, bidirectional
PROTEGO® DA-CG
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
164 KA / 4 / 0318 / GB
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DA-CG
N
/D
— NG
airflow in thousands of CFH
.
flow rate V (m³/h) Leistung-000042-en
N
/D
— NG
.
flow rate V (m³/h) Leistung-000061-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 4 / 0318 / GB 165
In-Line Detonation Flame Arrester
for unstable and stable detonations and deflagrations in right angle design
with a shock absorber, unidirectional
PROTEGO® DR/EU
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
166 KA / 4 / 0318 / GB
Stabilized FLAMEFILTER®
Discs (Flyer pdf)
KA / 4 / 0318 / GB 167
In-Line Detonation Flame Arrester
Flow Capacity Charts
PROTEGO® DR/EU
.
flow rate V (m³/h) 1792-L
P* see table 3
– – – DR/EU-IIB2-P1.4
pressure drop ∆p - inch W.C.
–––– DR/EU-IIB3-P*
pressure drop ∆p (mbar)
.
flow rate V (m³/h) 1793-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
168 KA / 4 / 0318 / GB
Notes:
169
www.protego.com
for safety and environment
PROTEGO® Pressure/Vacuum Relief Valves
end-of-line
Volume 5
Volume 5
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
172 KA / 5 / 0318 / GB
Selection and sizing
which needs 10% overpressure to reach full lift the set pres-
To operate the system properly, the right valve is to be sure may be chosen 10% below the fully open pressure (e.g.
selected. maximum allowable tank pressure). Attention: pressure drop of
The criteria for selecting the right device are: piping systems and other installed devices have to be con-
sidered!
Function – a pressure relief valve, a vacuum relief valve, or
a combined pressure/vacuum relief valve, with a pipe-away Many conventional valves need 100% overpressure to reach full
connection if needed. lift. In these cases the set pressure may be just half of the maxi-
mum allowable tank pressure. Consequently these valves open
Design – a combined end-of-line valve or separate pressure earlier and avoidable product losses occur.
relief and vacuum relief valves with a perpendicular connection
or horizontal connection. The devices are weight-loaded; there- Example 2
fore the valves are to be installed vertically. Alternatively the valve performance has to be checked if the size
The adjusted set pressure – the standard maximum and maximum allowable pressure are provided.
allowable (tank) pressure minus 10% overpressure; Given: Connection nozzle size and maximum allowable open-
it determines the combination of materials for the disc. ing pressure (e.g. tank pressure) p in mbar / inch W.C.
Type of seal – for disc valves according to the pressure level, Required: Volume flow in m3/h / CFH, set pressure pA in
either with an air cushion seal, or with a metal seal to provide an mbar / inch W.C.
extremely tight seal.
Procedure: From the intersection point of the straight line of p
Special operating conditions – for viscous and adhesive and the valve performance curve of the specific valve size the
.
media, for frost-protected operation, or for use with poly- volume flow Vmax is determined. The volume flow of the set pres-
merizing products. sure pA may be 10%, (PROTEGO® technology) or 40% or 100%
The nominal diameter of the valve is generally determined by below the opening pressure pT. Attention: pressure drop of pip-
the connecting flange of the pipe, tank, or system part, or by the ing systems and other installed devices have to be considered!
design specified in the performance diagram. To size a valve,
the flow must be known for the overpressure output (outbrea-
thing) and vacuum output (inbreathing). The nominal diameter
or number of valves may have to be adjusted. Take into account
potential system counterpressure when connecting a pipe. airflow in thousands of CFH
Sizing
The valve size results from the volume flow which has to be
vented to avoid an increase above the maximum allowable pres-
sure or vacuum. Certified volume flow diagrams are used for
sizing. For correct sizing the operating conditions and the pres-
ing of a storage tank this is the sum of the pump capacity and
The required set pressure (= start of opening) will be the open-
the thermal breathing requirement) and maximum allowable
ing pressure (valve fully open) minus the characteristic over-
opening pressure (e.g. tank pressure) pT in mbar / inch W.C.
pressure.
Requested: Valve size DN For PROTEGO® valves and end of line devices the overpres-
. sure characteristic is 10% unless otherwise stated. Within 10%
Procedure: The intersection point of V max and pT determines
overpressure the valve pallet will reach full lift. A further increase
the required valve size. Opening pressure = the maximum allow-
in flow performance will follow the pressure volume flow dia-
able tank pressure. The volume flow diagrams show the volume
gram.
flow as function of the opening pressure for a fully open valve.
Material selection is based on plant and
The set pressure of the valve has to be determined so that the
engineering specifications.
calculated volume flow can safely be discharged. For a valve
KA / 5 / 0318 / GB 173
Selection Guide
rosion, Cristallisation)
= horizontal connection
operating parameters
(Polymerisation, Cor
X = vertical connection
= Heating jacket,
X = metallic sealing
pressure setting
Heating coil
= soft sealing
positive negative
setting range setting range
Design
Type Size mbar / mbar / Page
inch W.C. inch W.C.
50 - 80 +3.5 up to +210/
P/EL X /X 176 - 177
2" - 3" +1.4 up to +84
80-200 +5 up to +210/
SD/BS-H X X 180 - 181
3" - 8" +2 up to +84
DN 200-350:
+5 up to +40/
200-700 +2 up to +16
ER/V X
8" - 28" DN 400-700:
+5 up to +25/
+2 up to +10
DN 200-350:
>+40 up to +60/
200-700 >+16 up to +24
ER/VH X 186 - 187
8" - 28" DN 400-700:
>+25 up to +60/
>+10 up to +24
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
174 KA / 5 / 0318 / GB
operating parameters
rosion, Cristallisation)
= horizontal connection
(Polymerisation, Cor-
X = vertical connection
= Heating jacket,
X = metallic sealing
pressure setting
Heating coil
= soft sealing
positive negative
setting range setting range
Design
Type Size mbar / mbar / Page
inch W.C. inch W.C.
KA / 5 / 0318 / GB 175
Pressure Relief Valve
PROTEGO® P/EL
Øa
lowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety relief
valve. This “full lift type” technology allows the valve to be set
just 10% below the maximum allowable working pressure of the
tank and still safely vent the required mass flow.
Due to our highly developed manufacturing technology the
tank pressure is maintained up to set pressure, with a tightness
that is far superior to the conventional standard. This feature is
achieved by valve seats made of high quality stainless steel and
with precisely lapped valve pallets (1) or with an air cushion seal
(2) in conjunction with high quality FEP diaphragm. The valve
pallets are also available with a PTFE seal to prevent the valve
pallets from sticking when sticky products are used, and they
b
Pressure settings: • the valve pallet is guided within the housing to protect
+3.5 mbar up to +210 mbar against harsh weather conditions
+1.4 inch W.C. up to +84 inch W.C. • can be used in areas subject to an explosion hazard
Higher pressure settings upon request.
• self-actuated condensate drain
Function and Description
The P/EL type PROTEGO® valve is a highly developed pressure Design Types and Specifications
relief valve. It is primarily used as a safety device for relieving The valve pallet is weight-loaded. At set pressures greater than
pressure in tanks, containers and process engineering equip- 80 mbar (32.1 inch W.C.), an elongated construction is used.
ment. The valve protect against unallowable overpressure and
There are two different designs:
prevents the unacceptable loss of product vapors close to the
set pressure. Pressure valve in basic design P/EL - –
The device will start to open as soon as the set pressure is Pressure valve with heating jacket P/EL - H
reached and only requires 10% overpressure to full lift. Con-
tinuous investments into research and development have al- Additional special devices available upon request
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
176 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf)
pacity Chart
Flow Capacity
P/EL
pressure - inch W.C.
pressure (mbar)
.
flow rate V (m³/h) 2341-L
The flow capacity curve has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 177
Pressure Relief Valve
PROTEGO® P/ELR
Øa
lowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety relief
valve. This “full lift type” technology allows the valve to be set
just 10% below the maximum allowable working pressure of the
tank and still safely vent the required mass flow.
Due to our highly developed manufacturing technology the
tank pressure is maintained up to set pressure with a tightness
that is far superior to the conventional standard. This feature
is achieved by valve seats made of high quality stainless steel
and with precisely lapped valve pallets (1) or with an air cushion
seal (2) in conjunction with high quality FEP diaphragm. The
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and to
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
178 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf)
Flow Capacity
apacity Chart
P/ELR
pressure - inch W.C.
pressure (mbar)
.
flow rate V (m³/h) 2352-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 179
Pressure Relief Valve
in heat jacketed design
PROTEGO® SD/BS-H
DN2
excess pressure is discharged, the valve reseats and
provides a tight seal again.
b
overpressure to reach full lift
• extreme tightness and hence least possible product
d
losses and reduced environmental pollution
DN2
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
180 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf)
SD/BS-H
pressure - inch W.C.
pressure (mbar)
.
flow rate V (m³/h) Leistung-000062-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 181
Pressure Relief Valve
PROTEGO® D/SVL
Øb
the same opening characteristic as a high pressure safety relief
valve. This “full lift type” technology allows the valve to be set
just 10% below the maximum allowable working pressure of the
tank and still safely vent the required mass flow.
Due to the highly developed manufacturing technology, the tank
X pressure is maintained up to the set pressure, with a tightness
that is far superior to the conventional standard. This feature is
achieved by valve seats made of high quality stainless steel and
with precisely lapped valve pallets (1) or with an air cushion seal
(2) in conjunction with high quality FEP diaphragm. The valve
a
pallets are also available with a PTFE seal to prevent the val-
ve pallet from sticking when sticky products are used, and they
Detail X enable the use of corrosive media. After the excess pressure is
discharged, the valve reseats and provides a tight seal again.
The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
1
stable operation of the valve pallet and optimized performance
resulting in reduction of product losses.
DN
Special Features and Advantages
2
• “full lift type” technology valve utilizes only 10% overpressure
to reach full lift
Pressure settings: • extreme tightness and hence least possible product losses
+2.0 mbar up to +60 mbar and reduced environmental pollution
+0.8 inch W.C. up to +24 inch W.C.
Higher pressure settings upon request. • the set pressure is close to the opening pressure which
results in best possible pressure management of the system
• extremely high flow capacity
Function and Description
• the valve pallet is guided within the housing to protect
The D/SVL type PROTEGO® valve is a high performance pres- against harsh weather conditions
sure relief valve. It is primarily used as a safety device for reli-
• can be used in areas subject to an explosion hazard
eving pressure in tanks, containers, and process engineering
equipment. The valve offers reliable protection against over- Design Types and Specifications
pressure and prevents the unacceptable loss of product vapors
close to the set pressure. The valve pallet is weight-loaded. Higher pressures can be
achieved upon request with a special spring-loaded design.
The device will start to open as soon as the set pressure is
reached and only requires 10% overpressure to full lift. Con- Pressure valve in basic design D/SVL -
tinuous investments into research and development have al-
lowed PROTEGO® to develop a low pressure valve which has Additional special devices available upon
request
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
182 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf)
D/SVL
.
flow rate V (m³/h) 2256-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 183
Emergency pressure relief valve
PROTEGO® ER-V-LP
b
DN
Øa
Pressure Settings:
+3.4 mbar up to +15 mbar
+1.4 inch W.C. up to +6 inch W.C.
For higher pressure settings, see types ER/V, ER/VH and
ER/V-F.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
184 KA / 5 / 0318 / GB
Emergency Relief Valve Vents - 10% Technology
(Flyer pdf) (Flyer pdf)
ER-V-LP
pressure - (inch W.C.)
pressure (mbar)
.
flow rate V (m³/h) Leistung-000079-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 185
Pressure Relief Valve
PROTEGO® ER/VH
d
c sure of the tank. Even in the low pressure range the vent has
Øa the opening characteristic comparable to a typical high pressure
safety relief valve. The full lift type pallets are a result of many
years of development. The valve pallet is mounted on one side.
Due to the highly developed manufacturing technology, the tank
pressure is maintained up to the set pressure, with a tightness
that is far superior to the conventional standard. This feature is
achieved by valve seats made of stainless steel with an inserted
b
O-ring seal, a precisely lapped valve pallet, as well as a rein-
forced housing design. After the excess pressure is discharged,
the valve reseats and provides a tight seal again.
When the set pressure is reached, the valve starts to open and Additional special devices available upon
is fully open within 10% overpressure. This unique 10% ”full lift request
type technology” enables a pressure setting that is only 10%
below the maximum allowable working pressure or design pres-
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
186 KA / 5 / 0318 / GB
Vents - 10% Technology
(Flyer pdf)
ER/VH
.
flow rate V (m³/h) Leistung-000222-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 187
Pressure Relief Valve
PROTEGO® ER/V-F
Øa
The device will start to open as soon as the set pressure is
reached and only requires 10% overpressure to full lift. Con-
tinuous investments into research and development have al-
lowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety relief
valve. This “full lift type” technology allows the valve to be set
just 10% below the maximum allowable working pressure of the
tank and still safely vent the required mass flow.
Due to the highly developed manufacturing technology, the tank
pressure is maintained up to the set pressure, with a tightness
that is far superior to the conventional standard. This feature
is achieved by valve seats made of high-grade steel with an
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
188 KA / 5 / 0318 / GB
Vents - 10% Technology
(Flyer pdf)
980 / 38.58 980 / 38.58 1490 / 58.66 1490 / 58.66 1490 / 58.66 1515 / 59.65 1660 / 65.35 1655 / 65.16 1910 / 75.20
b (>370 mbar (>240 mbar (>240 mbar (>270 mbar (>220 mbar (>170 mbar (>130 mbar (>140 mbar (>140 mbar
>148 inchW.C.) >96 inchW.C.) >96 inchW.C.) ≤108 inchW.C.) ≤88 inchW.C.) >68 inchW.C.) >52 inchW.C.) >56 inchW.C.) >56 inchW.C.)
ER/V-F
pressure - inch W.C.
pressure (mbar)
.
flow rate V (m³/h) Leistung-000121-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 189
Pressure Relief Valve
made of plastic
PROTEGO® D/KSM
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
190 KA / 5 / 0318 / GB
Vents for corrosive vapor service Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf) (Flyer pdf)
D/KSM
pressure - inch W.C.
pressure (mbar)
.
flow rate V (m³/h) 2465-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 191
Vacuum Relief Valve
PROTEGO® SV/E-1-0
c
junction with high quality FEP diaphragm. The valve
DN
pallets are also available with a PTFE seal to prevent
the valve pallets from sticking when sticky products are
used, and they enable the use of corrosive media. After
b
the vacuum is relieved, the valve reseats and provides
a tight seal again.
The device will start to open as soon as the set pressure is There are two different designs:
reached and only requires 10% overpressure to full lift. Con- Vacuum valve in basic design SV/E-1-0 - –
tinuous investments into research and development have al-
Vacuum valve with heating jacket SV/E-1-0 - H
lowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety relief Additional special devices available upon request.
valve. This “full lift type” technology allows the valve to be set
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
192 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf)
.
flow rate V (m³/h) Leistung-000080-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 193
Vacuum Relief Valve
in a special heat jacketed design
PROTEGO® SV/T-0-H
f
Øb When the set vacuum is reached, the valve starts to open
drawn displaced
and reaches full lift within a 40% vacuum increase. Up to the
set vacuum, the tank vacuum is maintained with a seal that
is far superior to the conventional standard due to the highly
developed manufacturing technology. This feature is achieved
DN2
by valve seats made of high quality stainless steel with precisely
lapped valve pallets and a reinforced housing design. After the
vacuum is relieved, the valve reseats and again provides a tight
seal.
a
• excellent tightness and hence least possible product losses
and reduced environmental pollution
d
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
194 KA / 5 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN) use the capacity chart on the following page
DN1 80 / 3" * 100 / 4" 150 / 6" 200 / 8" 250 / 10"
DN2 15 / ½" 15 / ½" 15 / ½" 15 / ½" 15 / ½"
a 570 / 22.44 570 / 22.44 720 / 28.35 920 / 36.22 1050 / 41.34
b 275 / 10.83 275 / 10.83 355 / 13.98 405 / 15.94 508 / 20.00
c 70 / 2.76 70 / 2.76 60 / 2.36 70 / 2.76 70 / 2.76
d 440 / 17.32 440 / 17.32 590 / 23.23 790 / 31.10 920 / 36.22
e 450 / 17.72 450 / 17.72 650 / 25.59 750 / 29.53 950 / 37.40
f 225 / 8.86 225 / 8.86 260 / 10.24 300 / 11.91 350 / 13.78
* also available with special flange DN 50 / 2"
KA / 5 / 0318 / GB 195
Vacuum Relief Valve
Flow Capacity Chart
PROTEGO® SV/T-0-H
SV/T-0-H
.
flow rate V (m³/h) Leistung-000089-en
Remark
opening pressure resp. tank design pressure
set pressure =
1.4
Set pressure = the valve starts to open
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
196 KA / 5 / 0318 / GB
Notes:
197
Vacuum Relief Valve
made of plastic
PROTEGO® V/KSM
b
pallet is a result of many years of research work, which allow a
stable operation of the valve pallet and optimized performance
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
198 KA / 5 / 0318 / GB
Vents for corrosive vapor service Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf) (Flyer pdf)
V/KSM
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) 2461-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 5 / 0318 / GB 199
Pressure and Vacuum Relief Valve
PROTEGO® PV/EL
Ød
allowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety re-
lief valve. This “full lift type” technology allows the valve to be
set just 10% below the maximum allowable working pressure or
vacuum (MAWP or MAWV) of the tank and still safely vent the
required mass flow. The opening characteristic is the same for
presssure and vacuum relief.
Due to the highly developed manufacturing technology, the tank
pressure is maintained up to the set pressure, with a tightness
that is far superior to the conventional standard. This feature is
achieved by valve seats made of high quality stainless steel and
a
with precisely lapped valve pallets (1) or with an air cushion seal
(2) in conjunction with high quality FEP diaphragm. The valve
pallets are also available with a PTFE seal to prevent the val-
ve pallet from sticking when sticky products are used, and they
enable the use of corrosive media. After the excess pressure is
X discharged or the vacuum is compensated, the valve reseats
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
200 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 5 / 0318 / GB 201
Pressure and Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® PV/EL
PV/EL
DN 50/2“ and 80/3“
pressure
.
flow rate V (m³/h) 2373-L
PV/EL
DN 50/2“ and 80/3“
vacuum vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) 2374-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
202 KA / 5 / 0318 / GB
Notes:
203
Pressure and Vacuum Relief Valve
PROTEGO® PV/ELR
Ød
set just 10% below the maximum allowable working pressure or
vacuum (MAWP or MAWV) of the tank and still safely vent the
required mass flow. The opening characteristic is the same for
presssure and vacuum relief.
Due to the highly developed manufacturing technology, the tank
pressure is maintained up to the set pressure, with a tightness
that is far superior to the conventional standard. This feature is
achieved by valve seats made of high quality stainless steel and
with precisely lapped valve pallets (1) or with an air cushion seal
(2) in conjunction with high quality FEP diaphragm. The valve
pallets are also available with a PTFE seal to prevent the val-
a
ve pallet from sticking when sticky products are used, and they
enable the use of corrosive media. After the excess pressure is
discharged or the vacuum is compensated, the valve reseats
and provides a tight seal.
The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
X
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
204 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 5 / 0318 / GB 205
Pressure and Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® PV/ELR
PV/ELR
DN 80/3“ and 100/4“
pressure
.
flow rate V (m³/h) Leistung-000092-en
PV/ELR
DN 80/3“ and 100/4“
vacuum vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000091-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
206 KA / 5 / 0318 / GB
Notes:
207
Pressure and Vacuum Relief Valve
PROTEGO® VD/SV
b
Øc
1
a
2
X
Settings:
Pressure: +2.0 mbar up to +60 mbar
+0.8 inch W.C. up to +24 inch W.C.
Vacuum: -2.0 mbar up to -60 mbar
-0.8 inch W.C. up to -24 inch W.C.
DN
Higher or lower settings upon request.
Function and Description Special Features and Advantages
The VD/SV type PROTEGO valve is a highly developed pres-
®
• “full lift type” technology valve utilizes only 10% overpressure
sure and vacuum relief valve with excellent flow performance. to reach full lift
Typically the valve is installed in the in- and outbreathing lines
• extreme tightness and hence least possible product losses
of tanks, vessels and process apparatus to protect against un-
and reduced environmental pollution
allowable high and low pressure. The valve prevents emission
losses almost up to the set pressure and prevents air intake • the set pressure is close to the opening pressure which re-
almost up to set vacuum. sults in best possible pressure management of the system
The device will start to open as soon as the set pressure is • very high flow capacity
reached and only requires 10% overpressure to full lift. Con-
• the valve pallet is guided within the housing to protect
tinuous investments into research and development have al-
against harsh weather conditions
lowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety relief • can be used in areas subject to explosion hazards
valve. This “full lift type” technology allows the valve to be set • self draining
just 10% below the maximum allowable working pressure or
vacuum (MAWP or MAWV) of the tank and still safely vent the • maintenance friendly design
required mass flow. The opening characteristic is the same for • best technology for API-tanks
presssure and vacuum relief.
Due to our highly developed manufacturing technology the Design Types and Specifications
tank pressure is maintained up to set pressure with a tightness
The valve pallets are weight-loaded. Higher pressures can be
that is far superior to the conventional standard. This feature
achieved upon request with a special spring-loaded design.
is achieved by valve seats made of high quality stainless steel
and with precisely lapped valve pallets (1) or with an air cushion There are two different designs:
seal (2) in conjunction with high quality FEP diaphragm. The Pressure/vacuum valve in basic design VD/SV- –
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and Pressure/vacuum relief valve with heating jacket VD/SV- H
to enable the use of corrosive fluids. After the excess pressure Additional special devices available
is discharged or the vacuum is compensated, the valve reseats upon request.
and provides a tight seal.
The optimized fluid dynamic design of the valve body and valve Any combination of vacuum and pressure levels can be set
pallet is a result of many years of research work, which allow a for the valve. When the difference between the pressure and
stable operation of the valve pallet and optimized performance vacuum exceeds 150 mbar / 60.2 inch W.C., special valve pal-
resulting in reduction of product losses. lets are used.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
208 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 5 / 0318 / GB 209
Pressure and Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/SV
VD/SV
pressure
.
flow rate V (m³/h) Leistung-000120-en
VD/SV
vacuum
vacuum – inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000119-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
210 KA / 5 / 0318 / GB
Notes:
211
Pressure and Vacuum Relief Valve
with pipe-away connection
PROTEGO® VD/SV-PA(L)
a
valve seats made of high quality stainless steel and
Øe with precisely lapped valve pallets (1) or with an air
cushion seal (2) in conjunction with high quality FEP
diaphragm. The valve pallets are also available with
a PTFE seal to prevent the valve pallets from stick-
ing when sticky products are used and to enable the
use of corrosive fluids. After the excess pressure is
discharged or the vacuum is compensated, the valve
DN 2
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
212 KA / 5 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 5 / 0318 / GB 213
Pressure and Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/SV-PA(L)
VD/SV-PA and
VD/SV-PAL
vacuum
.
flow rate V (m³/h) Leistung-000100-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
214 KA / 5 / 0318 / GB
Pressure and Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/SV-PA(L)
VD/SV-PA
pressure
.
flow rate V (m³/h) Leistung-000108-en
VD/SV-PAL
pressure
pressure – inch W.C.
pressure (mbar)
.
flow rate V (m³/h) Leistung-000105-en
KA / 5 / 0318 / GB 215
Pressure and Vacuum Relief Valve
made of plastic
PROTEGO® VD/KSM
b
Øc The device will start to open as soon as the set pressure is
reached and only requires 10% overpressure to full lift. Con-
tinuous investments into research and development have
allowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety relief
valve. This “full lift type” technology allows the valve to be set
just 10% below the maximum allowable working pressure and
vacuum (MAWP and MAWV) of the tank and still safely vent the
required mass flow. The opening characteristic for pressure and
vacuum side is the same.
Due to our highly developed manufacturing technology the
a
tank pressure is maintained up to set pressure with a tightness
that is far superior to the conventional standard. This feature is
achieved by special valve seats made of high quality synthetic
material or PTFE. After the excess pressure is discharged or
vacuum is compensated, the valve reseats and provides a tight
seal.
The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
DN stable operation of the valve pallet and optimized performance
resulting in reduction of product losses.
Settings:
Pressure: Special Features and Advantages
+6.0 mbar up to +100 mbar (DN 50/2”)
• “full lift type” technology valve utilizes only 10% overpressure
+2.4 inch W.C. up to +40 inch W.C.
to reach full lift
+4.0 mbar up to +100 mbar (DN 80/3”)
• extreme tightness and hence least possible product losses
+1.6 inch W.C. up to +40 inch W.C.
and reduced environmental pollution
+4.5 mbar up to +100 mbar (DN 100/4” - DN 200/8”)
+1.8 inch W.C. up to +40 inch W.C. • the set pressure is close to the opening pressure which
results in best possible pressure management of the system
Vacuum:
-6.0 mbar up to -100 mbar (DN 50/2”) • the valve pallet is guided within the housing to protect
-2.4 inch W.C. up to -40 inch W.C. against harsh weather conditions
-4.0 mbar up to -100 mbar (DN 80/3”) • corrosion resistant valve
-1.6 inch W.C. up to -40 inch W.C. • perfect solution for corrosive, polymerizing and sticky media
-4.5 mbar up to -100 mbar (DN 100/4” - DN 200/8”) • weight reduction in comparison to steel/stainless steel
-1.8 inch W.C. up to -40 inch W.C.
• vacuum side self draining and pressure side condensate
Higher and lower settings upon request drain
• smooth surface
• different plastics can be combined
• maintenance friendly design
Function and Description
The PROTEGO® valve VD/KSM is a state-of-the-art pressure Design Types and Specifications
and vacuum relief valve with excellent flow performance made The valve pallets are weight-loaded, and the highest pressure
of highgrade synthetic material. Typically the valve is installed levels are only attained with metal discs.
in the in- and out-breathing lines of tanks, vessels and process
Pressure/vacuum valve in basic design VD/KSM-
apparatus to protect against unallowable high or low pressure.
The valve prevents emission losses almost up to the set pres- Additional special devices available upon
sure. The valve is a perfect solution for corrosive, polymerizing request.
or sticky media.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
216 KA / 5 / 0318 / GB
Vents for corrosive vapor service Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 5 / 0318 / GB 217
Pressure and Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/KSM
VD/KSM
pressure
.
flow rate V (m³/h) 2453-L
VD/KSM
vacuum
vacuum – inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) 2454-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
218 KA / 5 / 0318 / GB
Notes:
219
Pressure and Vacuum Relief Valve
made of plastic
PROTEGO® VD/KSM-PA
a
Øe The device will start to open as soon as the set pressure is reached
and only requires 10% overpressure to full lift. Continuous invest-
ments into research and development have allowed PROTEGO®
to develop a low pressure valve which has the same opening
characteristic as a high pressure safety relief valve. This “full lift
type” technology allows the valve to be set just 10% below the
maximum allowable working pressure and vacuum (MAWP and
MAWV) of the tank and still safely vent the required mass flow. The
DN2
b
opening characteristic for pressure and vacuum side is the same.
Due to our highly developed manufacturing technology the
tank pressure is maintained up to set pressure with a tightness
d that is far superior to the conventional standard. This feature is
achieved by special valve seats made of high quality synthetic
material or PTFE. After the excess pressure is discharged or
vacuum is compensated, the valve reseats and provides a tight
DN1 seal.
c The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
Settings:
stable operation of the valve pallet and optimized performance
Pressure:
resulting in reduction of product losses.
+6.0 mbar up to +100 mbar (DN 50/2”)
+2.4 inch W.C. up to +40 inch W.C. Special Features and Advantages
+4.0 mbar up to +100 mbar (DN 80/3”) • “full lift type” technology valve utilizes only 10% overpressure
+1.6 inch W.C. up to +40 inch W.C. to reach full lift
+4.5 mbar up to +100 mbar (DN 100/4” - DN 200/8”) • extreme tightness and hence least possible product losses
+1.8 inch W.C. up to +40 inch W.C. and reduced environmental pollution
Vacuum: • the set pressure is close to the opening pressure which
-6.0 mbar up to -100 mbar (DN 50/2”) results in best possible pressure management of the system
-2.4 inch W.C. up to -40 inch W.C. • the valve pallet is guided within the housing to protect
-4.0 mbar up to -100 mbar (DN 80/3”) against harsh weather conditions
-1.6 inch W.C. up to -40 inch W.C. • corrosion resistant valve
-4.5 mbar up to -100 mbar (DN 100/4” - DN 200/8”) • perfect solution for corrosive, polymerizing and sticky media
-1.8 inch W.C. up to -40 inch W.C. • weight reduction in comparison to steel/stainless steel
Higher and lower settings upon request • vacuum side self draining and pressure side condensate
drain
• smooth surface
Function and Description • different plastics can be combined
The PROTEGO® valve VD/KSM-PA is a state-of-the-art pressure • maintenance friendly design
and vacuum relief valve with excellent flow performance made Design Types and Specifications
of highgrade synthetic material. Typically the valve is installed
The valve pallets are weight-loaded, and the highest pressure
in the in- and out-breathing lines of tanks, vessels and process levels are only attained with metal discs.
apparatus to protect against unallowable high or low pressure.
The valve prevents emission losses almost up to the set pres- Pressure/vacuum valve in basic design VD/KSM-PA-
sure. The valve is a perfect solution for corrosive, polymerizing Additional special devices available upon
or sticky media. request.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
220 KA / 5 / 0318 / GB
Vents for corrosive vapor service Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 5 / 0318 / GB 221
Pressure and Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/KSM-PA
VD/KSM-PA
pressure
.
flow rate V (m³/h) 2470-L
VD/KSM-PA
vacuum
vacuum – inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) 2471-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
222 KA / 5 / 0318 / GB
Notes:
223
www.protego.com
for safety and environment
PROTEGO® Pressure and Vacuum Relief Valves
in-line
Volume 6
Volume 6
The working principle and application of pressure and vacuum Special features and advantages
relief valves on tanks and process equipment is discussed in
Continuous investment in research and development has al-
“Technical Fundamentals” (Volume 1). In this chapter we intro-
lowed PROTEGO® to design valve pallets with the following ad-
duce in-line pressure and vacuum relief valves which can act in
vantages:
a pressure containing, relief or back flow protection function if
installed on a tank or other process equipment. • 10% full lift type technology results in product saving (reduc-
tion of breathing losses can be more than 30%)
Function and Description
• PROTEGO® valves open later and reseat earlier, thus provi-
These devices are direct acting weight or spring loaded in-line
ding optimized pressure management and additional saving
valves, pallet type, used to protect plant equipment (tanks, ves-
of inert/blanketing gases
sels, process technical apparatus, piping etc.) against unallow-
able operational high pressure or vacuum. In-line valves may • high flow performance allows cost reduction as smaller sized
also be installed as end-of-line valves. In end-of-line applica- valves can be installed
tions the open area to atmosphere has to be protected against
• tightness superior to the required national and international
weather impact, dirt particles or animals (Figure 1).
standards
Figure 1: • the valve pallet is guided within the housing to protect against
Pressure and Vacuum Relief Valve harsh weather conditions, e.g. preventing freezing of pallet in
PROTEGO® DV/ZT cold weather conditions
• can be installed in explosion hazardous areas
• maintenance friendly design
To reduce leak rates to a minimum and fulfill the highest expec-
tation of the industry the valve seats and valve pallets are manu-
factured from high quality stainless steel and lapped in a highly
developed manufacturing process. For low pressure settings
valve pallets are equipped with high quality FEP-diaphragm.
Preferred applications
• as pressure containment valve e.g. for blanketing systems
• as pressure reducing valve e.g. to connect to nitrogen blanke-
ting systems
• for controlled venting of plant or storage tanks into a vapour
header system
• as back flow protection device in exhaust or inerting systems
PROTEGO® pressure relief valves provide protection against Installation and servicing
unallowable high pressure and prevent emission losses almost All PROTEGO® devices are delivered with detailed installation
up to set pressure. and maintenance manuals. Please take notice of the instruc-
PROTEGO® vacuum relief valves provide safety against un- tions for the removal of the transport protection, if applicable.
allowable low vacuum and prevent intake of air almost up to set The special check lists should be followed to ensure the correct
vacuum. installation of the PROTEGO® devices.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
226 KA / 6 / 0318 / GB
Design type: Right angle or straight through design, horizontal Given: Connection nozzle size and maximum allowable
or vertical connection to the protected object. The devices are opening pressure (e.g. Tank pressure) p in mbar /
spring or weight loaded and therefore have to be installed with inch W.C.
the valve pallets in horizontal position. The maximum and mini-
Required: Volume flow in m3/h / CFH, set pressure pA
mum pressure settings depend on the specific design.
in mbar / inch W.C.
Sealing: Depending on the set pressures either metal sealing or
Procedure: From the intersection point of the straight line of p
soft sealing provide an extremely tight seal.
and the valve performance curve of the specific valve size the
.
Operating conditions and critical medium: Polymerisation volume flow Vmax is determined. The volume flow of the set pres-
problems, condensation problems, operating temperature, op- sure pA may be 10%, (PROTEGO®-technology) or 40% or 100%
erating pressure, volume flow are the main criteria for choosing below the opening pressure pT. Attention: pressure drop of
the correct devices. piping systems and other installed devices have to be consid-
ered!
Depending on the application, it may be important to select a de-
vice with a heating jacket, but please note that not all devices
are available with this feature. Electrical trace heating may be
an alternative.
Sizing airflow in thousands of CFH
The valve size results from the volume flow which has to be
vented to avoid an increase above the maximum allowable pres-
sure or vacuum. Certified volume flow diagrams are used for
sizing. For correct sizing the operating conditions and the pres-
sure drops of the piping system (including other installed de-
pT
account.
Detailed procedures and examples for sizing are described in
“Technical Fundamentals” (see Volume 1).
Example 1
. .
Given: Volume flow V max in m3/h / CFH (e.g. for in- or out V max
.
breathing of a storage tank this is the sum of the flow rate V (m³/h)
pump capacity and the thermal breathing require
ment) and maximum allowable opening pressure The required set pressure (= start of opening) will be the open-
(e.g. tank pressure) p in mbar / inch W.C. ing pressure (valve fully open) minus the characteristic over-
pressure.
Required: Valve size DN
. For PROTEGO® valves and end of line devices the overpres-
Procedure: The intersection point of Vmax and pT determines the sure characteristic is 10% unless otherwise stated. Within 10%
required valve size. Opening pressure = the maximum allowable overpressure the valve pallet will reach full lift. A further increase
tank pressure. The volume flow diagrams show the volume flow in flow performance will follow the pressure volume flow dia-
as function of the opening pressure for a fully open valve. gram.
The set pressure of the valve has to be determined so that the Material selection is based on plant and engineering specifica-
calculated volume flow can safely be discharged. For a valve tions.
which needs 10% overpressure to reach full lift the set pres-
sure may be chosen 10% below the fully open pressure (e.g. Guidelines for calculating the volume flow and considering the
maximum allowable tank pressure). Attention: pressure drop of density influence are given in „Technical Fundamentals“ (see
piping systems and other installed devices have to be con- Volume 1).
sidered! After completing all steps the device can be completely speci-
Many conventional valves need 100% overpressure to reach full fied and ordered.
lift. In these cases the set pressure may be just half of the maxi- To enable us to provide a quotation we recommend completing
mum allowable tank pressure. Consequently these valves open the data sheet from Vol.1 with the specific process data.
earlier and avoidable product losses occur.
Example 2
Alternatively the valve performance has to be checked if the size
and maximum allowable pressure are provided.
for safety and environment
KA / 6 / 0318 / GB 227
Selection Guide
(polymerisation, corrosion,
= straight through design
X = right angle design
= heating jacket
Pressure setting
X = spring loaded
crystallisation)
= soft sealing
positive or negative
Design
setting range
Type Size mbar / inch W.C. Page
Pressure or Vacuum Relief Valves
50 - 150 ±5 up to ±50
DZ/EA 2" - 6" ±2 up to ±20 X X 238- 239
50 - 200 ±5 up to ±100
R/KSM 2" - 8" ±2 up to ±40 X 252 - 253
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
228 KA / 6 / 0318 / GB
(polymerisation, corrosion,
= straight through design
X = right angle design
= heating jacket
Pressure setting
X = spring loaded
crystallisation)
= soft sealing
positive negative
setting setting
range range
Design
mbar / mbar /
Type Size inch W.C. inch W.C. Page
Pressure and Vacuum Relief Valves
upper valve lower valve
pallet pallet
40 - 150 ±2.0 up to ±3.5 up to
DV/ZT 1½" - 6" /X 254 - 256
±60 ±50
±0.8 up to ±1.4 up to
±24 ±20
+60 up to -3.5 up to
40 - 150 +500 -50
DV/ZT-F 1½" - 6" +24 up to -1.4 up to X X 258 - 260
+200 -20
+2.0 up to -3.5 up to
40 - 150 +60 -50
DV/ZU 1½" - 6" +0.8 up to -1.4 up to /X /X 262 - 264
+24 -20
+60 up to -3.5 up to
40 - 150 +500 -50
DV/ZU-F 1½" - 6" +24 up to -1.4 up to X /X X 266 - 268
+200 -20
+2.0 up to -3.5 up to
40 - 150 +60 -50
DV/ZW 1½" - 6" +0.8 up to -1.4 up to /X 270 - 272
+24 -20
+60 up to -3.5 up to
40 - 150 +500 -50
DV/ZW-F 1½" - 6" +24 up to -1.4 up to X X 274 - 276
+200 -20
Blanketing Valve
KA / 6 / 0318 / GB 229
Pressure or Vacuum Relief Valve, In-Line
PROTEGO® DZ/E
Ød
set pressure with a tightness that is far superior to the conven-
tional standard. This feature is facilitated by valve seats made
of high quality stainless steel and with individually lapped valve
pallets (1) or with an air cushion seal (2) in conjunction with high
quality FEP diaphragm. The valve pallets are also available with
a PTFE seal to prevent the valve pallets from sticking when sticky
products are used and to enable the use of corrosive fluids. After
the excess pressure is discharged or the vacuum is compen-
X
sated, the valve reseats and provides a tight seal.
DN
c
The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
stable operation of the valve pallet and optimized performance
b
resulting in reduction of product losses.
Special Features and Advantages
a
• “full lift type” technology valve utilizes only 10% overpressure
DN to reach full lift
Detail X • high performance seal reducing product loss below
EPA’s 500ppm rule preventing environmental pollution
1 2
• based on 10% technology the set pressure is close to the
= Tank connection for pressure relief function opening pressure which results in best possible pressure
management of the system compared to conventional 40%-
= Tank connection for vacuum relief function or 100%- technology valves
Flow direction marked at the housing by
• optimized flow performance, which reduces capital cost to a
minimum as smaller sized valves may be used
Pressure or vacuum settings:
DN 25 and 32 ± 3.5 mbar up to ±60 mbar • can be used as pressure or vacuum relief valve
DN 1" and 1¼" ± 1.4 inch W.C. up to ±24 inch W.C.
• compact right angle design saves space
DN 40 up to 300 ±2.0 mbar up to ±60 mbar
DN 1½" up to 12" ± 0.8 inch W.C. up to ±24 inch W.C. • can be installed in explosion hazardous areas
For higher set pressure or vacuum refer to type DZ/E-F • housing designed to 150 psi (PN 10)
• maintenance friendly design
Function and Description
The PROTEGO® in-line valve DZ/E is a state-of-the-art pressure
Designs and Specifications
or vacuum relief valve in right angle design. Typically the valve
is installed in the in- or outbreathing lines of tanks, vessels and The valve pallet is weight loaded. Higher set pressures for
process apparatus to protect against unallowable high or low pressure and vacuum are achieved by using spring loaded
pressure. The valve prevents emission losses almost up to the type DZ/E-F.
set pressure or provides protection from product entry into the
Two different right angle designs are available:
system.
In-line pressure or vacuum relief valve, DZ/E - –
The device will start to open as soon as the set pressure is standard design
reached and only requires 10% overpressure to full lift. Con-
tinuous investments into research and development have al- In-line pressure or vacuum relief valve with DZ/E - H
lowed PROTEGO® to develop a low pressure valve which has heating jacket
the same opening characteristic as a high pressure safety re- Additional special devices available upon request
lief valve. This “full lift type” technology allows the valve to be
set just 10% below the maximum allowable working pressure Within piping systems the influence of backpressure has
to be considered in deciding the set pressure and opening
or vacuum (MAWP or MAWV) of the tank and still safely vent
characteristics. For special design solutions (e.g. partial load
the required mass flow. The opening characteristic is the same
operation) the valve can be supplied with standard valve pallets
for pressure and vacuum relief. Due to our highly developed (with proportional opening function).
manufacturing technology the tank pressure is maintained up to
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
230 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 231
Pressure or Vacuum Relief Valve, In-Line
Flow Capacity Chart
PROTEGO® DZ/E
.
flow rate V (m³/h) Leistung-000127-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Technical Fundamentals.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
232 KA / 6 / 0318 / GB
Notes:
233
Pressure or Vacuum Relief Valve, In-Line
PROTEGO® DZ/E-F
Øc
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
234 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 235
Pressure or Vacuum Relief Valve, In-Line
Flow Capacity Chart
PROTEGO® DZ/E-F
.
flow rate V (m³/h) Leistung-000128-en
DZ/E-F
pressure or vacuum (mbar)
.
flow rate V (m³/h) 2750-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
236 KA / 6 / 0318 / GB
Notes:
237
Pressure or Vacuum Relief Valve, In-Line
With ETFE Lining
PROTEGO® DZ/EA
Ød
and vacuum relief. Due to our highly developed manufacturing
technology the tank pressure is maintained up to set pressure
with a tightness that is far superior to the conventional standard.
This feature is facilitated by specially finished PTFE valve seats
or by use of hastelloy valve seats and with individually lapped
valve pallets (1). After the excess pressure is discharged or the
vacuum is compensated, the valve reseats and provides a tight
seal.
DN The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
c
X
stable operation of the valve pallet and optimized performance
resulting in reduction of product losses.
Pressure or vacuum settings: • optimized flow performance, which reduces capital cost to a
±5.0 mbar up to ±50 mbar minimum as smaller sized valves may be used
± 2.0 inch W.C. up to ±20 inch W.C. • can be used as pressure or vacuum relief valve
For higher set pressure or vacuum refer to type DZ/EA-F
• compact right angle design saves space
• housing designed to 150 psi (PN 10)
Function and Description
• maintenance friendly design
The lined PROTEGO® in-line valve DZ/EA is a state-of-the-art
pressure or vacuum relief valve in right angle design. The lining
makes this model a perfect solution for corrosive, polymerizing Design and Specification
or sticky media. All internal parts are manufactured from PTFE The valve pallet is weight loaded. Higher set pressures for
or other highly corrosion resistant materials. Typically the valve pressure and vacuum are achieved by using spring loaded
is installed in the in- or out-breathing lines of tanks, vessels and type DZ/EA-F.
process apparatus to protect against unallowable high or low
pressure. The valve prevents emission losses almost up to the In-line pressure or vacuum relief valve, DZ/EA
set pressure or provides protection from product entry into the standard design
system.
Additional special devices available upon request
The device will start to open as soon as the set pressure is
reached and only requires 10% overpressure to full lift. Con- Within piping systems the influence of backpressure has
tinuous investments into research and development have to be considered in deciding the set pressure and opening
allowed PROTEGO® to develop a low pressure valve which has characteristics. For special design solutions (e.g. partial load
operation) the valve can be supplied with standard valve pallets
the same opening characteristic as a high pressure safety relief
(with proportional opening function).
valve. This “full lift type” technology allows the valve to be set just
10% below the maximum allowable working pressure or vacuum
(MAWP or MAWV) of the tank and still safely vent the required
mass flow. The opening characteristic is the same for pressure
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
238 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
DZ/EA
pressure or vacuum (mbar)
.
flow rate V (m³/h) 1381-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 6 / 0318 / GB 239
Pressure or Vacuum Relief Valve, In-Line
With ETFE Lining
PROTEGO® DZ/EA-F
Pressure or vacuum settings: • optimized flow performance, which reduces capital cost to a
minimum as smaller sized valves may be used
±60 mbar up to ±500 mbar
± 24 inch W.C. up to ±200 inch W.C. • can be used as pressure or vacuum relief valve
For lower set pressure or vacuum refer to type DZ/EA • compact right angle design saves space
The lined PROTEGO® in-line valve DZ/EA-F is a state-of-the-art • spring loaded design for higher set pressures
pressure or vacuum relief valve in right angle design for higher • maintenance friendly design
set pressures. The lining makes this model a perfect solution
for corrosive, polymerizing or sticky media. All internal parts are
manufactured from PTFE or other highly corrosion resistant
materials. Typically the valve is installed in the in- or out-breathing
lines of tanks, vessels and process apparatus to protect against
unallowable high or low pressure. The valve prevents emission
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
240 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 241
Pressure or Vacuum Relief Valve with ETFE Lining, In-Line
Flow Capacity Chart
PROTEGO® DZ/EA-F
.
flow rate V (m³/h) Leistung-000498-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
242 KA / 6 / 0318 / GB
Notes:
243
Pressure or Vacuum Relief Valve, In-Line
PROTEGO® DZ/T
Øc
with a tightness that is far superior to the conventional standard.
This feature is facilitated by valve seats made of high quality
stainless steel and with individually lapped valve pallets (1)
or with an air cushion seal (2) in conjunction with high
quality FEP diaphragm. The valve pallets are also available with
a PTFE seal to prevent the valve pallets from sticking when
X sticky products are used and to enable the use of corrosive
b
stable operation of the valve pallet and optimized performance
resulting in reduction of product losses.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
244 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 245
Pressure or Vacuum Relief Valve, In-Line
Flow Capacity Chart
PROTEGO® DZ/T
DZ/T
.
flow rate V (m³/h) Leistung-000129-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
246 KA / 6 / 0318 / GB
Notes:
247
Pressure or Vacuum Relief Valve, In-Line
PROTEGO® DZ/T-F
Øb
Vessels and process apparatus to protect against unallow-
able high or low pressure. The valve prevents emission losses
almost up to the set pressure or provides protection from product
entry into the system. As this device is equipped with a spring
higher set pressures can be reached compared to the DZ/T.
The device will start to open as soon as the set pressure
is reached and only requires 10% overpressure to full lift.
Continuous investments into research and development have
allowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety re-
lief valve. This “full lift type” technology allows the valve to be
set just 10% below the maximum allowable working pressure or
vacuum (MAWP or MAWV) of the tank and still safely vent the
c
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
248 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 249
Pressure or Vacuum Relief Valve, In-Line
Flow Capacity Charts
PROTEGO® DZ/T-F
.
flow rate V (m³/h) Leistung-000131-en
DZ/T-F
.
flow rate V (m³/h) 2514-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
250 KA / 6 / 0318 / GB
Notes:
251
Pressure or Vacuum Relief Valve, In-Line
PROTEGO® R/KSM
= Tank connection for pressure relief function • can be used as pressure or vacuum relief valve
= Tank connection for vacuum relief function • compact right angle design saves space
Flow direction marked at the housing by • optimized flow performance, which reduces capital cost to a
Pressure or vacuum settings: minimum as smaller sized valves may be used
±6.0 mbar up to ±100 mbar (DN 50/2”) • corrosion resistant valve
±2.4 inch W.C. up to ±40 inch W.C.
±4.0 mbar • weight reduction in comparison to steel/stainless steel
up to ±100 mbar (DN 80/3”)
±1.6 inch W.C. up to ±40 inch W.C. • smooth surface
±4.5 mbar up to ±100 mbar (DN 100/4” - DN 200/8”) • different plastics can be combined
±1.8 inch W.C. up to ±40 inch W.C.
• maintenance friendly design
Function and Description
The PROTEGO® in-line valve R/KSM is a state-of-the-art pres-
sure or vacuum relief valve in right angle design made out of Design and Specification
highgrade synthetic material. Typically the valve is installed The valve pallet is weight loaded. Highest set pressure range
in the in- or out-breathing lines of tanks, vessels and process can be reached with metal valve pallets.
apparatus to protect against unallowable high or low pressure.
The valve prevents emission losses almost up to the set pres- In-line pressure or vacuum relief valve, R/KSM -
sure or provides protection from product entry into the system. standard design
The valve is a perfect solution for corrosive, polymerizing or
sticky media. Additional special devices available upon request
The device will start to open as soon as the set pressure is Within piping systems the influence of backpressure has to
reached and only requires 10% overpressure to full lift. Con- be considered in deciding the set pressure and opening charac-
tinuous investments into research and development have teristics.
allowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety re-
lief valve. This “full lift type” technology allows the valve to be
set just 10% below the maximum allowable working pressure or
vacuum (MAWP or MAWV) of the tank and still safely vent the
required mass flow. The opening characteristic for pressure and
vacuum side is the same.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
252 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Vents for corrosive vapor service
(Flyer pdf) (Flyer pdf) (Flyer pdf)
R/KSM
pressure or vacuum (mbar)
.
flow rate V (m³/h) 2467-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 6 / 0318 / GB 253
Pressure and Vacuum Relief Valve, In-Line
PROTEGO® DV/ZT
Lower valve pallet: ±3.5 mbar up to ±50 mbar • housing designed to 150 psi (PN 10)
±1.4 inch W.C. up to ±20 inch W.C.
• maintenance friendly design
For higher set pressure refer to type DV/ZT-F. Lower set vacuum
upon request.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
254 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 255
Pressure and Vacuum Relief Valve, In-Line
Flow Capacity Charts
PROTEGO® DV/ZT
.
flow rate V (m³/h) Leistung-000002-en
DV/ZT
pressure or vacuum (mbar)
.
flow rate V (m³/h) Leistung-000001-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
256 KA / 6 / 0318 / GB
Notes:
257
Pressure and Vacuum Relief Valve, In-Line
PROTEGO® DV/ZT-F
Øb
Function and Description
The PROTEGO® in-line valve DV/ZT-F is a state-of-the-art pres-
sure and vacuum relief valve. Typically the valve is installed in
the in- and out-breathing lines of tanks, vessels and process
apparatus to protect against unallowable high and low pressure.
The valve prevents emission losses almost up to the set pres-
sure and provides protection from product entry into the system.
Due to its design the vacuum valve pallet is one size smaller
than the pressure valve pallet. Due to the spring loaded design
higher set pressures can be achieved.
The device will start to open as soon as the set pressure is
reached and only requires 10% overpressure to full lift. Con-
tinuous investments into research and development have
allowed PROTEGO® to develop a low pressure valve which
has the same opening characteristic as a high pressure safety
relief valve. This “full lift type” technology allows the valve to be
c
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
258 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 259
Pressure and Vacuum Relief Valve, In-Line
Flow Capacity Charts
PROTEGO® DV/ZT-F
DV/ZT-F
pressure
.
flow rate V (m³/h) Leistung-000003-en
DV/ZT-F
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000004-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
260 KA / 6 / 0318 / GB
Notes:
261
Pressure and Vacuum Relief Valve, In-Line
PROTEGO® DV/ZU
b
10% below the maximum allowable working pressure or vacuum
(MAWP or MAWV) of the tank and still safely vent the required
mass flow. The opening characteristic of the pressure and
X vacuum side is basically the same. However, the inbreathing will
start as soon as the differential pressure between the connected
inbreathing line and the tank is greater than the set pressure of
the vacuum pallet. Due to our highly developed manufacturing
DN
with an air cushion seal (2) in conjunction with high quality FEP
diaphragm. The valve pallets are also available with a PTFE
seal to prevent the valve pallets from sticking when sticky pro-
DN ducts are used and to enable the use of corrosive fluids. After
the excess pressure is discharged or vacuum is balanced, the
a
valve reseats and provides a tight seal.
Detail X The optimized fluid dynamic design of the vent body and vent
pallet is a result of many years of research work, which allow a
stable operation of the valve pallet and optimized performance
1 2
resulting in reduction of product losses.
= Tank connection
= Inbreathing
Special Features and Advantages
= Outbreathing
• “full lift type” technology valve utilizes only 10% overpressure
Settings: to reach full lift
Pressure: +2.0 mbar up to +60 mbar
• high performance seal reducing product loss below EPA’s
+0.8 inch W.C. up to +24 inch W.C.
500ppm rule preventing environmental pollution
Vacuum: -3.5 mbar up to -50 mbar
-1.4 inch W.C. up to -20 inch W.C. • based on 10% technology the set pressure is close to the
opening pressure which results in best possible pressure
For higher set pressure refer to type DV/ZU-F.
management of the system compared to conventional 40%-
Lower set vacuum upon request.
or 100%- technology valves
• optimized flow performance, which reduces capital cost to a
Function and Description
minimum as smaller sized valves may be used
The PROTEGO® in-line valve DV/ZU is a state-of-the-art pres-
• separate flange connection for in- and out-breathing line
sure and vacuum relief valve with separate flange connections
for pressure and vacuum breathing. Typically the valve is in- • can be installed in explosion hazardous areas
stalled in the in- and outbreathing lines of tanks, vessels and
• housing designed to 150 psi (PN 10)
process apparatus to protect against unallowable high and low
pressure. The valve prevents emission losses almost up to the • maintenance friendly design
set pressure and prevents air intake almost up to set vacuum.
The valve is designed so that in cases in which the set pressure
is exceeded the vapours are vented into a discharge pipe (e.g.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
262 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 263
Pressure and Vacuum Relief Valve, In-Line
Flow Capacity Charts
PROTEGO® DV/ZU
DV/ZU
pressure
.
flow rate V (m³/h) Leistung-000139-en
DV/ZU
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000132-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
264 KA / 6 / 0318 / GB
Notes:
265
Pressure and Vacuum Relief Valve, In-Line
PROTEGO® DV/ZU-F
relief valve. This “full lift type” technology allows the valve to
be set just 10% below the maximum allowable working pres-
sure or vacuum (MAWP or MAWV) of the tank and still safely
Y
vent the required mass flow. The opening characteristic of the
pressure and vacuum side is basically the same. However, the
inbreathing will start as soon as the differential pressure between
the connected inbreathing line and the tank is greater than the
X
set pressure of the vacuum pallet. Due to our highly developed
manufacturing technology the tank pressure is maintained up to
set pressure with a tightness that is far superior to the conven-
DN
high quality FEP diaphragm and a rugged valve body. After the
excess pressure is discharged or the vacuum is balanced, the
valve reseats and provides a tight seal.
DN The optimized fluid dynamic design of the valve body and valve
a pallet is a result of many years of research work, which allow a
stable operation of the valve pallet and optimized performance
Detail X resulting in reduction of product losses.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
266 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 267
Pressure and Vacuum Relief Valve, In-Line
Flow Capacity Charts
PROTEGO® DV/ZU-F
DV/ZU-F
pressure
.
flow rate V (m³/h) Leistung-000137-en
DV/ZU-F
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000138-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
268 KA / 6 / 0318 / GB
Notes:
269
Pressure and Vacuum Relief Valve, In-Line
PROTEGO® DV/ZW
Ød
The device will start to open as soon as the set pressure is
reached and only requires 10% overpressure to full lift. Con-
tinuous investments into research and development have
allowed PROTEGO® to develop a low pressure valve which has
the same opening characteristic as a high pressure safety relief
valve. This “full lift type” technology allows the valve to be set just
10% below the maximum allowable working pressure or vacuum
(MAWP or MAWV) of the tank and still safely vent the required
mass flow. The opening characteristic of the pressure and
b
vacuum side is basically the same. However, the inbreathing
will start as soon as the differential pressure between the
atmospheric pressure and the tank is greater than the set pres-
X sure of the vacuum pallet. Due to our highly developed manu-
facturing technology the tank pressure is maintained up to set
DN
pressure with a tightness that is far superior to the conventional
standard. This feature is facilitated by valve seats made of high
quality stainless steel and with individually lapped valve pallets
c
(1) or with an air cushion seal (2) in conjunction with high quality
FEP diaphragm. The valve pallets are also available with a PTFE
seal to prevent the valve pallets from sticking when sticky pro-
ducts are used and to enable the use of corrosive fluids. After
a the excess pressure is discharged or vacuum is balanced, the
valve reseats and provides a tight seal.
Detail X The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
1 2 stable operation of the valve pallet and optimized performance
resulting in reduction of product losses.
= Tank connection
= Inbreathing
Special Features and Advantages
= Outbreathing
• “full lift type” technology valve utilizes only 10% overpressure
Settings:
to reach full lift
Pressure: +2.0 mbar up to +60 mbar
+0.8 inch W.C. up to +24 inch W.C. • high performance seal reducing product loss below EPA’s
Vacuum: -3.5 mbar up to -50 mbar 500ppm rule preventing environmental pollution
-1.4 inch W.C. up to -20 inch W.C. • based on 10% technology the set pressure is close to the
For higher set pressure refer to type DV/ZW-F. opening pressure which results in best possible pressure
Lower set vacuum upon request. management of the system compared to conventional 40%-
or 100%- technology valves
Function and Description • optimized flow performance, which reduces capital cost to a
minimum as smaller sized valves may be used
The PROTEGO® in-line valve DV/ZW is a state-of-the-art pres-
sure and vacuum relief valve with separate flange connections • flange connection for discharge line
for use in a vent line. Typically the valve is installed in the in- and
• can be installed in explosion hazardous areas
outbreathing lines of tanks, vessels and process apparatus to
protect against unallowable high and low pressure. The valve • housing designed to 150 psi (PN 10)
prevents emission losses almost up to the set pressure and pre-
• maintenance friendly design
vents air intake almost up to set vacuum. The valve is designed
so that in cases in which the set pressure is exceeded the va-
pours are vented into a discharge pipe (e.g. vent header). When
the set vacuum is exceeded atmospheric air is pulled into the
system. Due to its design the vacuum valve pallet is one size
smaller than the pressure valve pallet.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
270 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 271
Pressure and Vacuum Relief Valve, In-Line
Flow Capacity Charts
PROTEGO® DV/ZW
DV/ZW
pressure
.
flow rate V (m³/h) Leistung-000141-en
DV/ZW
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000142-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
272 KA / 6 / 0318 / GB
Notes:
273
Pressure and Vacuum Relief Valve, In-Line
PROTEGO® DV/ZW-F
lapped valve pallets (1), (3) or with an air cushion seal (2) in
conjunction with high quality FEP diaphragm and a rugged valve
body. After the excess pressure is discharged or the vacuum is
balanced, the valve reseats and provides a tight seal.
b
The optimized fluid dynamic design of the valve body and valve
pallet is a result of many years of research work, which allow a
a stable operation of the valve pallet and optimized performance
resulting in reduction of product losses.
Detail X
Special Features and Advantages
1 2 • “full lift type” technology vent utilizes only 10% overpressure
to reach full lift
Detail Y = Tank connection
• high performance seal reducing product loss below EPA’s
= Inbreathing 500ppm rule preventing environmental pollution
3 = Outbreathing
Settings: • based on 10% technology the set pressure is close to the
Pressure: +60 mbar up to +500 mbar opening pressure which results in best possible pressure
+24 inch W.C. up to +200 inch W.C. management of the system compared to conventional
40%- or 100%- technology valves
Vacuum: -3.5 mbar up to -50 mbar
-1.4 inch W.C. up to -20 inch W.C. • optimized flow performance, which reduces capital cost to
Vacuum: -3.5 mbar up to -14 mbar a minimum as smaller sized valves may be used
-1.4 inch W.C. up to -5.6 inch W.C. • flange connection for discharge line
by set pressure up to +150 mbar / +60 inch W.C.
• can be installed in explosion hazardous areas
For lower set pressure refer to type DV/ZW.
Higher set pressure and lower set vacuum upon request. • housing designed to 150 psi (PN 10)
• spring loaded design on pressure side to achieve higher
Function and Description
set pressures
The PROTEGO® in-line valve DV/ZW-F is a state-of-the-art
pressure and vacuum relief valve with flanged connections for • maintenance friendly design
use in a vent line. Typically the valve is installed in the in- and
out-breathing lines of tanks, vessels and process apparatus to
protect against unallowable high and low pressure. The valve
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
274 KA / 6 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Coated Devices The optimised valve pallet
(Flyer pdf) (Flyer pdf) (Flyer pdf) (Flyer pdf)
KA / 6 / 0318 / GB 275
Pressure and Vacuum Relief Valve, In-Line
Flow Capacity Charts
PROTEGO® DV/ZW-F
DV/ZW-F
pressure
.
flow rate V (m³/h) Leistung-000143-en
DV/ZW-F
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000144-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
276 KA / 6 / 0318 / GB
Notes:
277
Blanketing Valve
low pressure reducing valve
ZM-R
Øa/c
Pressure range:
Supply pressure:
up to +16 bar /
+6424 inch W.C.
Set pressure for
e
overpressure function:
up to +500 mbar /
+200 inch W.C.
f
Set pressure for
vacuum function:
up to -200 mbar /
-80 inch W.C.
DN
d b
Function and Description Should the tank pressure decrease the valve will open. If the plant
is operated in a vacuum mode pressures down to -200 mbar /
The blanketing valve type ZM-R is a highly developed low pres-
-80 inch W.C. relative pressure can be accommodated.
sure reducing valve. This valve is typically used to inert or blan-
ket tanks, vessels or other process systems with nitrogen or
other blanketing gases by controlling the tank pressure to its Special features and advantages
desired value. High nitrogen or blanketing gas supply pressures • one stage pressure reduction within a relatively high pres-
up to 16 bar / 232 psi are safely reduced down to only a few sure range
mbar / inch W.C..
• large membrane surface to increase the closing force
The ZM-R low pressure reducing valve is a direct acting one
stage pressure control device. It is designed as a membrane • all functional and wetted parts are made of stainless steel (or
controlled, spring loaded proportional acting valve. The valve hastelloy if required)
controls the tank pressure by increasing flow as the tank pres- • easy adjustment of set pressure (within the pressure range
sure drops. This means that the mass flow through the device of the specific spring)
depends on the pressure differential of the set pressure to the
• vertical or horizontal installation (set pressure has to be
actual tank pressure. When the actual tank pressure reaches
adjusted for horizontal installation)
the set pressure the control unit closes and there is no flow.
• no external energy supply required
At the control membrane (which can be made from PTFE or
Viton) the tank pressure (P2) is balanced with the adjustment • optimized flow performance, which reduces capital cost to a
spring and the supply pressure (P1). minimum as smaller sized vents are needed
In a depressurized tank the adjustment opening
spring • the valve pallet is guided within the housing to protect
spring holds the valve pallet in the fully
against harsh weather conditions, e.g. preventing freezing of
open position. As the
pallet in cold weather conditions
tankpressure increases the P2
valve pallet moves toward closing • reducing within the vacuum range is possible
the seat and the mass flow 1:7
• high accuracy
is reduced. When the desired
tank pressure is reached the • can be installed in explosion hazardous areas
device will close.
P2 • housing designed to 16 bar / 150 psi
• maintenance friendly design
P1
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
278 KA / 6 / 0318 / GB
Design and Specification
Two different designs are available: For in-line valves any back pressure, which will influence the
Blanketing valve for overpressure, standard ZM-R – set pressure and opening characteristics, has to be taken into
design account.
KA / 6 / 0318 / GB 279
In-Line Pressure Reducing Valve
low pressure reducing valve
ZM-R
ZM-R 15 / ZM-R 25: flow rate (air, 0°C) at P = P1 - P2 and valve full open
ov
er P1 (bar) 0,15 0,25 0,40 0,65 1,00 1,50 2,50 4,00 6,00 10,00 Seat-Ø
pr
es
su
re
P2 (mbar) [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [mm]
10 6,2 8,1 10,3 13,2 16,5 20,6 28,8 41,1 57,5 90,3 Ø 4,5
12,4 16,2 20,7 26,5 33,0 41,2 57,6 82,2 115,0 180,7 Ø 7,5
17,5 23,0 29,3 37,6 46,7 58,4 81,6 116,5 163,0 256,0 Ø 10,0
24,8 32,5 41,4 53,1 66,0 82,4 115,2 164,5 230,1 361,4 Ø 14,0
20 6,0 7,9 10,2 13,2 16,5 20,6 28,8 41,1 57,5 90,3 Ø 4,5
12,0 15,9 20,5 26,4 33,0 41,2 57,6 82,2 115,0 180,7 Ø 7,5
17,0 22,6 29,1 37,5 46,7 58,4 81,6 116,5 163,0 256,0 Ø 10,0
24,0 31,9 41,1 52,9 66,0 82,4 115,2 164,5 230,1 361,4 Ø 14,0
100 3,8 6,7 9,4 12,8 16,4 20,6 28,8 41,1 57,5 90,3 Ø 4,5
7,7 13,4 18,9 25,6 32,8 41,2 57,6 82,2 115,0 180,7 Ø 7,5
10,9 18,9 26,8 36,3 46,5 58,4 81,6 116,5 163,0 256,0 Ø 10,0
15,4 26,8 37,9 51,3 65,6 82,4 115,2 164,5 230,1 361,4 Ø 14,0
200 - 4,0 8,0 12,1 16,1 20,6 28,8 41,1 57,5 90,3 Ø 4,5
- 8,0 16,1 24,2 32,3 41,2 57,6 82,2 115,0 180,7 Ø 7,5
- 11,4 22,9 34,3 45,8 58,4 81,6 116,5 163,0 256,0 Ø 10,0
- 16,1 32,3 48,4 64,6 82,4 115,2 164,5 230,1 361,4 Ø 14,0
500 - - - 7,8 14,2 20,1 28,8 41,1 57,5 90,3 Ø 4,5
- - - 15,6 28,5 40,3 57,6 82,2 115,0 180,7 Ø 7,5
- - - 22,1 40,4 57,1 81,6 116,5 163,0 256,0 Ø 10,0
- - - 31,2 57,0 80,7 115,2 164,5 230,1 361,4 Ø 14,0
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
280 KA / 6 / 0318 / GB
Low pressure reducing valve
Flow rates for P2 pressure range (Europe – metric units)
ZM-R
ZM-R 50: flow rate (air, 0°C) at P = P1 - P2 and valve full open
ov
er P1 (bar) 0,15 0,25 0,40 0,65 1,00 1,50 2,50 4,00 6,00 10,00 Seat-Ø
pr
es
su
re
P2 (mbar) [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [mm]
10 28,9 37,9 48,3 61,9 77,0 96,2 134,5 191,9 268,5 421,6 Ø 14,0
70,3 92,1 117,4 150,4 187,1 233,6 326,6 466,1 652,1 1024 Ø 18,0
150,0 196,5 250,4 320,8 399,1 498,3 696,5 994,0 1390 2183 Ø 26,0
20 28,0 37,3 47,9 61,7 77,0 96,2 134,5 191,9 268,5 421,6 Ø 14,0
68,1 90,6 116,5 150,0 187,1 233,6 326,6 466,1 652,1 1024 Ø 18,0
145,3 193,3 248,4 319,9 399,0 498,3 696,5 994,0 1390 2183 Ø 26,0
100 18,0 31,2 44,2 59,9 76,6 96,2 134,5 191,9 268,5 421,6 Ø 14,0
43,8 75,9 107,4 145,5 186,1 233,6 326,6 466,1 652,1 1024 Ø 18,0
93,5 162,0 229,1 310,2 396,9 498,3 696,5 994,0 1390 2183 Ø 26,0
200 - 18,8 37,7 56,5 75,4 96,2 134,5 191,9 268,5 421,6 Ø 14,0
- 45,8 91,6 137,4 183,2 233,6 326,6 466,1 652,1 1024 Ø 18,0
- 97,6 195,3 293,0 390,6 498,3 696,5 994,0 1390 2183 Ø 26,0
500 - - - 36,4 66,6 94,1 134,5 191,9 268,5 421,6 Ø 14,0
- - - 88,6 161,7 228,7 326,6 466,1 652,1 1024 Ø 18,0
- - - 188,9 344,9 487,8 696,5 994,0 1390 2183 Ø 26,0
ZM-R 100: flow rate (air, 0°C) at P = P1 - P2 and valve full open
ov
er P1 (bar) 0,15 0,25 0,40 0,65 1,00 1,50 2,50 4,00 6,00 10,00 Seat-Ø
pr
es
su
re
P2 (mbar) [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [Nm3/h] [mm]
10 346 453 587 741 922 1151 1609 2296 3212 5045 Ø 42,0
703 921 1174 1504 1871 2336 3266 4661 6512 10241 Ø 55,0
20 335 446 574 739 921 1151 1609 2296 3212 5045 Ø 42,0
681 906 1165 1500 1871 2336 3266 4661 6512 10241 Ø 55,0
100 216 374 529 716 917 1151 1609 2296 3212 5045 Ø 42,0
438 759 1074 1455 1861 2336 3266 4661 6512 10241 Ø 55,0
200 - 225 451 676 902 1151 1609 2296 3212 5045 Ø 42,0
- 458 916 1374 1832 2336 3266 4661 6512 10241 Ø 55,0
500 - - - 436 796 1127 1609 2296 3212 5045 Ø 42,0
- - - 886 1617 2287 3266 4661 6512 10241 Ø 55,0
Flow rates for P2 vacuum range (Type ZM-R/N) upon request
KA / 6 / 0318 / GB 281
In-Line Pressure Reducing Valve
Flow rates for P2 pressure range (english/american units – non-metric)
ZM-R
ZM-R 15 / ZM-R 25: flow rate (air, 32°F) at P = P1 - P2 and valve full open
ov
er P1 (psi) 2.18 3.63 5.80 9.43 14.50 21.76 36.26 58.02 87.02 145.04 Seat-Ø
pr
es
su
r
P2 ("wc) e [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [inch]
3.94 219 287 366 469 583 728 1018 1453 2032 3191 Ø 0.18
439 574 732 938 1166 1456 2036 2905 4064 6382 Ø 0.29
621 814 1037 1329 1652 2063 2884 4116 5758 9042 Ø 0.39
877 1149 1464 1876 2333 2913 4072 5810 8128 12764 Ø 0.55
7.87 212 282 363 468 583 728 1018 1453 2032 3191 Ø 0.18
425 565 726 935 1166 1456 2036 2905 4064 6382 Ø 0.29
602 800 1029 1325 1652 2063 2884 4116 5758 9042 Ø 0.39
849 1130 1452 1870 2333 2913 4072 5810 8128 12764 Ø 0.55
39.4 137 237 335 453 580 728 1018 1453 2032 3191 Ø 0.18
273 474 670 907 1166 1456 2036 2905 4064 6382 Ø 0.29
387 671 949 1285 1643 2063 2884 4116 5758 9042 Ø 0.39
547 947 1339 1814 2320 2913 4072 5810 8128 12764 Ø 0.55
78.7 - 143 285 428 571 728 1018 1453 2032 3191 Ø 0.18
- 285 571 856 1142 1456 2036 2905 4064 6382 Ø 0.29
- 404 809 1213 1617 2063 2884 4116 5758 9042 Ø 0.39
- 571 1142 1713 2284 2913 4072 5810 8128 12764 Ø 0.55
196.9 - - - 276 504 713 1018 1453 2032 3191 Ø 0.18
- - - 552 1108 1426 2036 2905 4064 6382 Ø 0.29
- - - 782 1428 2020 2884 4116 5758 9042 Ø 0.39
- - - 1104 2016 2851 4072 5810 8128 12764 Ø 0.55
ZM-R 50: flow rate (air, 32°F) at P = P1 - P2 and valve full open
ov
er P1 (psi) 2.18 3.63 5.80 9.43 14.50 21.76 36.26 58.02 87.02 145.04 Seat-Ø
pr
es
su
r
P2 ("wc) e [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [inch]
3.94 1023 1340 1708 2188 2722 3398 4750 6779 9483 14892 Ø 0.55
2486 3254 4149 5314 6610 8253 11536 16462 23030 36166 Ø 0.71
5300 6939 8846 11332 14094 17597 24600 35104 49109 77119 Ø 1.02
7.87 991 1318 1694 2182 2721 3398 4750 6779 9483 14892 Ø 0.55
2407 3201 4115 5298 6608 8253 11536 16462 23030 36166 Ø 0.71
5132 6827 8775 11298 14091 17597 24600 35104 49109 77119 Ø 1.02
39.4 638 1105 1563 2116 2707 3398 4750 6779 9483 14892 Ø 0.55
1549 2684 3795 5139 6573 8253 11536 16462 23030 36166 Ø 0.71
3304 5722 8093 10958 14017 17597 24600 35104 49109 77119 Ø 1.02
78.7 - 666 1332 1998 2664 3398 4750 6779 9483 14892 Ø 0.55
- 1617 3235 4852 6470 8253 11536 16462 23030 36166 Ø 0.71
- 3449 6898 10347 13796 17597 24600 35104 49109 77119 Ø 1.02
196.9 - - - 1288 2352 3327 4750 6779 9483 14892 Ø 0.55
- - - 3129 5713 8079 11536 16462 23030 36166 Ø 0.71
- - - 6672 12181 17227 24600 35104 49109 77119 Ø 1.02
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
282 KA / 6 / 0318 / GB
ZM-R 100: flow rate (air, 32°F) at P = P1 - P2 and valve full open
ov
er P1 (psi) 2.18 3.63 5.80 9.43 14.50 21.76 36.26 58.02 87.02 145.04 Seat-Ø
pr
es
su
r
P2 ("wc) e [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [SCFH] [inch]
3.94 12245 16033 20438 26181 32562 40656 56834 81101 113458 178171 Ø 1.65
24856 32544 41485 53144 66097 82525 115365 164624 230303 361660 Ø 2.17
7.87 11857 15772 20272 26102 32555 40656 56834 81101 113458 178171 Ø 1.65
24068 32014 41150 52984 66082 82525 115365 164624 230303 361660 Ø 2.17
39.4 7633 13221 18697 25316 32384 40656 56834 81101 113458 178171 Ø 1.65
15494 26836 37952 51387 65735 82525 115365 164624 230303 361660 Ø 2.17
78.7 - 7968 15937 23905 31874 40656 56834 81101 113458 178171 Ø 1.65
- 16175 32350 48525 64699 82525 115365 164624 230303 361660 Ø 2.17
196.9 - - - 15414 28142 39800 56834 81101 113458 178171 Ø 1.65
- - - 31289 57125 80788 115365 164624 230303 361660 Ø 2.17
Flow rates for P2 vacuum range (Type ZM-R/N) upon request
KA / 6 / 0318 / GB 283
www.protego.com
for safety and environment
PROTEGO® Pressure/Vacuum Relief Valves
with Flame Arrester - end-of-line
Volume 7
Volume 7
The working principle and location of the installation of valves on • increased flow performance (result: smaller valves can be in-
tanks and apparatus is discussed in „Technical Fundamentals“ stalled resulting in capital saving)
(Vol. 1). In this chapter we present end-of-line pressure/vacuum
• lowest leak rates world wide for low pressure valves
relief valves with integrated flame arrester units.
• flame transmission proof for almost any chemical mixture
Function and Description
• valve pallet is guided within the housing to protect against
These valves are used to protect process units and equipment
harsh weather conditions
(e.g. tanks, pipelines) from exceeding maximum allowable
operating pressures and vacuum. In addition theses devices • flame arrester unit is not in contact with product vapour under
protect against atmospheric deflagration. Some of the de- normal operating conditions, which reduces maintenance
vices are also designed to protect against endurance burning intervals
(Figure 1).
• endurance burning protection against alcohols
To achieve the highest expectations of the industry for the low-
est leak rates, our valve pallets and seats are manufactured
from high quality stainless steel and are hand lapped in a spe-
cial process. Air cushion membran technology is utilized for low
set pressures.
Valves with integrated flame arrester units are available for
substances from explosion groups IIA and IIB3 (NEC D and C)
Figure 1:
and special approvals are available for alcohols.
Pressure/Vacuum
Pressure/Vacu Relief Valve
PROTEGO® V VD/SV-HRL Main areas of application: as pressure and vacuum valves, as
pressure relief valves, as pressure holding/conservation valves,
as simple control valves for storage of flammable liquids
PROTEGO® Pressure Relief Valves with an integrated flame
arrester unit provide protection against unacceptable over- PROTEGO® Diaphragm Valves function as pressure vacuum
pressure, atmospheric deflagration and endurance burning. relief valves. The flexible diaphragm allows them to work as a
In addition the devices reduce emissions almost up to the set dynamic flame arrester, which provides endurance burning pro-
pressure. tection. For additional safety these devices are equipped with a
static flame arrester unit. This “one-of-a-kind” diaphragm valve
PROTEGO® Vacuum Relief Valves with an integrated flame
can be used under extreme cold weather conditions below
arrester unit provide protection against unacceptable vacuum
freezing and for problem products, which e.g. tend to polymerize
and atmospheric deflagration. In addition they avoid air intake
(Styrene, Acrylics). A specially designed valve seat combined
almost up to the set pressure.
with the flexible diaphragm prevents blocking of the valve through
PROTEGO® Pressure Vacuum Relief Valves with an integrated freezing product vapours at low temperatures. Ice bridges break
flame arrester unit fulfil all the above mentioned functions for and fall off through deformation of the diaphragm if pressure
pressure and vacuum relief and protect against atmospheric increases.
deflagration or against atmospheric deflagration and endurance
This device has no guiding elements which are likely to stick and
burning.
keep the device closed.
The special design of the PROTEGO® valves achieves full lift
Main areas of application: same as above in storage of flam-
after 10% overpressure above the set pressure. This “full-lift-
mable liquids and specifically for storage of monomers.
type-technology” allows for the use of set pressures just 10%
below the maximum allowable working pressure (MAWP or PROTEGO® High Velocity Pressure Relief Valves (Jet Valves)
Design Pressure) of the Tank. After just 10% overpressure above open and close almost immediately at set point. This function is
set pressure the valve will reach its full capacity to safely relieve achieved by an integrated magnet. Through this the overpres-
the required mass flow. Conventional relief valves for low pres- sure needed from set point to full lift is practically 0%, which
sure applications need 80%-100% overpressure (API 2000) for clearly reduces emissions. All PROTEGO® high velocity relief
reaching full lift and full relieving capacity. They open later and valves are tested for oscillating flow and are equipped with a
shut off earlier, which results in unnecessary product losses. specially designed valve cone and seat, which produces a
vertical upright free jet during pressure relief. This ensures an
Special features and advantages effective leaning of the discharged vapours and reduces the gas
Specific investments into research and development allowed concentration to a minimum in direct proximity (e.g. boat deck)
PROTEGO® to design a valve for low pressure applications pro- of the valve. The devices function on the working principal of a
viding you with the following advantages: dynamic flame arrester and are approved for the vapour groups
IIA, IIB3 and IIC (NEC D, C and B).
• 10% “full-lift-type-technology” reducing product losses (pos-
sible reduction of breathing losses greater than 30%) Main areas of application: transport of flammable liquids on
tank ships and special on shore applications.
• PROTEGO® valves open later and shut off earlier than con-
ventional valves, which results in optimized pressure manage-
ment and reduction of blanketing gas losses
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
286 KA / 7 / 0318 / GB
Installation and servicing The set pressure of the valve has to be determined such that
All PROTEGO devices are delivered with detailed installation
® the required volume flow can be discharged safely. A valve with
and maintenance manuals. Please pay special attention to 10% overpressure characteristic has to be set 10% below the
the warnings on how to remove transport protection if this has maximum allowable tank pressure.
been installed in the device to prevent damage during transport. Many conventional valves require 100% overpressure to reach
Specially developed check lists are available to ensure correct full lift. For these valves the set pressure will be 50% below
installation and operation of the device. of the maximum allowable tank pressure. These valves open
Selection and sizing earlier and shut off later allowing avoidable product losses.
For a safe operation and protection of a plant, the selection and Alternatively the valve performance may have to be checked
sizing of the correct PROTEGO® device is necessary. The fol- if the required size and maximum allowable tank pressure are
lowing criteria have to be considered for pre-selection: provided.
Function: Pressure relief, vacuum relief or combined pressure/ Given: (Tank-) nozzle size DN and maximum allowable
vacuum relief, protection against atmospheric deflagration, or (tank-) pressure p in mbar (inch W.C.)
atmospheric deflagration and endurance burning.
Desired: flow rate of valve in m3/h (CFH) and
Type of Valve: Weight loaded valve, diaphragm valve, high ve- set pressure pset
locity pressure relief valve or high velocity pressure relief valve
Procedure: The intersection point of the straight line through p
with combined vacuum valve.
and the valve performance
. curve of the (nozzle-) size DN de-
Design: with horizontal or vertical connection to the protected termine the flow rate V max. The set pressure pset will be 10%
vessel. These valves are weight loaded, so the pallet has to be (PROTEGO® - Technology), 40% or 100% below the maximum
installed in an horizontal orientation. The maximum achievable allowable (tank-) pressure pT.
pressure setting will depend on the design of the valve. Metallic
sealing or soft sealing are important criteria for low leak rates
and have to be chosen based on the intended use.
Explosion group: IIA, IIB3, IIC (NEC D, C, B).
airflow in thousands of CFH
Process of combustion: endurance burning or atmospheric
deflagration
Operating conditions: Polymerization, condensation, prob-
lems which lead to clogging of the FLAMEFILTER®, operating
temperature, operating pressure, oxygen concentration, volume
flow.
Given: Volume flow (e.g. in- or outbreathing of a storage tank The overpressure percentage of PROTEGO® valves is 10% (un-
. less supplied otherwise). Within 10% overpressure the device
as sum of the pump rates and thermal breathing) V max in m3/h
(CFH) and maximum allowable (tank-) pressure p in mbar will reach its performance at full lift. A further increase in flow
(inch W.C.). performance will follow the curve in the pressure volume flow
diagram.
Desired: Nominal valve size DN
For choosing the correct material the plant and engineering
Procedure: The required. size of the valve can be taken from specifications have to be considered.
the intersection point of V max and p valve operating pressure =
max. allowable tank pressure. The pressure diagram shows the
valves flow performance in relation to the opening pressure and
is determined at the full lift position of the pallet.
KA / 7 / 0318 / GB 287
Selection Guide
(polymerisation, corrosion,
= endurance burning proof
= horizontal connection
X = vertical connection
crystallisation)
group
= soft sealing
positive negative
setting setting
Approvals
range range
Design
mbar / mbar /
Type Size inch W.C. inch W.C. ATEX NEC Page
Pressure Relief Valves, Pallet Type
+3.5 up
50 - 80 to +210/
P/EB /X IIA D ATEX X /X 290 - 292
2" - 3" +1.4 up
to +84
+3.5 up
50 - 80 to +210/
P/EB-E /X IIB1 – ATEX X /X 294 - 296
2" - 3" +1.4 up
to +84
+3.5 up
80 - 100 to +210/ IIA, D, ATEX
P/EBR /X X /X 298 - 300
3" - 4" +1.4 up IIB3 C
to +84
+3.5 up
80 - 100 to +210/
P/EBR-E /X IIB1 – ATEX X /X 302 - 304
3" - 4" +1.4 up
to +84
+2.0 up
150 -200 to +60/
D-SVL-EB 6” - 8” /X IIA D ATEX X /X 306 - 308
+0.8 up
to +24
+2.0 up
150 -200 to +35/
BE/HR-D /X IIA D ATEX X /X 310 - 312
6" - 8" +0.8 up
to +14
Vacuum Relief Valves, Pallet Type
-2.0 up to IIB3, C, ATEX
50 - 300 -60/
SV/E X IIB B, IMO /X 314 - 317
2" - 12" -0.8 up to IIC B
-24
Pressure/Vacuum Relief Valves, Pallet Type
+2.0 up -3.5 up to
50 - 80 to +210/ -35/
PV/EB /X IIA D ATEX /X 318 - 320
2" - 3" +0.8 up -1.4 up to
to +84 -14
+2.0 up -3.5 up to
50 - 80 to +210/ -35/
PV/EB-E /X IIB1 – ATEX /X 322 - 324
2" - 3" +0.8 up -1.4 up to
to +84 -14
+2.0 up -3.5 up to
80 - 100 to +210/ -50/ IIA,
PV/EBR /X D ATEX /X 326 - 329
3" - 4" +0.8 up -1.4 up to IIB3
to +84 -20
+2.0 up -3.5 up to
PV/EBR-E 80 - 100 to +210/ -50/ IIB1 – ATEX
3" - 4" +0.8 up -1.4 up to /X /X 330 - 332
to +84 -20
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
288 KA / 7 / 0318 / GB
X = prevent flashback in case of
(polymerisation, corrosion,
= endurance burning proof
= horizontal connection
X = vertical connection
crystallisation)
Pressure setting Explosion
group
= soft sealing
positive negative
setting setting
Approvals
range range
Design
mbar / mbar /
Type Size inch W.C. inch W.C ATEX NEC Page
Pressure/Vacuum Relief Valves, Pallet Type (Continuation)
+3.5 up -2.0 up
VD/SV-AD 80 - 150 to +35/ to -35/
and X IIB3 C ATEX X /X 334 - 336
VD/SV-ADL 3” - 6”
+1.4 up -0.8 up
to +14 to -14
+3.5 up -2.0 up
80 - 100 to +35/ to -35/ IIA, D, ATEX
VD/SV-HR /X X /X 338 - 341
3" - 4" +1.4 up -0.8 up IIB3 C
to +14 to -14
+3.5 up -2.0 up
100-150 to +35/ to -35/
VD/SV-HRL 4" - 6" /X IIA D ATEX X /X 342 - 344
+1.4 up -0.8 up
to +14 to -14
+2.0 up -2.0 up
200 to +60/ to -60/
VD-SV-EB /X IIA D ATEX X /X 346 - 348
10“ +0.8 up -0.8 up
to +24 to -24
+3.5 up -2.0 up
50 - 300 to +50/ to -25/
VD/TS X IIB3 C ATEX X /X 350 - 353
2" - 12" +1.4 up -0.8 up
to +20 to -10
Pressure/Vacuum Relief Valves, Diaphragm Valves
+3.5 up -3.5 up
80 - 150 to +140/ to -35/
UB/SF /X IIB3 C ATEX X 354 - 361
3" - 6" +1.4 up -1.4 up
to +56 to -16
+3.5 up
80 - 150 to +140/
UB/DF /X IIB3 C ATEX X 362 - 367
3" - 6" +1.4 up
to +56
-3.5 up
80 - 150 to -35/
UB/VF X IIB3 C ATEX X 368 - 371
3" - 6" -1.4 up
to -16
Pressure Relief Valves, High Velocity Valve
-IIB -IIB3
+100 up
80 - 150 to +500/ IIB3, C, ATEX
DE/S / X IIB X X
3" - 6" +40 up to B
+200
+60 up to -IIB3 -IIC
KA / 7 / 0318 / GB 289
Pressure Relief Valve
deflagration- and endurance burning-proof
PROTEGO® P/EB
Øa sured by the valve seats made of high quality stainless steel and
4 with individually lapped valve pallets (1) or with an air cushion
seal (2) in conjunction with a high quality FEP diaphragm. The
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and to
enable the use in corrosive fluids. After the excess pressure is
discharged, the valve reseats and provides a tight seal.
If the set pressure is exceeded, explosive gas/product-vapour
air mixtures are released to the atmosphere. If this mixture ig-
nites, the integrated PROTEGO® flame arrester unit (3) prevents
flame transmission into the tank. If additional mixture continues
to flow and stabilized burning occurs, the integrated flame ar-
rester unit prevents flashback as a result from endurance burn-
b
ing. The valve is protected and also fulfils its function under this
X severe service conditions. The spring loaded weather hood
3 opens as soon as the fusible element (4) melts.
The valve can be used up to an operating temperature of +60°C /
140°F and meets the requirements of European tank design
standard EN 14015 – Appendix L and ISO 28300 (API 2000).
Type-approved in accordance with the current ATEX Directive
and EN 12874 as well as other international standards.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
290 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Demonstration of endurance burning
(Flyer pdf) (Flyer pdf) Video
KA / 7 / 0318 / GB 291
Pressure Relief Valve
Flow Capacity Chart
PROTEGO® P/EB
P/EB-IIA
DN 50 / 2" and 80 / 3"
.
flow rate V (m³/h) 2307-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
292 KA / 7 / 0318 / GB
Notes:
293
Pressure Relief Valve
deflagration- and endurance burning-proof
PROTEGO® P/EB-E
Øa
state of the art manufacturing. This feature is ensured by the
4 valve seats made of high quality stainless steel and with indi-
vidually lapped valve pallets (1) or with an air cushion seal (2) in
conjunction with high quality FEP diaphragm. The valve pallets
are also available with a PTFE seal to prevent the valve pallets
from sticking when sticky products are used and to enable the
use of corrosive fluids. After the excess pressure is discharged,
the valve reseats and provides a tight seal.
If the set pressure is exceeded, explosive gas/product-vapour
air mixtures are released to the atmosphere. If this mixture ig-
nites, the integrated PROTEGO® flame arrester unit (3) prevents
flame transmission into the tank. If additional mixture continues
b
DN
Special Features and Advantages
Detail X
• selecting set pressure close to relieving pressure results in
product loss reduction
1 2
• more design flexibility through higher reseating pressures;
Pressure settings: vents reseat when conventional vent is still discharging
+3.5 mbar up to +210 mbar costly product or nitrogen
+1.4 inch W.C. up to +84 inch W.C.
• the valve disc is guided within the housing to protect against
Higher pressure settings upon request.
harsh weather conditions
Function and Description • high performance seal reducing product loss below EPA’s
500ppm rule preventing environmental pollution
The deflagration proof and endurance burning-proof P/EB-E
type PROTEGO® valve is a highly developed pressure relief • can be used as protective system according to ATEX in
valve for large flows with an integrated flame arrester unit that areas subject to explosion hazards
is specially used for applications handling ethanol. It is primarily • safe against deflagration and endurance burning of alcohol/
used as a safety device for flame transmission proof outbreath- air mixtures from explosion group IIB1
ing on tanks, containers and process engineering apparatus.
The valve offers reliable protection against excess pressure and • high flow capacity through large FLAMEFILTER® cross-sec-
prevents product losses almost up to the set pressure; it also tion, results in low pressure drop
protects against atmospheric deflagration as well as endurance • PROTEGO® flame arrester unit provides protection against
burning if stabilized burning occurs. The PROTEGO® flame ar- atmospheric deflagration and endurance burning
rester unit is designed to achieve minimum pressure drop with
maximum safety. The P/EB-E valve is available for substances • flame arrester unit integrated into the valve saves space,
of explosion group IIB1 (MESG ≥ 0.85 mm) and provides spe- weight and reduces cost
cific protection against deflagration and endurance burning of • FLAMEFILTER® protected from clogging caused by product
alcohol/air mixtures (such as ethanol/air). vapours
The valve functions proportional, so the set pressures should • flame transmission proof condensate drain
be selected in relation to the proportional behaviour (such as
a 10%, 40%, or 100% overpressure from the set pressure to • maintenance friendly design
the relieving pressure at which the required flow performance • modular design enables individual FLAMEFILTER® and valve
is reached). pallets to be replaced
The tank pressure is maintained up to set pressure with a tight-
ness that is far superior to the conventional standard due to our
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
294 KA / 7 / 0318 / GB
Demonstration of endurance burning
Video
KA / 7 / 0318 / GB 295
Pressure Relief Valve
Flow Capacity Chart
PROTEGO® P/EB-E
overpressure
P/EB-E-IIB1
DN 50 / 2" and 80 / 3"
.
flow rate V (m³/h) Leistung-000145-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
296 KA / 7 / 0318 / GB
Notes:
297
Pressure Relief Valve
deflagration- and endurance burning-proof
PROTEGO® P/EBR
Øa
The tank pressure is maintained up to the set pressure with a
4 tightness that is far superior to the conventional standard due to
our state of the art manufacturing technology. This feature is en-
sured by the valve seats made of high quality stainless steel and
with individually lapped valve pallets (1) or with an air cushion
seal (2) in conjunction with high quality FEP diaphragm. The
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and to
enable the use of corrosive fluids. After the excess pressure is
discharged, the valve reseats and provides a tight seal.
If the set pressure is exceeded, explosive gas/product-vapour
air mixtures are released to the atmosphere. If this mixture
ignites, the integrated PROTEGO® flame arrester unit (3) prevents
3 flame transmission into the tank. If additional mixture continues
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
298 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Demonstration of endurance burning
(Flyer pdf) (Flyer pdf) Video
KA / 7 / 0318 / GB 299
Pressure Relief Valve
Flow Capacity Charts
PROTEGO® P/EBR
P/EBR-IIA
DN 80 / 3" and 100 / 4"
10 % overpressure
.
flow rate V (m³/h) Leistung-000424-en
P/EBR-IIB3
DN 80 / 3" and 100 / 4"
100 % overpressure
40 %
10 %
.
flow rate V (m³/h) Leistung-000146-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
300 KA / 7 / 0318 / GB
Notes:
301
Pressure Relief Valve
deflagration- and endurance burning-proof
PROTEGO® P/EBR-E
Øa
4 to our state of the art manufacturing technology. This feature is
ensured by the valve seats made of high quality stainless steel
and with individually lapped valve pallets (1) or with an air cush-
ion seal (2) in conjunction with high quality FEP diaphragm. The
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and
to enable the use corrosive fluids. After the excess pressure is
discharged, the valve reseats and provides a tight seal.
If the set pressure is exceeded, explosive gas/product-vapour
air mixtures are released to the atmosphere. If this mixture ig-
nites, the integrated PROTEGO® flame arrester unit (3) prevents
3 flame transmission into the tank. If additional mixture continues
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
302 KA / 7 / 0318 / GB
Demonstration of endurance burning
Video
KA / 7 / 0318 / GB 303
Pressure Relief Valve
Flow Capacity Chart
PROTEGO® P/EBR-E
P/EBR-E-IIB1
DN 80 / 3" and 100 / 4"
100 % overpressure
40 %
10 %
.
flow rate V (m³/h) Leistung-000370-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
304 KA / 7 / 0318 / GB
Notes:
305
Pressure Relief Valve
deflagration- and endurance burning-proof
PROTEGO® D-SVL-EB-IIA
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
306 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Demonstration of endurance burning
(Flyer pdf) (Flyer pdf) Video
KA / 7 / 0318 / GB 307
Pressure Relief Valve
Flow Capacity Chart
PROTEGO® D-SVL-EB-IIA
D-SVL-EB-IIA
.
flow rate V (m³/h) Leistung-000431-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
308 KA / 7 / 0318 / GB
Notes:
309
Pressure Relief Valve
deflagration- and endurance burning-proof
PROTEGO® BE/HR-D
Øa
NG Detail X
4
3
1
2
c
X Pressure settings:
+2.0 mbar up to +35 m
mbar
+0.8 inch W.C. up to +14 in
inch W.C.
Higher pressure settings upon request.
re
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
310 KA / 7 / 0318 / GB
Demonstration of endurance burning
Video
KA / 7 / 0318 / GB 311
Pressure Relief Valve
Flow Capacity Chart
PROTEGO® BE/HR-D
BE/HR-D-IIA
NG 400 / 16"
.
flow rate V (m³/h) Leistung-000229-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
312 KA / 7 / 0318 / GB
Notes:
313
Vacuum Relief Valve
deflagration-proof
PROTEGO® SV/E
c
DN
Type-approved in accordance with the current ATEX Directive and
EN ISO 16852 as well as other international standards. Addition-
al certificates from classification associations for use on ships
b
are also available.
-0.8 inch W.C. up to -24 inch W.C. • the valve disc is guided within the housing to protect against
Higher vacuum settings upon request harsh weather conditions
• can be used as protective system according ATEX in areas
Function and Description subject to explosion hazards
• FLAMEFILTER® provides protection against atmospheric
The deflagration-proof SV/E type PROTEGO® valve is a state
deflagration
of the art vacuum relief valve with an integrated flame arrester
unit. It is primarily used as a safety device for flame transmission • FLAMEFILTER® integrated into the valve saves space,
proof inbreathing on tanks, containers and process engineering weight and reduces cost
apparatus. The valve offers reliable protection against vacuum • FLAMEFILTER® protected from clogging through product
and prevents inbreathing of air almost up to the set pressure; it vapour
also protects against atmospheric deflagration. The PROTEGO® • PROTEGO® flame arrester unit has a low pressure drop
flame arrester unit is designed to achieve minimum pressure drop
• maintenance friendly design
with maximum safety. The PROTEGO® SV/E valve is available
for substances from explosion groups IIA to IIC. • modular design enables individual FLAMEFILTER® and valve
pallets to be replaced
When the set vacuum is reached, the valve starts to open and
• an additional lifting gear can be purchased
reaches full lift within 10% overpressure. This unique 10% tech-
nology enables a set vacuum that is only 10% above the maxi-
Design Types and Specifications
mum allowable working vacuum (MAWV) of the tank. After years
of development, this typical opening characteristic of a safety The valve disc is weight-loaded. Higher vacuum can be
relief valve is now also available for the low pressure range. achieved upon request with a special spring loaded design.
The tank pressure is maintained up to the set vacuum with a There are four different designs:
tightness that is far superior to the conventional standard due to Vacuum relief valve, basic design SV/E- – - –
our state of the art manufacturing technology. This feature is en-
Vacuum relief valve with heating jacket SV/E- – - H
sured by the valve seats made of high quality stainless steel and
(max. heating fluid temperature +85°C / 185°F)
with individually lapped valve pallets (1) or with an air cushion
Vacuum relief valve with lifting gear SV/E- S - –
seal (2) in conjunction with high quality FEP diaphragm. The
(ship design)
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and to Vacuum relief valve with lifting gear (ship de- SV/E- S - H
enable the use corrosive fluids. After the vacuum is equalized, sign) and heating jacket
the valve reseats and provides a tight seal. (max. heating fluid temperature +85°C / 185°F)
Additional special devices available upon request
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
314 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf)
KA / 7 / 0318 / GB 315
Vacuum Relief Valve
Flow Capacity Chart
PROTEGO® SV/E
SV/E-IIB3
.
flow rate V (m³/h) Leistung-000085-en
SV/E-IIB
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000469-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
316 KA / 7 / 0318 / GB
Vacuum Relief Valve
Flow Capacity Chart
PROTEGO® SV/E
SV/E-IIC
.
flow rate V (m³/h) Leistung-000487-en
KA / 7 / 0318 / GB 317
Pressure/Vacuum Relief Valve
deflagration- and endurance burning-proof
PROTEGO® PV/EB
Ød allowable working vacuum (MAWV) of the tank. After years of
3 4
development, this typical opening characteristic of a safety relief
valve is now also available for the low pressure range.
The tank pressure is maintained up to the set pressure with a
tightness that is far superior to the conventional standard due to
our state of the art manufacturing technology. This feature is en-
sured by the valve seats made of high quality stainless steel and
with individually lapped valve pallets (1) or with an air cushion
seal (2) in conjunction with high quality FEP diaphragm. The
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and to
a
X
continues to flow and stabilized burning occurs, the integrated
flame arrester unit prevents flashback as a result from endur-
ance burning. The valve is protected and also fulfils its function
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
318 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Demonstration of endurance burning
(Flyer pdf) (Flyer pdf) Video
Design Types and Specifications There are two different designs:
Almost any combination of vacuum and pressure levels can be Pressure/vacuum relief valve, basic design PV/EB- –
set for the valve. The valve discs are weight loaded. When the
Pressure/vacuum relief valve with heating jacket PV/EB- H
difference between the pressure and vacuum exceeds
(max. heating fluid temperature +85°C / 185°F)
150 mbar / 60.2 inch W.C., special valve discs are used.
Additional special devices available upon request
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
DN 50 / 2" 50 / 2" 80 / 3" 80 / 3"
≤ +60 mbar > +60 mbar ≤ +60 mbar > +60 mbar
Set pressure ≤ +24.1 inch W.C. > +24.1 inch W.C. ≤ +24.1 inch W.C. > +24.1 inch W.C.
Dimensions for pressure/
a 308 / 12.13 443 / 17.44 308 / 12.13 443 / 17.44 vacuum relief valve with
b 108 / 4.25 108 / 4.25 108 / 4.25 108 / 4.25 heating jacket upon request
c 165 / 6.50 165 / 6.50 167 / 6.57 167 / 6.57
d 218 / 8.58 218 / 8.58 218 / 8.58 218 / 8.58
KA / 7 / 0318 / GB 319
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® PV/EB
PV/EB-IIA
DN 50/2“ and 80/3“
pressure
.
flow rate V (m³/h) 2297-L
PV/EB-IIA
DN 50/2“ and 80/3“
vacuum vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) 2298-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
320 KA / 7 / 0318 / GB
Notes:
321
Pressure/Vacuum Relief Valve
deflagration- and endurance burning-proof
PROTEGO® PV/EB-E
Detail X
Special Features and Advantages
1 2 • selecting set pressure close to relieving pressure results in
Settings: product loss reduction
pressure: +2.0 mbar up to +210 mbar • increased design flexibility through higher reseating
+0.8 inch W.C. up to +84 inch W.C. pressures; vents reseat when conventional vent is still
vacuum: -14 mbar up to -35 mbar discharging costly product or nitrogen
-5.6 inch W.C. up to -14 inch W.C. • the valve disc is guided within the housing to protect against
vacuum: -3.5 mbar up to -14 mbar harsh weather conditions
-1.4 inch W.C. up to -5.6 inch W.C.
• high performance seal reducing product loss below EPA’s
for presssure up to max. + 150 mbar / 60.2 inch W.C.
500ppm rule preventing environmental pollution
Higher and lower settings upon request
Function and Description • can be used as protective system according to ATEX in
areas subject to explosion hazards
The deflagration-proof and endurance burning-proof PV/EB-E
type PROTEGO® valve is a highly developed combined pressure/ • safe against deflagration and endurance burning of alcohol/
vacuum relief valve for high flow capacities with an integrated air mixtures from explosion group IIB1
flame arrester unit that is specially used for applications handling • high flow capacity through large FLAMEFILTER® cross-sec-
ethanol. It is primarily used as a safety device for flame trans- tion, results in low pressure drop
mission proof in- and outbreathing on tanks, containers and pro-
cess engineering apparatus. The valve offers reliable protection • FLAMEFILTER® provides protection against atmospheric
against excess pressure and vacuum, prevents the inbreathing deflagration and endurance burning
of air and product losses almost up to the set pressure and also • FLAMEFILTER® integrated into the valve saves space,
protects against atmospheric deflagration as well as endurance weight and reduces cost
burning if stabilized burning occurs. The PROTEGO® flame
arrester unit is designed to achieve minimum pressure drop with • FLAMEFILTER® protected from clogging caused by product
maximum safety. The PROTEGO® PV/EB-E valve is available vapours
for substances of explosion group IIB1 (MESG ≥ 0.85 mm) and • flame transmission proof condensate drain
provides specific protection against deflagration and endurance
• maintenance friendly design
burning of alcohol/air mixtures (such as ethanol/air).
The valve functions proportionally, so the set pressures should • modular design enables individual FLAMEFILTER® and valve
be selected in relation to the proportional behaviour (such as pallets to be replaced
a 10%, 40%, or 100% overpressure from the set pressure to • special design with lifting gear can be purchased
the relieving pressure at which the required flow performance
is reached).
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
322 KA / 7 / 0318 / GB
Demonstration of endurance burning
Video
KA / 7 / 0318 / GB 323
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® PV/EB-E
overpressure
PV/EB-E-IIB1
DN 50/2“ and 80/3“
pressure
.
flow rate V (m³/h) Leistung-000149-en
overpressure
PV/EB-E-IIB1
DN 50/2“ and 80/3“
vacuum
.
flow rate V (m³/h) Leistung-000148-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
324 KA / 7 / 0318 / GB
Notes:
325
Pressure/Vacuum Relief Valve
deflagration- and endurance burning-proof
PROTEGO® PV/EBR
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
326 KA / 7 / 0318 / GB
Demonstration of endurance burning
Video
Design Types and Specifications There are two different designs:
Almost any combination of vacuum and pressure levels can Pressure/vacuum relief valve, basic design PV/EBR- –
be set for the valve. The valve discs are weight loaded. When Pressure /vacuum relief valve with heating jacket PV/EBR- H
the difference between the pressure and vacuum exceeds (max. heating fluid temperature +85°C / 185°F)
150 mbar / 60.2 inch W.C., special valve discs are used. Additional special devices available upon request
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
DN 80 / 3" 80 / 3" 100 / 4" 100 / 4"
≤ +35 mbar > +35 mbar ≤ +35 mbar > +35 mbar
Set pressure ≤ +14 inch W.C. > +14 inch W.C. ≤ +14 inch W.C. > +14 inch W.C.
Dimensions for pressure/
a 345 / 13.58 475 /18.70 345 / 13.58 475 /18.70 vacuum relief valve with
b 141 / 5.55 141 / 5.55 141 / 5.55 141 / 5.55 heating jacket upon request
c 218 / 8.58 218 / 8.58 218 / 8.58 218 / 8.58
d 353 / 13.90 353 / 13.90 353 / 13.90 353 / 13.90
KA / 7 / 0318 / GB 327
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® PV/EBR
overpressure
PV/EBR-IIA
DN 80/3“ and 100/4“
pressure
.
flow rate V (m³/h) 2301-L
overpressure
PV/EBR-IIA
DN 80/3” and 100/4”
vacuum
.
flow rate V (m³/h) 2302-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
328 KA / 7 / 0318 / GB
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® PV/EBR
overpressure
PV/EBR-IIB3
DN 80/3” and 100/4”
pressure
.
flow rate V (m³/h) Leistung-000189-en
overpressure
PV/EBR-IIB3
DN 80/3” and 100/4”
vacuum
.
flow rate V (m³/h) Leistung-000150-en
KA / 7 / 0318 / GB 329
Pressure/Vacuum Relief Valve
deflagration- and endurance burning-proof
PROTEGO® PV/EBR-E
Ød
The tank pressure is maintained up to the set pressure with a
4 tightness that is far superior to the conventional standard due
to our state of the art manufacturing technology. This feature is
ensured by the valve seats made of high quality stainless steel
3 and with individually lapped valve pallets (1) or with an air cushion
seal (2) in conjunction with high quality FEP diaphragm. The
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and
to enable the use corrosive fluids. After the excess pressure is
discharged, the valve reseats and provides a tight seal.
If the set pressure is exceeded, explosive gas/product-vapour
a
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
330 KA / 7 / 0318 / GB
Demonstration of endurance burning
Video
Almost any combination of vacuum and pressure levels can Pressure/vacuum relief valve, basic design PV/EBR-E- –
be set for the valve. The valve discs are weight loaded. When Pressure/vacuum relief valve with heating PV/EBR-E- H
the difference between the pressure and vacuum exceeds 150 jacket (max. heating fluid temperature
mbar / 60.2 inch W.C., special valve discs are used. +85°C / 185°F)
Additional special devices available upon request
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
DN 80 / 3" 80 / 3" 100 / 4" 100 / 4"
≤ +35 mbar > +35 mbar ≤ +35 mbar > +35 mbar
Set pressure ≤ +14 inch W.C. > +14 inch W.C. ≤ +14 inch W.C. > +14 inch W.C.
Dimensions for Pressure/
a 345 / 13.58 475 / 18.70 345 / 13.58 475 / 18.70 Vacuum Relief Valve with
b 141 / 5.55 141 / 5.55 141 / 5.55 141 / 5.55 heating jacket upon request
c 218 / 8.58 218 / 8.58 218 / 8.58 218 / 8.58
d 353 / 13.90 353 / 13.90 353 / 13.90 353 / 13.90
KA / 7 / 0318 / GB 331
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® PV/EBR-E
overpressure
PV/EBR-E-IIB1
DN 80/3“ and 100/4“
pressure
.
flow rate V (m³/h) Leistung-000491-en
overpressure
PV/EBR-E-IIB1
DN 80/3“ and 100/4“
vacuum
.
flow rate V (m³/h) Leistung-000492-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
332 KA / 7 / 0318 / GB
Notes:
333
Pressure/Vacuum Relief Valve
atmospheric deflagration-proof
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
334 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf)
Design Types and Specifications
Any combination of vacuum and pressure levels can be set for the valve
The valve discs are weight-loaded.
There are two different designs:
Pressure/vacuum relief valve with housing, standard design VD/SV-AD
Pressure/vacuum relief valve with expanded housing VD/SV-ADL
Additional special devices available upon request
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), please use the flow capacity charts on the following pages
VD/SV-AD VD/SV-ADL
DN 80 / 3" 100 / 4" 100 / 4" 150 / 6"
a 540 / 21.26 565 / 22.24 650 / 25.59 760 / 29.92
b 475 / 18.70 575 / 22.64 700 / 27.56 855 / 33.66
c 350 / 13.78 350 / 13.78 600 / 23.62 600 / 23.62
KA / 7 / 0318 / GB 335
Pressure/Vacuum Relief Valve
Flow Capacity Charts
VD/SV-AD-IIB3 VD/SV-ADL-IIB3
pressure
.
flow rate V (m³/h) 2387-L
VD/SV-AD-IIB3 and
VD/SV-ADL-IIB3
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) 2234-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
336 KA / 7 / 0318 / GB
Notes:
337
Pressure/Vacuum Relief Valve
deflagration- and endurance burning-proof
PROTEGO® VD/SV-HR
a
If the set pressure is exceeded, explosive gas/product-vapour
air mixtures are released to the atmosphere . If this mixture ig-
nites, the integrated PROTEGO® flame arrester unit (3) prevents
flame transmission into the tank. If additional mixture continues to
X flow and stabilized burning occurs, the integrated flame arrester
unit prevents flashback as a result from endurance burning.
The valve is protected and also fulfils its function under this se-
vere service conditions. The spring loaded weather hood opens
as soon as the fusible element (4) melts.
The valve can be used up to an operating temperature of +60°C /
3 140°F and meets the requirements of European tank design
DN
standard EN 14015 – Appendix L and ISO 28300 (API 2000).
Type-approved in accordance with the current ATEX Directive
Detail X
and EN ISO 16852 as well as other international standards.
Special Features and Advantages
1 2
Settings: • requires only 10% overpressure to full lift for explosion group
pressure: +3.5 mbar up to +35 mbar IIA (NEC group D) vapours
+1.4 inch W.C. up to +14 inch W.C. • through 10% technology higher set pressures can be used
vacuum: -2.0 mbar up to -35 mbar which results in product loss reduction compared to con-
-0.8 inch W.C. up to -14 inch W.C. ventional 40% and 100% overpressure technology vents
Higher and lower settings upon request (compare API 2000)
Function and Description • more design flexibility through higher reseating pressures;
The deflagration-proof and endurance burning-proof VD/SV-HR vents reseat when conventional vent is still discharging
type PROTEGO® valve is a highly developed combined pressure/ costly product or nitrogen
vacuum relief valve for high flow capacities with an integrated • the valve disc is guided within the housing to protect against
flame arrester. It is primarily used as a safety device for flame- harsh weather conditions
transmission-proof in- and outbreathing in tanks, containers • high performance seal reducing product loss below EPA’s
and process engineering apparatus. The valve offers reliable 500ppm rule preventing environmental pollution
protection against excess pressure and vacuum, preventing
• can be used as protective system according to ATEX in
outbreathing of product vapour and inbreathing of air almost
areas subject to explosion hazards
up to the set pressure and also protects against atmospheric
deflagration as well as endurance burning if stabilized burning • safe against deflagration and endurance burning for explo-
occurs. The PROTEGO® flame arrester unit is designed to sion group IIA and IIB3 (NEC group D and C) vapours
achieve minimum pressure drop with maximum safety. The defla- • high flow capacity through large FLAMEFILTER® cross-
gration and endurance burning proof PROTEGO® VD/SV-HR section, results in low pressure drop
device is available for substances from explosion groups IIA to • FLAMEFILTER® provides protection against atmospheric
IIB3 (NEC group D to C MESG ≥ 0.65 mm). deflagration and endurance burning
If the set pressure is reached for a valve approved for explosion • FLAMEFILTER® integrated into the valve saves space,
Group IIA (NEC group D), the valve starts to open and reaches weight and reduces cost
full lift within 10% overpressure. This unique 10% technology
• FLAMEFILTER® protected from clogging caused by product
enables a set pressure that is only 10% below the maximum
vapours
allowable working pressure (MAWP) of the tank. After years of
development, this typical opening characteristic of a safety relief • flame transmission proof condensate drain
valve is now also available for the low pressure range. Valves • maintenance friendly design
approved for explosion group IIB3 (NEC group C) function pro- • modular design enables individual FLAMEFILTERS® and
portionally, so the set pressures should be selected in relation valve pallets to be replaced
to the proportional behaviour (such as a 10%, 40%, or 100%
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
338 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf)
KA / 7 / 0318 / GB 339
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/SV-HR
VD/SV-HR-IIA
pressure
.
flow rate V (m³/h) Leistung-000358-en
VD/SV-HR-IIA
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000361-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
340 KA / 7 / 0318 / GB
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/SV-HR
overpressure
VD/SV-HR-IIB3
DN 80/3" and 100/4"
pressure
.
flow rate V (m³/h) Leistung-000363-en
VD/SV-HR-IIB3
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000364-en
KA / 7 / 0318 / GB 341
Pressure/Vacuum Relief Valve
deflagration- and endurance burning-proof
PROTEGO® VD/SV-HRL
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
342 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology
(Flyer pdf) (Flyer pdf)
KA / 7 / 0318 / GB 343
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/SV-HRL
VD/SV-HRL-IIA
pressure
.
flow rate V (m³/h) Leistung-000359-en
VD/SV-HRL-IIA
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000360-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
344 KA / 7 / 0318 / GB
Notes:
345
Pressure/Vacuum Relief Valve
deflagration- and endurance burning-proof
PROTEGO® VD-SV-EB
e
tightness that is far superior to the conventional standard due to
our state of the art manufacturing technology. This feature is en-
sured by the valve seats made of high quality stainless steel and
DN2 with individually lapped valve pallets (1) or with an air cushion
seal (2) in conjunction with a high quality FEP diaphragm. The
valve pallets are also available with a PTFE seal to prevent the
valve pallets from sticking when sticky products are used and to
b
enable the use in corrosive fluids. After the excess pressure is
discharged, the valve reseats and provides a tight seal.
If the set pressure is exceeded, explosive gas/product-vapour
X air mixtures are released to the atmosphere. If this mixture ig-
nites, the integrated flame arrester PROTEGO® EB (3) prevents
flame transmission into the tank. If additional mixture continues
to flow and stabilized burning occurs, the integrated flame ar-
rester unit prevents flashback as a result from endurance burn-
ing. The valve is protected and also fulfils its function under this
DN severe service conditions. The spring loaded weather hood
d opens as soon as the fusible element (4) melts.
The valve can be used up to an operating temperature of +60°C /
140°F and meets the requirements of European tank design
standard EN 14015 – Appendix L and ISO 28300 (API 2000).
Type-approved in accordance with the current ATEX Directive
and EN ISO 16852 as well as other international standards.
g
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
346 KA / 7 / 0318 / GB
Vents - 10% Technology Leak Rate/10% Technology Demonstration of endurance burning
(Flyer pdf) (Flyer pdf) Video
KA / 7 / 0318 / GB 347
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD-SV-EB-IIA
VD-SV-EB-IIA
pressure
.
flow rate V (m³/h) Leistung-000425-en
VD-SV-EB-IIA
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000426-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
348 KA / 7 / 0318 / GB
Notes:
349
Pressure/Vacuum Relief Valve
atmospheric deflagration-proof
PROTEGO® VD/TS
Settings: • the valve disc is guided within the housing to protect against
pressure: +3.5 mbar up to +50 mbar harsh weather conditions
+1.4 inch W.C. up to +20 inch W.C. • can be used as protective system according ATEX in areas
vacuum: -2.0 mbar up to -25 mbar subject to explosion hazards
-0.8 inch W.C. up to -10 inch W.C.
• FLAMEFILTER® provides protection against atmospheric
Higher and lower settings upon request
deflagration
Function and Description
• FLAMEFILTER® integrated into the valve saves space and
The atmospheric deflagration-proof VD/TS type PROTEGO® reduces cost
valve is a highly developed combined pressure/vacuum relief
valve for high flow capacities with an integrated flame arrester • FLAMEFILTER® protected from clogging through product
unit. It is primarily used as a safety device for flame transmission vapour
proof in- and outbreathing on tanks, containers and process en- • PROTEGO® flame arrester unit has low pressure drop
gineering apparatus. The valve offers reliable protection against
excess pressure and vacuum, prevents the inbreathing of air • optimized flow performance
and product losses almost up to the set pressure and also pro- • maintenance friendly design
tects against atmospheric deflagration. The PROTEGO® flame
arrester unit is designed to achieve minimum pressure drop with • sturdy housing design
maximum safety. The PROTEGO® VD/TS device is available for • superior technology for API tanks
substances from explosion groups IIA to IIB3 (NEC group D to
C MESG ≥ 0.65 mm). Design and Specifications
When the set pressure is reached, the valve starts to open Any combination of vacuum and pressure levels can be set for
and reaches full lift within 10% overpressure. This unique 10% the valve. The valve discs are weight loaded.
technology enables a set pressure that is only 10% below the Pressure/vacuum relief valve, basic design VD/TS-
maximum allowable working pressure (MAWP) or maximum al-
lowable working vacuum (MAWV) of the tank. After years of de- Additional special devices available upon request
velopment, this typical opening characteristic of a safety relief
valve is now also available for the low pressure range.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
350 KA / 7 / 0318 / GB
P/V-Valve with integrated Flame Arrester
Safety Risk P/V-Valve with integrated Vents - 10% Technology Leak Rate/10% Technology
Many traditional configurations are a
(Video) Flame Arrester (Video) (Flyer pdf) (Flyer pdf)
safety risk. (Flyer pdf)
Design F G H I
Pressure range (mbar) >+35 up to +50 +3.5 up to +5,0 >+5.0 up to +14 >+14 up to +35
(inch W.C.) >+14 up to +20 +1.4 up to +2.0 >+2.0 up to +5.6 >+5.6 up to +14
Valve pallet Stainless Steel Titanium Hastelloy Hastelloy
Sealing PTFE FEP FEP Metal to Metal
Weight Lead Hastelloy Hastelloy Hastelloy
Special material as well as higher set pressure upon request
KA / 7 / 0318 / GB 351
Pressure/Vacuum Relief Valve
atmospheric deflagration-proof
PROTEGO® VD/TS
Design G H
Vacuum range (mbar) <-3.5 up to -14 <-14 up to -25
(inch W.C.) <-1.4 up to -5.6 <-5.6 up to -10 Special material as well as higher set vacuum upon
Valve pallet Hastelloy Hastelloy request
Sealing FEP Metal to Metal
Weight Hastelloy Hastelloy
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
352 KA / 7 / 0318 / GB
Pressure/Vacuum Relief Valve
Flow Capacity Charts
PROTEGO® VD/TS
VD/TS-IIB3
pressure
.
flow rate V (m³/h) Leistung-000233-en
VD/TS-IIB3
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000234-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 7 / 0318 / GB 353
Pressure/Vacuum Diaphragm Valve
deflagration- and endurance burning-proof
PROTEGO® UB/SF
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
354 KA / 7 / 0318 / GB
UB/SF-IIB3 Frost-Proof P/V Diaphragm
(Flyer pdf) Valve (Video)
The valve can be used up to an operating temperature of +60°C / Design Types and Specifications
140°F and meets the requirements of European tank de-
Almost any combination of vacuum and pressure settings can
sign standard EN 14015 – Appendix L and ISO 28300
be utilized for the valve. The diaphragm is pressurized by liquid.
(API 2000).
Higher pressures can be achieved upon request with a special
Type-approved in accordance with the current ATEX Directive liquid reservoir. When there is a substantial difference between
and EN ISO 16852 as well as other international standards. the pressure and vacuum, special designs with weight-loaded
vacuum discs are used.
Special Features and Advantages
There are two different designs:
• high performance seal reducing product loss below EPA’s Pressure/vacuum diaphragm valve, basic UB/SF - –
500ppm rule preventing environmental pollution design
• set pressure close to opening pressure enables optimum Pressure/vacuum diaphragm valve with heating UB/SF - H
pressure maintenance in the system coil
• high flow capacity (max. heating fluid temperature +85°C / 185°F)
• can be used as a protective system according to In addition to the standard design, a series of specially devel-
ATEX in areas subject to an explosion hazard oped designs, which are particularly suitable for operating con-
ditions to which these products are subjected, can be provided
• protection against atmospheric deflagrations and endurance
upon request (for example, for acrylics or styrene storage tanks,
burning for products up to explosion group IIB3 (NEC group
etc.).
C MESG ≥ 0.65 mm)
• minimum pressure drop of the FLAMEFILTER®
• flame-transmission-proof pressure and vacuum chambers Remark
• freeze protection at sub-zero conditions opening pressure resp. tank design pressure
set pressure =
1,4
• self draining function for condensate
• liquid column height is monitored by level indicators
• easy maintenance through hinged vent cap Set pressure = the valve starts to open
• modular design enables individual FLAMEFILTER® discs and
valve diaphragm to be replaced Opening pressure = set pressure plus overpressure
• particularly suitable for problematic products such as
Overpressure = pressure increase over the set pressure
styrene, acrylics, etc.
KA / 7 / 0318 / GB 355
Pressure/Vacuum Diaphragm Valve
deflagration- and endurance burning-proof
PROTEGO® UB/SF
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
356 KA / 7 / 0318 / GB
Pressure/Vacuum Diaphragm Valve
Flow Capacity Charts - Pressure
PROTEGO® UB/SF-80
UB/SF-80-IIB3 - pressure
set pressure from +3.5 up to 25 mbar /
+1.4 up to 10 inch W.C.
interpolate intermediate sizes
.
flow rate V (m³/h) 2085-L
UB/SF-80-IIB3 - pressure
set pressure from >+25 up to 140 mbar /
>+10 up to 56 inch W.C.
interpolate intermediate sizes
tank pressure - inch W.C.
tank pressure (mbar)
.
flow rate V (m³/h) 2085-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 7 / 0318 / GB 357
Pressure/Vacuum Diaphragm Valve
Flow Capacity Charts - Pressure
PROTEGO® UB/SF-100
UB/SF-100-IIB3 - pressure
set pressure from +3.5 up to 25 mbar /
+1.4 up to 10 inch W.C.
interpolate intermediate sizes
.
flow rate V (m³/h) 2086-L
UB/SF-100-IIB3 - pressure
set pressure from >+25 up to 140 mbar /
>+10 up to 56 inch W.C.
interpolate intermediate sizes
tank pressure - inch W.C.
tank pressure (mbar)
.
flow rate V (m³/h) 2086-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
358 KA / 7 / 0318 / GB
Pressure/Vacuum Diaphragm Valve
Flow Capacity Charts - Pressure
PROTEGO® UB/SF-150
UB/SF-150-IIB3 - pressure
set pressure from +3.5 up to 25 mbar /
+1.4 up to 10 inch W.C.
interpolate intermediate sizes
.
flow rate V (m³/h) 2087-L
UB/SF-150-IIB3 - pressure
set pressure from >+25 up to 140 mbar /
>+10 up to 56 inch W.C.
interpolate intermediate sizes
tank pressure - inch W.C.
tank pressure (mbar)
.
flow rate V (m³/h) 2087-L
KA / 7 / 0318 / GB 359
Pressure/Vacuum Diaphragm Valve
Flow Capacity Charts - Vacuum
UB/SF-80-IIB3
vacuum
.
flow rate V (m³/h) 2088-L
pressure difference = max. allowable tank design vacuum - valve set vacuum
adjusted set vacuum:
≤ -5 mbar / ≤ -2 inch W.C.
> -5 mbar up to ≤ -7 mbar / > -2 inch W.C. up to ≤ -2.8 inch W.C.
> -7 mbar up to ≤ -35 mbar / > -2.8 inch W.C. up to ≤ -14 inch W.C.
UB/SF-100-IIB3
vacuum pressure difference ∆p - inch W.C.
pressure difference ∆p in mbar
.
flow rate V (m³/h) 2089-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
360 KA / 7 / 0318 / GB
Pressure/Vacuum Diaphragm Valve
Flow Capacity Chart - Vacuum
PROTEGO® UB/SF-150
UB/SF-150-IIB3
vacuum
.
flow rate V (m³/h) 2090-L
pressure difference = max. allowable tank design vacuum - valve set vacuum
adjusted set vacuum:
≤ -5 mbar / ≤ -2 inch W.C.
> -5 mbar up to ≤ -7 mbar / > -2 inch W.C. up to ≤ -2.8 inch W.C.
> -7 mbar up to ≤ -35 mbar / > -2.8 inch W.C. up to ≤ -14 inch W.C.
KA / 7 / 0318 / GB 361
Pressure Diaphragm Valve
deflagration- and endurance burning-proof
PROTEGO® UB/DF
Øb
When the pressure in the tank reaches the set pres-
5 4 sure, the diaphragm (1) on the outer valve seat ring (2)
is lifted and vapors vent to the environment. The set
pressure is adjusted by the liquid (water-glycol mix-
ture) column height, which is filled into the outer ring
chamber (3). The overpressure chamber is equipped
with an opening (4) to keep the pressure in balance
with the ambient pressure. The opening is equipped
with a FLAMEFILTER® to avoid flame transmission
3
into the overpressure chamber. Ambient air can now
flow into the tank. The liquid column height which
affect the set pressures is checked by a floating level
a
indicator (5).
The tank pressure is maintained up to the set pres-
sure with a tightness that is far superior to the conven-
tional standard due to our highly developed manufac-
turing technology. This is achieved because the liquid
loaded diaphragm presses tightly around the special
designed valve seat surface area, even when the op-
erating pressure increases. This is extremely impor-
tant to reduce leakage to an absolute minimum. After
the excess pressure is discharged, the valve reseats
6 2 1
and provides a tight seal.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
362 KA / 7 / 0318 / GB
Frost-Proof P/V Diaphragm
Valve (Video)
KA / 7 / 0318 / GB 363
Pressure Diaphragm Valve
deflagration- and endurance burning-proof
PROTEGO® UB/DF
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
364 KA / 7 / 0318 / GB
Pressure Diaphragm Valve
Flow Capacity Charts
PROTEGO® UB/DF
UB/DF-80-IIB3
set pressure from +3.5 up to 25 mbar /
+1.4 up to 10 inch W.C.
interpolate intermediate sizes
.
flow rate V (m³/h) 2708-L
UB/DF-80-IIB3
set pressure from >+25 up to 140 mbar /
>+10 up to 56 inch W.C.
interpolate intermediate sizes
tank pressure - inch W.C.
tank pressure (mbar)
.
flow rate V (m³/h) 2708-L
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 7 / 0318 / GB 365
Pressure Diaphragm valve
Flow Capacity Charts
PROTEGO® UB/DF
UB/DF-100-IIB3
set pressure from +3.5 up to 25 mbar /
+1.4 up to 10 inch W.C.
interpolate intermediate sizes
.
flow rate V (m³/h) 2709-L
UB/DF-100-IIB3
set pressure from >+25 up to 140 mbar /
>+10 up to 56 inch W.C.
interpolate intermediate sizes
tank pressure - inch W.C.
tank pressure (mbar)
.
flow rate V (m³/h) 2709-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
366 KA / 7 / 0318 / GB
Pressure Diaphragm valve
Flow Capacity Charts
PROTEGO® UB/DF
UB/DF-150-IIB3
set pressure from +3.5 up to 25 mbar /
+1.4 up to 10 inch W.C.
interpolate intermediate sizes
.
flow rate V (m³/h) 2710-L
UB/DF-150-IIB3
set pressure from >+25 up to 140 mbar /
>+10 up to 56 inch W.C.
interpolate intermediate sizes
tank pressure - inch W.C.
tank pressure (mbar)
.
flow rate V (m³/h) 2710-L
KA / 7 / 0318 / GB 367
Vacuum Diaphragm Valve
deflagration-proof
PROTEGO® UB/VF
Øb
vacuum chamber, is reached the atmospheric pres-
6 sure lifts the diaphragm (3) up off the inner and outer
valve seat rings (4,5). Ambient air can now flow into
the tank. The liquid column heights, which affect the
set vacuum, can be checked by a floating level indica-
tor (6).
The tank vacuum is maintained up to the set vacuum
with a tightness that is far superior to the conventional
1 2 standard due to our highly developed manufacturing
technology. This is achieved because the liquid loaded
diaphragm presses tightly around the special designed
valve seat surface area, even when the operating vac-
a
If a vacuum builds up in the tank, it is transmitted through pres- • liquid column height is monitored by level indicators
sure balancing tubes into the vacuum chambers (1), (2). If the • easy maintenance through hinged vent cap
set vacuum, which depends on the liquid column height in the
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
368 KA / 7 / 0318 / GB
Frost-Proof P/V Diaphragm
Valve (Video)
• modular design enables individual FLAMEFILTER® discs Design Types and Specifications
and valve diaphragm to be replaced
The diaphragm is pressurized by liquid.
• particularly suitable for problematic products such as
There are two different designs:
styrene, acrylics, etc
Vacuum diaphragm valve, basic design UB/VF - –
Vacuum diaphragm valve with heating coil UB/VF - H
(max. heating fluid temperature +85°C / 185°F)
In addition to the standard design, a series of specially
developed designs, which are particularly suitable for the
operating conditions to which these products are subjected, can
be provided upon request (for example, for acrylics or styrene
storage tanks, etc.).
KA / 7 / 0318 / GB 369
Vacuum Diaphragm Valve
Flow Capacity Charts
PROTEGO® UB/VF
UB/VF-80-IIB3
.
flow rate V (m³/h) 2109-L
pressure difference = max. allowable tank design vacuum - valve set vacuum
adjusted set vacuum:
≤ -5 mbar / ≤ -2 inch W.C.
> -5 mbar up to ≤ -7 mbar / > -2 inch W.C. up to ≤ -2.8 inch W.C.
> -7 mbar up to ≤ -35 mbar / > -2.8 inch W.C. up to ≤ -14 inch W.C.
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
370 KA / 7 / 0318 / GB
Vacuum Diaphragm Valve
Flow Capacity Charts
PROTEGO® UB/VF
UB/VF-100-IIB3
.
flow rate V (m³/h) 2111-L
pressure difference = max. allowable tank design vacuum - valve set vacuum
adjusted set vacuum:
≤ -5 mbar / ≤ -2 inch W.C.
> -5 mbar up to ≤ -7 mbar / > -2 inch W.C. up to ≤ -2.8 inch W.C.
> -7 mbar up to ≤ -35 mbar / > -2.8 inch W.C. up to ≤ -14 inch W.C.
UB/VF-150-IIB3
.
flow rate V (m³/h) 2112-L
KA / 7 / 0318 / GB 371
www.protego.com
for safety and environment
PROTEGO® Tank Accessories
and Special Equipment
Volume 8
Volume 8
Tanks in tank farms and large vessels not only need to be Floating Roof Tank Equipment
equipped with flame arresters or pressure and vacuum valves
For floating roof tanks the drainage system for the floating
but; in addition they need special equipment, which similar
roof must be designed very precisely. Every movement of the
meets high requirements to operate safely.
floating roof must be taken into account and the load on the
joints must not affect the free moving space. In case of restricted
movement the system will crack, the pipes will bend and the
Special Valves with Safety Functions
joints will be stuck. In order to prevent the water in the system
For emergency shut-off or for extraordinary operating conditions from standing and freezing, ensure sufficient drain to the lateral
it is necessary to provide internal safety valves so that product tank nozzle. Many years of experience are incorporated in the
leakage can be prevented quickly after a pipe burst. supplied systems that work without disruptions – starting from
the roof drain valves to the systems with ball bearing joints or
metal hose joints. With lowered floating roofs in maintenance
Gauging and Sampling Equipment positions the completely drained space below the floating roof
Gauge and sampling hatches allow the use of gauging and must be vented through a lift-actuated vent valve. When stor-
sampling devices in the tank. For horizontal tanks deflagration ing flammable liquids in the tank venting is to be done through
proof gauging pipes are available. flame arresters.
For sampling and local venting in tanks that store flammable liq-
uids PROTEGO® has designed special sampling and air bleed Special Equipment
valves with flame arrester elements.
Hygroscopic products must be vented with dry air when stored.
Explosion-proof floor drains for heliports pass flammable liquids Air-drying devices with drying pearls prevent the air from satu-
(such as Kerosene) into catch tanks and prevent ignition inside. rating with humidity.
If an outside ignition source ignites the explosive atmosphere
there is no flame transmission. A special safety device is the hydraulic flame arrester. It is
a collection device for large volume flows in pipelines collect-
ing exhaust air from various plant areas, and it also functions
Floating Suction Units and Skimming Systems as a backflow prevention device as it prevents the exchange of
vapours. With extremely low pressure losses thanks to its rela-
Floating Suction Units PROTEGO® SA/S are designed to en- tively large drill holes in the sparge pipes the hydraulic flame
sure that product in a storage tank is drawn off just below the arrester is insusceptible to clogging and therefore provides
surface of the liquid where it is cleanest. high plant availability. It can be used as flame arrester with sub-
Fixed roof tanks that store liquids with different density, so-called stances of all explosion groups and provides protection against
slop tanks, are fitted with the Float-Operated Skimming System all types of combustion. The hydraulic flame arrester has to be
PROTEGO® SA/DA for separating the phases. monitored and controlled by instrumentation. Early involvement
of our engineers in plant design is necessary to make the right
Together with the tank operator or tank contractor we develop selection.
the best way to ensure both economical and safe operation.
Selection
The special valves, systems and devices are designed together
with the operator, engineering company and tank contractor.
PROTEGO® prepares a quotation based on the detailed system
specifications.
80 - 100
SE/K Floating Roof Drainage System with Metal Hose Joint 382 - 383
3" - 4"
80 - 150
SE/CK Floating Roof Drainage System with Swivel Joints 384 - 385
3" - 6"
25 - 50 Gauging Pipe,
PU-IIA 1" - 2" deflagration proof
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
376 KA / 8 / 0318 / GB
Type Size Description Page
Deflagration proof Special Valves
Air-Drying Devices
50 - 150
LA Air-Drying Device
2" - 6"
50 - 150
LA/V Air-Drying Device with Check Valve
2" - 6"
In-Tank Valve
50 - 200
SI/F Internal Safety Valve 400 - 401
2“ - 8“
KA / 8 / 0318 / GB 377
Floating Suction Unit
PROTEGO® SA/S
RIM Vent
PROTEGO® SA/S for fixed roof tanks PROTEGO® SA/S for floating roof tanks
PROTEGO® Floating Suction Units are „Made in Germany“ and will provide many years of
trouble free tank operation.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
378 KA / 8 / 0318 / GB
Project Data Sheet
for Floating Suction Units
PROTEGO® SA/S
*Project:
Location:
Client:
*Enduser:
*Engineering:
*Fixed roof tank *Fixed roof tank with internal floating roof
*Horizontal tank
Tank-No.: *Tank height: mm *Tank diameter: mm
Product details
*Stored product:
Tank details
*Manhole size: DN
KA / 8 / 0318 / GB 379
Floating Skimmer System
PROTEGO® SA/DA
PROTEGO® SA/DA for fixed roof tanks PROTEGO® SA/DA with double-bend for fixed roof tanks
PROTEGO® Floating Skimmer Systems are „Made in Germany“ and will provide many years
of trouble free tank operation.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
380 KA / 8 / 0318 / GB
Project Data Sheet
for Floating Skimmer Systems
PROTEGO® SA/DA
*Project:
Location:
Client:
*Enduser:
*Engineering:
Product Details
Tank Details
*Manhole size: DN
KA / 8 / 0318 / GB 381
Floating Roof Drainage System with Metal Hose Joints
PROTEGO® SE/K
Bottom pipe
PROTEGO® Floating Roof Drainage Systems are „Made in Germany“ and will provide many
years of trouble free tank operation.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
382 KA / 8 / 0318 / GB
Project Data Sheet
for Floating Roof Drainage System with Metal Hose Joints
PROTEGO® SE/K
*Project:
Location:
Client:
*Enduser:
*Engineering:
Product Details
*Product stored:
*Specific gravity:
Tank Details
*Manhole size: DN
KA / 8 / 0318 / GB 383
Floating Roof Drainage System with Swivel Joints
PROTEGO® SE/CK
Bottom pipe
PROTEGO® Floating Roof Drainage Systems are „Made in Germany“ and will provide many
years of trouble free tank operation.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
384 KA / 8 / 0318 / GB
Project Data Sheet
for Floating Roof Drainage System with Swivel Joints
PROTEGO® SE/CK
*Project:
Location:
Client:
*Enduser:
*Engineering:
Product Details
*Product stored:
*Specific gravity:
Tank Details
*Manhole size: DN
KA / 8 / 0318 / GB 385
Roof Drain Valves
D/SR
Øa
Øf
DN
f f
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
386 KA / 8 / 0318 / GB
Table 3: Material selection Application Examples
Design A B
RIM Vent D/SR
Housing Steel Stainless Steel
Non-return valve Red Brass Red Brass
Valve disc Steel Stainless Steel
Quick-action shut-off Steel Stainless Steel
Gasket PUR PUR
The device must have sufficient corrosion resistance with re-
gards to the stored media. If necessary, designs in special stain-
less steel quality should be selected.
Flange Connection Type PROTEGO® roof drain valve type D/SR in combination with
In type PROTEGO® D/SR the housing bottom is equipped with Floating roof drainage system PROTEGO® SE/CK
a loose flange with threaded holes according to EN 1092-1 or
optionally according to any other international standard.
In the standard model of PROTEGO® D/SR-W the housing is RIM Vent D/SR-W
equipped with a lateral flange connection to EN 1092-1. Option-
ally, the connecting flanges can be made according to any other
international standard. An additional flange connection is avail-
able.
KA / 8 / 0318 / GB 387
Vent Valve, Lift-actuated
AL/DK b b AL 200
Øa
3
DN DN Ø 308 / 12.13
4
8 6
f
2 2
5 5
720 / 28.35
4 3
e
7 1
h2
h2
6
NG NG 200 / 8“
Floating roof Floating roof
Ø 450 /
h1
Ød
17.72
h1
Bottom of the tank Bottom of the tank
Dimensions in mm / inches
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
388 KA / 8 / 0318 / GB
Designs and Specifications Application Examples for PROTEGO® AL/DK
Table 1: Dimensions for AL/DK Lift-actuated vent valves of type PROTEGO® AL/DK can be
combined with vent caps type EB which are deflagration proof
NG 200 / 8" 200 / 8" 200 / 8"
and resistant against endurance burning. This ensures flame
DN 100 / 4" 150 / 6" 200 / 8" transmission proof ventilation.
a 350 / 13.78 350 / 13.78 350 / 13.78 RIM Vent with
EB
b 465 /18.31 465 / 18.31 515 / 20.28 flame arrester
c 870 / 34.25 870 / 34.25 870 / 34.25
d 450 / 17.72 450 / 17.72 450 / 17.72
e 385 / 15.16 385 / 15.16 415 / 16.34
f 420 / 16.54 285 / 11.22 370 / 14.57
Dimensions in mm / inches
Table 2: Material
Housing Steel
special materials upon
Valve guide Stainless Steel
request
Gasket FPM
If resistance against endurance burning is not required the val-
Table 3: Flange connection type DN ves can alternatively be combined with PROTEGO® deflagrati-
on proof devices type PROTEGO® LH/AD. The applicable data
EN 1092-1, Form B1
other types upon request sheets are available in volume 2 “Deflagration Flame Arresters,
ASME B16.5; 150 lbs RFSF end-of-line and Vent Caps”.
KA / 8 / 0318 / GB 389
Vent Valve, Lift-actuated
Flow Capacity Charts
AL/DK
.
flow rate V (m³/h) Leistung-000432-en
.
flow rate V (m³/h) 2804-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
390 KA / 8 / 0318 / GB
Notes:
391
Gauge Hatch
with flange
DN
DN
a1
DN
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
392 KA / 8 / 0318 / GB
Design Types and Specifications Application Examples
Depending on the intended use the following designs are Gauge Hatches can for instance be used in combination with the
available: manual gauge devices type PROTEGO® H/P or with the gau-
Gauge hatch with flange PF/K design I and II ging and sampling device PROTEGO® VP/HK.
„I“ : remaining open
„II“ : automatic cover closing
PF/TK
Gauge hatch with flange and PF/TK automatic cover closing
pedal
Gauge hatch with flange nozzle PS/KF design I and II
„I“ : remaining open
„II“ : automatic cover closing
Gauge hatches for welding to the tank are available as types
PROTEGO® PS/K and PS/TK. A separate data sheet is
available.
Table 1: Dimensions Dimensions in mm / inches
DN 100 / 4" 150 / 6" 200 / 8"
a 260 / 10.24 305 / 12.01 335 / 13.19
b 150 / 5.91 155 / 6.10 175 / 6.89
c 160 / 6.30 205 / 8.07 235 / 9.25
a1 225 / 8.86 265 / 10.43 300 / 11.81 Gauge Hatches can be applied on tanks with floating roof.
b1 315 / 12.40 360 / 14.17 405 / 15.94
The nominal size depends on the dimensions of the gauging
RIM Vent PF/K
and sampling device.
KA / 8 / 0318 / GB 393
Gauge Hatch
with welded nozzle
PROTEGO® PS/K
Design “I” Design “II”
c remaining open automatic cover closing
b
B
a
6
DN
Ød
PROTEGO® PS/TK
Pedal-operated version
c1
automatic cover closing
b
B
a
6
DN
B Welding on-site
Ød
or sampling.
The gauge hatches PROTEGO® PS/K and PS/TK mainly con- Gauge hatch with welding PS/K design I and II
sist of housing, cover and bracket. As a standard the housing nozzle „I“ : remaining open
has stainless steel gauge marks. „II“ : automatic cover closing
In the pedal-operated version PROTEGO® PS/TK the gauging Gauge hatch with welding PS/TK automatic cover closing
nozzle pedal is connected to both the housing and the bracket. nozzle and pedal
Gauge hatches with flange are available as type PROTEGO®
PF/K, PF/TK and PS/KF. A separate data sheet is available.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
394 KA / 8 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches Application Examples
DN 100 / 4" 150 / 6" 200 / 8" Gauge Hatches can for instance be used in combination with the
a 175 / 6.89 225 / 8.86 250 / 9.84 manual gauge devices type PROTEGO® H/P or with the gau-
ging and sampling device PROTEGO® VP/HK.
b 265 / 10.43 320 / 12.60 355 / 13.98
c 160 / 6.30 205 / 8.07 235 / 9.25
c1 260 / 10.24 305 / 12.01 335 / 13.19
PS/K
d 275 / 10.83 350 / 13.78 450 / 17.72
The nominal size depends on the dimensions of the gauging
and sampling device.
KA / 8 / 0318 / GB 395
Sampling and Air Bleed Valve
deflagration proof
PROTEGO® ZE/WU
Øc
tures ignite during venting, the valve prevents flash back into the
system to be protected.
The sampling and air bleed valve PROTEGO® ZE/WU consists
of the threaded angle valve in pressure stage PN25 (1) with
1
d
DN*
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
396 KA / 8 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
DN a b Øc d e f
40 / 140 / 70 / 80 / 96 / 67 /
15 / G½"
1.57 5.51 2.76 3.15 3.78 2.64
50 / 165 / 85 / 80 / 89 / 67 /
20 / G¾"
1.97 6.50 3.35 3.15 3.50 2.64
65 / 200 / 100 / 95 / 104 / 67 /
25 / G1"
2.56 7.87 3.94 3.74 4.09 2.64
Table 3: Material
Design A
Threaded angle valve Stainless Steel
Elbow Stainless Steel
Cover Stainless Steel
FLAMEFILTER ®
Stainless Steel
The valve must be sufficiently resistant to corrosion through
the gas/air mixtures or product vapor/air mixtures. This applies
mainly to the FLAMEFILTER®.
KA / 8 / 0318 / GB 397
Condensate Drain Valve
deflagration proof
PROTEGO® ZE/TK
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
398 KA / 8 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
DN a b c Ød e f g h i k l
15 / G½" 60 / 2.36 30 / 1.18 33 / 1.30 32 / 1.26 110 / 4.33 55 / 2.17 27 / 1.06 45 / 1.77 54 / 2.13 38 / 1.50 67 / 2.64
20 / G¾" 65 / 2.56 35 / 1.38 33 / 1.30 38 / 1.50 110 / 4.33 60 / 2.36 34 / 1.34 45 / 1.77 54 / 2.13 38 / 1.50 67 / 2.64
25 / G1" 73 / 2.87 40 / 1.57 33 / 1.30 45 / 1.77 110 / 4.33 65 / 2.56 41 / 1.61 45 / 1.77 54 / 2.13 38 / 1.50 67 / 2.64
Table 3: Material
Ball valve Stainless Steel
Elbow Stainless Steel
Cover Stainless Steel
FLAMEFILTER ®
Stainless Steel
The valves must be sufficiently resistant to corrosion through
the gas/air mixtures or product vapour/air mixtures. This applies
mainly to the FLAMEFILTER®. If necessary, designs in special
stainless steel quality should be selected.
KA / 8 / 0318 / GB 399
In-tank Valve
Internal Safety Valve
PROTEGO® SI/F
a g i
Øf
Ød
Øh
k
DN
Øe
DN
6 1 2 3 5 4 7
30°
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
400 KA / 8 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
DN a b c d e f g h i k m n
50 / 2" 371/14.61 75/2.95 170/6.69 240/9.45 205/8.07 14/0.55 30/1.18 305/12.01 250/9.84 54/2.13 200/7.87 8
65 / 2 ½" 400/15.75 85/3.35 190/7.48 305/12.01 205/8.07 14/0.55 30/1.18 305/12.01 240/9.45 45/1.77 200/7.87 8
80 / 3" 416/16.38 90/3.54 200/7.87 330/12.99 230/9.06 14/0.55 30/1.18 330/12.99 290/11.42 53/2.09 200/7.87 8
100 / 4" 434/17.09 100/3.94 225/8.86 270/10.63 230/9.06 14/0.55 30/1.18 330/12.99 270/10.63 40/1.57 200/7.87 8
150 / 6" 658/25.91 130/5.12 320/2.60 410/16.14 370/14.57 18/0.71 40/1.57 505/19.88 440/17.32 78/3.07 400/15.75 12
200 / 8" 725/28.54 145/5.71 365/14.37 540/21.26 405/15.94 18/0.71 45/1.77 540/21.26 450/17.72 68/2.68 400/15.75 12
KA / 8 / 0318 / GB 401
www.protego.com
for safety and environment
PROTEGO® Equipment for Cryogenic Storage Tanks
Volume 9
Kapitel 99
Volume
Volume
In-Tank Valves
So-called In-Tank Valves (internal safety valves) are used main-
ly in cryogenic tanks where the tank wall or the bottom is pene-
trated by the discharge pipe. In an emergency case of a failure
of such lines the In-Tank Valve is working as a shut-off-valve to
minimize spill of product and spread of danger.
operating parameters
rosion, Cristallisation)
= horizontal connection
(Polymerisation, Cor-
X = vertical connection
= Heating jacket,
X = metallic sealing
Heating coil
= soft sealing
positive negative
setting range setting range
Design
Type Size mbar / mbar / Page
inch W.C. inch W.C.
NEW
300 -2.0 up to -16 /
V/SV-XL X /X 416 - 417
12“ -0.8 up to -6.4
NEW
300 -2.0 up to -16 /
V/SV-XXL X /X 418 - 419
12“ -0.8 up to -6.4
Change-Over Valve
80 - 250
WV/T 420 - 421
3“ - 10“
In-Tank Valves
In-Tank Valve
150 - 200
NB/AP Fast Action Bottom Drain Valve 422 - 423
6" - 8"
with pneumatic actuator
Description
In-Tank Valve
NEW
ITV-S with side 424 - 425
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
406 KA / 9 / 0318 / GB
Application Examples
for Cryogenic Tanks
VN-A-PCPF-NV DA-SB
VN-A-PCPF-NV
V/SV
DA-SB-T
SI/DP
Products
VN-A-PCPF-NV, V/SV, ITV-S (→ )
VN-A-PCPF-NV DA-SB
VN-A-PCPF-NV
NB/AP, SI/DP, PM-HF (→ Volume 9)
N
V/SV-XXL V/SV-XL, V/SV-XXL(→ Volume 9)
V
DA-SB, DA-SB-T (→ Volume 4)
D
VD/SV, ER/V (→ Volume 5)
V
ZM-R (→ Volume 6)
Z
DA-SB-T
KA / 9 / 0318 / GB 407
Pressure/Vacuum Relief Valve
Pilot-operated diaphragm valve
PROTEGO® PM/(D)S
DN2
valve
d0 • pop-open characteristic from a minimum pressure rise to full
lift
b
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
408 KA / 9 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
To select the nominal size (DN), use the flow capacity charts on the following pages
DN1 80 / 3" 100 / 4" 150 / 6" 200 / 8" 250 / 10" 300 / 12" 300 / 12"
DN2 100 / 4" 150 / 6" 200 / 8" 250 / 10" 300 / 12" 350 / 14" 400 / 16"
a 225 / 8.86 250 / 9.87 325 / 12.80 375 / 14.76 450 / 17.72 500 / 19.69 500 / 19.69
b 150 / 5.91 175 / 6.89 225 / 8.86 250 / 9.84 270 / 10.63 300 / 11.81 325 / 12.79
c 275 / 10.83 330 / 12.99 445 / 17.52 550 / 21.65 665 / 26.18 785 / 30.91 785 / 30.91
d 370 / 14.57 425 / 16.73 530 / 20.87 605 / 23.82 675 / 26.57 785 / 30.91 835 / 32.87
e 615 / 24.21 685 / 26.97 770 / 30.31 825 / 32.48 935 / 36.81 1005 / 39.57 1055 / 41.53
f 35 / 1.38 40 / 1.57 40 / 1.57 50 / 1.97 50 /1.97 50 / 1.97 50 / 1.97
g 160 / 6.30 195 / 7.68 250 / 9.84 315 / 12.40 370 / 14.57 425 / 16.73 425 / 16.73
DN1 80 / 3" 100 / 4" 150 / 6" 200 / 8" 250 / 10" 300 / 12" 300 / 12"
DN2 100 / 4" 150 / 6" 200 / 8" 250 / 10" 300 / 12" 350 / 14" 400 / 16"
do 81 / 3.19 107 / 4.21 160 / 6.30 208 / 8.19 260 / 10.24 310 / 12.20 310 / 12.20
KA / 9 / 0318 / GB 409
Pressure/Vacuum relief valve
Flow Capacity Charts
PROTEGO® PM/(D)S
DN1 = DN
PM/(D)S
pressure
.
flow rate V (m³/h) 1457-L
DN1 = DN
PM/(D)S
vacuum
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) 1459-L
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
410 KA / 9 / 0318 / GB
Pressure/Vacuum relief valve
Technical Data Sheet
PROTEGO® PM/(D)S
signed: date:
KA / 9 / 0318 / GB 411
Pressure/Vacuum Relief Valve
Pilot-operated diaphragm valve
PROTEGO® PM-HF
Øc
Ø 280 The main valve is controlled by a pilot valve. The latter in turn
f is controlled by the tank pressure. A small amount fluid stored
in the tank released into the atmosphere by the pilot when the
valve opens. The set-to-operate pressure is adjusted on the pilot
valve by increasing or decreasing (as appropriate) the tension
of a spring.
As the working pressure rises, the closing force acting on the
main valve increases, i.e. the valve's tight-sealing is enhanced
until the set-to-operate pressure is reached, thus preventing
leakage. Once the valve has commenced to lift it opens fully
within a 10% pressure rise or the opening pressure difference
and the nominal volumetric flow is discharged through a fully
open valve. If and when this level is exceeded the pressure in-
.
crease will follow the performance curve (∆p/V curve). From set
e
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
412 KA / 9 / 0318 / GB
PROTEGO® PM-HF
(Flyer pdf)
DN1 80 / 3" 100 / 4" 150 / 6" 200 / 8" 250 / 10" 300 / 12" 300 / 12"
DN2 100 / 4" 150 / 6" 200 / 8" 250 / 10" 300 / 12" 350 / 14" 400 / 16"
do 81 / 3.19 107 / 4.21 160 / 6.30 208 / 8.19 260 / 10.24 310 / 12.20 310 / 12.20
KA / 9 / 0318 / GB 413
Pressure/Vacuum relief valve
Flow Capacity Charts
PROTEGO® PM-HF
DN1 = DN
PM-HF
pressure
10% overpressure
.
flow rate V (m³/h) Leistung-000356-en
* = DN1
N1 300/12" / DN2 350/14"
** = DN1
N1 300/12" / DN2 400/16"
DN1 = DN
PM-HF
vacuum
vacuum - inch W.C.
vacuum (mbar)
100% overpressure
..
flflow
ow rate
rate VV (m³/h)
(m³/h) Leistung-000357-en
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
414 KA / 9 / 0318 / GB
Pressure/Vacuum relief valve
Technical Data Sheet
PROTEGO® PM-HF
signed: date:
KA / 9 / 0318 / GB 415
Vacuum Relief Valve
PROTEGO® V/SV-XL
Detail X
a
X
DN
b
Settings: 2
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
416 KA / 9 / 0318 / GB
Table 1: Dimensions Dimensions in mm / inches
DN 300 / 12"
a 649 / 25.55
b 946 / 37.24
Dimensions of pressure and vacuum relief valves with heating jacket upon request
V/SV-XL
vacuum - inch W.C.
vacuum (mbar)
.
flow rate V (m³/h) Leistung-000446-en
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 9 / 0318 / GB 417
Vacuum Relief Valve
PROTEGO® V/SV-XXL
a
DN
b
Function and Description • the valve pallet is guided within the housing to protect
against harsh weather conditions
The V/SV-XXL type PROTEGO® valve is a highly developed op-
timized vacuum relief valve with excellent flow performance. It is • can be used in areas subject to explosion hazards
primarily used as a safety device for relieving vacuum in tanks, • self draining
containers and process engineering equipment.
• maintenance friendly design
When the set vacuum is reached, the valve starts to open
and reaches full lift within a 100% vacuum increase. Up to the • best technology for API-tanks
set vacuum, the tank vacuum is maintained with a seal that
• designed for use on cryogenic tanks
is far superior to the conventional standard due to the highly
developed manufacturing technology. This feature is achieved Design Types and Specifications
by valve seats made of high quality stainless steel with precisely
lapped valve pallets and a reinforced housing design. After the The valve pallets are weight-loaded. Higher vacuum can be
vacuum is relieved, the valve reseats and again provides a tight achieved upon request with a special spring-loaded design.
seal. There are two different designs:
The optimized fluid dynamic design of the valve body and valve
Pressure/vacuum valve in basic design V/SV-XXL - –
pallet is a result of intensive research and development activi-
ties, which allow a stable operation of the valve pallet and opti- Pressure/vacuum relief valve with V/SV-XXL - H
mized performance resulting in reduction of product losses. heating jacket
Additional special devices available
upon request.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
418 KA / 9 / 0318 / GB
Table 2: Material selection for housing
Design A B C
Housing Aluminium Steel Stainless Steel
Heating jacket (V/SV-XXL-H-...) – Steel Stainless Steel Option: Housing ECTFE-coated
Valve seat Stainless Steel Stainless Steel Stainless Steel Special materials upon request
Sealing PTFE PTFE PTFE
Cover Aluminium Steel Stainless Steel
V/SV-XXL
.
flow rate V (m³/h) Leistung-000449-en
Remark
opening pressure resp. tank design pressure
set pressure =
2
The flow capacity chart has been determined with a calibrated and TÜV certified flow capacity test rig.
.
Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar).
Conversion to other densities and temperatures refer to Vol. 1: “Technical Fundamentals”.
KA / 9 / 0318 / GB 419
Change-Over Valve
PROTEGO® WV/T
DN2 DN2
c
Øe
Ød
b
DN1
3 9 1 2 10 4 6 7 5 8
f
Function
unction and Description
PROTEGO® change-over valves type WV/T are mainly Due to their design and appropriately selected materials the
used together with other valves or safety devices (e.g. valves are distinguished by their high functional safety and very
PROTEGO® flame arresters) on cryogenic storage tanks good flow rates. All elements that affect the function are made
and on tanks in process plants of chemical, petrochemi- out of stainless steel.
cal and pharmaceutical industries. They increase the
Because of the variable nozzle positions the design of the
operating safety of the technical equipment to be protected
PROTEGO® change-over valves WV/T facilitates connection of
because each valve or safety device can be checked, main-
valves or other safety devices both with angle or straight through
tained or repaired without any service break-down.
connection without additional adaptors.
The valves mainly consist of housing (1) with flange connections
Positions of nozzles
DN 1 and two lateral connection elbows (3, 4) with flange con-
nections DN 2 and the valve disc (2). If necessary it is possible to I.
displace and turn the connection elbows. The valve seats (9, 10)
are replaceable. The valve disc with metallic sealing surface is
movable on the valve spindle (6). This ensures good adjustment
to the valve seats even with high temperature differences. The II.
sealing between valve disc and valve spindle is provided by an
O-ring. The valve spindle is guided by bearing bushings; to the
outside it is sealed by an adjustable packing (7). III.
The change-over valve allows the operator to block one valve
or safety device at a time by operating the hand wheel (8). In
normal operation the valve disc is in central position and the drag coefficient ζ = 1,2 for valve in center position
gas/liquid flows through the two connection elbows. By turn- ζ = 2,6 if one side of valve closed
ing the hand wheel to the stop, one of the connection elbows
(3 or 4) is blocked while the other one remains open. The actual Change-over valves of type WV/T stand out by their simple
position of the valve disc can be identified from the position indi- design, easy handling, the option of quick replacement of com-
cator (5) displayed on the valve spindle. ponents that effect the function and consequently by their excel-
lent availability and operational reliability. The lapped metallic
Depending on the requirements, the change-over valve in nor- sealing surfaces ensure a high degree of tightness even in low
mal operation can be in mid-position or in end position: Mid- temperature ranges.
position, e.g. when a high capacity of relief is required through
emergency relief valves controlled in parallel, or end position, These valves are not flame transmission proof and do not refer
e.g. in case of flame arresters which, controlled in parallel, can to the European Explosion Protection Directive 94/9/EC, even if
be used or cleaned alternately as necessary. installed in explosive atmospheres.
A hazard analysis (which considers the material selection and
function of the device) shows that the device doesn’t have any
potential sources of ignition.
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
420 KA / 9 / 0318 / GB
Design Types and Specifications
Special devices in heatable design can be used under specific
operating conditions:
• with crystallizing products or products which tend to form de-
posits that affect the function
• in use under extreme weather conditions in winter (frost),
when product vapour might condensate in the undercooled
valve, so ice bridges could develop, which could probly block
the valve disc
KA / 9 / 0318 / GB 421
In-tank Valve
with pneumatic actuator
PROTEGO® NB/AP
Øa
Function and Description
In-Tank Valves such as the PROTEGO® NB/AP are used in
storage tanks for cryogenic liquids in order to seal off discharge
lines in the event of an accident or emergency (pipe bursting).
These devices comply with the requirements of API 625.
The device consists of the bottom plate (1), which has to be
welded onto the vessel bottom, a nozzle (2), which is to be weld-
ed to the discharge line and the flanged fast acting valve (3) with
valve piston (4) and release valve cone (5) and the complete
pneumatic actuating device (6), which is mounted to the roof of
b
pneumatic actuating
the tank. Through lapped metallic valve pallet and release vent
device
cone the required leak tightness is achieved.
c
The fast acting valve (3) and the actuator system (6) are con-
nected by an actuator rope (7). An additional emergency rope
allows the opening of the fast acting valve if the main actuator
rope is damaged.
6
During normal operation a pneumatic cylinder holds the device
in the open position. The pneumatic cylinder is actuated by a
control line to lift the valve piston. IIn case of emergency, the
electromagnetic bottom assembly will rapidly close. This is achieved by interrupt-
valve ing the energy supply to the actuating unit, which will cause the
valve piston to fall on the valve seat using the deadweight of the
outbreathing valve pallet (fail safe concept).
The design of the device is independent of the nominal dia-
DN 2 meter. The nominal diameter DN 1 is preset by the nominal di-
ameter of discharge line.
Material selection is in accordance to the product and the
operating temperature.
7
3
f
lift
1
e
2
DN 1
NW
Ød
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
422 KA / 9 / 0318 / GB
In-Tank Valves
(Flyer pdf)
KA / 9 / 0318 / GB 423
In-tank Valve
with pneumatic actuator
PROTEGO® ITV-S
Download Flyer
In-Tank Valves
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
424 KA / 9 / 0318 / GB
Notes:
425
In-tank Valve
Internal Safety Valve
PROTEGO® SI/DP
external internal
tank shell tank shell X
5 1 9 1 2 7 9 1 6 8 4 3
a
DN
L* approx. 1650 L1
*depends on actuator
10
All rights and alterations reserved acc. ISO 16016 - Active data sheet at www.protego.com
426 KA / 9 / 0318 / GB
Download Flyer
In-Tank Valves
Table 2: Materialselection
Design A
Housing Stainless Steel
Valve disc Stainless Steel
Valve spindle Stainless Steel In-tank valve PROTEGO® SI/DP for a full containment tank sys-
Spindle sealing PTFE tem as per API 625.
Bushing PTFE
O-rings PTFE
KA / 9 / 0318 / GB 427
Germany
PROTEGO Head Office:
Braunschweiger Flammenfilter GmbH
Industriestrasse 11
38110 Braunschweig
: PROTEGO® Head Office
phone: +49(0)5307-809-0
fax: +49(0)5307-7824 : PROTEGO® Subsidiaries
email: office@protego.com : PROTEGO® Representatives
www.protego.com
for safety and environment
52